Request for Information

Date: June 12, 2017 Project: FMCSA Office Renovation & Security Upgrade E.S. Muskie Fed Bldg.

RFI Log: #1 To: Kevin Morris From: Sean Coleman

1. Per Section 16130 1.2 B1, it refers to Division 7 Section “Firestopping” there is not a Division 7Section “Firestopping” in the documents. Please clarify.

Answer: The following specifications will be included in the amendment.

B&C were included due to references from other supplied specs.

A. 078413 - Penetration Fire-stopping B. 260533 - Raceways & Boxes C. 271100 - Communications Equipment Room Fittings

2. Per Section 271500 2.5 A, we are asked to comply with requirements in Division 26 Section “Grounding and Bonding for Electrical Systems”.

There is not a Division 26 section “Grounding and Bonding for Electrical Systems” given in documents. Please clarify.

Answer: Spec #260526 “Grounding & Bonding for Electrical Systems” is included in the amendment.

3. Per Section 10615 2.01 A, ULTRAWALL partition system is called out for the manufacture product. ULTRAWALL is not in production. The only ULTRAWALL panels we have a lead on are unfinished. Is there a spec for wall paper or a substation for the panel? How do you wish to proceed?

Answer: At this time, the replacement of the glass partitions has been removed (cancelled) as a new work detail in the scope.