GEMS 15 kVA UPS Technical Specifications - BR LS.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
Open Market Small Purchase IL|26-588IEMA-MGMTA-P-95778
Contract number
26-588IEMA-MGMTA-P-95778
Issued by
Illinois

About this file

This document is a technical specifications sheet for a 15 kVA Uninterruptible Power Supply (UPS) system procured through the GEMS (Government Entities Membership Consortium) cooperative purchasing program. The document outlines detailed technical requirements and performance standards for UPS equipment, establishing baseline specifications for potential state and local government procurement activities.

The specifications detail a 15 kVA UPS unit with comprehensive technical parameters including input/output voltage ratings, frequency specifications, battery backup duration requirements, efficiency ratings, physical dimensions, and environmental operating conditions. The document serves as a procurement standard to ensure equipment consistency and performance across GEMS member jurisdictions. Key technical features include redundancy capabilities, automatic voltage regulation, surge protection, and monitoring systems. The specifications establish minimum performance thresholds for equipment selection and vendor proposals, enabling standardized procurement across multiple government entities while maintaining quality assurance and operational reliability standards for critical power infrastructure.

View the file

Other files

File Type Posted
B-51543 Q and A.docx DOCX document
Standard Illinois Certifications v.26.2.pdf PDF
7700310589 National Tek_Redacted.pdf PDF
standard-terms-and-conditions 4~51.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Cabinet Style3 High w/ 64 Battery
Power
Ratings15 KVA / 13.5KW @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion<= 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 70 min @ full load (> 8 hours @ 15% full load)
External Battery Cabinet (EBM) ConfigurationEBM 96 (Quantity 2)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card (P/N: 103003055), X-slot Industrial Gateway Card (P/N: INDGW-X2)
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Braidwood and LaSalle Nuclear Generating Stations
Tech Support Availability24/7 (Unlimited)