JOHN J PERSHING VA MEDCIAL CENTER KOHLER PM REPORT 2020.pdf

PDF 115 KB Posted

Attached to
J059--Tri-Annual Electrical Testing Federal contract opportunity
Solicitation number
36C25522Q0184
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This generator maintenance inspection report details servicing performed on a Kohler 2500REOZDB generator at the John J Pershing VA Medical Center. Key maintenance tasks completed include changing the oil and oil filter, fuel filter, inspecting and cleaning the air filter, checking coolant and antifreeze levels, inspecting hoses and belts, and load testing the batteries. The report recommends replacing the batteries due to age.

The related federal contract opportunity solicits offers for tri-annual electrical testing services at the Poplar Bluff, MO VA Medical Center. The Department of Veterans Affairs Veterans Health Administration VISN 15 is the contracting agency. The solicitation includes electrical testing and likely seeks a contractor to perform the maintenance and inspections detailed in the generator report, including battery replacement.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Comments

YOUR COMPLETE SOURCE OF ENGINE AND GENERATOR POWER

314-868-8620 www.ckpower.com

Generator Maintenance Inspec�on Report

ORDER NO. SVO096637_10000 DATE 06/22/2020

COMPANY JOHN J PERSHING VA MEDICAL CENTER SITE NAME SERVICE ITEM NO. SVI056753

MAKE KOHLER GENERATOR MODEL 2500REOZDB SERIAL NO. SGM3255N5

GENERATOR MFG GENERATOR SPEC ENGINE MFG

ENGINE MODEL ENGINE S/N ENGINE SPEC

ATS MFG ATS MODEL ATS S/N

ATS PHASE CUST UNIT NO.

HOURS 26.7

Verify and Document Generator Informa�on MODEL # 2500REOZDB S/N SGM3255N5 Lube and Oil Filter changed OIL QTY 320 FILTER QTY 5 Check Engine Oil Level Oil Sample Taken for Spectro-Analsis Fuel Filter(s) Changed FILTER QTY 2 Inspect and Clean Air Filter(s) Coolant Level Checked FULL ADDED QTY An�-Freeze Checked NITRATE PPM 1600 PROTECTION -34 Engine Heater Opera�on Checked Radiator Moun�ng Brackets and Braces Checked Silencer and Plumbing Inspected All Engine Hoses and Clamps Checked Belts inspected and Adjusted as Required Front and Rear Engine Supports Checked Generator Set Checked for Fuel, Oil, Coolant Leaks Ba�ery Charger Opera�on Checked, Charge Rate Ba�ery Electrolyte Levels Checked Ba�ery Load Tested BATTERY QTY 4 Cold Cranking Amps Recorded 1400 Ba�ery Date Recorded Month/Year 07-2016 Engine Alternator Charge Rate Checked / Recorded 27.4 Governor Adjusted, Frequency Recorded 60 Generator Output Voltage Adjusted and Recorded 13800 Oil Pressure Recorded 105 Water Temperature Recorded 174 Emergency Systems with Load Transfer Tested Transfer Switch Inspected and Cleaned Reset Maintenance Reminder Circuit Breaker Checked Emergency Shutdown Func�ons and Emergency Stop Tested Load Bank Performed Load Bank Recommended

Fuel Level 1/2 Exercise Program NA

BATTERIES PASS LOAD TEST. REQUEST REPLACING BATTERIES DUE

TO AGE.

BATTERIES PASS LOAD TEST. REQUEST REPLACING BATTERIES DUE TO AGE.

Performed by CHARLES SKILES

File details come from the government source that posted it. Updated .