FRC52.pdf
PDF 116 KB Posted
- Attached to
- Chiller Replacement Federal contract opportunity
- Solicitation number
- HSFE10-15-B-0001
About this file
Attachment A. to SF1442 Section J.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Chiller_Bid_Questions.txt | TXT text file | |
| Chiller_replacement_SOW.doc | DOC document | |
| Interested_Vendor_List.pdf | ||
| valve_photos.pdf | ||
| lower_floor_Evac_Route_2015.pdf | ||
| Updated_Chiller_replacement_SOW.doc | DOC document | |
| Questions_Chiller_Project.doc | DOC document | |
| top_floor_Evac_Route_2015.pdf | ||
| Chiller_SF1442.docx | DOCX document | |
| 52_of_65.JPG | JPG image | |
| Chiller_Wage_Determination.pdf | ||
| lower_floor_8_5x11.pdf | ||
| Chiller_replacement_SOW.doc | DOC document | |
| Chiller_SF1442.docx | DOCX document |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5 4 3 2 1
D
C
B
A
5 4 3 2 1
A
B
C
D
BOTHELL WASHINGTON
REGION EIGHT OCD
FEDERAL REGIONAL CENTER
EQUIPMENT ROOM PLAN AND DETAILS
DSGN. BY: DR. BY: CK BY:
PREPARED:
REVIEWED:
SUBMITTED:
CHIEF, SPECS. & REVIEW SECT.
CH. MIL. PROJ. & CIV. DEF. SECT.
RECOMMENDED:
CH. DESIGN BRANCH
U.S. ARMY ENGINEER DISTRICT, SEATTLE
CORPS OF ENGINEERS, SEATTLE, WAOMAHA, NEBRASKA
OMAHA DISTRICT, CORPS OF ENGINEERS
APPROVED FOR THE DISTRICT ENGINEER:
CHIEF ENGINEERING DIVISION
DATE:
SPEC. NO.:SCALE: AS SHOWN
DRAWING NUMBER
SHEET 52
60-02-01AS BUILT
District File No. 127 S/60-02-01WA 0880 KB
REVISIONS
SYMBOL DESCRIPTION DATE APPROVAL
A (1)REVISED EMERGENCY SEWER PIT. (2)REVISED NOTE. (3)ADDED
CONTRACT NO. 67-0064
17 MAY 67
OF 65
8 JUN 67
J.H.W. G.D.D. H.L.W.
NOTE: (4)CHANGED WORD. (5)ADDED NOTE
B (1)ADDED GRD JUMPER ACROSS NEOPRENE SECTION. (2)ADDED 22 APR 68
GRD FOR DIESEL EXHAUST STACK.
(1)NOTED 3/4" VALVE IN RISER (2)IN 3" WST. LINE ADDED GATE & CHK. VALVE
(3) IN 4" W. SER. LINE. ADDED PRV. & CHK. VALVE. (4)HATCHED 1 1/2"W.
INDICATED "ABANDONDED"(5) ADDED 3" PLUG V. IN LINE TAPPING FROM
MAKE-UP TO 3" WSTE. DR. & PROVIDED PRV W/BY PASS ABOUT VALVE(6)ADDED
CIRC. PUMP IN BY-PASS CIRCUIT & TAPPED INTO WATER S. & R. LINES TO
COOLING TWR.(7)ADDED FLOAT CONTROL W. FEEDER TO 180 GAL. SUMP
TANK W/BYPASS(8)ADDED EVAP. W. SUMP TNK DRAIN & OVERFLOW W/VALVES
(9) ADDED 3/4" VALVE - ALL AS BUILT 17 FEB 69
C
SECTION
EMERGENCY
SEWER PIT
12" 0 2' 4' 6'
SCALE: 3/8 INCH = 1 FOOT
NEW 4"
TO METER PIT
SEE SH.3
TO HOSE BIBBS
LAWN FAUCET
NEAR RECEPTION
BUILDING
3/4" GATE VALVE IN RISER
METER
620 GAL.
HYDRO-PNEU. STOR.
TANK
PIPE PRESSURE
RELIEF TO 6" ABOVE
FLOOR
FIRE WATER
STORAGE TANK
2500 GAL.
TO WASTE AREA
AT SE CORNER
OF SITE-SEE SH. 3
HEATER
H.W.
80 GAL.
AIR COMP.
DIESEL START
STORAGE TANK
BLAST VALVE AIR
FROM W. SERV. WELL P-9
SUPPLY SOURCE
BLAST VALVES EST. WT. OF
GOV'T. FURNISHED
HEAVIEST PART 400LBS.
TOTAL ASS'M. WT. 1400LBS.
BLAST VALVES
EC1
TYPICAL WALL PENETRATION
NO SCALE
BITUMASTIC
OAKUM
EXTRA HEAVY STEEL PIPE
SLEEVE THREADED BOTH
ENDS FOR FLANGES
FOR 2 STUDS PER
EA. SIDE-TAP & TH'D
EXTRA HEAVY FLANGES
FLANGE
EA. SIDE
HOT LEAD
POURED &
CAULKED
DIESEL EXHAUST STACK
NO SCALE
WATERSTOP
CEILING
18" SLEEVE
12" DBL EXTRA STRONG PIPE
BLOCK INSULATION
SILICATE SEGMENTED
2 1/2" CALCIUM
WELD OF BRAZE #2(MIN)
CU TO FLANGE AND SLEEVE
CONNECT TO BLDG. GRD.
PLAN
BLIND FLANGE
6" TEES
ADAPTER PLASTIC TO C.I. PIPE
6" C.I. PIPE TO 5' OUTSIDE BLDG.
2"X2"X1/4"
2"X3/4" REDUCER
6" BLIND FLANGE
3/4" GATE VALVE
6" TEE
3/4" CAP
6" PLUG VALVE
INV. EL. 430.417
FLOOR SLAB
CAST IRON
PIPE SUPPORTS
2"X11" REDUCING FLANGE
3/4"X1/8" BAR SIZE, SPACED 1 3/16"X4"
OPEN STEEL GRATING IN 2'
PANELS 3'-0" LONG
SLEEVE DIAMETER
THROUGH WALL,
INCHES
DIA. OF PIPE DIA. OF REQUIRED
SLEEVE
INCHES
1/2 -1
1 1/4 - 1 1/2
2 - 2 1/2
SEE PIT DETAIL
THIS SHEET
A
AA
A A
G A S
D R
IV
E
EL
EC
TR
IC
D
R
IV
E
SWITCHGEAR
WATER CHILLER
WATER CHILLER
A
A
HOSE
BIBB
3/4" VALVE
F 3 F 3
M. O. DAMPERS TO LAWN FAUCETS ON
SOUTH SIDE OF FRC
LOCATION SHOWN ON
SHEET 7
BLAST VALVES
F 1BLAST VALVE AIR
STORAGE TANK
11 cu. ft. nom. BOTH
TANKS EQUIPPED WITH
GLOBE VALVE DRAIN.
3/4"
3/4"
ELECTRIC
AIR COMPRESSOR
ENGINE DRIVEN
AIR COMPRESSOR
3"
G F
1C
N
1 1/4"
2 1/2" 1 1/2"
3/4"
FIRE PUMP
2"
RECIRC.
PUMP
1 1/2" PRV.
1 1/2" CHK.
SEE SHT. 53
RVSN.
1" 2C 3C
A
3" 1 1/2"
ABANDONED
4C
2 1/2"
1 1/2"
1"
RA FAN #1
2"
E
D
IE
SE
L G
EN
ER
A
TO
R
G
EN
ER
A
TO
R D
IE
SE
L
5C
5CP.R.V. 70 GPM. AT 50 PSIG.
3" PLUG N
TO BLAST VALVE
AIR RECEIVER
CAP
3"
P-6 3"
D
CIRC. PUMP
3" 4"
CIRC.PUMP (CHILLER-BY-PASS)
SEE SHT. 53
EXP. TANK BY-PASS
1"
MAKE UP
MANUAL
180 GAL. REMOTE
SUMP TANK
6C
7C
WATER
FEEDER
OVER FLOW
EXP. TANK
TO DR.
8C
C
A
9C
B A
1"Ø U-BOLT
PIPE SUPPORT 4'O.C.
EXHAUST PIPE
SIZE DETERMINED
BY ENGINE MFR.
ADJ. PIPE
SADDLE SUPPORT
SPLIT STEEL
ESCUTCHEAN
WELD TO
PIPE
1" DRAIN
TERMINATE @ EL. 475.75FLAP
VALVE
15"[ 50.0
5 X 1/2 X 1'-4"
1" Ø ANCHOR
3/4" Ø ANCHOR
12" [ 25.0
MECHANICAL ROOM PLAN
SCALE: 1/4 INCH = 1 FOOT
5'012"
TO SECOND
ENGINE
ENGINE MOUNTED
STARTER CONTROL
VALVE
AIR RELAY VALVE
AIR STARTER
1/4"
1/4"
1/4"
1" 1"
DRAIN
DEISEL START
AIR COMPRESSOR
NO SCALE
3A
1B
5A
2A
4A
NOTE: THIS DETAIL IS TYPICAL FOR
NON-EXPENDIBLE CONNECTIONS
(FUEL, WELL WATER, EMERG. SEWER)
PROVIDE NEOPRENE GASKET
ALLOW FOR 5" DIFFERENTIAL
MOTION.
WELD OR BRAZE
#2/O CU.
SEE TYP.
WALL PENE-
TRATION DET.
42" Ø CMP-10 USS GAGE,
EXCEPT AT WELL STRUCTURE, 48" Ø
1/4" OVER END
OF CMP. DO
NOT WELD
NEOPRENE FLEX.
HOSE
MASTIC SEAL
2-2X2X1/4
HOOPS
ACCESS HOLE DETAILS
SHOWN ON SHEET 31.
TYP. ARRANGEMENT OF
PIPE SLEEVE AND MANHOLE
EXCEPT FOR WELL STRUCTURE.
VIEW ABOVE IS INSIDE
OF FRC BLDG. LOOKING OUT.
SIZE OF FLANGE DETERMINED
BY PENETRATION WALL
42" CMP 10 USS GAGE
ACCESS HOLE
20" DIA.
FLANGE-30" DIA.
HORIZ.
OF CMP
ELEVATION EXTERIOR FLEXIBLE CONNECTIONS
SCALE: 1/2" INCH = 1 FOOT
12" 0 2'1' 3' 4'
16"
5 1/2"
CL
5'-0"
6"
NEOPRENE GASKET
PL
10 5/8"
1' 6"
6" 6"
2B
6'-0"
1A
PL
PL
4' 0"
Model