Attachment_5_-_UPS_PM.pdf
PDF 226 KB Posted
- Attached to
- Uninterruptible Power Supply Systems
- Solicitation number
- HQ0034-14-R-0082
- Issued by
-
DOD Washington Headquarters Service
About this file
Attachment 5
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment_ii_Site_Visit.pdf | ||
| HQ0034-14-R-0082-0002.pdf | ||
| Attachment_i_RFIs.pdf | ||
| HQ0034-14-R-0082-0001.pdf | ||
| HQ0034-14-R-0082-0001_Full.pdf | ||
| Attachment_9_-_Pricing_worksheet.xls | XLS spreadsheet | |
| Attachment_3_-_Battery_List.pdf | ||
| Attachment_2_-_DD254.pdf | ||
| Attachment_6_-_WD_05-2103.pdf | ||
| RFP-HQ0034-14-R-0082.pdf | ||
| J-L1_PAST_PERFORMANCE_DATA_revised_12-13.doc | DOC document | |
| Attachment_1_-_FY_14-19_UPS_Maintenance_Equipment_List.pdf | ||
| Attachment_4_-_UPS_Spare_Parts_Kit.pdf | ||
| J-L2_PAST_PERFORMANCE_QUESTIONNAIREv1.doc | DOC document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HQ0034-14-R-0082; Attachment 5; April 1, 2014
ITEM #
SYSTEM AND
AREA
EQUIPMENT ID ITEM DESCRIPTION DATE FOUND
a EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/17/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/17/2009 c Replace all DC filter capacitors. 9/17/2009 d Replace all AC input and output filter capacitors. 9/17/2009 a Neutral wire not properly secured. 9/17/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/17/2009 c Replace all DC filter capacitors. 9/17/2009 d Replace all AC input and output filter capacitors. 9/17/2009 a Phase A input cap amps low (71 compared with 121 & 122 on B and C).
Caps need to be replaced per field mod #44. EPS6-FM-044 A (Input Cap & Transformer replacement) is needed.
9/21/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/21/2009 c Replace all DC filter capacitors. 9/21/2009 d Replace all AC input and output filter capacitors. 9/21/2009 a EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/21/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/21/2009 c Replace all DC filter capacitors. 9/21/2009 d Replace all AC input and output filter capacitors. 9/21/2009
5 C10, BB1040 BAT-BB1040A-2C, String 1 a Jar #23 bad due to low VDC (13.22 VDC). 9/12/2009 6 C10, BB1040 BAT-BB1040A-1D, String 2 a Jar #23 bad due to low VDC (13.06 VDC). 9/12/2009 a ICOZ PCA not working will schedule repair. 9/14/2009 b Found Output capacitor leaking with burned wires. 9/14/2009 c EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/14/2009 d EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/14/2009 e Replace all DC filter capacitors. 9/14/2009 f Replace all AC input and output filter capacitors. 9/14/2009 a EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/14/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/14/2009 c Replace all DC filter capacitors. 9/14/2009 d Replace all AC input and output filter capacitors. 9/14/2009 a EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/14/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/14/2009 c Replace all DC filter capacitors. 9/14/2009 d Replace all AC input and output filter capacitors. 9/14/2009 a ICOZ PCA not working will schedule repair. 9/27/2009 b EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/27/2009 c EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/27/2009 d Replace all DC filter capacitors. 9/27/2009 e Replaced 3rd output cap bank from top. All AC caps need to be replaced. Replace all AC input and output filter capacitors.
9/27/2009 a EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/27/2009
10 C10, BC1040 UPS-BC1040-1C
UPS-BC1040-1A
8 C10, BC1040 UPS-BC1040-1B
9 C10, BC1040 UPS-BC1040-2B
7 C10, BC1040
UPS-BB852-2B
Pentagon Discrepancies and Repairs (Through April 2014)
1 B8B, BB852 UPS-BB852-1A
2 B8B, BB852 UPS-BB852-2A
3 B8B, BB852 UPS-BB852-1B
4 B8B, BB852
Pentagon Discrepancies and Repairs (Through April 2014) b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/27/2009 c Replace all DC filter capacitors. 9/27/2009 d Replace all AC input and output filter capacitors. 9/27/2009 a EPS6-FM-044 A (Input Cap & Transformer replacement) is needed. 9/27/2009 b EPS6-FM-050 Thermal wires from transformer to TREZ PCA. 9/27/2009 c Replace all DC filter capacitors. 9/27/2009 d Found ARUZ (72-130055-00 Rev B01 TV3) and CRIZ boards to be faulty, both need to be replaced.
9/27/2009 e Replace all AC input and output filter capacitors. 9/27/2009 13 C10, BC1040 UPS-BC1040-2A a Replace DC and AC output filters 14 C10, BC1040 UPS-BC1040-2C a Replace DC and AC output filters
15 C10, BB888 STS/PDU-BB888-01 a IR scan found hot-spots at PNL-BB888-2, bkrs 20 (13 amps) and 22 (14 amps).
9/16/2009
16 RDF, 1J7BHV1 BAT-1J7BHV1-2A a Jar 30 had voltage of 13.10 VDC, 567 millivolts. 9/15/2009 a String A2 - Connectors for cells 137 and 44 have corrosion and should be replaced.
10/28/2009 b String B1 - Connectors for cells 20/21, 69, and 161 have corrosion and should be replaced.
10/28/2009 c String B1 - Jar with cell #198 has small crack in cell cover. 10/28/2009 d String B2 - Connectors for cells 237 and 216/217 have corrosion and should be replaced.
10/28/2009
Mother UPS System A, ME846
BAT-ME846-05, String 1 a Jar #9 had low DC voltage (12.36 VDC) and high ripple voltage (229 mV).
9/30/2009
Mother UPS System A and B, ME846
MBC-ME846-A, B a GUIs for both MBC’s not working, need to be shipped off for repair.
Mother UPS System B, ME846
UPS-ME846-01 a Found communication issue and fan fail alarm. 10/5/2009
21 Segment 1, BG849 PDU-BG849-10 a Panel B breaker 1 has 19 amp load, should be no more than 16 amps. 10/7/2009
Con Serv W1, 5B400
BAT-5B400-1B a Jar #18 has corroded positive post due to seal leak. 10/13/2009
23 E6B, BD728 PDU-BD728-01R a IR fault found, priority 2, PNL-BD728-7, breaker #35 overloaded. 10/26/2009 a Cell #14 was found to be bad.
b Cell #34 and #174 are also bad.
a Replace all DC filter capacitors.
b Replace all AC input and output filter capacitors.
Con Serv W2, 4B555
BAT-4B555-1A a Jars #26 and 39 have corroded positive posts due to seal leakage. 10/14/2009
27 C6, 1D629 BAT-1D629-1A a Connector for cell #77 was corroded. 10/19/2009
28 C6, 1B524 STS/PDU-1B524-01 a IR scan revealed distribution panel B, breaker #5, operating at 130 F.
Found that breaker is rated @ 20 amps with 24 amp load on it.
Tripped several times during pm.
10/30/2009 a Replace all DC filter capacitors.
b Replace all AC input and output filter capacitors.
a Cells #142, 165, 230, 235, and 238 have high specific gravity.
b Cells #15, 18, and 29 have peroxidaton on posts.
a Cell #18 is bad and is jumped out.
11/10/2009
10/27/2009
30 C7, 1D745 BAT-1D745-1A
29 C6, 1D629 UPS-1D629-1A, 2A, 1B, 2B 5/24/2010
25 E6B, ME659 UPS-ME660-01, 02 present
24 E6B, ME659 BAT-ME659-02
12 C10, BC1040 UPS-BC1040-2D
17 B8B, BB852 BAT-BB852-2A, 1B, 2B
11 C10, BC1040 UPS-BC1040-1D
b Cells #9 and #70 have corroded bus bars that need to be replaced.
32 C7, 1D745 BAT-1D745-1B a Cell #40 has low voltage and needs to be jumped out. 11/10/2009
33 C7, 1D745 BAT-1D745-2B a Cells # 129, 130, 131, 124, 132, 122, 148, 97, 146, 147, 98, 100, 123, 139, 110, 121, 104, 112, 145, 103, 102, 138, 144, 151, and 152 all have high specific gravities.
11/10/2009 a Replace all DC filter capacitors.
b Replace all AC input and output filter capacitors.
a Replace all DC filter capacitors.
b Replace all AC input and output filter capacitors.
36 C7, 4C833 PDU-4C833A-02 a Panel C breaker #1 (20 amp breaker) has 20 amp load, should be no more than 16 amps.
11/16/2009
37 C8, 1C887 BAT-1C887-02 a The following cells had high voltage: 157, 131, 158, 119, 159, 160, 107, 11/6/2009 a Cell #14 has a post seal leak, (+) post.
b Cell #232 has low voltage and low specific gravity (2.075 VDC, 1.214
SG).
c Cell #185 has high voltage - 2.580 VDC, SG is ok.
d Cell #115 needs a new fill tube - it is broken.
e Cell #60 has high voltage (2.325 VDC).
39 CCSP W1, 1B462 BAT-1B462-2B a Found heavy corrosion on negative terminals for jars 3, 24, and 32 11/17/2009
40 IEOC (Navy), 1A310 BAT-1A310A-1 a Jar #20 had low voltage (13.14 VDC) and needs to be monitored. 11/19/2009
41 Radio Room 5B400 BAT-5B400A-01 a Jars #25 and #30 were measured at 13.15 VDC and 13.17 VDC resp.
during PM and need to be replaced.
11/30/2009
Mother UPS, ME846
UPS-ME846-01, 02, 03, 04, 05,
a Replace DC cap banks, p/n 87-134187-30, qty. 3 per unit. 10/1/2009
43 C1, 1D135 UPS-1D135A-01, 02 a Replace DC cap banks, p/n 87-134187-30, qty. 3 per unit. 11/1/2009 44 C8, 1C881 UPS-1C881-01, 02 a Replace DC cap banks, p/n 87-134187-30, qty. 3 per unit. 11/1/2009 45 C8, 1C889 UPS-1C889-01, 02 a Replace DC cap banks, p/n 87-134187-30, qty. 3 per unit. 11/1/2009 46 C9, 1C938 UPS-1C938-01, 02 a Replace DC cap banks, p/n 87-134187-30, qty. 3 per unit. 11/1/2009
47 B8B, BB852
UPS-BB852-1A, 1B, 2A, 2B and
MBC-BB852-A, B
a Metasys building monitoring system was not communicating properly.
Determined that communication cables were improperly wired.
12/29/2009
48 B8B, BE877 PDU-BE877-01 a Left side of PDU EPO’d accidently by NMCC technician. EPO button did not have safety cover to prevent accidental activation.
12/29/2009
49 E6B, ME659 BAT-ME659-01 a Cell 120 has electrolyte leak in case. Leaking fluid is puddling and running off of cell 41 below it.
2/6/2009
50 C10, BC1040 MBC-BC1041-C a All UPSs and MBCs except MBC-1041-C were communicating with Metasys.
12/30/2009
51 C1, 1D135 UPS-1D135A-01 ,02 a Serial numbers on Pentagon Schedule were reversed (R07-10120 for unit 01 and R07-101121 for unit 02).
12/1/2009
52 Segment 1, BE884 PDU-BE884-4R a Output panel board 9, breaker 13 IR reading was 113 F. Breaker is rated at 20 amps, probably overloaded.
1/5/2010
53 C7, 1D745 BAT-1D745-1A, 2A, 1B, 2B a Battery rundown was conducted on 4 battery strings. Currently all 4 strings have multiple low specific gravity readings and string 1B now has 6 more cells with high voltage than before (total of 8).
3/1/2010
11/10/2009
11/5/2009
11/11/2009
C7, 1C744 UPS-1C744A-1A, 2A
35 C7, 1C744 UPS-1C744A-1B, 2B
11/11/2009
38 C9, 1C926 BAT-1C926-01
31 C7, 1D745 BAT-1D745-2A
54 C8, 1C879, 1C887, BAT-1C887-01, 02
BAT-1C879-01, 02
a
Battery rundown was conducted on 4 battery strings. Currently all 4 strings have multiple low specific gravity readings and strings 1C887-01 and –02 have multiple cells with significantly high voltage readings as follows: String 01 cells 81-86 and 121 had high voltages (all between
2.487 and 2.5 VDC); String 02 cells 105-120, 129-160, and 225-228 had high voltages (all above 2.4 VDC).
3/1/2010
55 C9, 1C926 BAT-1C926-01 a
Cell #14 has a post seal leak, (+) post.
Battery rundown was conducted on battery strings BAT-1C926-01 and -
02. Currently both strings have multiple low specific gravity readings.
String 01 cell #232 still has low voltage (2.084 VDC) and cell #185 still has high voltage (2.574 VDC) after battery rundown.
Cell #115 needs a new fill tube - it is broken.
3/1/2010
56 TENANT O UPS-BB926A-01 a Rectifier fault, blown input fuses 2/27/2010
Con Serv W2, 4B555
BAT-4B555-1A a Jar #4 has dent in front right corner of jar. No leakage was noticed. 3/8/2010
Con Serv W2, 4B555
BAT-4B555-1A a Jar #8 had leak in front right corner. CO and WJ cleaned leak at time of discovery.
3/8/2010
Radio Room, 5B400
BAT-5B400A-01 a Jars #25 and #30 (repl. 12/22/09) each were measured at 13.07 VDC during PM (2/4) and need to be monitored.
2/4/2010
Radio Room W1, 5B400
BAT-5B400A-01 a Jars #25 and #30 (repl. 12/22/09) were measured at 13.12 and 13.13 VDC resp. during follow-up from 2/4/2010 PM.
3/8/2010
61 B8B, BB852 BAT-BB852-1A a During the visual inspection many cells were found with minor post seal leaks. The following cells have major post seal leaks - #6, 7, 18, 19, 27, 28, and 38. Cell #53 post also had minor peroxidation.
3/8/2010
62 B8B, BB852 BAT-BB852-2A a During the visual inspection many cells were found with minor post seal leaks. These cells listed have major post seal leaks: #8, 20, 26, 27, 29, 35, 38, 42, 43, 45, 72, 85, 99, 95, 96, 105, 111, 152 and 137.
3/8/2010
63 B8B, BB852 BAT-BB852-1B a
During the visual inspection many cells were found with minor post seal leaks. These cells listed have major post seal leaks - #25, 26, 27, 29, 32, 191, 200, 222, 223, 237, 238, and 239. These cells had peroxidation on the posts: #69, 191, and 161.
3/8/2010
64 B8B, BB852 BAT-BB852-2B a During the visual inspection many cells were found with minor post seal leaks. The following cells have major post seal leaks - #12, 17, 18, 36, 39, 49, 50, 56, 170, and 180.
3/8/2010
65 B8B, MC851 STS/PDU-MC853-01 a STS display is displaying incorrect input amps/KVA output. 3/16/2010 66 C10, MB851 STS/PDU-MB851-01 a Display needs to be calibrated. 3/18/2010 67 C10, BE1022 STS/PDU-BE1022-02 a Display needs to be calibrated. 3/18/2010
68 C10, BB1040 BAT-BB1040A-1B, String 3 a Jar 12 had reading of 13.24 VDC which was trending down from previous readings.
3/11/2010
69 C10, BB1040 BAT-BB1040A-2B, String 2 a Jar 40 had reading of 11.51 VDC (200 mVAC). 3/11/2010
70 C10, BB1040 BAT-BB1040A-1D, String 1 a Jars 4 and 17 had heavy corrosion on posts due to post seal leakage 3/11/2010
71 C10, BB1040 BAT-BB1040A-1D, String 3 a Jar 7 had heavy corrosion from post seal leakage. Jar 34 had voltage trending down from last PMs (13.29 VDC from 13.32 9/2009, flagged in 9/2009 report by P Shagena/D Nosic).
3/11/2010
Con Serv W1, 3B400
BAT-3B400-1C a Undervoltage trip on battery breaker is not working. 4/12/2010
Con Serv W1, 3B400
UPS-3B400-01 a
After PM on 4/12 unit went into alarm with “Input Current Imbalance” condition. While checking unit 4/13 determined that display was showing input phase currents as follows: phase A – 161 A, low limit – 129 A, high limit – 174 A; phase B – 151 A, low limit – 120 A, high limit 159 A; phase C – approx. 260 A, low limit 209 A, high limit 278A. At time of departure 4/12 phase C current was 158 amps with no alarm.
4/13/2010
Con Serv W1, 5B400
UPS-5B400-01 a Attempted to transfer UPS to bypass but bypass was inhibited despite adjusting output voltage slightly above bypass (approx. 492 VAC between all 3 phases). Inverter was leading bypass by 4 degrees.
4/13/2010
75 E6B, ME659 BAT-ME659-01 a
The intercell resistances are all tier or rack connections with the exception of cell #4. The string average is 10uOhm or less and #4 is reading 29. It read 32 during the 10/27/09 QPM. On 11/25/08 it was only 12uO.
4/8/2010
76 E6B, ME659 BAT-ME659-02 a Intercell resistance for cells 13, 33, and 173 all appear to correspond with a cell that is jumped out, so jumper accounts for the higher resistance. Cell #4 and 216 are at 18uO.
4/8/2010
77 C6, 1D629 BAT-1D629-2B a Cell 45 has corrosion forming on post and cable. 4/7/2010 78 E6B, ME659 BAT-ME659-01 a Cell 177 has high voltage reading (2.466 VDC). 4/8/2010
79 E6B, ME659 BAT-ME659-01 a
The following cells had high specific gravity readings: 116 (1.289), 118 (1.29), and 125 (1.286).
The following cells had low specific gravity readings: 163 (1.238), 165 (1.22), 166 (1.237), 181 (1.218), and 182 (1.237).
4/8/2010
80 C8, 1C887 BAT-1C887-01, 02 a
Battery rundown was conducted on 4 battery strings 2/24/2010.
Currently string 1C887-01 has multiple high voltage readings as follows: cells 81-88 and 121 have voltages between 2.487 and 2.5 VDC.
String 1C887-02 cells 105-120, 129-160, and 225-228 have high voltages (all above 2.4 VDC). Most if not all of these cells were treated with Depolarization pills 5/19/2010. Many cells in string 1C887-02 still have low SGs.
5/19/2010
81 C9, 1C926 BAT-1C926-01 a Cell #185 still has high voltage (2.574 VDC) as of PM on 5/19/2010.
Cell was treated with Depolarization pills 5/19/2010.
5/19/2010
Con Serv W4, 2B960 & 3B957
UPS-2B960-01
UPS-3B957-01
a Float voltages are currently 550 and 548 VDC respectively for UPS- 2B960-01 and UPS-3B957-01.
4/21/2010
83 IEOC, 1A310A UPS-1A310A-1 a DC capacitors (4 assemblies in each unit) need to be replaced due to age. Parts are in stock.
present
Radio Room, 5B400A
UPS-5B400A-01 a DC capacitors (4 assemblies in each unit) need to be replaced due to age. Parts are in stock.
present
Radio Room, 5B400A
UPS-5B400A-01 a UPS float voltage was too low for battery string (485 VDC, needed to be 490 VDC).
5/6/2010
86 CCSP, 1B458 UPS-1B458-01 a UPS-1B458-01 - Found burnt connection to one AC output capacitor wire.
5/5/2010
87 C7, 1D669-01 STS-1D669-01 a At time of PM 5/18/2010 found that air in room was very warm.
Room is basically a closet with roll-up door – no ventilation.
5/18/2010
88 C7, 1D745 BAT-1D745-1B a Cells 42, 44, 73, 74, 76, 137, 138, 139, and 140 have slightly high voltage readings (all below 2.315 VDC) and cell 40 is jumped out.
5/17/2010
Tenant O, BB926A-
BAT-BB926A-01B a Jar 16 (13.35 VDC) appears to be trending downward in voltage.
Previous readings were: 13.44 on 2/16/2010; 13.48 on 11/23/2009;
and 13.6 on 12/10/2008.
5/11/2010
90 E6B, ME660 UPS-ME660-02 a UPS was in alarm with fan fail. 6/3/2010
91 C6, 1D629
UPS-1D629-1B, UPS-1D629-
2B, and MBC-1D629-B a
At time of arrival F Johnson found C6 System B in alarm due to “Transfer Lockout”. Shut both UPS units down and restarted but with no change in status on either unit. Was not able to shut MBC down due to not being able to contact Matt Morris.
6/23/2010
92 C6, 1D629 UPS-1D629-1A, UPS-1D629-2A a Replace all DC filter capacitors.
Replace all AC output filter capacitors. 5/25/2010
93 C6, 1D629 UPS-1D629-1B, UPS-1D629-2B a Replace all DC filter capacitors.
Replace all AC output filter capacitors. 5/27/2010
94 C7, 1C744
UPS-1C744A-1A
UPS-1C744A-2A a
Replace all DC filter capacitors.
Replace all AC output filter capacitors. 5/19/2010
95 C7, 1C744
UPS-1C744A-1B
UPS-1C744A-2B a
Replace all DC filter capacitors.
Replace all AC output filter capacitors. 5/20/2010
Mother UPS, ME846
BAT-ME846-03, String 4 a Jar 33 is bad (13.01 VDC, 166 mVAC). 7/6/2010
Mother UPS, ME846
BAT-ME846-06, String 2 a Jar 40 is bad (12.75 VDC, 26 mVAC). 7/6/2010
98 Segment 1, BE833 PDU-BE833-3 a Breakers 21 and 23 in Panel C (double pole breaker) are carrying load of 16 amps at a temperature of 99F.
7/13/2010
99 Segment 1, BE884 PDU-BE884-4R a Bkrs 12 and 13 of Pnl 9 are operating at 125 F (bolt side), are overloaded or have loose connection (could not check amps).
7/13/2010
100 Segment 1, BE884 PDU-BE884-13R a Breakers 38-42 of panel 9 are operating at 116 F and may be overloaded (could not get amp probe around cables).
7/13/2010
101 Segment 1, BE884 PDU-BE884-13R a Breakers 12 and 13 of panel 9 are operating at 125 F (on bolt side), are overloaded or have loose connection (could not check amps).
7/13/2010
102 Segment 1, BE833 PDU-BE833-17 a Input breaker phase B load side connection has temperature of 101 F. 7/13/2010
103 Segment 1, BE833 PDU-BE833-18 a Input breaker phase A load side connection has temperature of about 82 F where other phases are at 72 F.
7/13/2010
104 Segment 1, BE833 PDU-BE833-18 a Breaker 7, Panel B (rated 20 amps) is carrying 17.5 amp load and should carry no more than 16 amps. Temperature of breaker is 99 F.
7/13/2010
105 Segment 1, BE833 PDU-BE833-18 a Breaker 25, Panel D (rated 20 amps) is carrying 16 amp load and has temperature of 99 to 100 F.
7/13/2010
106 Segment 1, BE833 PDU-BE833-18 a Breaker 32, Panel D (rated 20 amps) is carrying 15.9 amp load and has temperature of 100 F.
7/13/2010
107 C6, 1D629
UPS-1D629-1B
BAT-1D629-1B a
The float voltage for battery string BAT-1D629-1B is higher than the other three C6 strings. UPS display reading for string voltage is 558 VDC but actual reading on battery string is 561 VDC. These batteries are being charged at 2.26 VDC per cell.
7/19/2010
Con Serv W4, 2B960
BAT-2B960-1A a Jar 16 had corrosion on positive terminal. 7/28/2010
Con Serv W4, 2B960
BAT-2B960-1A a Jar 15 is bad (12.00 VDC and 645 mVAC) and needs to be replaced 7/28/2010
110 C6, 1D629 UPS-1D629-2B a Display is showing battery DC current at 12 amps but there is no DC current actually flowing
7/19/2010
111 C6, 1D629 UPS-1D629-1B a Display is showing battery DC current flashing between 0-1 amps or 10- 13 amps
7/19/2010
112 C6, 1D629 BAT-1D629-1A, 2A, 1B, 2B a 10 flame arrestors, 14 cell connection covers, and 12 flame cap covers needed to be replaced.
7/20/2010
113 C7, 1D745 BAT-1D745-2A a Cell 17 has high intercell reading (45 uOhm). 8/16/2010
114 C8, 1C887 BAT-1C887-02 a
Cells 129-160 still have voltage readings well above the upper voltage tolerance (all readings are between 2.468 and 2.503 VDC). Sure Power treated those cells (along with cells 127 and 128) with Depolarization pills 8/17/2010
8/17/2010
115 C9, 1C926 BAT-1C926-01 a Cell #185 was treated with Depolarization pills 5/19/2010 and still has slightly high voltage reading (2.317 VDC).
8/18/2010
116 C9, 1C926 BAT-1C926-01 a Cell #157 had low specific gravity reading (1.225). 8/18/2010
117 E6B, ME659 BAT-ME659-02 a
Sure Power tech Nick Slota checked cells 4 and 216 with following readings: cell 4 – 2.295 VDC, 19 Uohms Intercell, 230 Uohms internal resistance; cell 216 – 2.277 VDC, 25 Uohm intercell, 248 Uohm internal resistance.
8/19/2010
118 B8B, BB852 UPS-BB852-2A a After completing APM on UPS, C-phase inverter leg blew and took UPS offline.
9/7/2010
119 C10, BB1040A BAT-BB1040A-1A a String 1, jar 18 and string 3, jar 21 had corrosion on one terminal each. 9/14/2010
120 C10, BB1040A BAT-BB1040A-1C a String 1, jars 26 and 31, and string 4, jar 40 had corrosion on one terminal each.
9/14/2010
121 B8B, BE877 STS/PDU-BE877-01 a Panel PNL-BE877-4, bkr 14 is very hot (122F). Breaker is carrying 18 amps and is only rated for 20 A.
9/9/2010
122 C10, MB851 STS/PDU-MB851-01 a Panel 4, breaker 31 was found tripped during pm (breaker was tripped prior to pm, not during, and was left off).
9/9/2010
123 C10, BD1041 UPS-BD1041-2D a Found micro-switch that could not be cleaned and repaired during PM. 9/21/2010
124 C6, 1D629 UPS-1D629-2A a Found hot inverter module hardware on phase C module due to loose hardware.
9/30/2010
125 C6, 1D629 BAT-1D629-1B a Cell 81 had low voltage reading (2.104 VDC) and needs to be jumped out.
10/20/2010
Con Serv W4, 3B957
UPS-3B957-01 a Blower in upper left section of UPS has failed and needs to be replaced.
10/20/2010
127 IEOC, 1A310 BAT-1A310A-1 a Jar 10 voltage is 13.22 – almost at low end of tolerance. 11/2/2010
W1 LS (BOCC),
1A340
BAT-1A340-1 a Jar 15 has corroded connector which needs to be cleaned or replaced. 11/2/2010
129 Tenant O, BB926 BAT-BB926-01B a Jar 16 voltage has been dropping since 12/08 and is now at 13.26 VDC.
By the time the next PM cycle comes jar may have already failed.
11/10/2010
130 C8, 1C887 BAT-1C887-01 a Cell 87 had slightly high voltage measurement during annual PM
11/15/2010 (2.317 VDC).
11/15/2010
131 C8, 1C887 BAT-1C887-02 a
Cells 129-160 still have voltage readings well above the upper voltage tolerance (all readings are between 2.467 and 2.511 VDC) as of annual PM 11/15/2010. Sure Power treated those cells with Depolarization pills 11/17/2010
11/15/2010
132 C9, 1C938 UPS-1C938-02 a
Input filter capacitor tray for phase B showed higher amperage than other 2 phases (80 and 81 amps compared with 61, 63, and 64 A).
Pulled phase B filter and determined that tray capacitance was 374 uF compared with 280 and 294 uF for other two phases. It appears that that tray was built with 20 uF caps compared with 15 uF caps for good trays.
11/16/2010
133 IEOC, 1A310 BAT-1A310A-1 a Jar 10 voltage is 13.22 – almost at low end of tolerance. 11/2/2010
134 RDF, 1J7BHV1 BAT-1J7BHV1-1A a Jar 31 has low voltage reading (13.14 VDC) and needs to be replaced. 11/29/2010
135 RDF, 1J7BHV1 BAT-1J7BHV1-1A a Jar 3 voltage (13.39 VDC) is trending downward and will eventually need to be replaced. Previous readings for that jar were 13.58 VDC on 3/2 and 13.45 VDC on 6/9.
11/29/2010
136 RDF, 1J7BHV1 BAT-1J7BHV1-1A a Jar 32 voltage (13.33 VDC) is trending downward and will eventually need to be replaced. Previous readings for that jar were 13.41 VDC on 3/2 and 13.37 VDC on 6/9.
11/29/2010
137 RDF, 1J7BHV1 BAT-1J7BHV1-1A a Jar 34 voltage (13.23) is trending downward and will eventually need to be replaced. Previous readings for that jar were 13.27 VDC on 3/2 and 13.26 VDC on 6/9.
11/29/2010
138 RDF, 1J7BHV1 BAT-1J7BHV1-1B a Jar 35 voltage (13.27) is trending downward and will eventually need to be replaced. Previous readings for that jar were 13.34 VDC on 3/2 and 13.29 VDC on 6/9.
11/29/2010
139 RDF, 1J7BHV1 BAT-1J7BHV1-2A a Jar 3 voltage (13.26) is trending downward and will eventually need to be replaced. Previous readings for that jar were 13.40 VDC on 3/2 and
13.34 VDC on 6/9.
11/29/2010
Con Serv W1, 5B400
BAT-5B400-1B a Jar 13 has low voltage reading (12.68 VDC) and needs to be replaced. 1/3/2011
141 C7, 5B755 STS-5B755-01 a Fan #3 needed to be replaced. 1/5/2011
142 C6, 1D629 BAT-1D629-1A a Cell 77 connector has been damaged by corrosion and needs to be replaced.
1/17/2011
143 C6, 1D629 BAT-1D629-1B a Cell 215 voltage is close to low end of tolerance (2.181 VDC). 1/17/2011
144 Segment 1, BE833 PDU-BE833-18 a Attempted to perform SAPM on PDU - was not able to due to locked up metering display.
1/26/2011
145 IEOC, 1A310 BAT -1A310A-1,2 a All jars in both strings have date code of 12/2006 1/31/2011
Mother UPS, ME846
BAT-ME846-05, String 1 a BAT-ME846-05, String 1 - Jar 25 has low voltage (12.64 VDC). 4/6/2011
Mother UPS, ME846
BAT-ME846-01, String 3 a BAT-ME846-01, String 3 - Jar 23 has low voltage (11.41 VDC). 4/5/2011
Mother UPS, ME846
BAT-ME846-03, String 3 a BAT-ME846-03, String 3 - Jar 17 has low DC voltage (13.10 VDC) and high millivolt reading (330 mVAC).
4/5/2011
Mother UPS, ME846
BAT-ME846-03, String 4 a BAT-ME846-03, String 4 - Jar 38 has low voltage (11.45 VDC). Millivolt reading was 101 mVAC).
4/5/2011
150 Con Serv W2 UPS-2B555-01 a After deenergizing UPS and performing maintenance, UPS logic would not boot back up.
4/27/2011
151 Con Serv W2 BAT-4B555-1A a Found corrosion on jar 39, positive post . 4/26/2011
152 Con Serv W1
UPS-3B400-01
UPS-5B400-01
a All UPSs are over 9 years old and AC and DC capacitors need to be replaced.
4/28/2011
153 Con Serv W2
UPS-2B555-01
UPS-3B555-01
UPS-4B555-01
UPS-5B647-01
a All UPSs are over 9 years old and AC and DC capacitors need to be replaced.
4/28/2011
154 C10 STS-BE983-01 a Internal fault alarm displayed on STS. Display showed that load was interrupted but load was not actually down.
3/24/2011;
5/3/2011
155 CCSP, 1B458 UPS-1B458-01 a Found burnt wire on one AC input capacitor. 5/10/2011
156 Segment 1 STS-BE983-01 a
STS occasionally goes into internal alarm mode, locking display into a false representation of loading – load continues to be fed from source 2 but display shows no loading. Fred Johnson and Matt Morris have reset unit several times but after a week or so problem returns. Load has also been transferred from source 2 to source 1 and failures continue.
last event- 5/11/2011
157 C7 BAT-1D745-2A a Cell 115 has a low voltage reading (2.092 VDC) and a low specific gravity reading (1.229).
5/17/2011
158 CCSP UPS-1B458-01 a AC and DC capacitors are old and need to be replaced 159 CCSP UPS-1B462-02 a AC and DC capacitors are old and need to be replaced
160 C10 BAT-BB1040A-1B, String 2 a Found that jar 35 was leaking electrolyte out of negative post onto jar below.
6/15/2011
161 C10 BAT-BB1040A-2A, String 3 a Jar 12 was bad, 11.90 VDC, 150 mVAC. 6/13/2011
162 C10 BAT-BB1040A-1C, String 3 a Jar 22 has high millivolt reading (110 mVAC) and DC volt reading that is jumping around between 13.35 VDC and 13.45 VDC.
6/14/2011
163 RDF UPS-1J7BHV1-01 a AC and DC capacitors are old and need to be replaced present 164 RDF UPS-1J7BHV1-02 a AC and DC capacitors are old and need to be replaced present
165 Mother UPS MBC-ME846-B a
After transferring System B to bypass during annual PMS it was difficult at first to get current readings on bypass cables inside MBC.
Within a few minutes the amp readings as listed above became available but these amp readings are not what the system was delivering to load before transfer to bypass. Before transfer the system was delivering over 300 KW to the load. Within about 20 minutes of load loss on system, Don Erickson reset all load breakers and full load (300 KW plus) was delivered to load again. At this time it appears that all load breakers may have tripped after transfer but the reason has not yet been determined.
7/7/2011
166 Mother UPS MBC-ME846-B a
A test was conducted Wednesday, 7/19/2011 presided over by Rob Walker with Bill Thomas, George Corron, Piyush Patel, Matt Morris and others in attendance. Test purpose was to reproduce loss of load on system as experienced 7/7 but, despite multiple transfers to bypass no load was lost from system and no load breakers tripped. Although no load was lost it was determined that , when transferring to bypass by dropping module 1 first the system experienced “Transfer Lockout” due to UPS loads on modules 3 and 6 having skewed and reduced output voltages (440s for phases A and B and 460s for phase C).
Group agreed to have MC Dean troubleshoot system and then re-attempt test again later.
7/19/2011
Mother UPS, ME846
BAT-ME846-01, String 4 a
Due to problems discovered during testing 7/19 and 7/20, FJ, TG, and TD calibrated System A UPSes on 8/8 and System B UPSes on 8/9. The following problems were discovered or re-visited:
A – Sys A mod 2 growled when loaded with full system load but held load.
B – Sys A mod 4 phase C inverter legs failed.
C – Sys B mod 1 continued to cause “Transfer Inhibited” condition when loaded with system load.
7/20/2011
Mother UPS, ME846
BAT-ME846-03, String 2 a Jar 10 has low DC voltage (12.99 VDC) and high AC voltage (560 mVAC) and is bad
7/5/2011
Mother UPS, ME846
BAT-ME846-01, String 4 a Jar 29 has high AC ripple voltage reading (300 mVAC) and is bad. 7/5/2011
Mother UPS, ME846
BAT-ME846-03, String 2 a Jar 10 has low DC voltage (12.99 VDC) and high AC voltage (560 mVAC) and is bad
7/5/2011
Mother UPS, ME846
BAT-ME846-03, String 4 a Jar 13 had low DC voltage and high AC voltage readings after battery run-down due to generator failure 7/27.
7/27/2011
172 C6, 1D629 BAT-1D629-1A a Sure Power determined that there is still a peroxidation problem with cell #77 terminal.
7/18/2011
Radio Room, 5B400A
UPS-5B400A-01 a Had to raise DC link voltage once again (should be 490 VDC). 8/15/2011
174 C10 STS-BE983-01 a STS went back into alarm despite all components that were replaced previously.
5/30/2011
175 B8B BAT-BB852-1A a
B8B BATTERIES: THE BATTERIES ARE SHOWING SIGNS OF RAPIDLY
AGING. THE POSITIVE PLATES ARE GROWING WHICH IS PUSHING UP
ON THE POSITIVE POSTS CAUSING POST SEAL LEAKS. These batteries are schedule for full replacement
9/1/2011
176 B8B BAT-BB852-2B a
B8B BATTERIES: THE BATTERIES ARE SHOWING SIGNS OF RAPIDLY
AGING. THE POSITIVE PLATES ARE GROWING WHICH IS PUSHING UP
ON THE POSITIVE POSTS CAUSING POST SEAL LEAKS. These batteries are schedule for full replacement
9/1/2011
177 C10
BAT-BB1040A-1D
String 4 a
Jar 5 had a low DC voltage reading (12.31 VDC) and a high AC ripple voltage reading (63 mVAC) and needs to be replaced.
9/7/2011
178 C10 UPS-BC1040-1A a While performing visual inspection found that inverter #4 fuse sensor was broken off.
9/12/2011
179 C10 STS/PDU-BC1039-01 a While performing visual inspection found that Mere Interface board had at least one bad electrolytic capacitor.
9/13/2011
180 B8B BAT-BB852-2A a Jars are showing signs of rapid aging. The positive plates are growing which is pushing up on the positive posts and has caused a small crack in the jar cover between cells 93 and 94.
9/21/2011
181 B8B BAT-BB852-1B a Jars are showing signs of rapid aging. The positive plates are growing which is pushing up on the positive posts and has caused a small crack in the jar cover between cells 29 and 30.
9/21/2011
182 RDF UPS-1J7BHV1-02 a After replacing DC caps 9/29/2011, forming caps, then placing load back on unit one DC cap exploded. After replacing bad and damaged capacitors found that unit had inverter Fault.
9/29/2011
183 RDF UPS-1J7BHV1-02 a While attempting to start UPS after replacing DC caps that were damaged, found that a fan sail switch had become loose and was not registering an operating fan status.
9/30/2011
184 Mother UPS
UPS-ME846-01
UPS-ME846-03
UPS-ME846-06
a Each UPS needs a new AMUZ board for appropriate backlighting. 9/30/2011
185 Mother UPS BAT-ME846-02 a String 2, jar 21 has low VDC reading and needs to be replaced. 10/4/2011
186 Mother UPS BAT-ME846-05 a String 1, jars 14 -20 have low VDC readings and need to be replaced. 10/5/2011
187 Mother UPS BAT-ME846-01 a String 2, jars 13 and 19 have low VDC readings and need to be replaced.
10/5/2011
188 C6 UPS-1D629-2A a During System A PM inverter leg #5 failed. 10/19/2011 189 C6 UPS-1D629-1A a Cell 77 terminal is wicking acid and corroding bus connector. 10/27/2011 190 C6 UPS-1D629-2B a Cell 45 has crack in front post seal. 10/27/2011
191 Con Serv W4 BAT-3B957-1C a Jar 27 has low DC voltage and high AC voltage readings (11.51 VDC, 523 mVAC) and needs to be replaced.
10/27/2011
192 IEOC BAT-1A310A-2 a Jar 8 has low DC voltage reading (13.18 VDC) and needs to be replaced. 11/2/2011
193 Con Serv W2
UPS-2B555-01
UPS-4B555-01
Contractor and PBMO personnel were conducting switchgear maintenance 11/20/2011 and allowed UPSes in 2B555 and 4B555 to run down on batteries. After battery rundown UPSes attempted to transfer to bypass and blew multiple static switch fuses.
11/20/2011
194 C7 STS/PDU-4C833A-01 a STS display backlight is bad and needs to be replaced. 11/9/2011 195 C7 BAT-1D745-1A a Cell 209 has crack from post to cover. 11/15/2011
196 C9 BAT-1C926-01 a There are 9 cells with voltage readings slightly above tolerance and overall string voltage is higher than nominal (average is 2.77 V/Cell)
11/17/2012
197 Con Serv W1 UPS-3B400-01 a UPS was on bypass with Load on Bypass, Un-Volts, and Reverse Power, and H/W Shutdown alarms.
12/4/2011
198 Con Serv W1 UPS-3B400-01 a UPS was in Bypass with Load on Bypass and Not OK to Transfer alarms at about 7:00 pm due to vault maintenance. UPS batteries were fully discharged and opened 2 of 3 static switch fuses (A and B phases).
12/4/2011
199 Con Serv W2 UPS-3B555-01 a Found unit alarming and entered room to find unit in bypass and Load on Bypass and Not ok to Transfer alarms.
12/5/2011
200 Con Serv W2 UPS-5B647-01 a POC Dwayne Lingenfelter found unit in bypass with OK to Transfer condition, no other alarms. Unit apparently went to bypass during vault maintenance.
12/5/2011
201 RDF BAT-1J7BHV1-2A a Jar 19 has low DC and high AC voltage readings (12.64 VDC and 140 mVAC) and needs to be replaced.
12/6/2011
202 C10 BAT-BB1040A-2A, String 1 a Jar 39 had low DC voltage (12.22 VDC) and slightly high AC voltage (35 mVAC) readings and needs to be replaced.
12/5/2011
203 C10 BAT-BB1040A-2C, String 2 a Jar 17 had low DC voltage (13.06 VDC) and slightly high AC voltage (90 mVAC) readings and needs to be replaced.
12/9/2011
204 C10 BAT-BB1040A-2D, String 1 a Jar 26 had low DC voltage (11.41 VDC) and slightly high AC voltage (80 mVAC) readings and needs to be replaced.
12/9/2011
205 Con Serv W1 BAT-3B400-1A,B,C a All jars in both strings have date code of 12/2006 1/1/2012
206 C6 BAT-1D629-1B a Cell 215 voltage fell back down to 2.183 VDC since last PM cycle. 1/16/2012
207 E6B BAT-ME659-01 a Cell 120 is continuing to leak onto jar and rack below. There are 2 leaks now.-
1/17/2012
208 C7
MBC-1C744A-A
MBC-1C744A-B
a During generator testing bypass sensing fuses in both MBCs were blown during open transfers.
1/29/2012
209 Con Serv W4 UPS-3B957-01 a
UPS went on battery during open-transition testing Sunday 1/29/2012 and ran down on battery before power came back. UPS then shut rectifier down, tripped input breaker and tripped main battery breaker. UPS was found to be in bypass 2/2/2012.
1/29/2012
210 Tenant O BAT-BB926A-1B a Jar 16 voltage is below the lower threshold voltage (13.20 VDC) and needs to be replaced.
2/6/2012
211 CCSP BAT-1B462-2B a Jar #5 voltage is below lower voltage tolerance (13.19 VDC) and needs to be replaced.
2/7/2012
212 C7 BAT-1D745-2A a Cell 115 has low DC voltage (2.150 VDC) and may eventually need to be jumped out.
2/9/2012
213 C7 BAT-1D745-2A a Cell 115 was not successfully charged by single cell charger between 2/15/12 and 2/19/12.
3/1/2012
214 C6 BAT-1D629-1B a Cell 215 was charged at 2.4 VDC for over 100 hours ending 3/15/2012 and is now only at 2.077 VDC.
3/15/2012
215 C10B BAT-BB1040A-1B, String 2 a Jar 10 had low DC voltage reading and needed to be replaced. 3/6/2012
216 C10B BAT-BB1040A-1D, String 4 a Jar 28 had low DC voltage reading (12.33 VDC) and needed to be replaced.
3/7/2012
217 C10B BAT-BB1040A-2D, String 1 a Jars 13 and 18 had low DC voltage readings (11.41 and 11.25 VDC) and needed to be replaced.
3/13/2012
218 C10B BAT-BB1040A-2D, String 3 a Jars 27 and 36 had low DC voltage readings (12.99 and 13.00 VDC) and needed to be replaced.
3/13/2012
219 C10B BAT-BB1040A-2D, String 4 a Jar 4 had low DC voltage reading (13.02 VDC) and needed to be replaced.
3/13/2012
220 Con Serv W2 UPS-5B647-01 a UPS went into alarm (DC Ground Fault) 3/18/2012 at 17:45 pm. Alarm condition was found by Data Center personnel early 3/19/2012.
3/18/2012
221 RDF BAT-1J7BHV1-1A a Jar 23 has low DC voltage reading and needs to be replaced. 3/22/2012
222 C7 BAT-1D745-2A a Cell 115 was charged at 2.4 VDC between 3/15/12 and 3/19/12. At time charger was removed cell voltage was 2.254 VDC (8:30 am). As of 11:00 am the voltage had dropped to 2.138 VDC
3/19/2012
223 Con Serv W1 BAT-3B400-1C a Found serious corrosion on tray for jars 29-32. 4/2/2012 224 Con Serv W1 BAT-3B400-1C a One of jars 29-32 leaked at one time but leak was never found. 4/2/2012
225 Segment 1 PDU-BG849-1 a Display showing BRD1 instead of Input. BRD1 KW = 212, KVA = 218. 4/11/2012
226 E6B UPS-ME660-01 a EPO pushbutton shield is missing and needs to be replaced. 4/23/2012 227 C6 MBC-1D629-B a EPO pushbutton shield is missing and needs to be replaced. 4/25/2012
228 Segment 1
PDU-BG849-7
PDU-BG849-8
PDU-BG849-9
PDU-BG849-10
a All of these PDUs are currently being disconnected and replaced by 2 new RPPs, RPP 8 and RPP10.
4/11/2012
229 Con Serv W2 UPS-5B647-01 a UPS has been experiencing “DC Ground Faults” for awhile now. present
230 IEOC BAT-1A310A-2 a Jar 26 has low DC voltage measurement (13.19 VDC) and should be replaced.
5/1/2012
231 Tenant O UPS-BB926A-01 a During annual PM VETI board partially failed for one fan circuit and had to be replaced along with 2 fuses (see FSR for parts list)
5/8/2012
232 CCSP
UPS-1B458-01, 02 UPS-
1B462-01, 02 a
All batteries checked good during PM. Battery string is 2007 date code.
Approaching end of manufacturers recommended life.
5/10/2012
233 C7 STS/PDU-4C833A-02 a Display shows Source 2 measurements as S1. 5/15/2012 234 B8B UPS-BB852-2A a Phase B DC capacitors failed and took out 3 fuses. 6/8/2012
235 C10B BAT-BB1040A-1D a String 3, jar 38 has a low DC volt reading and needs to be replaced. 6/7/2012
236 C10B BAT-BB1040A-2D a String 1, jars 24, 27, and 30 have low DC voltage and high AC ripple voltage readings and need to be replaced.
6/7/2012
237 C10B BAT-BB1040A-2D a String 2, jars 2, 7, 27, and 38 have low DC voltage and high AC ripple voltage readings and need to be replaced.
6/7/2012
238 C10B BAT-BB1040A-2D a String 3, jars 31 and 39 have low DC voltage and high AC ripple voltage readings and need to be replaced.
6/7/2012
239 C10B BAT-BB1040A-2D a String 4, jars 1, 26, 29, and 35 have low DC voltage and high AC ripple voltage readings and need to be replaced.
6/7/2012
240 Mother UPS MBC-ME846-A, B a GUIs for both MBCs were removed due to failure many years ago. present
241 Con Serv W1 BAT-3B400-1C a Jar 29 has low DC voltage reading and needs to be replaced. 7/16/2012
242 C10B BAT-BB1040A-1B a String 2, Jar #13 has a low DC volt reading and should be replaced. 9/6/2012
243 C10B BAT-BB1040A-1D a String 2, Jar #10 has low DC and high AC voltage readings and needs to be replaced.
9/5/2012
244 C10B BAT-BB1040A-2D a String 1, Jars #4, 7, 8, 16, and 17 have low DC voltage readings and need to be replaced
9/4/2012
245 C10B BAT-BB1040A-2D a String 2, Jar #37 has low DC and high AC voltage readings and needs to be replaced.
9/4/2012
246 C10B BAT-BB1040A-2D a String 3, Jars #10, 11, and 19 have low DC and high AC voltage readings and need to be replaced.
9/4/2012
247 C10B BAT-BB1040A-2D a String 4, Jars #2, 14, 21, 32, 33, and 37 have low DC and high ac voltage readings and need to be repl.
9/4/2012
248 RDF BAT-1J7BHV1-2A a Jar #12 has low DC volt reading and needs to be repl. 9/25/2012
249 RDF
BAT-1J7BHV1-1A BAT-
1J7BHV1-2A BAT-
1J7BHV1-1B
BAT-1J7BHV1-2B
a All jars are more than 5 years old and should be replaced. 10/12/2012
250 C6 UPS-1D629-2A a Could not turn inverter off during APM. 10/10/2012
251 Con Serv W5 BC-2B240-03 a Jar 14 has low DC and high AC voltage readings (12.39 VDC and 43 mVAC) and needs to be replaced.
10/11/2012
252 Con Serv W4 BAT-3B957-1E a Jar 11 has low DC and high AC voltage readings (11.36 VDC and 98 mVAC) and needs to be replaced.
10/19/2011
253 C10B BAT-BB1040A-1D a String 2, Jar 10 has low DC and high AC voltage readings and needs to be replaced.
12/13/2012
254 C10B BAT-BB1040A-2D a String 1, Jars 4, 6, 8, 11, 12, 17, and 28 have low DC and/or high AC ripple voltage readings and need to be replaced.
12/13/2012
255 C10B BAT-BB1040A-2D a String 2, Jars 3, 5, 14, 16, and 37 have low DC and high AC ripple voltage readings and need to be replaced.
12/13/2012
256 C10B BAT-BB1040A-2D a String 3, Jars 1, 14, 19, 26, and 40 have low DC voltage and high AC ripple voltage readings and need to be replaced
12/13/2012
257 C10B BAT-BB1040A-2C a Replacement jars for items 183 – 186 above were taken from string 4 which was eliminated.
12/20/2012
258 Mother UPS UPS-ME846-02 a
During PM, found that phase-to-neutral output voltage for phase B was 0 VAC and phase -to-phase output voltages for phases A and B were displayed as phase-to-neutral (274 and 275 VAC). Found that fuse was blown on ACPZ (Transfer Acquisition) Board. Replaced fuse but problem was not entirely resolved. Next day found capacitor on same board melted and fuse 4 blown.
1/8/2013
259 Tenant O UPS-BB926A-02 a UPS registered intermittent fan failure alarms beginning 1/30. 1/30/2013 260 C1 BAT-1D135-01 a Cells #93, 143, and 226 have broken flame arrestors. 2/5/2013 261 C1 BAT-1D135-02 a Cells #34, 43, 63, 67, and 68 have broken flame arrestors. 2/5/2013 262 C7 BAT-1D745-2A a Cells #7 and 9 have serious corrosion on intercell straps 2/11/2013
263 C7 BAT-1D745-2B a The cable which attaches to cell #41 has serious corrosion which needs to be cleaned.
2/11/2013
264 C8
BAT-1C879-01
UPS-1C881-01
a While performing quarterly PM on string BAT-1C879-01 found that ripple voltage and current was unusually high (1.825 VAC and 30.5
AAC).
2/12/2013
265 C8
BAT-1C879-02
UPS-1C881-02
a While performing quarterly PM on string BAT-1C879-02 found that ripple voltage and current was unusually high (1.135 VAC and 21.4
AAC).
2/12/2013
266 Mother UPS UPS-ME846-04 a Jeremy Henning (Gen shop) discovered fan fail alarm on UPS-ME846- 04 2/27/2013.
2/27/2013
267 B8B BAT-BB852-2B a During initial PM completed soon after all jars in B8B were replaced with new jars, cell 126 was found to have very low voltage and specific gravity reading along with a slightly high intercell reading.
3/14/2013 a TD and JI tested all batteries for C10B modules 2C, 1D, and 2D on 3/1/2013. The following jars were found to be bad and replaced the same day (all in module 2D):
a1 String 1 - cells 10, 14, 15, 23, 38, and 40.
a2 String 2 - cells 6, 8, 34, and 35.
a3 String 3 - cells 2, 4, 15, 21, 22, 27, 28, 29, 31, 32, 33, 34, 35, and 39.
269 C10B MBC-BD1041-D a On Tuesday, April 2 2013, UPS isolation breaker Q5N opened up for no reason at approximately 5:00 or 6:00 pm.
4/2/2013
270 Con Serv W2 UPS-3B555-01 a
After completing PM and while attempting to start UPS back up, UPS registered a Hardware Failure condition and would not start back up.
After troubleshooting unit, discovered that ground fuse (small 2 amp) on power supply board was blown.
4/16/2013
271 Con Serv W5 BC-3B240-05 a Jar 35 has low DC and high AC voltage readings and needs to be replaced.
4/24/2013
272 C10B BAT-BB1040A-1A a Module batteries (4 strings) due for replacement. 4/19/2013 273 C10B BAT-BB1040A-1B a Module batteries (4 strings) due for replacement. 4/12/2013 274 C10B BAT-BB1040A-1C a Module batteries (4 strings) due for replacement. 4/19/2013 275 C10B BAT-BB1040A-1D a Module batteries (4 strings) due for replacement. 4/1/2013 276 C10B BAT-BB1040A-2A a Module batteries (4 strings) due for replacement. 3/28/2013 277 C10B BAT-BB1040A-2B a Module batteries (4 strings) due for replacement. 4/10/2013 278 C10B BAT-BB1040A-2C a Module batteries (4 strings) due for replacement. 4/3/2013 279 C10B BAT-BB1040A-2D a Module batteries (4 strings) due for replacement. 4/5/2013
3/1/2013268 C10B BAT-BB1040A-2D
280 C10B BAT-BB1040A-2C, String 4 a Jar 22 had low DC and high AC voltage readings during initial PM on string.
5/9/2013
281 Con Serv W1 BAT-5B400-1A, 1B a All jars in both strings have date code of 03/08. 3/1/2013
282 C7 STS/PDU-4C833A-01 a Before taking display readings found that a fan was making excessive noise (customer had already submitted request for maintenance a few days prior but CPG was never notified).
5/15/2013
283 B8B UPS-BAT-BB852-1A a There are 15 cells with slightly high voltage readings (all between
2.321 and 2.30 VDC).
6/11/2013
284 C10B MBC-BC1040-B a
CPG received an emergency call on the night of 7/2/2013 at around 8 pm for System B Q5N opening for no apparent reason. PBMO reclosed Q5N and reset system back to normal configuration. This seems to be the same issue as was experienced a couple of months ago with trip element on System D. CPG tech downloaded the report from the personalization but nothing stands out.
Merlin Gerin 1600 A CAT No: 54754
7/2/2013
285 Mother UPS BAT-ME846-04 String 2 a Jar 33 has low DC and high AC voltage readings (11.47 VDC and 450 mVAC) and needs to be replaced.
7/1/2013
286 Mother UPS BAT-ME846-06 String 2 a Jar 38 has low DC voltage reading (13.19 VDC) and needs to be replaced.
7/3/2013
287 Con Serv W2
UPS-4B555-01
UPS-5B647-01
a Both UPS units have been experiencing nuisance alarms (Static Switch Unable) for some time now. The alarms come and go throughout the day but are momentary in duration.
7/1/2013
287 Con Serv W2
UPS-4B555-01
UPS-5B647-01
b Both UPS units have been experiencing nuisance alarms (Static Switch Unable) for some time now. The alarms come and go throughout the day but are momentary in duration.
7/1/2013
288 B8B MBC-BB852-A a Output breaker Q5N tripped on 8/31/2013. 8/31/2013
289 Mother UPS MBC-ME846-A a Output breaker (same style as Q5N) downstream from Q5N tripped on 9/4/2013.
9/4/2013
290 Tenant O UPS-BB926A-01 a Batts in all 4 strings would be 5 years old by Nov. 2013. N/A a Batts for UPS-2B555-01 string 1 and 2 would be 5 years old by Dec 2013.
b Batts for UPS-3B555-01 string 1 and 2 would be 5 years old by Dec 2013.
c Batts for UPS-4B555-01 string 1 and 2 would be 5 years old by Nov 2013.
a Batts for UPS-2B960-01 strings 1 thru 5 would be 5 years old by Oct 2014.
b Batts for UPS-2B957-01 strings 1 thru 5 would be 5 years old by Oct 2014.
293 RDF BAT-RDF1J7B-01 a Jars 7, 8, and 13 thru 20 (10 jars all total) are all below DC voltage tolerance (13.20 VDC) and should be replaced.
9/23/2013
294 Mother UPS BAT-ME846-01, String 4 a Jar 30 has high AC voltage reading (150 mVAC) and needs to be replaced.
10/1/2013
295 Mother UPS UPS-ME846-02 a On 10/11/2013 UPS shut down and dropped out of System A due to input caps failing.
10/11/2013
296 Mother UPS UPS-ME846-05 a Inverter legs were shorted out when phase rotation was reversed during power relocation in Mother UPS.
10/12/2013
9/25/2013 9/26/2013
291 Con Serv W2
UPS-2B555-01
UPS-3B555-01
UPS-4B555-01
N/A
292 Con Serv W4
UPS-2B960-01
UPS-3B957-01
297 Con Serv W4 BAT-3B957-1B a Tested batteries during annual PM on 10/30/2013. There are seven jars with DC voltage readings below tolerance and 9 jars with DC voltage readings at or slightly above tolerance.
10/30/2013
298 C1 BAT-1D135-02 a During semi-annual pm on 5/20/2013 hairline cracks were discovered in jar 12 (cells 45-48).
5/20/2013
BAT-1D745-2B a All jars have date code 9/2004 and are scheduled for replacement. 11/1/2013
BAT-1D745-2A b All jars have date code 9/2004 and are scheduled for replacement. 11/1/2013
BAT-1D745-1A c All jars have date code 9/2004 and are scheduled for replacement. 11/1/2013
BAT-1D745-1B d All jars have date code 9/2004 and are scheduled for replacement. 11/1/2013
300 C8 BAT-1C879-01 a Cell 156 has low DC voltage measurement (2.111 VDC) as well as low specific gravity reading (1.237) and will require single cell charge. If charge doesn't raise voltage cell will have to be jumped out.
11/11/2013
301 Mother UPS System A:
UPS-ME846-02
a Monday, December 9, NMCC personnel called the BOCC complaining about large scale power outages in NMCC. PESP engineers were called 12/9/2013
302 Mother UPS BAT-ME846-05, String 4 a Jar 27 has low DC and high AC voltage readings (12.31 VDC and .130 VAC) and needs to be replaced. 1/7/2014
303 Mother UPS BAT-ME846-01, String 4 a Jar 30 has low DC voltage reading (13.17 VDC) and needs to be replaced. 1/2/2014
304 E6B BAT-ME659-02 a One jar damaged during installation and could not be used. Battery string installation was completed missing that jar, float voltage 2/7/2014
305 E6B BAT-ME659-01 a Battery string is aging and needs to be replaced (date code for jars 2/2003). 2/1/2013
306 E6B BAT-ME659-02 a Battery string is aging and needs to be replaced (date code for jars 2/2003). 2/1/2013
307 C6 BAT-1D629-2B a Battery string is aging and needs to be replaced (date code for jars 3/2003). 3/1/2013
299 C7
308 C6 BAT-1D629-1A a Battery string is aging and needs to be replaced (date code for jars 3/2003). 3/1/2013
309 C6 BAT-1D629-2A a Battery string is aging and needs to be replaced (date code for jars 3/2003). 3/1/2013
310 C6 BAT-1D629-1B a Battery string is aging and needs to be replaced (date code for jars 3/2003). 3/1/2013
311 C9 BAT-1C926-02 a
During quarterly PM, 32 cells were tested with slightly high voltage readings (all between 2.30 and 2.329 VDC). Number of high DC voltage readings is increasing from PM to PM and string voltages need to be evened out.
2/11/2014
312 RDF BAT-RDF1J7B-01 a
Jars 7, 8, and 13 thru 20 (10 jars all total) are all below DC voltage tolerance (13.20 VDC, all jars are between 13.12 and 13.17 VDC) and have been below tolerance most of the time since they were installed.
Room temperature is 58 F and is most likely the main reason for the unbalanced battery voltages.
3/5/2014
313 C1 UPS-1D135A-01 a Unit was in alarm with fan failure at time of arrival. 3/24/2014 314 Mother UPS UPS-ME846-04 a Phase C load current was not displayed properly on UPS display. 3/25/2014 315 Mother UPS UPS-ME846-04 a Input capacitors are original and are failing. 3/26/2014 316 Mother UPS UPS-ME846-05 a Input capacitors are original and are failing. 3/27/2014
317 Mother UPS UPS-ME846-01, string 4 a Jar 30 has low DC voltage reading (13.11 VDC) despite being a new jar installed 1/13/2014.
4/2/2014
317 Mother UPS UPS-ME846-05, string 4 a Jar 27 has low DC voltage reading (13.11 VDC) despite being a new jar installed 1/13/2014.
4/8/2014
318 C6…