JOHN J PERSHING VA MEDCIAL CENTER GENERAC PM REPORT 2020.pdf

PDF 113 KB Posted

Attached to
J059--Tri-Annual Electrical Testing Federal contract opportunity
Solicitation number
36C25522Q0184
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document contains a generator maintenance inspection report for the John J Pershing VA Medical Center and information on a related federal contract opportunity for tri-annual electrical testing at the Poplar Bluff, MO VAMC. The inspection report details maintenance and testing performed on a Generac generator, including oil and filter changes, engine checks, battery inspections, and load testing. It notes generator output voltage and engine parameters. The related opportunity is a solicitation from the Department of Veterans Affairs for tri-annual electrical testing services at the specified location. No further details are provided on response dates, pricing terms, or other requirements for the testing contract.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Comments

YOUR COMPLETE SOURCE OF ENGINE AND GENERATOR POWER

314-868-8620 www.ckpower.com

Generator Maintenance Inspec�on Report

ORDER NO. SVO096636_10000 DATE 06/22/2020

COMPANY JOHN J PERSHING VA MEDICAL CENTER SITE NAME SERVICE ITEM NO. SVI074554

MAKE GENERAC GENERATOR MODEL 10656570100 SERIAL NO. 2101352

GENERATOR MFG GENERATOR SPEC ENGINE MFG

ENGINE MODEL ENGINE S/N ENGINE SPEC

ATS MFG ATS MODEL ATS S/N

ATS PHASE CUST UNIT NO.

HOURS 261.4

Verify and Document Generator Informa�on MODEL # 10656570100 S/N 2101352 Lube and Oil Filter changed OIL QTY 36 FILTER QTY 1 Check Engine Oil Level Oil Sample Taken for Spectro-Analsis Fuel Filter(s) Changed FILTER QTY 2 Inspect and Clean Air Filter(s) Coolant Level Checked FULL ADDED QTY An�-Freeze Checked NITRATE PPM 1600 PROTECTION -34 Engine Heater Opera�on Checked Radiator Moun�ng Brackets and Braces Checked Silencer and Plumbing Inspected All Engine Hoses and Clamps Checked Belts inspected and Adjusted as Required Front and Rear Engine Supports Checked Generator Set Checked for Fuel, Oil, Coolant Leaks Ba�ery Charger Opera�on Checked, Charge Rate Ba�ery Electrolyte Levels Checked Ba�ery Load Tested BATTERY QTY 20 Cold Cranking Amps Recorded NI CAD Ba�ery Date Recorded Month/Year 11-08 Engine Alternator Charge Rate Checked / Recorded 28 Governor Adjusted, Frequency Recorded 60 Generator Output Voltage Adjusted and Recorded 209 Oil Pressure Recorded 57 Water Temperature Recorded 172 Emergency Systems with Load Transfer Tested Transfer Switch Inspected and Cleaned Reset Maintenance Reminder Circuit Breaker Checked Emergency Shutdown Func�ons and Emergency Stop Tested Load Bank Performed Load Bank Recommended

Fuel Level 80% Exercise Program MANUAL RU

REPLACED AIR FILTER.

REPLACED AIR FILTER.

Performed by CHARLES SKILES