Questions and Answers for FA9101-20-Q-0003: 6” Ball Valves
Q1. SOW No 11207-19-0XX for the Electric Motor Operated valves: Section 3:10 list a Limitorque SMC actuator.. without motor starter. Is that a special model for AEDC? I don’t see a standard offering from Limitorque for a SMC model. Typically, AEDC has gone with the L120 when they didn’t want the motor starter installed inside the actuator.
A1. Per the spec, a motor starter is not required. The L120 is the typical unit used at AEDC.
Q2. Specifically on the Electric Motor Operated SOW No 11307-19-0XX 5 June 2019, Valve No: 1107
Per Sections 3.9 to 3.12:
Do the actuators need local controls / a local pushbutton station (local-off-remote aka sw 3/2/3), or will the units have no pushbutton stations? They are not mentioned in the SOW.
A2. Local control is not required per the spec.
Q3. Specifically on the Electric Motor Operated SOW No 11307-19-0XX 5 June 2019, Valve No: 1107
What is the control voltage signal (I am assuming 120vac/1/60hz)?
A3. Correct - 120vac/1/60hz