CLIN Item Requirement QTY Units
Part Number Eaton BladeUPS Model ZC121P068100000 with Power Xpert SNMP/ModBus card and Hot Sync CAN Bridge card
Capacity 12 kW of 208 volt, 3-phase power
Communications
• Able to communicate with all modular UPS units connected to the common bus.
• Automatically detects parallel units and fully configures units for parallel operation.
LCD Display Able to provide access to system information including voltage, amps, and power for any and every unit in a multi-module configuration
Internal Battery Runtime Minimum of 8.7 minutes at 67% full load External Battery Capacity Up to four external battery modules for increased runtime Battery Management Automatically test battery health and provide notification of required maintenance
Serviceability
• Hot swappable electronics module and internal battery modules to allow replacement without interrupting power to the loads
• internal switch to activate the bypass mode automatically
Common Interface Cord to connect to a common busbar/wireway
CLIN Item Requirement QTY Units Part Number Eaton BladeUPS Model ZC121P060100000 Capacity 12 kW of 208 volt, 3-phase power
Communications
• Able to communicate with all modular UPS units connected to the common bus.
• Automatically detects parallel units and fully configures units for parallel operation.
LCD Display Able to provide access to system information including voltage, amps, and power for any and every unit in a multi-module configuration
Internal Battery Runtime Minimum of 8.7 minutes at 67% full load External Battery Capacity Up to four external battery modules for increased runtime Battery Management Automatically test battery health and provide notification of required maintenance
Serviceability
• Hot swappable electronics module and internal battery modules to allow replacement without interrupting power to the loads
• Internal switch to activate the bypass mode automatically
Common Interface Cord to connect to a common busbar/wireway
CLIN Item Requirement QTY Units Part Number Eaton BladeUPS Series Model 103005747-6591
Battery Valve Regulated Lead Acid (VRLA) type, with Absorbent Glass Mat (AGM) power storage media
UPS Interface Cable to connect directly to modular UPS units
Battery Runtime Minimum of 28 minutes at 67% full load for two (2) battery modules added to each modular UPS unit
CLIN Item Requirement QTY Units Part Number Eaton BladeUPS S-Series Model ETN-BLADERACK6T
Top entry racks with parallel bar/wireway for Eaton BladeUPS modular UPS units Parallel bar able to accept up to six modular UPS units to provide future capacity of 60kW in an N+1 configuration.
CLIN Item Requirement QTY Units Part Number Eaton BladeUPS S-Series Model ETN-ENC422442S
42U racks with top entry for wiring and front entry for cooling air Nominal size: 24 inches wide x 42 inches deep x 81 inches high Fully welded with a weight load capacity of 2,200 pounds Ventilated single doors in the front and ventilated, vertically split doors in the rear Doors have keyed locks Top panel with brush strips and cableways Removable divider on one side for bayed enclosures
CLIN Item Requirement QTY Units Part Number Eaton Basic ePDU Model ePBZ96 Description 24 NEMA 5-20R receptacles and a six foot power cord with a NEMA L5-20 plug.
CLIN Item Requirement QTY Units Part Number Equivalent to Cooper B-Line SBVB72K buss bar and hardware kits
Ground Bar 1/4 inch x 5/8 inch x 72 inch bare copper bar with mounting holes, studs for two-hole grounding lugs, and tapped holes for equipment grounding connections
Hardware Kit hardware includes isolators, compression lug, bolts, and lock washers
Delivery
• Deliver FOB Destination to: Missile Defense Agency, Bldg. 3302, Hercules Road, Redstone Arsenal, Alabama 35898
• Delivery POC: Dennis Smith, 256-955-4352, dennis.smith.ctr@mda.mil
14 EA
2 EA
12 EA
20 EA
Racks for Battery Modules and Other Equipment
Racks for Modular UPS Units
MDA Specifications for UPS Equipment and Racks
12 EA
External Battery Modules
4 EA
Modular Uninterruptible Power Supply Unit
Power Distribution Strips for Racks
Vertical Ground Bar Kits
Description
Description
2 EA
Modular Uninterruptible Power Supply Unit
File details come from the government source that posted it.