Additional Chiller Bid Questions
Text of this file
1. Can a cleaner mechanical drawing be provided? The scanned drawings and original .dwg file are what we have electronically and should be on FEDBIZOPS. You are welcome to see the original prints and we can copy sections as needed.
2. Can you provide Size and specifications on the 8 gateway valves that must be replaced? I believe they are all 8” valves. Different configurations per the photos previously attached. Specs will have to be verified once awarded.
3. Are we able to anchor to cement lid(ceiling ) for lift rigging? Yes
4. Will an x-ray be needed for cement ceiling? No
5. Can we remove cabinet? Yes
6. Can we remove tower electrical disconnect? Yes, as long as reinstalled to original condition
7. Can we remove Fire alarm Electrical box? Yes, as long as reinstalled to original condition
8. Can the wall adjacent to distribution panel be cut out? Yes, as long as rebuilt/repaired to original condition
9. Also I would like to confirm there is currently a 225 amp breaker available per machine? Yes there is currently a 225amp breaker for each
10. I did not see a sign in sheet from the job walk on the new uploaded info, was that something that will be provided? Rick will provide after follow-up site visit.
11. Can we move diesel generator and open sheetrock wall next to air compressors? Previously answered: Can the generators one of them be moved? Yes, one generator can be taken off line and moved if disconnected and reconnected by properly trained and approved personnel. Make hole in wall by 2 compressors? How many compressors need to be running all the time? Yes this option is available. One needs to stay operational at all times and wall needs to be rebuilt/repaired to original condition.
12. Can we go through wood cabinet between column and generator switchgear? It would require removing disconnect Yes, as long as rebuilt/repaired to original condition. Yes, as long as cooling tower/fire panel disconnects are reinstalled.
13. Can I use the stair way of freight elevator and set up beams and columns on landing to rig chillers down the stairs? Yes and long as any repairs made and brought to original condition
14. Will ASHRAE 15 refrigerant alarm system be required and can the existing ventilation system be used for that purpose? Yes, include the alarm system in your bid. The existing ventilation system can be used.
15. Just so I am clear when all is said and done the capacity of the chillers will total 200 tons? No, 2ea 50ton chillers, 100 ton total.
16. Can we demo the wall adjacent to the freight elevator? Yes, as long as rebuilt/repaired to original condition.
Contact Eric Shimmin from ESC Automation/Delta Connects for price quote on required work in section 5.1.3 of the SOW.
ESC Automation – FEMA Energy Management System management company
Eric Shimmin, Branch Service and Operations Manager
DIRECT 425 487 8613 x 2021 CELL 425 877 6762 TOLL FREE 1 800 692 4746 EMAIL eshimmin@deltaconnects.com ADDRESS 22522 - 29th Drive SE, Suite 104 Bothell, Bothell, WA 98021 WEBSITE www.deltaconnects.com
BUILDING INTELLIGENCE. BUILDING SUCCESS.
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Interested_Vendor_List.pdf | ||
| Chiller_replacement_SOW.doc | DOC document | |
| Questions_Chiller_Project.doc | DOC document | |
| top_floor_Evac_Route_2015.pdf | ||
| valve_photos.pdf | ||
| lower_floor_Evac_Route_2015.pdf | ||
| Updated_Chiller_replacement_SOW.doc | DOC document | |
| Chiller_SF1442.docx | DOCX document | |
| Chiller_replacement_SOW.doc | DOC document | |
| Chiller_SF1442.docx | DOCX document | |
| 52_of_65.JPG | JPG image | |
| FRC52.pdf | ||
| Chiller_Wage_Determination.pdf | ||
| lower_floor_8_5x11.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .