IFB1 PMAA 2027000013 - Drawing Set 1 of 2.pdf
PDF 17 MB Posted
- Attached to
- Project Number: CC2501T11
- Solicitation number
- IFB1 PMAA 2027000013 1
- Issued by
- Denver County, Denver City, Colorado
About this file
This is a construction drawing set for the North Connector Pedestrian Bridge Replacement project, a joint initiative between Colorado Parks and Wildlife (CPW) and the U.S. Army Corps of Engineers (USACE) at Cherry Creek Reservoir in Parker, Colorado. The project involves the replacement of a pedestrian bridge crossing Cherry Creek, including associated trail improvements, abutment protection measures, and erosion control features. The design is 90% complete as of August 28, 2026, and was prepared by Muller Engineering Company Inc. under the supervision of Shawn Krier (Project Manager) and Michelle Seubert (Park Manager). The construction scope includes a single-span prefabricated weathering steel Pratt pony half-through truss bridge, reinforced concrete abutments founded on drilled shafts, approximately 165 cubic yards of borrow material, 23 square yards of concrete trail replacement, Class 6 aggregate base course trail construction with a 5% maximum running slope, and Type H void-filled riprap abutment protection measuring 3 feet thick. The project site is subject to periodic flooding within the USACE reservoir storage zones, with water surface elevations ranging from 5550.0 feet (multipurpose pool) to 5648.0 feet (maximum pool).
The project specifications require compliance with Colorado Department of Transportation standards and the 2025 CDOT Standard Specifications for Road and Bridge Construction. Reinforced concrete is specified as Class DF with f'c = 4,500 psi, and Grade 60 reinforcing steel is mandatory. The design utilizes AASHTO LRFD specifications with a pedestrian live load of 90 PSF, H5 truck loading, and base wind speed of 115 MPH. Geotechnical investigation conducted by CTL Thompson Inc. identified bedrock at approximately 17 feet below grade at the boring location, though previous investigations suggest potential bedrock depths of approximately 40 feet at the bridge site, requiring contractor-performed sounding holes and bedrock verification prior to drilled shaft construction. High groundwater (approximately elevation 5549.00 to 5552.50) and soft soil conditions necessitate temporary casing during drilling operations. All construction must comply with permit requirements including U.S. Fish and Wildlife Service migratory bird protection protocols and U.S. Army Corps of Engineers notification for any discovered historic or archaeological remains. The contractor is solely responsible for water management, stream crossing control, and ensuring structural stability during construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB1 PMAA 2027000013 - APPENDICIES.pdf | ||
| IFB1 PMAA 2027000013 - Drawing Set 2 of 2.pdf | ||
| IFB1 PMAA 2027000013 - Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT
LOCATION
Cherry Creek ReservoirI-2
E. Belleview Ave.
P arker R oad
E. Hampden Ave.
E. Quincy Ave.
Cherry Creek
Shop Creek
C ot to nw oo d
C re ek
Quincy O utfall
PL
O
TT
ED
: 8 /2
8/
0:
:3
AM
N
AM
E:
P :\2
PR
O
JE
C
TS
\2
5-
4.
N O
R
TH
C O
N N
EC
TO
R P
ED
ES
TR
IA
N B
R
ID
G E
R
EP
LA
C
EM
EN
T
- C
PW
\C
AD
\D
R
AW
IN
G
S\
-1
.0 1_
TI
TL
E
SH
EE
T.
D W
G
LOCATION MAP
2000'1000'0'
CONTRACT DRAWINGS FOR THE CONSTRUCTION OF:
NORTH CONNECTOR BRIDGE REPLACEMENT
COLORADO PARKS AND WILDLIFE
AUGUST 2026
CMH
JAY
CRV
G-1
8/28/2026
TITLE SHEET
GENERAL
INDEX OF DRAWINGS
SHEET
NO.
DRAWING
NO.
TITLE
GENERAL
1 G-1 TITLE SHEET
2 G-2 GENERAL NOTES
3 G-3 SITE PLAN
CIVIL
4 C-1 GRADING PLAN
5 C-2 RIPRAP ABUTMENT PROTECTION DETAIL
6 C-3 TRAIL PLAN AND PROFILE
7 C-4 MISC DETAILS
STRUCTURAL
8 S-1 GENERAL NOTES
9 S-2 GENERAL LAYOUT
10 S-3 ABUTMENT 1 LAYOUT
11 S-4 ABUTMENT 2 LAYOUT
12 S-5 DRILLED SHAFT DETAILS
13 S-6 ABUTMENT DETAILS
LANDSCAPE
14 L-1 LANDSCAPE PLAN
15 L-2 LANDSCAPE NOTES
EROSION CONTROL
16 EC-1 EROSION CONTROL PLAN
17 - 20 EC-2 - EC-5 EROSION CONTROL DETAILS
7245 W ALASKA DR. SUITE 300, LAKEWOOD, COLORADO 80226
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
MULLER ENGINEERING COMPANY INC.
PREPARED BY:
COLORADO PARKS AND WILDLIFE
SHAWN KRIER, PROJECT MANAGER DATE
MICHELLE SEUBERT, PARK MANAGER DATE
DATE
CMH
JAY
CRV
G-2
8/28/2026
GENERAL NOTES
GENERAL
PL
O
TT
ED
: 8 /2
8/
0:
:4
AM
N
AM
E:
P :\2
PR
O
JE
C
TS
\2
5-
4.
N O
R
TH
C O
N N
EC
TO
R P
ED
ES
TR
IA
N B
R
ID
G E
R
EP
LA
C
EM
EN
T
- C
PW
\C
AD
\D
R
AW
IN
G
S\
-1
.0 1_
TI
TL
E
SH
EE
T.
D W
G
GENERAL NOTES
1. ALL CONSTRUCTION SHALL CONFORM TO THE COLORADO DEPARTMENT OF TRANSPORTATION STANDARDS
UNLESS NOTED OTHERWISE. ANY CONSTRUCTION NOT SPECIFICALLY ADDRESSED BY THESE PLANS AND SPECIFICATIONS WILL BE BUILT IN COMPLIANCE WITH THE LATEST EDITION OF THE MOST STRINGENT OF THE
FOLLOWING:
· THE COLORADO DEPARTMENT OF HIGHWAYS STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE
CONSTRUCTION
· THE COLORADO DEPARTMENT OF TRANSPORTATION M STANDARDS
2. CONSTRUCTION WILL NOT BEGIN UNTIL ALL APPLICABLE PERMITS HAVE BEEN ISSUED.
3. CONTACT THE U.S. FISH AND WILDLIFE SERVICE, OFFICE OF MIGRATORY BIRDS, AT (303) 236-8171, FOR
PERMITTING REQUIREMENTS PRIOR TO THE REMOVAL OR DESTRUCTION OF ANY BIRD NEST.
4. IF ANY PREVIOUSLY UNKNOWN HISTORIC OR ARCHEOLOGICAL REMAINS ARE DISCOVERED DURING
CONSTRUCTION, IMMEDIATELY STOP ACTIVITIES AND NOTIFY THE PROJECT REPRESENTATIVE AND THE U.S.
ARMY CORPS OF ENGINEERS.
5. LOCATION OF EXISTING UTILITIES SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO ACTUAL CONSTRUCTION. CONTACT THE UTILITY NOTIFICATION CENTER OF COLORADO AT TOLL FREE 1-800-922-1987.
6. THE CONTRACTOR SHALL HAVE ONE (1) SIGNED COPY OF THE PLANS AND ONE (1) COPY OF THE COLORADO
DEPARTMENT OF TRANSPORTATION SPECIFICATIONS AT THE JOB SITE AT ALL TIMES.
7. THE CONSTRUCTION PLANS SHALL BE CONSIDERED VALID FOR TWO (2) YEARS FROM THE DATE OF COUNTY ACCEPTANCE, AFTER WHICH TIME THESE PLANS SHALL BE VOID AND WILL BE SUBJECT TO RE-REVIEW AND
RE-ACCEPTANCE BY COLORADO PARKS AND WILDLIFE.
8. EXCEPT WHERE OTHERWISE PROVIDED FOR IN THESE PLANS AND SPECIFICATIONS, THE COLORADO
DEPARTMENT OF TRANSPORTATION SPECIFICATIONS SHALL APPLY.
9. TOPOGRAPHIC MAPPING SHOWN ON THE DRAWINGS WAS PREPARED BY TOPOGRAPHIC LAND SURVEYORS BASED ON FIELD SURVEY IN DECEMBER 2024. ACTUAL FEATURES AND TOPOGRAPHY COULD VARY. THE
CONTRACTOR SHALL VERIFY SITE CONDITIONS BEFORE THE START OF WORK.
10. SUBSURFACE UTILITY MAPPING SHOWN ON THE DRAWINGS IS QUALITY LEVEL B, PREPARED BY TOPOGRAPHIC LAND SURVEYORS IN JANUARY 2026. THE MAPPING WAS BASED ON A SUBSURFACE UTILITY
INVESTIGATION PERFORMED BY SURVWEST THAT INCLUDED THE FOLLOWING:
· UTILITY OWNERS WERE CONTACTED, AND UTILITY MAPS WERE COLLECTED/REVIEWED.
· THE SUBSURFACE UTILITY INVESTIGATION WAS PERFORMED UNDER THE RESPONSIBLE CHARGE OF A
COLORADO PROFESSIONAL LAND SURVEYOR AND NOT A PROFESSIONAL ENGINEER.
11. VERTICAL SURVEY CONTROL IS BASED ON THE USACE LOCAL VERTICAL DATUM (NAVD88 - 1.38').
SITE BENCHMARK:
SITE BENCHMARK IS A SET #5 REBAR W/GREEN PLASTIC CAP AT THE WEST END OF THE PROJECT ALONG THE WEST RIGHT OF WAY OF COLORADO FRONT RANGE TRAIL, AS SHOWN HEREON, WITH A NAVD 88 ELEVATION OF 5566.41' PER CHERRY CREEK STATE BY HKS SURVEY GPS OBSERVATIONS. ALL DIRECTIONS, DISTANCES AND DIMENSIONS ARE BASED ON COORDINATES FROM THE COLORADO COORDINATE SYSTEM OF 1983
CENTRAL ZONE (C.R.S. 38-52-102).
12. HORIZONTAL SURVEY CONTROL IS BASED ON COLORADO STATE PLAN COORDINATE SYSTEM, CENTRAL ZONE 83 (2011).
13. PROJECT FACILITIES ARE TO BE LOCATED BASED ON THE SURVEY COORDINATES, ELEVATIONS, DIMENSIONS, AND/OR GEOMETRIC DESIGN DATA PROVIDED ON THE DRAWINGS.
14. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR PROVIDING STABLE EXCAVATIONS AND TEMPORARY SLOPES AND FOR SATISFYING ALL APPLICABLE OSHA, FEDERAL, STATE, AND LOCAL REGULATIONS.
TEMPORARY EXCAVATIONS SHALL PROVIDE, AT MINIMUM, THE TRENCH DIMENSIONS AND CLEARANCES SHOWN OR SPECIFIED. TEMPORARY CONSTRUCTION SLOPES SHALL BE SLOPED, SHORED, SHEETED, AND/OR BRACED IN ACCORDANCE WITH STABILITY REQUIREMENTS AND APPLICABLE REGULATIONS, AND SHALL BE NO STEEPER THAN THE SLOPES SHOWN OR SPECIFIED WITHOUT THE APPROVAL OF THE ENGINEER. ANY SUCH APPROVALS BY THE ENGINEER WILL NOT RELIEVE THE CONTRACTOR FROM SOLE
RESPONSIBILITY FOR PROVIDING STABLE EXCAVATIONS AND TEMPORARY SLOPES.
15. ALL EXISTING UTILITIES SHALL BE PROTECTED BY THE CONTRACTOR IN PLACE.
16. EXISTING TREES, VEGETATION, AND FACILITIES NOT INDICATED TO BE REMOVED SHALL BE PROTECTED IN
PLACE OR REMOVED AND REPLACED IN KIND, AS APPROVED BY ENGINEER.
17. THE WORK WILL TAKE PLACE IN AND AROUND A STREAM, SUBJECT TO PERIODIC FLOODING. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF SURFACE AND SUBSURFACE WATER DURING THE COURSE OF THE WORK. ANY DAMAGE TO THE WORK RESULTING FROM SURFACE FLOWS, BASE FLOWS OR FLOOD FLOWS INCLUDING BUOYANCY FORCES ON PIPELINES AND OTHER FACILITIES SHALL BE CORRECTED BY THE CONTRACTOR AT THE CONTRACTOR'S SOLE COST. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND SATISFYING THE REQUIREMENTS OF ANY APPLICABLE PERMITS
PERTAINING TO WATER AND EROSION CONTROL.
18. CONTACT THE ENGINEER FOR CLARIFICATIONS OF ANY ABBREVIATIONS SHOWN ON THE DRAWINGS.
19. CONTRACTOR SHALL CONFINE WORK TO THE CONSTRUCTION LIMITS SHOWN ON THE GESC PLAN.
ABBREVIATIONS
CP CONTROL POINT
DIA DIAMETER
DP DESIGN POINT
DWG DRAWING
EL ELEVATION
EX EXISTING
EW EACH WAY
GESC GRADING , EROSION, AND SEDIMENT CONTROL
INV. INVERT
LF LINEAR FEET
MAX MAXIMUM
MIN MINIMUM
NO. NUMBER
O.C. ON CENTER
STA STATION
TOR TOP OF RIPRAP
TOW TOP OF WALL
TYP. TYPICAL
WSEL WATER SURFACE ELEVATION
3:1
PROPOSED VOID-FILLED RIPRAP OR SOIL RIPRAP
EXISTING TREES
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
NEW EMBANKMENT SLOPE AS INDICATED (HORIZ:VERT)
SPOT ELEVATIONEL. 5600
REMOVE TREE
EXISTING SHRUB BOUNDARY LINE
EXISTING CONCRETE
PROPOSED BURIED VOID-FILLED RIPRAP
DESIGN POINT
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
LEGEND
w w w w w w w w w w w w w w ww w w w w w w w w w w w w w w w w w w w w w w w
Cherry Creek Reservoir
Lakeview Drive
Parker R oad
C ottonw ood C reek
Pipeline Trail
W etland L oop Trail
North Connector Trail
Q uincy
South C onnector
T rail
Multi-Purpose Pool (Elev. 5550.0), Approx. Normal Operating WSE
Flood Control Pool (Elev. 5598.0)
O utfall
NORTH CONNECTOR
TRAIL BRIDGE
DRAWING NUMBER, TYP.
Shop C reek
SHEET WINDOW, TYP.
STAGING AREA
SITE ACCESS FOR WEST
ABUTMENT VIA PIPELINE TRAIL
SITE ACCESS FOR WEST
ABUTMENT VIA PIPELINE TRAIL
AND WETLAND LOOP TRAIL
EAST SITE ACCESS LOCATION
La ke vie w
D riv e
Concrete Bike Path
C-1
40" And 54" Water Lines
Che rry
C ree k w
LIMITS OF CONSTRUCTION
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
EXISTING WATER LINE
EXISTING SHRUB BOUNDARY LINE
EXISTING CONCRETE
EXISTING CHANNEL CENTERLINE
EXISTING WETLAND
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
STAGING AREA
LEGEND
PROJECT SITE CONTROL SUMMARY TABLE
POINT #
NORTHING
1659123.67
1659029.71
1656868.25
1656350.60
EASTING
3186828.66
3186900.48
3186781.07
3186830.93
ELEVATION
5647.4
5648.3
5566.4
5563.1
DESCRIPTION
MAG CENTERED CAP 2.5" STEEL PIPE IN LOCKBOX
3.5" BC US ARMY CORPS ENGINEERS SURVEY STATION R-4-4
SET #5 REBAR W/ GREEN PLASTIC CAP (SITE BENCHMARK)
SET #5 REBAR W/ GREEN PLASTIC CAP
5566.41
CMH
JAY
CRV
G-3
8/28/2026
SITE PLAN
GENERAL
PL
O
TT
ED
: 8 /2
8/
0:
:1
AM
N
AM
E:
P :\2
PR
O
JE
C
TS
\2
5-
4.
N O
R
TH
C O
N N
EC
TO
R P
ED
ES
TR
IA
N B
R
ID
G E
R
EP
LA
C
EM
EN
T
- C
PW
\C
AD
\D
R
AW
IN
G
S\
-1
.0 1_
SI
TE
P
LA
N .D
W G
500'250'0'
USACE RESERVOIR STORAGE ZONES
ZONE NAME ELEVATION RANGE*
MULTIPURPOSE POOL 5504.0 - 5550.0
FLOOD CONTROL POOL 5550.0 - 5598.0
MAXIMUM POOL 5598.0 - 5648.0
* ALL ELEVATIONS IN LOCAL PROJECT DATUM
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
X
X
X X
X X
X X w w w w w w w w w w w w w w
E . L ake V iew
R d.
C he rry C re ek
Shop Creek
55 5
5555 55
PEDESTRIAN BRIDGE. SEE
DETAILS ON DWG. S-1 to S-6
BRIDGE ABUTMENT PROTECTION,
TYPE H VOID-FILLED RIPRAP. SEE
DETAIL ON DWG. C-2
BORROW AREA,
165 CY
WEST SITE ACCESS VIA
PIPELINE TRAIL AND
WETLAND LOOP TRAIL
REMOVE AND REPLACE 23 SY OF
CONCRETE TRAIL DAMAGED
DURING CONSTRUCTION
LIMITS OF CONSTRUCTION, TYP.
Existing Wetlands, Typ.
Existing Wooden Fence
Stream Monitoring Station
PROTECT
BRIDGE ABUTMENT PROTECTION,
TYPE H VOID-FILLED RIPRAP. SEE
DETAIL ON DWG. C-2
CLASS 6 AGGREGATE BASE COURSE
TRAIL. SEE DETAIL ON DWG. C-3
Existing Ordinary High Water Mark, Typ.
Existing Trail, Typ. Existing Wooden Fence
STAGING AREA
0+
1+00
2+00
3+
4+00
5+
5+
6:1
6:1
6:1
6:1
Existing Concrete Trail
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
50'25'0'
CMH
JAY
CRV
C-1
8/28/2026
GRADING PLAN
CIVIL
NOTE:
1. SEE DWG. G-2 FOR USACE SECTION 408 CUT/FILL BALANCE TABLE
X
X
X
X
X
X
C he rr y
C re ek
Existing Crusher Fines Trail
Stream Monitoring Station
PROTECT
Existing Wetlands, Typ.
North Connector Trail
LIMITS OF CONSTRUCTION
CLASS 6 AGGREGATE BASE COURSE
TRAIL. SEE DETAIL ON DWG. C-4
ABUTMENT PROTECTION
TYPE H VOID-FILLED RIPRAP,
BURIED WITH 4" TOPSOIL
SEE NOTE 2
ABUTMENT PROTECTION
TYPE H VOID-FILLED RIPRAP,
BURIED WITH 4" TOPSOIL
SEE NOTE 2
1.1
1.10
1.2
1.9
1.4
1.7
1.5 1.6
1.23
1.22
1.24
1.21
PEDESTRIAN BRIDGE. SEE
DETAILS ON DWG. S-1 TO S-6
0+
1+
2+
3+
0+
1+
2+
3+ 001.26
1.19
5557 5558 5558
1.3
1.8
1.11 1.12
1.13
1.14
1.15
1.16 1.17
1.18
1.20 1.25
A A
TRAIL APPROACH SECTION,
SEE DETAIL DWG. C-4
CONTROL POINT NO. (TYP.)
ABUTMENT GRADING TIE-IN
WITH EXISTING GRADE
6' ADDITIONAL RIPRAP TO PROTECT
ABUTMENT FROM SCOURING
1.271.28
1.29
1.30
1.31 1.32
HORZ SCALE: 1"=10'
VERT SCALE: 1"=5'
RIPRAP ABUTMENT PROTECTION SECTION
0+00 0+50 1+00 1+50 2+00 2+50 2+80
Existing Ground
5% MAXFINAL GRADE
CLASS 6 AGGREGATE BASE COURSE TRAIL,
TYP. BOTH SIDES. SEE DETAIL ON DWG. C-4
TYPE H VOID-FILLED RIPRAP, 3' THICKTYPE H VOID-FILLED RIPRAP, 3' THICK
PEDESTRIAN BRIDGE. SEE
DETAILS ON DWG. S-1 TO S-6
5% MAX
BRIDGE ABUTMENT
(TYP. BOTH SIDES)
4" TOPSOIL ABOVE RIPRAP
OUTSIDE TRAIL EXTENTS
TRANSITION DEPTH OF RIPRAP FROM 3' - 4"
TO BOTTOM OF ABUTMENT OVER 2',
TYP. BOTH SIDES
100-YR
WSEL = 5559.410-YR
WSEL = 5557.1
RIPRAP ABUTMENT PROTECTION CONTROL POINT TABLE
POINT NO.
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
TOP OF RIPRAP EL.
5554.78
5554.87
5554.98
5555.10
5555.20
5555.24
5554.84
5554.85
FINAL GRADE EL. NORTHING
1656184.57
1656200.68
1656236.16
1656251.25
1656209.91
1656225.00
1656188.97
1656181.14
EASTING
3186336.31
3186353.84
3186377.48
3186393.49
3186402.94
3186419.03
3186361.00
3186338.63
RIPRAP ABUTMENT PROTECTION CONTROL POINT TABLE
POINT NO.
1.9
1.10
1.11
1.12
1.13
1.14
1.15
1.16
TOP OF RIPRAP EL.
5554.96
5554.89
5555.25
5555.30
5557.29
5557.20
5557.92
5558.00
FINAL GRADE EL. NORTHING
1656176.96
1656184.60
1656205.58
1656220.66
1656206.21
1656210.60
1656225.50
1656221.09
EASTING
3186342.57
3186365.07
3186407.10
3186423.11
3186376.32
3186372.24
3186388.43
3186392.48
RIPRAP ABUTMENT PROTECTION CONTROL POINT TABLE
POINT NO.
1.17
1.18
1.19
1.20
1.21
1.22
1.23
1.24
TOP OF RIPRAP EL.
5558.00
5557.93
5557.20
5557.29
5555.05
5555.27
5555.56
5556.10
FINAL GRADE EL. NORTHING
1656303.67
1656308.05
1656324.12
1656319.81
1656305.11
1656320.18
1656329.96
1656339.73
EASTING
3186480.46
3186476.35
3186493.47
3186497.64
3186449.55
3186465.56
3186488.04
3186510.52
RIPRAP ABUTMENT PROTECTION CONTROL POINT TABLE
POINT NO.
1.25
1.26
1.27
1.28
1.29
1.30
1.31
1.32
TOP OF RIPRAP EL.
5556.20
5555.92
5555.74
5555.55
5556.28
5556.04
5555.83
5555.65
FINAL GRADE EL. NORTHING
1656335.26
1656314.03
1656292.80
1656277.88
1656330.75
1656311.54
1656288.40
1656273.44
EASTING
3186514.52
3186502.95
3186491.37
3186475.27
3186518.54
3186507.95
3186495.45
3186479.29
5555.11
5555.20
5555.32
5555.43
5555.53
5555.58
5555.17 5558.26
5557.22
5557.27
5555.63
5555.59
5555.22
5555.29 5558.33
5558.26
5557.22
5557.28
5555.39
5555.60
5555.89
5556.61
5555.89
5556.08
5556.25
5556.54
5555.18 5558.33 5556.43 5555.99
5556.37
5556.17
PL
O
TT
ED
: 8 /2
8/
0:
:5
AM
N
AM
E:
P :\2
PR
O
JE
C
TS
\2
5-
4.
N O
R
TH
C O
N N
EC
TO
R P
ED
ES
TR
IA
N B
R
ID
G E
R
EP
LA
C
EM
EN
T
- C
PW
\C
AD
\D
R
AW
IN
G
S\
-1
.0 1_
BR
ID
G E
PR
O
TE
C
TI
O
N D
ET
AI
L.
D
W G
RIPRAP ABUTMENT PROTECTION PLAN
20'10'0'
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
CMH
JAY
CRV
C-2
8/28/2026
RIPRAP ABUTMENT PROTECTION DETAIL
CIVIL
NOTE:
1. BURIED VOID-FILLED RIPRAP TO BE PLACED 4" BELOW FINAL GRADE. COVERED WITH 4" TOPSOIL.
2. VOID-FILLED RIPRAP SHALL BE MIXED AND PLACED PER THE SPECIFICATION PROVIDED IN THE
SPECIAL CONDITIONS INCLUDING WASHING A 50/50 MIXTURE OF TYPE 2 BEDDING AND PIT RUN MATERIALS INTO THE VOIDS AND COMPACTION BY TRACKING OVER THE VOID-FILLED RIPRAP TO
ENSURE ALL VOIDS ARE FILLED TO PREVENT FUTURE SETTLEMENT OF THE CRUSHER FINES
TRAIL MATERIAL AND TOPSOIL PLACED OVER THE TOP.
HORZ SCALE: 1"=5'
VERT SCALE: 1"=1'
TRAIL PROFILE
0+00 1+00 2+00 3+00 4+00 5+00 5+20
Existing Ground
FINAL GRADE
TRANSITION FROM PROPOSED
BRIDGE TO EXISTING TRAIL
WITH CRUSHER FINES
CLASS 6 AGGREGATE BASE COURSE
TRAIL. SEE DETAIL ON DWG. C-4
TYPE H VOID-FILLED RIPRAP, 3' THICK
TYPE H VOID-FILLED RIPRAP, 3' THICK
PEDESTRIAN BRIDGE. SEE
DETAILS ON DWG. S-1 TO S-6
TR
AI
L
ST
AR
T
ST
A.
+1
R
IP
R
AP
E N
D
ST
A.
+5
TR
AI
L
EN
D
ST
A.
+7
BR
ID
G E
ST
AR
T
ST
A.
+0
BR
ID
G E
EN
D
ST
A.
+0
4" TOPSOIL OVER RIPRAP
OUTSIDE OF TRAIL EXTENTS
10-YR
WSEL = 5557.1
100-YR
WSEL = 5559.4
X X
X X
X X
X X
X X
X
C he rr y
C re ek
Shop Creek
Existing Wetlands, Typ.
Existing Wooden Fence
REMOVE
Stream Monitoring Station
PROTECT
Existing Ordinary High Water Mark, Typ.
Existing Crusher Fines Trail
PEDESTRIAN BRIDGE. SEE
DETAILS ON DWG. ---- to ----
BRIDGE ABUTMENT PROTECTION,
TYPE H VOID-FILLED RIPRAP. SEE
DETAIL ON DWG. C-2
WEST SITE ACCESS VIA
PIPELINE TRAIL AND
WETLAND LOOP TRAIL
LIMITS OF CONSTRUCTION, TYP.
BRIDGE ABUTMENT PROTECTION,
TYPE H VOID-FILLED RIPRAP. SEE
DETAIL ON DWG. C-2
CLASS 6 AGGREGATE BASE COURSE
TRAIL, SEE SECTION DWG. C-4
0+
1+00
2+00
3+
4+
5+
5+
0+
1+00
2+00
3+
4+
5+
5+
TRAIL TO DRAIN
TO NORTH, TYP.
2.1
2.2
2.3
2.4
2.5
2.6 2.7
2.8 2.9
2.10
2.11
2.12
2.13
MATCH EXISTING TRAIL
MATCH EXISTING TRAIL
Existing Crusher Fines Trail
Trail Horizontal Control Line
DESIGN POINT TABLE
POINT NO.
2.1
2.2
2.3
2.4
2.5
ELEVATION
5555.11
5556.19
5557.13
5558.27
5558.28
NORTHING
1656182.70
1656194.06
1656207.20
1656223.38
1656305.86
EASTING
3186337.57
3186357.27
3186372.97
3186390.43
3186478.40
DESIGN POINT TABLE
POINT NO.
2.6
2.7
2.8
2.9
2.10
ELEVATION
5556.41
5556.73
5557.18
5557.92
5558.31
NORTHING
1656334.93
1656345.38
1656349.07
1656347.08
1656344.05
EASTING
3186509.36
3186528.48
3186549.91
3186603.41
3186620.10
DESIGN POINT TABLE
POINT NO.
2.11
2.12
2.13
ELEVATION
5558.68
5559.54
5559.62
NORTHING
1656337.89
1656319.67
1656293.53
EASTING
3186635.92
3186669.08
3186716.70
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
40'20'0'
CMH
JAY
CRV
C-3
8/28/2026
TRAIL PLAN AND PROFILE
CIVIL
PL
O
TT
ED
: 8 /2
8/
0:
:2
AM
N
AM
E:
P :\2
PR
O
JE
C
TS
\2
5-
4.
N O
R
TH
C O
N N
EC
TO
R P
ED
ES
TR
IA
N B
R
ID
G E
R
EP
LA
C
EM
EN
T
- C
PW
\C
AD
\D
R
AW
IN
G
S\
-1
.0 1_
TR
AI
L
PN
P.
D
W
G TRAIL PLAN
HORZ SCALE: 1"=5'
VERT SCALE: 1"=5'
TRAIL APPROACH SECTION
0+00 0+10 0+20 0+30 0+40 0+50
4'-0"
FINAL GRADE
4" TOPSOIL OVER
VOID-FILLED RIPRAP, TYP.
TYPE H VOID-FILLED RIPRAP, 3' THICK
SEE NOTE 2 ON DWG. C-2 FOR
DIRECTION REGARDING INSTALLATION
Existing Ground
CLASS 6 AGGREGATE BASE COURSE TRAIL
(SEE DETAIL THIS SHEET)
1' SHOULDER ALONG TRAIL,
TYP. BOTH SIDES
6'-0"
ADDITIONAL RIPRAP PROTECTION
ALONG UPSTREAM SIDE OF
ABUTMENT TO PREVENT SCOUR
2%
RIPRAP CONTROL POINT, TYP.
SEE TABLE ON DWG. C-2 FOR
NORTHING. EASTING AND ELEVATION
2%
4'-0" 2'-0" VARIES
TIE-IN TO EXISTING
GRADES AT 3:1
CLASS 6 AGGREGATE BASE
COURSE TRAIL, 5% MAX
RUNNING SLOPE
4"
0%
CLASS 6 AGGREGATE BASE COURSE TRAIL
(LOOKING EAST)
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
2'1'0'
CMH
JAY
CRV
C-4
8/28/2026
MISC DETAILS
CIVIL
PL
O
TT
ED
: 8 /2
8/
1:
:3
AM
N
AM
E:
P :\2
PR
O
JE
C
TS
\2
5-
4.
N O
R
TH
C O
N N
EC
TO
R P
ED
ES
TR
IA
N B
R
ID
G E
R
EP
LA
C
EM
EN
T
- C
PW
\C
AD
\D
R
AW
IN
G
S\
-1
.0 1_
TR
AI
L
PN
P.
D
W G
A
PROJECT NO. 25-104.01
DRAWING NO.
SHEET NO.
OF
SHEET REVISIONS
NO. DATE DESCRIPTION BY
PREPARED UNDER
THE SUPERVISION OF
DATEDESIGNED:
DRAWN:
CHECKED:
90% DESIGN
NORTH CONNECTOR BRIDGE REPLACEMENT
STRUCTURAL NOTES:
1. ALL WORK SHALL BE DONE IS ACCORDANCE WITH THE COLORADO DEPARTMENT OF TRANSPORTATION (CDOT)
2025 STANDARD SPECIFICATION FOR ROAD AND BRIDGE CONSTRUCTION, AS APPLICABLE TO THE PROJECT, AS
MODIFIED BY THE PROJECT SPECIFICATIONS AND THESE PLANS.
2. REFERENCE THE TRAIL CIVIL DRAWINGS FOR HORIZONTAL AND VERTICAL CONTROL INFORMATION.
3. STRUCTURE EXCAVATION AND BACKFILL SHALL BE AS SHOWN ON THE ABUTMENT DETAIL SHEET.
4. THE SOILS AND FOUNDATION INVESTIGATION WAS PERFORMED BY CTL THOMPSON INC. THE SUBSURFACE CONDITIONS AND RECOMMENDATIONS ARE CONTAINED IN A REPORT DATED 07/09/2026, PROJECT NO
DN52,903.000-125-R1.
5. EXPANSION JOINT MATERIAL SHALL MEET AASHTO SPECIFICATION M213.
6. COVERAGE FROM THE FACE OF CONCRETE TO THE OUTSIDE OF REINFORCEMENT SHALL BE 2 INCHES, UNLESS
NOTED OTHERWISE.
7. GRADE 60 REINFORCING STEEL IS REQUIRED.
8. ALL REINFORCING STEEL SHALL BE BLACK UNCOATED REINFORCING UNLESS NOTED OTHERWISE.
9. E DENOTES EPOXY COATED REINFORCING STEEL.
10. THE FOLLOWING TABLE GIVES THE MINIMUM CLASS B LAP SPLICE LENGTH FOR EPOXY COATED REINFORCING BARS PLACED IN ACCORDANCE WITH SUBSECTION 602.06. THESE SPLICE LENGTHS SHALL BE INCREASED BY
25% FOR BARS SPACED AT LESS THAN 6" ON CENTER.
11. WHEN THE CONTRACTOR ELECTS TO SUBSTITUTE EPOXY COATED REINFORCEMENT FOR BLACK REINFORCING
BARS, THE MINIMUM LAP SPLICE SHALL BE AS DESCRIBED ABOVE.
12. THE FOLLOWING TABLE GIVES THE MINIMUM CLASS B LAP SPLICE LENGTH FOR BLACK REINFORCING BARS PLACED IN ACCORDANCE WITH SUBSECTION 602.06. THESE SPLICE LENGTHS SHALL BE INCREASED BY 25% FOR
BARS SPACED AT LESS THAN 6" ON CENTER.
13. ALL CONCRETE SHALL BE CDOT CLASS DF, f'c = 4,500 psi, UNLESS NOTED OTHERWISE.
14. STRUCTURAL CONCRETE SHALL CONFORM TO CEMENTIOUS MATERIALS REQUIREMENT CLASS 0, CORRESPONDING TO SULFATE RESISTANCE CLASS 0.
15. EXPOSED OUTSIDE CORNERS SHALL RECEIVE A 34" CHAMFER, UNLESS NOTED OTHERWISE.
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE DURING CONSTRUCTION.
IN NO CASE SHALL STRUCTURES BE BACKFILLED UNTIL ALL MEMBERS HAVE REACHED 80% OF DESIGN
STRENGTH.
17. THE INFORMATION SHOWN ON THESE PLANS CONCERNING THE TYPE AND LOCATION OF UNDERGROUND UTILITIES IS NOT GUARANTEED TO BE ACCURATE OR ALL INCLUSIVE. THE CONTRACTOR IS RESPONSIBLE FOR MAKING HIS OWN DETERMINATION AS TO THE TYPE AND LOCATION OF UNDERGROUND UTILITIES AS MAY BE NECESSARY TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT THE UTILITY NOTIFICATION CENTER AT 811 AT LEAST 2 DAYS (NOT INCLUDING THE DAY OF NOTIFICATION) PRIOR TO ANY EXCAVATION OR
OTHER EARTHWORK.
BAR SIZE #4 #5 #6 #7 #8 #9 #10 #11
SPLICE LENGTH FOR
CONCRETE CLASS DF 1'-10" 2'-3" 3'-4" 3'-11" 4'-5" 5'-6" 6'-10" 8'-2"
BAR SIZE #4 #5 #6 #7 #8 #9 #10 #11
SPLICE LENGTH FOR
CONCRETE CLASS DF 1'-6" 1'-11" 2'-3" 2'-7" 3'-0" 3'-8" 4'-7" 5'-5"
ABBREVIATIONS:
EF = EACH FACE
BO = BOTTOM OF
TO = TOP OF
BRG = BEARING
BF = BACK FACE
OC = ON CENTER
TOW = TOP OF WALL
FF = FRONT FACE
CONCRETE FINISH NOTES:
1. EXPOSED CONCRETE FACES SHALL RECEIVE A CLASS 2 RUBBED FINISH PER SECTION 601.14 OF THE CDOT
STANDARD SPECIFICATIONS.
2. ALL OTHER CONCRETE SURFACES SHALL RECEIVE A CLASS 1, ORDINARY SURFACE FINISH PER SECTION 601.14.
3. COST FOR SURFACE FINISH SHALL BE INCLUDED IN THE COST FOR ITEM 601: CONCRETE CLASS DF.
4. DECK AND APPROACH SLAB CONCRETE SHALL BE FINISHED WITH A LIGHT TRANSVERSE BROOM UNLESS
OTHERWISE SPECIFIED BY THE OWNER.
DESIGN DATA:
AASHTO LRFD GUIDE SPECIFICATIONS FOR THE DESIGN OF PEDESTRIAN BRIDGES,
2ND EDITION (2016 INTERIM)
AASHTO LRFD BRIDGE DESIGN SPECIFICATIONS 2024 (10TH EDITION)
DESIGN METHOD: LOAD AND RESISTANCE FACTOR DESIGN
PEDESTRIAN LIVE LOAD: 90 PSF
VEHICULAR LIVE LOAD: H5 TRUCK
WIND LOAD: BASE WIND SPEED: 115 MPH (3 SEC GUST)
STREAM LOAD:
10 YEAR: V = 5.0 ft/s, APPLIED IN STRENGTH I LC 100 YEAR: V = 5.3 ft/s, APPLIED IN EXTREME II LC
REINFORCED CONCRETE:
CLASS DF CONCRETE: f'c = 4,500 psi REINFORCING STEEL: fy = 60,000 psi
SOILS DATA:
EQUIV. FLUID PRESSURE: 55 pcf (AT-REST)
BRIDGE SUPERSTRUCTURE REACTIONS (SERVICE LEVEL, ASSUMED):
DEAD LOAD: 32.2 KIPS/ABUT
LIVE LOAD: 27.8 KIPS/ABUT
BRIDGE NOTES:
1. BRIDGE SHALL BE SINGLE (CLEAR) SPAN PREFABRICATED WEATHERING STEEL TRUSS, PER THE PLANS AND
SPECIFICATIONS.
2. CONSTANT DEPTH PRATT PONY HALF-THROUGH TRUSSES SHALL BE THE MAIN LOAD CARRYING MEMBERS.
THE VERTICAL WEB MEMBERS AT THE ENDS OF THE BRIDGE SHALL BE PLUMB.
SHEET INDEX:
S-1 GENERAL NOTES
S-2 GENERAL LAYOUT
S-3 ABUTMENT 1 LAYOUT
S-4 ABUTMENT 2 LAYOUT
S-5 DRILLED SHAFT DETAILS
S-6 ABUTMENT DETAILS
ENGINEERING
REVIEWED BY:
DATE
PLANNING
REVIEWED BY:
DATE
APPROVED BY:
DATE
PROJECT #
AMJ
ASP
BRS
S-1
8/28/2026
GENERAL NOTES
STRUCTURAL
DRILLED SHAFT NOTES:
1. THE CONTRACTOR SHALL FOLLOW THE FOLLOWING STEPS FOR CAISSON CONSTRUCTION
a. DRILL A SOUNDING HOLE AT EACH ABUTMENT PRIOR TO CONSTRUCTION. BE PREPARED TO
ADVANCE THE SOUNDING HOLE TO BEDROCK. THE CONTRACTOR IS RESPONSIBLE FOR
PROVIDING A LICENSED GEOTECHNICAL ENGINEER TO OBSERVE THE SOUNDING AND RECORD
THE DEPTH OF BEDROCK.
b. REPORT BEDROCK DEPTHS TO THE ENGINEER. ALLOW 2 WEEKS OF REVIEW TIME. THE
ENGINEER WILL PROVIDE UPDATED PILE TIP ELEVATIONS FOR CONSTRUCTION.
c. ORDER REINFORCEMENT CAGES FOR DRILLED SHAFTS AND PROVIDE SHOP DRAWING
SUBMITTAL TO THE ENGINEER FOR REVIEW.
d. FABRICATE THE REINFORCING CAGES.
e. CONSTRUCT DRILLED SHAFT FOUNDATIONS BASED ON THE PLANS AND UPDATED TIP
ELEVATIONS.
2. THE BORING IN THE GEOTECHNICAL REPORT IS LOCATED APPROXIMATELY 226 FEET NORTHWEST OF
ABUTMENT 2. BEDROCK WAS FOUND AT APPROXIMATELY 17 FEET BELOW GRADE. PREVIOUS
INVESTIGATIONS INDICATE POTENTIAL FOR BEDROCK AT BRIDGE LOCATION APPROXIMATELY 40 FEET BELOW GRADE. SEE BEDROCK SOUNDING DETAIL (DWG NO S-5) AND PROJECT SPECIFICATIONS FOR GEOTECHNICIAL INVESTIGATION AND VERIFICATION TO BE PERFORMED BY THE CONTRACTOR PRIOR TO
CONSTRUCTION OF DRILLED SHAFTS.
3. PRESENCE OF HIGH GROUNDWATER AND SOFT, SLOUGHING SOIL CONDITIONS WERE NOTED DURING GEOTECHNICAL INVESTIGATION. TEMPORARY CASING WILL BE REQUIRED TO SUPPORT THE EXCAVATION WHERE THE GROUND WATER EXISTS AND/OR WHERE HOLES ARE UNSTABLE DUE TO SOIL CONDITIONS.
DURING DRILLING OPERATIONS, GROUNDWATER WAS ENCOUNTERED AT APPROXIMATE ELEVATION
5549.00 TO 5552.50.
4. CONCRETE SHALL NOT BE PLACED BY FREE FALL METHODS IN MORE THAN 3 INCHES OF WATER. PUMPING THE CONCRETE FROM THE BOTTOM OF THE PIER IS REQUIRED BY A TREMIE PIPE TO DISPLACE WATER.
5. ALL CONCRETE SHALL BE CLASS BZ
6. DRILLED SHAFT REINFORCEMENT SHALL BE NON-EPOXY COATED.
7. DRILLED SHAFT SHALL BE CONSTRUCTED IN ACCORDANCE WITH CDOT SECTION 503. PAYMENT FOR DRILLED SHAFT (LF) INCLUDES ALL MATERIALS (INCLUDING TEMPORARY CASING) AND WORK NECESSARY
TO CONSTRUCT THE DRILLED SHAFT.
8. THE CONTRACTOR SHALL COORDINATE AND PROVIDE ON-SITE OBSERVATION OF THE DRILLING BY A
QUALIFIED GEOTECHNICAL ENGINEER.
9. CONCRETE FOR EACH DRILLED SHAFT SHOULD BE FORMED TO MAINTAIN UNIFORM DIAMETER AT THE
TOP OF THE PIER.
10. DRILLED SHAFTS SHALL EXTEND AT LEAST TO THE MINIMUM TIP ELEVATION. DRILLED SHAFTS SHALL BE FURTHER ADVANCED INTO BEDROCK IF NECESSARY TO OBTAIN THE SPECIFIED MINIMUM EMBEDMENT.
11. THE HORIZONTAL TOLERANCE FOR CENTROID OF DRILLED SHAFT FOR THIS PROJECT SHALL BE +/- 2
INCHES.