Salient Characteristics

Salient requirements for the UPS/Battery Back-up include:

· CyberPower PR1500LCDRT2U 1350 Watts, 1500 VA UPS or equivalent

· Salient requirements:

· Input

· International Version: 120V

· Input Voltage Range: 80 - 150 V

· Input Frequency: 47Hz - 63Hz (auto-sensing)

· Input Connection: NEMA 5-15P

· Output

· VA Rating: 1500 VA (Volt-ampere)

· Watts: ≥1350 Watts or higher

· Output Voltage: 120Vac +/- 5%

· Output Frequency: 60Hz

· Outlets: ≥4

· Outlet Type: ≥4 x NEMA 5-15R

· Battery

· Battery Run Time: At Half Load (min): ≥11; At Full Load (min): ≥4

· Battery Recharge Time: Less than 6 Hours (90% charged)

· Battery Replaceable: Yes

· Specifications

· Alarms: On Battery, Low Battery, Overload

· Approvals: UL1778, CSA C22.2 NO.107.3, FCC DOC Class A

· Surge Protection

· Surge Energy Rating: ≥2060 Joules

· Protection: Internal circuitry limiting / circuit breaker

· Physical Specifications

· Rackmountable: 2U

· Weight: ≤56 lbs.

· Dimensions: 3.50" x 17.25" x 15.75" (H x W x D)

· Mountable vertically or horizontally