J01-B Economizer and Control Requirements.pdf

PDF 412 KB Posted

Attached to
HVAC Replacement & TAB Services – White Swan, WA Federal contract opportunity
Solicitation number
75H70122Q00039
Issued by
Department of Health and Human Services Indian Health Service

View the file

Other files for this federal contract opportunity

Other files attached to HVAC Replacement & TAB Services – White Swan, WA, newest first.
File Type Posted
75H70122Q00039-A00002.pdf PDF
75H70122Q00039-A00001.pdf PDF
B01 75H70122Q00039.pdf PDF
J01-D Site Map.pdf PDF
J01-A Ventilation Schedule.pdf PDF
J03 PPQ.docx DOCX document
J01-C Building Drawings - White Swan.pdf PDF
J02 SCA WD 2015-5543 Rev 18 dated 06272022.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Economizer and Control Requirements – Sequence and Priority Operations

Required inputs and logging ~ 5 Minute Intervals

Outdoor-air-temperature (OAT)

Mixed-air temperature (MAT)

Return-air temperature (RAT)

Discharge-air temperature and set point (DAT and DATSP)

Outdoor-air damper position signal (OAD)

Cooling and heating signal

Pressure transducer signal

Sequence of Operation in Priority Order

1. The economizer must maintain a minimum or greater than 20% damper position at all times to provide code-compliant ventilation.

2. The economizer must provide freeze protection when outside air temperatures drop below freezing. In extreme cold situations, the damper may be closed to prevent damage. A warning indicator inside the building must illuminate to notify staff that fresh air ventilation has been reduced below minimum or is at zero.

3. The economizer must modulate to maintain an indoor building differential pressure of 0.02 in.wg. This is due to multiple building exhaust fans that require makeup air. These fans are manually operated and do not have predictable operation. Damper position for maximum makeup air is approximated at 50%.

4. In cooling mode, when the RAT > OAT, then the economizer shall modulate to increase the amount of outside air to the system to reduce the MAT.

5. In heating mode, when the RAT < OAT, then the economizer shall modulate to increase the amount of outside air to the system to increase the MAT.