Question Set 5 Answered.pdf
PDF 421 KB Posted
- Attached to
- FA8604-20-R-8108 Storage Aid System New Hampshire & Mobility Processing System Vermont Federal contract opportunity
- Solicitation number
- FA8604-20-R-8108
About this file
This document contains a federal contract solicitation and related question and answer file. The solicitation seeks proposals for a Storage Aid System for Building 262 at Pease Air National Guard Base in New Hampshire, and a F-35 DSP Storage and Mobility Processing System for Building 70 at Vermont Air National Guard Base in Vermont. The performance period is 238 days from contract award. Proposals are due by July 28, 2020 through the DoD Safe system. The solicitation is set aside for small businesses with a NAICS code of 333922 and size standard of 500 employees. The contract will be awarded based on lowest price technically acceptable criteria to the responsible offeror with the lowest evaluated price.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Question and Answer Set 8 and 9.pdf | ||
| Question and Answer Set 7.pdf | ||
| Question and Answer Set 6 Answered.pdf | ||
| Question Set 4 Answered.pdf | ||
| FA860420R8108 0001.pdf | ||
| Question Set 3 Answered.docx.pdf | ||
| Proposal Checklist 8108.pdf | ||
| RFP FA860420R8108.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question Set 5 (ANSWERED)
Pease ANGB
Vertical Carousels
3.2.11 and 3.3.9 Hand Crank and Back Up Power If a back-up power cable is required in the event of a power outage, then the requirement for a hand-crank is redundant. Additionally, this would restrict competition as this feature is only available from one vertical carousel manufacturer. Please advise.
Redundancy is essential, both features shall be included.
3.2.12 Work Counter
Can the work counter be positioned at 45” above the floor.
Work counters shall be at specified heights and locations.
3.2.15 Containers
There are several Akro-Mils containers that are close in dimensions to the sizes specified for Type A and B in varying thicknesses and styles. Please identify the Akro-Mils part number referenced so the appropriate equivalent can be determined.
The contractor shall propose the closest dimensions to specification, not allowing for loss of storage volume.
3.2.16 Fire Suppression System
Are drawings, inspection records and specifications for the Fire Suppression system currently installed in Building 262 available to review to insure that the successful contractor can be compliant with applicable requirements?
The drawings can’t be provided at this time. Detailed drawings will be reviewed at Post Award.
Turret Truck System Operation 3.2.1.1 Our concern would be the side with the vertical carousels. That aisle is only showing 11’ 8” from the edge of the rack. Our man up turret truck is 12’ 2” in head length alone not counting the pallet which would add a few more inches. We require at least 14’ which they have on the other side, so the top two aisle are fine but we want to point out that that side with the verticals would be impossible to turn.
Looking at the drawing we see the 11’ 8” being an issue.
The turret truck is only intended for use in pallet rack ‘A’ aisles. The trucks are intended to be driven forward in, then backed out. Floor space is very limited in this facility. Small pick vehicles are intended for use with pallet rack ‘A1’.