Uninterruptable Power Supply (UPS) Maintenance Federal contract opportunity
Solicitation number
HQC00716T0020
Issued by
Defense Commissary Agency

About this file

Additional answers to questions resulted in additional acceptable batteries and information on remote monitoring.

View the file

Other files for this federal contract opportunity

Other files attached to Uninterruptable Power Supply (UPS) Maintenance, newest first.
File Type Posted
QA_13JUN.docx DOCX document
HQC007-16-T-0020-0002.pdf PDF
HQC007-16-T-0020-0002_Conformed.pdf PDF
HQC007-16-T-0020-0001_Conformed_Copy.pdf PDF
HQC007-16-T-0020-0001.pdf PDF
Amended_J A_Redacted.pdf PDF
Delivery_Checklist_DeCA_HQ.docx DOCX document
Delivery_Checklist_DeCA_West.docx DOCX document
QA_05APR.docx DOCX document
JA_Redacted.pdf PDF
HQC007-16-T-0020.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q&A as of May 12, 2016 Q1: What is the actual KVA size of the units?

A1: 100KVA or PDU for each unit.

Q2: There are several companies that make a 540 watt battery that is the same case size, wattage and warranty. The solicitation should probably read "or equal" for that portion.

Will you consider the following batteries acceptable for the Powerware system?

Enersys HX540
C&D UPS12-540MR
CSB HRL12540WFR
Fiamm 12FLX540
A2: Yes, DeCA finds the above listed batteries acceptable substitutes for the Powerware system.

Q3: Do either of the UPS systems currently have an SNMP/ Web card installed? Without an SNMP remote monitoring is not available.

A3: No, the UPS systems do not have SNMP/Web cards installed. DeCA understands that remote monitoring is not possible as a result.