CLIN Item Requirement QTY Units

Part Number Eaton BladeUPS Model ZC121P068100000 with Power Xpert SNMP/ModBus card and Hot Sync CAN Bridge card

Capacity 12 kW of 208 volt, 3-phase power

Communications

• Able to communicate with all modular UPS units connected to the common bus.

• Automatically detects parallel units and fully configures units for parallel operation.

LCD Display Able to provide access to system information including voltage, amps, and power for any and every unit in a multi-module configuration

Internal Battery Runtime Minimum of 8.7 minutes at 67% full load External Battery Capacity Up to four external battery modules for increased runtime Battery Management Automatically test battery health and provide notification of required maintenance

Serviceability

• Hot swappable electronics module and internal battery modules to allow replacement without interrupting power to the loads

• internal switch to activate the bypass mode automatically

Common Interface Cord to connect to a common busbar/wireway

CLIN Item Requirement QTY Units Part Number Eaton BladeUPS Model ZC121P060100000 Capacity 12 kW of 208 volt, 3-phase power

Communications

• Able to communicate with all modular UPS units connected to the common bus.

• Automatically detects parallel units and fully configures units for parallel operation.

LCD Display Able to provide access to system information including voltage, amps, and power for any and every unit in a multi-module configuration

Internal Battery Runtime Minimum of 8.7 minutes at 67% full load External Battery Capacity Up to four external battery modules for increased runtime Battery Management Automatically test battery health and provide notification of required maintenance

Serviceability

• Hot swappable electronics module and internal battery modules to allow replacement without interrupting power to the loads

• Internal switch to activate the bypass mode automatically

Common Interface Cord to connect to a common busbar/wireway

CLIN Item Requirement QTY Units Part Number Eaton BladeUPS Series Model 103005747-6591

Battery Valve Regulated Lead Acid (VRLA) type, with Absorbent Glass Mat (AGM) power storage media

UPS Interface Cable to connect directly to modular UPS units

Battery Runtime Minimum of 28 minutes at 67% full load for two (2) battery modules added to each modular UPS unit

CLIN Item Requirement QTY Units Part Number Eaton BladeUPS S-Series Model ETN-BLADERACK6T

Top entry racks with parallel bar/wireway for Eaton BladeUPS modular UPS units Parallel bar able to accept up to six modular UPS units to provide future capacity of 60kW in an N+1 configuration.

CLIN Item Requirement QTY Units Part Number Eaton BladeUPS S-Series Model ETN-ENC422442S

42U racks with top entry for wiring and front entry for cooling air Nominal size: 24 inches wide x 42 inches deep x 81 inches high Fully welded with a weight load capacity of 2,200 pounds Ventilated single doors in the front and ventilated, vertically split doors in the rear Doors have keyed locks Top panel with brush strips and cableways Removable divider on one side for bayed enclosures

CLIN Item Requirement QTY Units Part Number Eaton Basic ePDU Model ePBZ96 Description 24 NEMA 5-20R receptacles and a six foot power cord with a NEMA L5-20 plug.

CLIN Item Requirement QTY Units Part Number Equivalent to Cooper B-Line SBVB72K buss bar and hardware kits

Ground Bar 1/4 inch x 5/8 inch x 72 inch bare copper bar with mounting holes, studs for two-hole grounding lugs, and tapped holes for equipment grounding connections

Hardware Kit hardware includes isolators, compression lug, bolts, and lock washers

Delivery

• Deliver FOB Destination to: Missile Defense Agency, Bldg. 3302, Hercules Road, Redstone Arsenal, Alabama 35898

• Delivery POC: Dennis Smith, 256-955-4352, dennis.smith.ctr@mda.mil

14 EA

2 EA

12 EA

20 EA

Racks for Battery Modules and Other Equipment

Racks for Modular UPS Units

MDA Specifications for UPS Equipment and Racks

12 EA

External Battery Modules

4 EA

Modular Uninterruptible Power Supply Unit

Power Distribution Strips for Racks

Vertical Ground Bar Kits

Description

Description

2 EA

Modular Uninterruptible Power Supply Unit

File details come from the government source that posted it.