FAR_7878582_JOHN J PERSHING VA MED CTR_EC154CBA02__MO - EESDUS_07022020.pdf
PDF 51 KB Posted
- Attached to
- J059--Tri-Annual Electrical Testing Federal contract opportunity
- Solicitation number
- 36C25522Q0184
About this file
This document is a field activity report for electrical testing and maintenance services performed at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. Eaton technician Bryan Bartsch updated the UPS firmware from version 5.00 to 6.14, replaced the capacitor tray and seven cooling fans in the input feeder, and calibrated all AC and DC voltages with no issues. He also tested bypass, normal and on battery functions and load transfer, and calibrated input and output currents. Readings were within normal ranges and the UPS was supporting the load with no alarms. The technician noted the capacitor and fan replacement was complete.
The related federal contract opportunity is solicitation number 36C25522Q0184 for tri-annual electrical testing services at the Poplar Bluff VAMC. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25522Q0184 0001.docx | DOCX document | |
| SOW Trienniel Electrical SS R1 - Final.doc | DOC document | |
| Edited VA_657A-16-101-100__ASI_001_Dwgs.pdf | ||
| JOHN J PERSHING VA MEDCIAL CENTER KOHLER PM REPORT 2020.pdf | ||
| JOHN J PERSHING VA MEDCIAL CENTER GENERAC PM REPORT 2020.pdf | ||
| STL20547-000 VA Hospital Poplar Bluff MO Report_Rev0.pdf | ||
| Attachment (1) - Wage Determinations Incorporated by Reference.pdf | ||
| 36C25522Q0184_2.docx | DOCX document | |
| Edited Electrical - One-Line Diagrams - 6-14-16.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
50 SOCCER PARK RD
FENTON,MO.63026-2564
Service Dispatch: (800)843-9433 www.eaton.com/powerquality
Field Activity Report
MO - EESDUS
For
JOHN J PERSHING VA MED CTR
1500 N WESTWOOD BLVD
POPLAR BLUFF,MO 63901
DATA ROOM
Attention: MIKE WRIGHT Phone: 573-686-4151 Email: DONALD.WRIGHT3@VA.GOV
Inspection Date: 7/1/2020
Service Performed By: Bartsch, Mr. Bryan
Service Request: Serial Number: Customer ID#
7878582 EC154CBA02
Cust. Unit ID:
CSE Signature Digitally Signed by Bartsch, Mr. Bryan Date 7/1/2020
Customer Signature Date 7/1/2020
MIKE WRIGHT
http://www.eaton.com/powerquality
Date 7/1/2020
SR# 7878582
Party # 743918 Contract 113398
Expiration 31-Jul-2020 Customer ID
Field Activity Report
Site Information: Equipment Information:
Name JOHN J PERSHING VA MED CTR Unit / Model 9390-40-80 KVA 50 KW 45
Address 1500 N WESTWOOD BLVD Serial # EC154CBA02 CTO or PN# TB0511021110010
City POPLAR BLUFF ST MO Zip 63901 Location DATA ROOM
QOS Information: Battery Information:
POC MIKE WRIGHT Manufacturer Eaton
Company JOHN J PERSHING VA MED CTR Battery Model PWHR12280W4FR Address 1500 N WESTWOOD BLVD # of Strings 1 Trays/Str 8 Jars/Tray 4
Date Code 11/2017 Age (Years) 2.66 City POPLAR BLUFF ST MO Zip 63901 Battery Type Sealed TEL 573-686-4151 FAX Battery Cabinet Type Cabinet
ALT TEL
Email: DONALD.WRIGHT3@VA.GOV
Service Information Service Type: MODIFICATION Billing Type: QUOTED PM Frequency: Semi Annual
Battery Maintenance Type: Semi Annual
Notes:
I ARRIVED ON SITE AND UPS WAS IN NORMAL WITH A CONFIG ALARM. I TRANSFERRED THE LOAD TO MAINTENANCE BYPASS AND SHUTDOWN THE UPS. WHILE IN LOGIC POWER I UPDATED THE UPS FIRMWARE FROM 5.00 TO 6.14 WITH NO ISSUE. I OPENED THE INPUT FEEDER (BIB) TO THE UPS AND REPLACED THE CAPACITOR TRAY AND 7 COOLING FANS. I RETURNED POWER TO THE UPS AND CALIBRATED ALL AC AND DC VOLTAGES WITH NO ISSUES. I TESTED BYPASS, NORMAL AND ON BATTERY FUNCTION WITH NO ISSUES. I RETURNED LOAD TO UPS IN NORMAL AND I CALIBRATED THE AC INPUT AND OUTPUT CURRENT WITH NO ISSUES. UPS IS IN
NORMAL SUPPORTING LOAD WITH NO ALARMS ACTIVE.
CAPACITOR AND FAN REPLACEMENT COMPLETE
BDB
Date 7/1/2020
SR# 7878582
Party # 743918 Contract 113398
Expiration 31-Jul-2020 Customer ID
Field Activity Report Site Information: Equipment Information:
Name JOHN J PERSHING VA MED CTR Unit / Model 9390-40-80 KVA 50 KW 45 Address 1500 N WESTWOOD BLVD Serial # EC154CBA02
CTO or PN# TB0511021110010 City POPLAR BLUFF ST MO Zip 63901 Location DATA ROOM
QOS Information: Battery Information:
POC MIKE WRIGHT Manufacturer Eaton
Company JOHN J PERSHING VA MED CTR Battery Model PWHR12280W4FR Address 1500 N WESTWOOD BLVD # of Strings 1 Trays/Str 8 Jars/Tray 4
Date Code 11/2017 Age (Years) 2.66 City POPLAR BLUFF ST MO Zip 63901 Battery Type Sealed TEL 573-686-4151 FAX Battery Cabinet Type Cabinet
ALT TEL
Email: DONALD.WRIGHT3@VA.GOV
Input Readings
Nominal 208
A-B VAC 205.5
B-C VAC 205.4
C-A VAC 204.3
A-N VAC 118.0
B-N VAC 119.3
C-N VAC 117.9
A-I 56.6 B-I 56.6 C-I 56.6
Frequency 59.9
Output Readings
Nominal 208
A-B VAC 209.5
B-C VAC 208.0
C-A VAC 208.2
A-N VAC 120.2
B-N VAC 120.5
C-N VAC 120.6
A-I 30.8 B-I 47.4 C-I 51.2 N-I 0
Frequency 59.9 Percent Load 31.0
Output KVA 15.5 Output KW 14.5
Bypass Readings
Nominal 208
A-B VAC 205.9
B-C VAC 205.7
C-A VAC 204.8
A-N VAC 118.4
B-N VAC 119.4
C-N VAC 118.1
DC Readings
Nom. DC Link 320 DC Link Volts 319.3 Battery Volts 443.4 Pos/Ground 283.2 Neg/Ground 160.1 AC Ripple .27
Inverter Readings
Nominal 208
A-B VAC 209.5
B-C VAC 208.0
C-A VAC 208.2
A-N VAC 120.2
B-N VAC 120.5
C-N VAC 120.6
Electronic Visual Inspection Good Remote Monitor Panel Operation Good Electronic Room Temperature 62 Electronic Fans - Monitor Panel Function Good Electronic Room Ventilation Good
Electronic Metering Good Communication Function Good Electronic Room Cleanliness - Ctrl & Pwr Wire Heating Good Mimic Screen Good Electronic Room Floor Type Good
AC/DC Caps - Cellwatch / Battery Monitor N/A Electronic Air Filters - Static Switch Fuses Good Time and Date Set Correctly Good Battery Room Temperature
Output Fuses Good Download/Check Event Log Good Battery Room Ventilation Good Connector (Crimp&Bolt) Good Download EEPS Good Battery Room Cleanliness Good
Waveform Distortion Good Download Configuration Report Good Battery Room Floor Type Good System Transfers Good Download Unit Stats N/A Battery Visual Inspection Good
FSB's checked Good
Notes from the Equipment Inspection Test Result Form