For Official Use Only
Facilities Engineering
Minimum Technical Specifications for
Structures, Systems, Equipment, & Components:
Identification, Labeling, and Marking
Table of Contents
1. Purpose
2. Scope
3. References. See Appendix 1
4. Definitions. See Appendix 2
5. General Requirements
5.1. Labeling
5.2. Color Coding
5.3. Language
5.4. Other Identification Systems
6. Facilities
6.1. Structures
6.1.1. Identification
6.1.2. Labeling
6.2. Rooms, Cubicles, Partitions, and Enclosures
6.3. Raised Floor
6.3.1. Non-IT Systems, Equipment, and Components
6.3.2. IT Equipment
6.3.3 Whips
7. General Requirements - Systems, Equipment, and Components Labeling
7.1. Physical Format
7.2. Unique Identifier (UID) Number
7.3. Physical Characteristics
7.3.1. Materials
7.3.2. Attachment
7.3.3. Character Design and Size
8. Mechanical Systems, Equipment, & Components
8.1. General Requirements
8.1.1. Labeling
8.1.2. Color Coding – Labels
for
Structures, Systems, Equipment, & Components:
Version Date: 30 June 2017 Page 2 of 34
8.2. Typical Mechanical Systems, Equipment, and Components
8.3. Valves & Dampers
8.4. Dual-Fed Mechanical Systems, Equipment, & Components
8.5. Mechanical Piping and Electrical Conduit Systems, Equipment, and Components
8.5.1. Color Coding – Pipe and Conduit
9. Electrical Systems, Equipment, & Components
9.1. General Requirements
9.1.1. Labeling
9.1.2. Color Coding - Labels
9.2. Typical Electrical Systems, Equipment, and Components
9.3. Other Electrical Systems, Equipment, and Components
9.3.1. Electrical Raceways, Junctions, and Boxes
9.3.2. Devices
9.3.3. Security Systems, BAS, Equipment, and Components
Appendix 1. References
Appendix 2. Definitions
Appendix 3. Systems, Equipment, & Components Designator List
Appendix 4. Switchgear/Motor Control Labeling Example
Appendix 5. Switchboard/Large Panelboard Labeling Example
Appendix 6. Panel Schedule Labeling Example
Appendix 7. PDU Schedule Labeling Example for
Structures, Systems, Equipment, & Components:
Version Date: 30 June 2017 Page 3 of 34
Figures
Figure 1 – Compliant Column Label Figure 2 – Sample Unit/Cabinet Unique Identifier Figure 3 – Compliant Cabinet Unique Identifier Figure 4 – Compliant Cabinet Unique Identifier Figure 5 – Compliant Whip/MPDU A-Feed Figure 6 – Compliant Whip/MPDU B-Feed Figure 7 – Compliant Label Figure 8 – Compliant Mechanical SEC Label Figure 9 – Compliant Mechanical SEC Label Figure 10 – Compliant Mechanical SEC Label Figure 11 – Compliant Mechanical SEC Label Figure 12 – Compliant Piping System Marking and Labeling Figure 13 – Sample IT Power Whip Label Figure 14 – Compliant Electrical Distribution SEC Label Figure 15 – Compliant Electrical Distribution SEC Label Figure 16 – Compliant Junction Box Label Figure 17 – Compliant Electrical Label Figure 18 – Compliant Electrical Label Figure 19 – Switchgear Figure 20 – Panelboard Figure 21 – Panel Schedule Template Figure 22 – Electrical Panel Figure 23 – PDU Panel Figure 24 – PDU/RDC/STS Panel Schedule Template Figure 25 – PDU/RDC/STS Panel Schedule Template for
Structures, Systems, Equipment, & Components:
Version Date: 30 June 2017 Page 4 of 34
Tables Table 1 – Compliant Color-Coding for Mechanical Piping and Electrical Conduit SEC Table 2 – Compliant Color-Coding for Electrical and Mechanical SEC Labels Table 3 – SEC Designator
Version Date: 30 June 2017 Page 5 of 34
Minimum Technical Specifications for
1. Purpose The purpose of this Facilities Engineering specification is to establish guidance for identifying, marking and labeling Structures, Systems, Equipment, and Components (SSEC)
2. Scope This specification contains instruction for uniform identification, labeling, and marking of SSEC at DISA Enterprise Services locations. Applications include:
• Establishing standardized SSEC identification, labeling, and marking schemes
• Identifying, labeling, and marking new SSEC when installed
• Ensure uniform identification of SSEC across the enterprise
Within this specification, a ‘shall’ statement identifies mandatory elements and requirements. A ‘should’ statement is a recommendation that is based on standard industry practice and good business policy. In limited circumstances, the word ‘may’ is used when permission is granted rather than constituted as a requirement.
3. References. See Appendix 1
4. Definitions. See Appendix 2
5. General Requirements SSEC shall be labeled per operational requirements before being designated operable or in service.
Labeling of SSEC in areas where hazards exist (i.e., high structures and confined spaces) shall be evaluated against safety requirements. For example, to reduce personnel risk, some SSEC could be labeled as site conditions permit (e.g., shutdown), or when scheduled maintenance is performed.
5.1. Labeling
Labels shall be permanently attached and designed to withstand wear, erosion and corrosion. They shall be heat resistant in high temperature areas and corrosion resistant in acidic or caustic areas.
Position labels so they are readily visible and, oriented in a horizontal position on a flat surface, where feasible. Labels shall be legible without manipulation by site personnel. Large SSEC shall be labeled in multiple locations, in close proximity to where workers perform their tasks.
Labels or tags installed under this specification shall not interfere or alter existing manufacturer’s nameplate or code information.
Labels shall be mounted in such a way as to preclude accidental removal and located to eliminate any possible confusion as to the item being identified and shall not obscure other items nearby.
Label size shall be based on available lighting and anticipated reading distances. SSEC which require local operation during blackout or reduced visibility conditions shall be marked with reflective or glow-in-the-dark tape.
Labels shall not interfere with an operator’s ability to read the instrument, display, or gauge.
Version Date: 30 June 2017 Page 6 of 34
Minimum Technical Specifications for
5.2. Color Coding
Label colors shall provide a high contrast between characters and background to enhance legibility. Color coding for SSEC shall be assigned only one meaning per color scheme and shall be consistent.
5.3. Language
Use of SSEC unique identifiers (UIDs) and noun descriptions shall be consistent among SSEC labels, equipment lists, drawings, procedures, checklists, and load lists. Checklists, procedures, and installed labels shall use UIDs to describe the name and number nomenclature for the SSEC.
Abstract symbols shall be used only if they have a commonly accepted meaning for all intended users (e.g.
Brevity should not be stressed if the results will be unfamiliar to operating personnel. Words on labels should be concise and still convey the intended meaning.
5.4. Other Identification Systems
This specification is not intended to conflict with any other mandatory standard(s) or guidance affecting the data center environment. If conflicts are identified, DISA Facilities Engineering will make a determination on the governing standard(s) or guidance. This specification does not define identification, labeling, and marking standards for communications, data cabling, computing and storage enclosures, or non-raised floor IT equipment.
Identification tools such as Information Technology Service Management (ITSM), Data Center Information Management (DCIM), and Computerized Maintenance Management System (CMMS) shall include database fields (where applicable) to identify the standardized UID Number as specified herein.
These fields are not intended to supplant or replace other identification numbers already in use by other systems.
“Common” or “Legacy” and BAS Name information shall be retained in written and supplementary database field formats for historical cross-reference compatibility.
6. Facilities
6.1. Structures
6.1.1. Identification
DISA occupied space, on load-bearing columns (or posts), shall have column labels to identify the proper column number. This column number is considered a unique identifier (UID); an associated attribute that serves to uniquely define a quadrant around the specific column and abuts quadrants of adjacent columns.
Using an alphanumeric system, column UIDs shall designate A01 as the first corner column of the building as defined by current architectural and MEP drawings. UIDs shall reference the original A&E drawings, as applicable. For structures without internal columns (i.e., only four (4) corner columns), designate A01 for the whole structure. In absence of a column on quadrant boundaries provide ceiling-hung UIDs.
Version Date: 30 June 2017 Page 7 of 34
Minimum Technical Specifications for
6.1.2. Labeling
Column UIDs shall be a four (4) inch character, semi-gloss black lettering with the top of character not more than six
(6) inches below ceiling, concrete slab, truss line or typically accepted physical divider between workspace and ceiling line. UIDs may be applied using paint, adhesives, or other means that meet the required dimensions and characteristics mentioned above. UIDs shall be located on all sides with a minimum of two (2) opposing sides of each column; orientation lengthwise or widthwise of each room is not prescribed. For round columns, UIDs shall be located at N, S, E and W column locations.
6.2. Rooms, Cubicles, Partitions, and ISO Enclosures
All rooms, cubicles, partitions, and enclosures within each facility shall be labeled with the appropriate room, cubicle, or partition (UID) numbers at all entrances. Signage shall be posted immediately adjacent to the entrance designating the room, cubicle, or partition area being entered. Room numbers should be three (4) numbers in length, with the first number designating the floor number before the underscore and three numbers uniquely designating the room to match the archive drawings. For example, RM_1-101 (Room 101) is on the first floor and is the first room designated. Rooms may also retain their name; e.g., Battery Room as long as the name is in line with the current room function and is included as part of the room number; e.g., Battery Room RM_1-103. Cubicles, partitions, and enclosures should be four (5) numbers in length, with the first number designating the floor number before the underscore and the remaining numbers uniquely designating the cubicle, partition, or enclosure. For example, Cubicle 2000 is CUB_2-001 on the second floor and is the first cubicle designated. Subsequent cubicles numbers should be in sequential order; i.e., CUB_2-002, CUB_2-003, etc.
6.3. Raised Floor
In order to cross-identify Computer Room Air Handler (CRAH) units, In Row Coolers (IRC), Water Distribution Units (WDU), Humidifiers (HUM), Critical Distribution Panel (UDP), Static Transfer Switches (STSs), Power Distribution Units (PDUs), Remote Distribution Cabinets (RDCs), and other relevant miscellaneous facility equipment physically located on the raised floor, each unit or cabinet shall be tagged with its alphanumeric UID.
The IT unit or cabinet grid location should consist of one or more letters followed by three numbers. The numeric portion of the UID will include leading 0s. As examples, the unit or cabinet whose right front corner, (from the perspective of the unit or cabinet / the left front corner when looking at the front of the rack) is at AJ-006 will be named AJ006, the unit or cabinet whose right front corner is at AK-009 will be named AK009, the unit whose right front corner is at AV-002 will be labeled AV002, and the unit whose right front corner is at AC-014 will be named AC014 (Figure 2).
Figure 1 – Compliant Column Label
Version Date: 30 June 2017 Page 8 of 34
Minimum Technical Specifications for
If units or cabinets rest on more than one tile, the grid location for the units or cabinets can be determined by using the same corner on every unit or cabinet (the right front corner; from the perspective of the unit or cabinet / the left front corner when looking at the front of the rack). This grid location is determined not only from the right front corner of the unit or cabinet, but also by the ‘front’ tile upon which the unit or cabinet predominantly rests (front majority). As an example, in Figure 2, there are two Units that don’t line up with the grid: Unit 1 and Unit 2. Sample Unit 1 rests on four adjacent tiles with its right front corner resting predominantly on tile/grid AC-014. Its UID would therefore be AC014. Sample Unit 2 rests on six adjacent tiles with its right front corner resting predominantly on tile/grid AJ-006.
In data centers the floor number should be added as a prefix to the unit or cabinet number. For example, 3AJ006 is the label for the unit or cabinet whose right front corner is at tile AJ006 on the 3rd floor of the data center.
Figure 2 – Sample Unit/Cabinet Unique Identifier
6.3.1. Non-IT Systems, Equipment, and Components
For non-IT Systems, Equipment, and Components (SEC) on the raised floor, the grid location shall be captured on Line 1 of the SEC label as outlined under Section 7.
6.3.2. IT Equipment
For IT equipment on the raised floor, the UID label information shall be posted on the front and rear exterior of each rack or cabinet, on the rack unit’s top right side (top left as facing it) of the frame above the door. The minimum standard for these UID labels is machine-printed paper tags secured with clear plastic or acetate adhesive tape. Font style shall be bold sans serif font with a typical font size of 28.
Labels shall consist of a rectangular tag imprinted with one plus (1+) lines of information:
Line 1: Floor Number (required) Grid designator (required)
Version Date: 30 June 2017 Page 9 of 34
Minimum Technical Specifications for
Line 2: PDU # - panel # - circuit # (as required)
Additional Lines: PDU # - pnl # - ckt # (as required)
For Line 1, the raised floor grid designator of the IT equipment is required and shall appear as follows: the floor number (as applicable), and the corresponding alphanumeric grid UID as outlined in Section 6.3. Line 2, all information is required, to include the PDU sequence number followed by a dash, the panel number followed by a dash, and the circuit number. Additional lines are to be added for each additional circuit with all information is required, to include the PDU sequence number followed by a dash, the panel number followed by a dash, and the circuit number.
Figure 3 – Compliant Cabinet Unique Identifier
Figure 4 – Compliant Cabinet Unique Identifier
6.3.3 Whips and MPDUs
Underfloor whips provide power from the PDU to the rack or cabinet on the raised floor. Whip cables shall have continuous external jacketing to correspond with the feed: 1) white for A-feed and 2) blue for B-feed (see Figure 5 and 6). Whips shall be connected to an underfloor receptacle for placement of the Master Power Distribution Units (MPDUs).
The MPDU cords shall be marked with tape to demarcate the feed: 1) white for A-feed and 2) blue for B-feed. The tape shall be placed in two locations: 1) within one (1) foot from where the MPDU plugs into the whip receptacle/socket and 2) where the MPDU cord enters the rack. The width of the tape application shall be a minimum of four (4) inches wide.
The underfloor receptacle, MPDU cord and in rack MPDU shall be labeled to identify the supporting PDU, panel, and circuit (see Figure 5 and 6). The minimum standard for these UID labels is machine-printed paper tags secured with clear plastic or acetate adhesive. Font style shall be bold sans serif font with a typical font size of 28.
Labels shall consist of a rectangular tag imprinted with one (1) line of information:
Line 1: PDU # - pnl # - ckt # (required)
4AZ023
PDU_1-A-02-Pnl 01-Ckt 05,07,09 PDU_1-B-02-Pnl 01-Ckt 05,07,09
1AH078
PDU_1-A-04-Pnl 02-Ckt 01 PDU_1-B-04-Pnl 02-Ckt 01
PDU_1-A-04-Pnl 03-Ckt 07 PDU_1-B-04-Pnl 03-Ckt 07
Version Date: 30 June 2017 Page 10 of 34
Minimum Technical Specifications for
For Line 1, all information is required, to include the PDU sequence number followed by a dash, the panel number followed by a dash, and the circuit number (see Figure 5 and 6). The interior rack MPDU shall be identified in the same way (figure not shown).
Figure 5 – Compliant Whip/MPDU A-Feed Figure 6 – Compliant Whip/MPDU B-Feed
7. General Requirements - Systems, Equipment, and Components Labeling
7.1. Physical Format
The standard format for compliant System, Equipment, and Component (SEC) labels shall contain all necessary information to completely identify the labeled SEC for purposes of property accountability, operations and maintenance procedures and processes, and safety. Labels shall consist of a rectangular tag or pendant engraved, embossed, or imprinted with five (5) lines of information:
Line 1: Unique Identifier (UID)
Number (required) Line 2: Descriptor (Capacity)
(required) Line 3: Parent or From UID
(electrical source) (required) Line 4: “Common” or “Legacy” name (optional) Line 5: BAS Device name
(as applicable) (optional)
An explanation of Line 1 UID Number is found in the following section, Section 7.2.
• Line 2 varies by SEC type. For most SEC, this line captures the capacity of the SEC and is a required field. For valves, it captures the valve position and is required.
• Line 3 is a required field and refers to the upstream electrical SEC. Line 3 captures the Parent
Line 1
Line 2
Line 3
Line 4
Line 5
Figure 7 – Compliant Label
PDU_4-B-06
225 kVA
UDP_1–B–02-Ckt 17,19,21
“PDU303B”
Version Date: 30 June 2017 Page 11 of 34
Minimum Technical Specifications for
UID Number for the SEC in question. On the label, it is reflected with the Parent UID Number immediately following.
• For Line 4, the “Common” or “Legacy” name is optional. Double quotes will be used around “Common” or “Legacy” names to differentiate between BAS Device names in Line 4 and “Common” or “Legacy” names in Line 4.
• For Line 5, the BAS Device name is required when applicable. If an SEC has a BAS Device name, which can be found in the BAS OEM Manuals, it is a required field. If an SEC does not have a BAS Device name, then the field is left blank.
7.2. Unique Identifier (UID) Number
All systems, equipment, and components (SEC) shall be assigned a Unique Identifier (UID) Number.
Line 1 of Figure 7 – Compliant Label, designates the UID Number of the SEC to which the label is attached. The UID Number shall (unless otherwise noted) have four (4) fields with the 1st Field as the SEC Designator then underscore then 2nd Field the floor number, as the System Designator, and the 3rd and 4th Fields as Sequence Numbers, with dashes separating each field.
The first character set (1st Field) of the UID Number represents the SEC Designator shall be up to six (6) total characters in length. The first characters, one (1) to five (5), are alpha, and the last character is numeric. The alpha characters are the SEC Designators. The SEC Designators are required. Reference Appendix 3 for approved SEC Designators.
The second character set (2nd Field) of the UID Number represents the floor number. An underscore will separate the SEC Designator from the floor number.
The third character set (3rd Field) represents the System Number and shall be used to designate sequential SEC with the same SEC Designator (e.g., sequential distribution panels connected to a critical UPS bus would be distinguished as UDP_1-A-01, UDP_1-A-02, etcetera) and shall be alphanumeric.
The fourth character set (4th Field) is an additional Sequence Number, which shall only be used for specifically identified SEC Designators. When required, it shall be a single numeric character. For example, a distribution panel also has a sub-panel, the distribution panel would be referred to as DP_1-A- 01-01 and the sub-panel would be referred to as DP_1-A-01-02.
Examples:
PDU_4-B-06 (PDU on the 4th Floor connected to the B Bus, Unit # 6) MTS_1-CD-01 (Mechanical transfer switch on the 1st floor connected to both C & D Buses, Unit # 1) EDP_1-C-01-02 (Essential distribution panel on the 1st floor connected to the C bus, Unit #1 subpanel #2) CRAH_3-D-15 (CRAH unit on the 3rd floor connected to the D bus, Unit #15)
7.3. Physical Characteristics
7.3.1. Materials
Plastic Labels: Flexible engraving stock (aka Lamicoid or Phenolic) with at least a two-color plastic material to obtain the required color coding combination is the preferred material for permanent SEC labels described in Sections 7 and 8. Characteristics of flexible engraving stock include abrasion, heat, wear, and chemical resistance. Machine-printed identification information, if used, shall be indelible, environmentally stable, and chemically resistant. Machine-printed identification information is only allowed if spelled out in this
Version Date: 30 June 2017 Page 12 of 34
Minimum Technical Specifications for specification or by special permission through the Chief of Facilities Engineering or Chief of BOS Maintenance.
Metal Labels: Metal tags are acceptable for permanent equipment SEC labels described in Sections 7 and 8.
Paints or powder coatings used on these tags shall be environmentally stable, chemically resistant, and wear resistant.
Identification Tape: Commercially available tape products may be used for labeling of common SEC where detailed UID’s and other information is not necessary; for example, on insulated piping systems, labels indicating contents and direction of flow are generally sufficient.
Machine-Printed Identification Tags: On SEC subject to frequent modification or replacement (for example, power whips from a PDU to an IT equipment rack), machine-printed labels are acceptable. These typically print on a flexible form of machine-generated plastic-coated material, which shall be secured to the SEC in such a manner as to protect the labeling information from degradation.
Unapproved Materials: Materials which can be lost, damaged, rendered unreadable, easily removed, soiled or degraded by operating environment, or which are of a non-permanent nature shall not be used for labeling or identification purposes. This includes (but is not limited to) paper, paper in clear plastic protectors, and direct labeling of SEC with markers or paint.
7.3.2. Attachment
Adhesives: Adhesives may be used to secure labels or tags to SEC. Adhesives should securely fasten the label to the component without causing degradation to the SEC or the label. The adhesive shall be chemically compatible with the label material, the component material, and the environment. Adhesives shall not be used on stainless steel piping or components.
Wire: Bare wire may be used for attaching labels to SEC where use of adhesives is not practical and there is no risk of the bare wire becoming electrically energized (e.g., valve tags).
Cable Ties: Standard 50lb cable ties (a.k.a. zip ties, nylon ties, plastic ties, tie wraps) may be used for attaching labels to SEC where use of adhesives is not practical (e.g., valve tags).
Chain: Zinc plated general utility chain may be used for attaching labels to SEC. The type of chain shall be single-jack chain of trade size 20 or 18.
Screws or Rivets: Screws or rivets may be used to secure labels to SEC as long as the attachment does not cause degradation to the SEC or label. Screws shall be metal type, with size, length, diameter, head, pitch, and axis not prescribed, but sufficient to adequately adhere labels. Rivets shall be steel, with type and dimensions not prescribed, but sufficient to adequately adhere labels.
7.3.3. Character Design and Size
Labels shall be formed with upper and lower case letters using simple letter styles as reflected in Figures 8 - 1 1 . A bold sans serif font, minimum font size 24, is standard for SEC labeling purposes. The maximum standing viewing distance for minimum font sizes is 60 inches (from label to the eye of the standing individual). With this font size, a 3” x 5” label is recommended. Labels not visible from this distance will use bold sans serif font 28 (24 for Line 1 of 7). With this font size, a 4” x 6” label is recommended. No additional restrictions are set on other labels in order to allow flexibility in aesthetic design.
Version Date: 30 June 2017 Page 13 of 34
Minimum Technical Specifications for
8. Mechanical Systems, Equipment, & Components
8.1. General Requirements
8.1.1. Labeling
Mechanical distribution systems, equipment, and components (SEC) including, but not limited to, chillers, cooling towers, pumps, valves, Air Handler Units, tanks, generators, Computer Room Air Handlers (CRAHs), compressors, air dryers, fans, boilers, hot water heaters, backflow preventer assemblies, fire protection SEC, filters, Variable Air Volume (VAVs), Variable Frequency Drive (VFDs), feed systems, etcetera, shall be labeled with plastic labels. Labels shall be attached to a structural member of the SEC not normally removed during routine maintenance (e.g., base plate) and in a consistent location for similar SEC.
All mechanical distribution within the datacenter shall incorporate specific color identification to differentiate between fire protection, non-critical/non-essential, dual-fed, and essential SEC.
8.1.2. Color Coding – Labels
Color coding assignment for mechanical SEC labels shall be in accordance with Table 3 – Compliant Color-Coding for Electrical and Mechanical SEC.
8.2. Typical Mechanical Systems, Equipment, and Components
Typical mechanical systems, equipment, and components (SEC) include chillers, cooling towers, AHUs, tanks, generators, CRAHs, etcetera, and shall be labeled in the following manner defined by Figure 7.
8.3. Valves & Dampers
Facility valves and dampers shall be labeled separately from the associated systems, equipment, and components (SEC), unless part of an assembly.
Stainless steel tagging wire shall be placed in such a manner so as not to damage the valve stem or impede operation of the valve. Label plates and connecting wire shall not be threaded through the valve hand wheels, operating chains, or damper linkage.
CRAH_4–B–16
40 Ton
UDP_1-B-02 Ckt 01,03,05
“CRAC 15”
Line 3
Line 4
Line 5
Figure 8 – Compliant Mechanical SEC Label
Figure 9 – Compliant Mechanical SEC Label
DT_1-FO-01
200 GAL
“Fire Pump Tank 9”
Version Date: 30 June 2017 Page 14 of 34
Minimum Technical Specifications for
Chain-operated valves shall be labeled at the valve body. In addition, labels shall be placed on a small piece of plastic pipe or metal ring through which the chain can easily pass, allowing the label to remain at the bottom of the chain loop.
Valves associated with a piece of equipment or component, such as backflow preventers (BFPs), do not require a separate UID; the UID of the BFP encompasses that assembly.
When numbering manually operated valves and check valves which have no associated process and instrumentation diagram, start numbering at the source and sequentially follow the process flow of that system.
Any valve equipped with other than a manual operator shall be considered an instrument valve and identified with the appropriate system designator (reference Appendix 3).
8.4. Dual-Fed Mechanical Systems, Equipment, & Components
Dual-fed mechanical Systems, Equipment, & Components (SEC) are those that are powered from upstream systems that transfer from the primary/normal source to the alternate/backup source through a transfer switch or similar, or are otherwise generally considered to have power that can be routed from multiple sources. This transfer may be automatic or manual.
In the figure 11 above, the system designator (AB, CD, etc) shall reflect both feeds in the dual-fed system. The color (brown) also provides this same designation.
8.5. Mechanical Piping and Electrical Conduit Systems, Equipment, and Components Mechanical piping systems, equipment, and components (SEC) and conveyed materials, unless otherwise noted in this specification, shall follow the current version of the “Scheme for Identification of Piping Systems” (ANSI/ASME A13.1). For the purposes of this specification, piping SEC shall include pipes of any kind and, in addition, fittings, valves, and pipe coverings. Supports, brackets, or other accessories are specifically excluded from applications of this specification. This section further does not apply to pipes buried in the ground. Pipes are defined as conduits for the transport of gases, liquids, semi-liquids, or fine particulate dust.
V_1-FP-02
Normally Closed
DP_1-B-09
“Solenoid Valve”
IRC_2–CD–10
8 Ton
EDP_1-C-03 Ckt 02,04,06 EDP_1-D-03 Ckt 02,04,06
Line 1
Line 2
Line 3
Line 4
Line 5
Figure 10 – Compliant Mechanical SEC Label
Figure 11 – Compliant Mechanical SEC Label
Version Date: 30 June 2017 Page 15 of 34
Minimum Technical Specifications for
Electrical conduit SEC shall follow this specification. For the purposes of this specification, electrical conduit SEC shall include tubes or pipes of any kind that protects or covers electrical cables. Conduit is defined as rigid or flexible, metallic or non-metallic, tubing or pipe, which covers and protects electrical cables or conductors.
Positive identification of the contents of a piping system shall be by a lettered legend giving the name of the contents in full or abbreviated form. Arrows shall be used to indicate direction of flow.
Piping labels shall be placed on the horizontal center line of pipe, with the following exceptions: 1) If the piping is located above the normal line of vision, the label shall be placed below the horizontal center line of the pipe to maximize visibility; and 2) If the piping is located below the normal line of vision, the label shall be placed above the horizontal center line of the pipe to maximize visibility. Piping shall be labeled on either side of wall penetrations.
Legends shall be applied close to valves or flanges and adjacent to changes in direction, branches, at any line entry or re-entry point, where pipes pass through walls or floors, and at 50 foot intervals on straight pipe runs.
Piping insulation shall be enclosed in color-coded plastic (vinyl or PVC). Color coding assignment for mechanical SEC labels shall be in accordance with Table 1
8.5.1. Color Coding – Pipe and Conduit
Color coding assignment for mechanical piping and electrical conduit systems, equipment, and components (SEC) shall be according to the following table:
Fluid Type Field Color Text Color
Flammable Yellow Black
Fire Systems Red White
Aspirating Smoke Detection (aka Very Early-Warning Smoke Detection
Apparatus – VESDA)
Orange
White
Steam Pink Black
Figure 12 – Compliant Piping System Marking and Labeling
Version Date: 30 June 2017 Page 16 of 34
Minimum Technical Specifications for
Boiler Hot Water Orange Black
Domestic Hot/Cold Water White Black
Chilled Water Supply Blue White
Chilled Water Return Light Blue White
Condenser Water Supply Green White
Condenser Water Return Light Green White
Security Systems Purple White
Building Automation System Green Black
Table 1 – Compliant Color-Coding for Mechanical Piping and Electrical Conduit SEC
All piping shall be labeled with flow arrows as well as labeling for the type of service for the piping. Label spacing shall be industry standard.
Legacy color schemes in use at DISA datacenters are authorized to remain in use. Any and all insulation replacements, projects affecting piping and conduit systems, and new color coding shall be completed to this standard.
9. Electrical Systems, Equipment, & Components
9.1. General Requirements
9.1.1. Labeling
Electrical distribution systems, equipment, and components (SEC) including, but not limited to, transformers, switchgear, switchboards, UPS modules, generators, motor control centers, distribution panels (both primary & secondary), and bus and switchyard components shall be labeled with plastic labels.
Smaller components such as breakers, switches, IT equipment power circuits (“whips”), and associated receptacle boxes shall be labeled with approved machine-printed paper tags secured with clear plastic or adhesive tape, cable tags or other approved methods. Hand written labels of any type are not permitted.
Figure 13 – Sample IT Power Whip Label
Version Date: 30 June 2017 Page 17 of 34
Minimum Technical Specifications for
All redundant power distribution within the datacenter shall incorporate specific color identification to differentiate between different electrical bus powers. Use of specific color identification for each electrical bus shall stay consistent throughout building critical distribution. Labels installed internal to electrical or electronic components shall not provide a ground or short circuit path or interfere with the operation of components. All electrical equipment which is served by or which contains multiple sources of power shall comply with NFPA 70 standards to identify both disconnecting means. Breakers for remote shutdown equipment that must be operated from the local breaker shall have an additional label fabricated from luminescent or reflective tape material to aid in identification during blackout or remote shutdown.
Emergency Power Off (EPO) buttons for remote emergency shutdown of SEC shall have an additional label fabricated from luminescent or reflective tape material to aid in identification during blackout or remote shutdown.
9.1.2. Color Coding - Labels
Color coding assignment for electrical (and mechanical) systems, equipment, and components (SEC) labeling shall be according to the following table:
SEC Field Color Text Color Fire Detection/Protection, Fire Alarm, & Emergency Power Off Red White
“A” Bus Distribution White Black
“B” Bus Distribution Blue White
Building Tan White
Building Automation System Green Black
Boiler Orange Black
“C” Bus Distribution Black White
Compressed Air Dark Red White
Version Date: 30 June 2017 Page 18 of 34
Minimum Technical Specifications for
Chilled Water Blue White
Chilled Water Return Light Blue White
Condenser Water Supply Green White
Condenser Water Return Light Green White
“D” Bus Distribution Gray Black
Dual-fed “A” / “B” or “C” and “D” Bus Distribution Brown White
Direct Current Dark Blue White
Domestic Hot/Cold Water Light Blue Black
“E” Bus Distribution Gold White
“F” Bus Distribution Silver Black
Essential (Emergency Generator) Distribution White White
Fuel Oil Yellow Black
Fire Systems Red White
Ground Dark Green Black
Natural Gas Dark Gray White
Security Purple White
Steam Pink Black
Table 3 – Compliant Color-Coding for Electrical and Mechanical SEC Labels
Version Date: 30 June 2017 Page 19 of 34
Minimum Technical Specifications for
9.2. Typical Electrical Systems, Equipment, and Components
Typical electrical Systems, Equipment, and Components (SEC) include Motor Control Centers (MCCs), Distribution Panelboards (DPs), Power Distribution Units (PDUs), Remote Distribution Cabinets (RDCs), power transformation and switching equipment (transformers, switchgear (SWGR), switchboards (SWBDs), UPSs, contactors, and disconnects), and similar SEC.
SWGR, SWBDs, MCCs, and other SEC shall be labeled to the section level. See Appendix 4 (Labeling Examples) for a visual representation.
All DPs that distribute power shall have associated panel schedules or circuit directories physically located at each panel. This includes switchboards and large DPs (typically greater than 225A), which shall be physically labeled adjacent to each circuit (See Appendix 5).
Individual circuit breakers inside DPs (typically rated less than or equal to 225A) shall be physically numbered adjacent to each breaker, corresponding to the panel schedule (See Appendix 7).
Individual circuit breakers inside PDUs, RDCs, and STSs shall be physically numbered adjacent to each breaker, corresponding to the PDU panel schedule (See Appendix 8). On Line 1, SWGR, SWBDs, RDCs, MCCs, and DPs with sections or sub-panels shall utilize the 4th Field Sequence of the UID Number to differentiate panels. For all other SWGR, SWBDs, RDCs, MCCs, and DPs, the 4th Field Sequence Number of the UID Number is not required.
9.3. Other Electrical Systems, Equipment, and Components
9.3.1. Electrical Raceways, Junctions, and Boxes
Electrical raceways shall be identified and labeled at the points of origin and destination.
Identification and labeling shall also be made on all junction and terminal boxes and when raceways transit through walls, floors, partitions, and other locations where the raceway is not visually continuous. Label all junction and terminal box covers with all circuits transitioning the box. Labels will consist of machine- generated plastic-coated tags; e.g., P-touch, secured with acetate adhesive and will include the Voltage, Parent UID Number
MCC_1-C-01-02
800 A
DP_1-B-09 Ckt 01,03,05 “MCC-1 Section 1”
PDU_3-A-11
225 kVA
CDP_1-A-03 Ckt 02,04,06
“PDU A11”
Line 1
Line 2
Line 3
Line 4
Line 5
Figure 14 – Compliant Electrical SEC Label
Figure 15 – Compliant Electrical SEC Label
Version Date: 30 June 2017 Page 20 of 34
Minimum Technical Specifications for
(From), and Child UID Number (To).
Line 1: Unique Identifier (UID)
Number (required) Line 2: Descriptor (Capacity)
(required) Line 3: Parent or From UID
(electrical source) (required) Line 4: Child or To UID
(electrical source) (required)
9.3.2. Devices
Devices include non-technical power, switch covers, receptacle covers, and emergency light fixtures. Non-technical power, switch covers, and receptacle covers shall have labels consisting of machine- generated tags secured with clear plastic or acetate adhesive and will include Supplying Panel and Circuit Number. Emergency light fixtures (power supplied from emergency panels, battery-backed, or similar) shall be identified by a one- (1)-inch red circular sticker on the underside of the fixture, such that all emergency light fixtures can be easily visually identified when walking through the area.
9.3.3. Security Systems, BAS Systems, Equipment, and Components Labeling for security (Automated Control Systems (ACSs) and Intrusion Detection Systems (IDSs)) Systems, Building Automation Systems (BAS) systems, Equipment and Components (SEC) compliant label examples:
JBOX_4-B-01
480 V
UDP_1–B–02 Ckt 17,19,21
PDU_4-B-01
Line 3
Line 4
Figure 16 – Compliant Junction Box Label
BASP_1-B-08
120 V CDP_6-B-09 Ckt 01
BAS Panel 8
IDSP_2-A-01
120 V
CDP_1-A-03 Ckt 06 “2nd Floor IDSP”
IDS Panel 2
Line 1
Line 2
Line 3
Line 4
Line 5
Figure 17 – Compliant Electrical SEC Label
Figure 18 – Compliant Electrical SEC Label
Version Date: 30 June 2017 Page 21 of 34
Minimum Technical Specifications for
Appendix 1. References
• American National Standards Institute / American Society of Mechanical Engineers
(ANSI/ASME A13.1), “Scheme for Identification of Piping Systems”
• ANSI and Instrument Society of America (ISA) S5.1, “Instrumentation Symbols and
Identification”
• ANSI and ASME, (ANSI/ASME Y.1.1), Abbreviations for Use on Drawings
• Federal Standard 795 for accessibility
• Institute of Electrical and Electronics Engineers (IEEE)
• NFPA 70 (NEC)
• Occupational Safety and Health Administration (OSHA) Standards for safety signs
• UFAS/ADA Guidelines
• Underwriters Laboratory (UL) – Illuminated Signs Standard
Version Date: 30 June 2017 Page 22 of 34
Minimum Technical Specifications for
Appendix 2. Definitions Assembly. A collection of equipment, parts, or components that serve together to perform an intended function.
Component. A constituent part of a system; includes valves, instruments, pumps, motors, etcetera.
Some components may also be equipment. Some components may also be LRUs.
Conduit. An electrical metallic, non-metallic, or PVC pipe or tubing that covers and protects electrical cables or conductors.
Contactor (CTC). An electrically controlled switch used for switching a power circuit with high current ratings.
Control Panel (CP). Refers to a cabinet that contains electrical display components which control or monitor both motors and equipment.
Disconnect. A switch that has the capability to interrupt power to an electrical circuit or to a group of electrical circuits, usually manually operated.
Distribution Panel (DP). A component of an electrical supply system which divides an electrical power feed into subsidiary circuits, while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Also referred to as a distribution board, power panel, breaker panel, electrical panel, etc.
Equipment. Personal property that is functionally complete for its intended purpose, durable, and nonexpendable. Equipment generally is constructed from an assembly of parts, components, and/or LRUs; does not ordinarily lose its identity or become a component part of another article when put into use; is designed and manufactured to perform a specific function; has an expected service life of two years or more; has been acquired or constructed with the intention of being used; typically has a unique manufacturer’s model number. Some equipment may also be LRUs.
Essential Power (E). Refers to connection of any distribution panel, load or electrical device to the emergency standby power system (generator plant) without backup or failover support from the UPS.
Exhaust Fan. A fan which is used to control the interior environment by venting out unwanted odors, particulates, smoke, moisture, and other contaminants which may be present in the air.
Identification. The action of uniquely naming or identifying structures, systems, equipment, or components with a standardized grid or nomenclature.
Labeling. A tag, card, or other material device attached to an object to identify or give instructions or details regarding its ownership, manufacture, nature, etc.
Line Replaceable Unit (LRU). A complex component or piece of equipment that is designed to be replaced quickly at the organizational level. See section “Equipment Identification” in TIM (CSI 360-95-
Version Date: 30 June 2017 Page 23 of 34
Minimum Technical Specifications for
3A) O&M Module 7 (Documentation, Tracking, and Reporting) for a detailed contextual explanation and examples of LRUs.
Marking. An identifying mark, usually a colored symbol to identify or differentiate a unique aspect of a system, equipment, component or assembly.
Master Power Distribution Unit (MPDU). A device fitted with multiple outputs designed to distribute electric power, especially to cabinets/racks of computers and networking equipment located on the raised floor.
Motor Control Center. Motor Control Centers are combination starters grouped into an assembly. A combination starter is an enclosure that houses the motor starter, or device that regulates an electric motor’s performance, and the fuses, or devices used in electrical systems that prevent excessive current.
Personal Property. All property (systems, equipment, components, materials, and supplies) except real property and records of the Federal Government.
Pipes. Conduits for the transport of gases, liquids, semiliquids, or fine particulate dust. Does not include electrical or data communications conduits or raceways for the purposes of this specification.
Property. All references to property contained herein include structures, systems, equipment, components, and similar assets.
Raceways. An enclosed channel of metal or nonmetallic materials designed expressly for holding wires, cables or busbars, with additional functions as permitted by the NEC. Raceways include, but are not limited to, rigid metal conduit, rigid nonmetallic conduit, intermediate metal conduit, liquidtight flexible conduit, flexible metallic tubing, flexible metal conduit, electrical nonmetallic tubing, electrical metallic tubing, underfloor raceways, cellular concrete floor raceways, cellular metal floor raceways, surface raceways, wireways, and busways.
Return Fan. A fan which withdraws air from an air-conditioned space and returns to the central air-conditioning unit.
System. A collection of interconnected and interactive items composed of equipment, piping, ducts, or components, which perform in unison to accomplish a specific result or results.
Structure. Buildings, towers, roof systems, shelters, foundations, parking structures and lots, permanent fixed utilities, and other real property and real property systems or components. The removal of these items would diminish the value of the property or its ability to perform the basic function of the structure.
Systems, equipment, and components are removable and non-permanent in this context.
Supply Fan. A fan which supplies conditioned-air from an air-conditioning unit to a conditioned space.
Switchboard. A large single panel, frame, or assembly of panels in which are mounted switches, over-current, and other protective devices, buses, and usually instruments. The role of the switchboard is to
Version Date: 30 June 2017 Page 24 of 34
Minimum Technical Specifications for allow the division of the current supplied to the switchboard into smaller currents for further distribution and to provide switching, current protection and metering for those various currents.
Switchgear. Switchgear is the combination of electrical disconnect switches, fuses or circuit breakers used to control, protect, and isolate electrical equipment.
Uninterruptible Power (U). The term critical power refers to the connection of any distribution panel, load or electrical device to the output circuitry of the UPS system. Sometimes referred to as Critical Power (C). Critical loads are powered in an A-B bus manner.
Unique Identifier (UID). A character string, number, or sequence of bits assigned to a discrete entity or its associated attribute which serves to uniquely distinguish it from other like and unlike entities. Each unique identifier has only one occurrence within its defined scoped of use.
Version Date: 30 June 2017 Page 25 of 34
Minimum Technical Specifications for
Appendix 3. Systems, Equipment, & Components Designator List
The following is a list of System, Equipment, & Component Designators (part of the first field of the UID Number). The intent of this list is to provide guidance and consistency in labeling of systems, equipment and components. UID Numbers shall be defined on a legend for new projects.
Also included in this list are the recommended System Designators that correspond with each SEC Designator.
SEC Designators
ACU Air Conditioning Unit AC Air Compressor
ACA Air Cooled Aftercooler ACSP Access Control System Panel ACT Actuator AD Air Dryer
AHU Air Handler Unit AS Air Separator AT Air Tank (Captive) ATS Automatic Transfer Switch
BASM Building Automation System Monitor
BASP Building Automation System Panel BAT Battery String (UPS System) BC Battery Charger
BCC Battery Charger Controller
BDS Battery Disconnect Switch (UPS System)
BFP Back-Flow Preventer BH Basin Heater
BRKR Breaker
BMS Battery Monitoring System (UPS System)
BO Boiler
Version Date: 30 June 2017 Page 26 of 34
Minimum Technical Specifications for
BT Belly Tank CAP Capacitor CAT Clean Agent Tank CFSC Chemical Feed Sys Controller CFSP Chemical Feed Sys Pump
CH Chiller (generic, including DX) CHCS Chiller Compressor Starter
CHWRP Chilled Water Return Pump CHWSP Chilled Water Supply Pump CHWV Chilled Water Valve
CP* Control Panel CTC Contactor
CRAC Computer Room Air Conditioner CRAH Computer Room Air Handler CRU Condensate Return Unit CRP Condensate Return Pump CRT Condensate Return Tank CT Cooling Tower
CTLR Controller CTBH Cooling Tower Basin Heater CTP Cooling Tower Pump CUB Cubical Furniture CVS Central Vacuum System CWF Condenser Water Filter
CWP Condenser (Cooling Tower) Water Pump
CWV Condenser Water Valve DISC* Disconnect
DHWRP Domestic Hot Water Return Pump DHWSP Domestic Hot Water Supply Pump
DP* Distribution Panel DT Day Tank EF Exhaust Fan
EFORK Electric Forklift
Version Date: 30 June 2017 Page 27 of 34
Minimum Technical Specifications for
EGEN Emergency Generator ELEV Elevator EMIF Electromagnetic Interference Filter ENG Engine Fire Pump
EPJAC Electric Pallet Jack EPOS Emergency Power Off System
ET Expansion Tank EWASH Eyewash
F Furnace FACP Fire Alarm Control Panel FASD Fire Alarm Smoke Detector FCU Fan Coil Unit FIL Filter FT Fuel Tank
FMS Fuel Monitoring System FP Fire Pump
FTP Fuel Transfer Pump GATE Gate, Electric
HB Heat Box HC Heating Coil
HDSC Hydrogen Detection Sys Controller
HDSD Hydrogen Detection System Detector
HUM Humidifier HUMCU Humidifier Control Unit
HWP Hot Water Pump HX Heat Exchanger (all types)
IDSP Intrusion Detection System Panel IRC In Row Cooler JBOX Junction Box
LB Load Bank LIFT Loading Dock Lift LP* Lighting Panelboard LPS Lightning Protection System
Version Date: 30 June 2017 Page 28 of 34
Minimum Technical Specifications for
LDSD Leak Detection System Detector LDSM Leak Detection System Monitor LVR Louver
MCC* Motor Control Center MTR Meter MTS Manual Transfer Switch
OHDR Overhead Door P Pump (Generic)
PDU Power Distribution Unit PRV Pressure Reduction Valve
RDSM Refrigerant Detection System Monitor
RDSD Refrigerant Detection System Detector
RDC Remote Distribution Cabinet RECT Rectifier
RF Return Fan RM Room RMSP Remote Monitoring System Panel ROS Reverse Osmosis System RW Raceway
SBM Static Bypass Module (UPS system) SBP Standby Booster Pump SF Supply Fan
SPD Surge Protective Device SRG Signal Reference Grid SSD Security System Detector SSP Security System Panel
STRNR Strainer STS Static Transfer Switch
STRTR Starter SUB Substation
SUMP Sump/Ejector Pump SWBD* Switchboard SWGR* Switchgear
Version Date: 30 June 2017 Page 29 of 34
Minimum Technical Specifications for
Table 3 – SEC Designator
* If a System, Equipment, or Component is part of a Critical electrical/UPS bus, then the SEC Designator shall be preceded by the letter ‘U’; if part of an Essential system, then the SEC Designator shall be preceded by the letter ‘E’; e.g., Critical SWBD = USWBD and Essential Distribution Panel = EDP.
SEC Designators
TGEN Temporary Generator TUPS Temporary UPS UH Unit Heater
UPS Uninterruptible Power Supply UTIL Utility
V Valve (generic) VAV Variable Air Volume VFD Variable Frequency Drive VRV Variable Refrigerant Volume WDU Water Distribution Unit WTS Water (Softener) Treatment System WH Water Heater
XFMR* Transformer
Version Date: 30 June 2017 Page 30 of 34
Minimum Technical Specifications for
Appendix 4. Switchgear/Motor Control Labeling Example All switchgear and motor control centers shall be labeled by section as well as compartment. Each compartment will be labeled both with a numeric-alpha number and a downstream designator.
Section Labeling In the example below, the manufacturer provided the switchgear in…