Text version
Support Equipment and Vehicle Management Group
PD07WRGBGBLC48
Flightline Equipment Engineering Squadron
642 CBSSS/GBEA
27 January 2009
CAGE 98752
Revised 02 June 2009
PURCHASE DESCRIPTION
WATER SYSTEM, BEAR (Revision 1)
1. SCOPE
1.1 Scope. This specification defines the Basic Expeditionary Airfield Resources (BEAR) Water System herein referred to as “the water system”. The water system shall be of a modular and scalable design and will consist of a series of pumping, piping, and storage equipment; applicable fittings; and other components such as fluid control valves. The water system shall be capable of drawing water from a natural source, purifying, storing, and delivering the water while maintaining sufficient pressure, quantity, and quality for an entire base. The water system is intended to supply 30 gallons of water per person per day (gpppd) for an 1100 person camp (expandable to 3300 person camp) and maintain enough storage capacity to sustain the camp with 30 gpppd for 4 days with no new water introduction. One complete water system is comprised of five distinct subsystems: Source Run, Water Production (with 1500 Reverse Osmosis Water Purification Unit (ROWPU) or 600 ROWPU), 550 Initial, 550 Follow-on, and Industrial Operations & Flightline Extension. Features and Type designations of the subsystems are specified below in Table 1 and in the paragraphs contained within this purchase description.
These subsystems shall be compatible with the existing BEAR water systems.
Table 1. Water subsystems.
| Part # |
| NOMENCLATURE |
| PARAGRAPH |
| PD07WRGBGBLC48-1 |
| Source Run |
| 3.2.1 |
| PD07WRGBGBLC48-2 |
| ROWPU Water Production |
| 3.2.2 |
| PD07WRGBGBLC48-3 |
| 550 Initial |
| 3.2.3 |
| PD07WRGBGBLC48-4 |
| 550 Follow-on |
| 3.2.4 |
| PD07WRGBGBLC48-5 |
| Industrial Operations & Flightline Extension |
| 3.2.5 |
| PD07WRGBGBLC48-6 |
| 400GPM Pump w/Trailer |
| 3.2.1, 3.2.1.1, 3.2.1.1.1, 3.2.1.1.2 |
| PD07WRGBGBLC48-7 |
| Dual Pump Station |
| 3.2.3, 3.2.3.1 |
| PD07WRGBGBLC48-8 |
| 125GPM Pump (Diesel) |
| 3.2.2, 3.2.3, 3.2.4, 3.2.6.2 |
| PD07WRGBGBLC48-9 |
| 1500 ROWPU |
| 3.2.2.1 |
2. APPLICABLE DOCUMENTS
2.1 Government Documents.
2.1.1 Specifications, Standards, and Handbooks. The following documents form a part of this specification to the extent specified herein. Unless otherwise specified, the issues of these documents shall be those listed in the January 2004 issue of the Department of Defense Index of Specifications and Standards (DODISS), and supplement thereto.
SPECIFICATIONS
MILITARY
MIL-PRF-52109
Pumping Assemblies, Portable, Bulk Transfer, Fuel and Water Pumping Service
MIL-T-53029
Tanks, Fabric, Collapsible: 3,000, 10,000, 20,000, And 50,000 Gallon, Drinking Water
MIL-DTL-22992
Connectors, Plugs and Receptacles, Electrical, Waterproof, Quick Disconnect, Heavy Duty Type, General Specification for:
COMMERCIAL
A-A-52550
Pintle Assembly, Towing, Manual Release, 18,000, 40,000 and
100,000 lbs Capacity A-A-59326
Coupling Halves, Quick-Disconnect, Cam-Locking Type A-A-59326/1A Coupling Half, Male by Internal Pipe Thread, Type I
A-A-59326/2A Coupling Half, Male by Hose Shank, Type II
A-A-59326/3A Coupling Half, Male by External Pipe Thread, Type III
A-A-59326/6A Coupling Half, Female by Hose Shank, Type VI
A-A-59326/7A Coupling Half, Female by External Pipe Thread, Type VII
STANDARDS
MILITARY
AFOSH STD 48-8
Controlling Exposures to Hazardous Materials
FED-STD-595
Colors Used in Government Procurement
MIL-STD-130
Identification Marking of US Military Property
MIL-STD-209
Interface Standard for Lifting and Tiedown Provisions
MIL-STD-889B
Dissimilar Metals
MIL-STD-2073-1D
Standard Practice for Military Packaging
MIL-STD-129P(4)
Military Marking for Shipment and Storage
MS90555
Connector, Receptacle, Electrical, Wall Mounting, Class L
Power Source Receptacle)
MS90556
Connector, Plug, Electrical, Straight, Class L
MS90557
Connector, Plug, Electrical, Cable Connecting, (Without
Coupling Ring), Class L
MS90558
Connector, Receptacle, Electrical, Wall Mounting, Class L
HANDBOOKS
MILITARY
MIL-HDBK 138B Container Inspection
MIL-HDBK-808
Finish, Protective and Codes for Finishing Schemes for Ground and Ground Support and Equipment
2.2 Drawings. The following drawings and all drawing and changes referenced thereon form a part of this specification to the extent specified herein.
ARMY, FSCM 97403
13227E9787
Flaking Box Assembly
2.2.1 Drawings. The following drawings are provided for reference only for interface requirements with the BEAR Power.
AIR FORCE, FSCM 98752
8335844
Secondary Distribution Center
8642414
Power Distribution Panel, PEU-159/E, 60 KW
8642307
Power Distribution Panel, PEU-156/E, 25 KW
(Copies of specifications, standards, drawings, and other Government documents required by the
Contractor in connection with specific acquisition functions should be obtained from the contracting activity or as directed by the contracting activity.)
2.3 Other Publications. The following documents form a part of this purchase description to the extent specified herein.
International Organization for Standardization (ISO)
Containers, Series 1 Freight, Classification, Dimensions, and Ratings
Containers, Series 1 Freight, Corner Fittings, Specifications
1496-1
Containers, Series 1 Freight, Specification and Testing, Part 1: General Cargo Containers for General Purposes
Freight Containers, Coding, Identification and Marking
10012
Measurement Management Systems - Requirements for Measurement
Processes and Measuring Equipment-First Edition
(Applications for copies should be addressed to ISO, Case postale 56, 1211 Geneva 20, Switzerland, Fax +41 22 734 10 79.)
National Fire Protection Association (NFPA).
NFPA-70
National Electrical Code
(Applications for copies should be addressed to National Fire Protection Association, Batterymarch Park, Quincey MA 02269).
Occupational Safety and Health Administration (OSHA).
OSHA Standards
Code of Federal Regulations (CFR) title 29, Vol. 5, chapter XVII, parts 1900 through 2007, (Applications for copies should be addressed to Superintendent of Documents, US Government Printing Office, and Washington, DC 20402).
Underwriters Laboratories (UL).
UL Standards
(Applications for copies should be addressed to Underwriter’s Laboratories Inc, 333 Pfingsten Rd, Northbrook IL 60062).
2.4 Order of Precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document shall take precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained.
3. REQUIREMENTS
3.1 General Design. The water system shall be designed and constructed in accordance with the following general requirements:
a. The system shall be deployable and re-locatable and shall not require special tooling unless included with the system or applicable subsystem.
b. The system shall be designed and constructed to be transported, stored, assembled, disassembled, and operated at military installations and austere environments world wide. The system will be subjected to extreme climatic conditions that include but are not limited to the following environmental conditions and climates: arctic, desert, temperate-industrial, and tropical-marine. (See para. 3.3.10).
c. The system shall be modular in nature and constructed of interchangeable pieces to maximize configuration flexibility. The system shall also be capable of being indefinitely expanded upon through the connection of additional subsystems.
d. The system shall be capable of being entirely packed in weatherproof shipping and non-ventilated storage containers that is suitable for long-term outdoor storage. The water system sub-systems shall be packed for multimodal transportation. For surface transportation configuration the sub-systems shall be packed in Tricons, BiCons, or combination of both type containers (See Paragraph 5.1). Major components, i.e. Dual Pump Station (PD07WRGBGBLC48-7) and 1500 ROWPU (PD07WRGBGBLC48-9) shall be configured/sized to be compatible with the 463L pallet system and air transportable by C-130 aircraft. The restrictions for being C-130 transportable are that all components, when positioned on a 463L pallet, shall not exceed 96 inches in height and 84 inches in width, and 104 inches in depth. Combined weight of contents and container or contents and pallet shall not exceed 10,000 pounds. Any additional components required for packaging shall be reusable and shall be furnished with each subsystem. (See para. 3.3.10).
e. The contractor shall maximize the use of commercial-off-the-shelf components and shall strive to minimize the weight of the overall system without adversely affecting performance.
3.1.1 Engineering Change Proposal (ECP). After the configuration baseline has been established with either the approval or waiver of first article test, all design changes shall be submitted by ECP in accordance with the contract.
3.1.2 Identification plate. Equipment, assemblies, and parts shall be permanently, securely, and clearly marked for identification, specifically utilizing Unique Identification (UID), in accordance with MIL-STD-130. The identification plate shall contain the following information:
i) Nomenclature
ii) Manufacturer’s part number
iii) Serial number
iv) Manufacturer’s name/Cage code
v) Date of manufacture
vi) Contract number
vii) Warranty information
viii) National stock number An additional 2 blank lines after information above will be provided for etching future TCTOs. All plates must follow material requirements as specified in this document.
3.1.3 Instruction plates. Any special or important procedures that are to be followed during assembly, operation, and/or service shall be permanently marked and securely attached to the applicable component(s) in a readily accessible location. Lettering shall be a minimum of 1/8” black on a light background. All plates must follow material requirements as specified in this document.
3.1.4 Materials. Selection of materials, processes, and parts utilized in the design and construction of the unit shall meet best commercial practices and quality, unless otherwise noted, and shall be commensurate with the overall operational and performance requirements specified herein. The materials shall be of uniform quality and condition, free from any defects that may adversely affect appearance, strength, endurance, wear resistance, and/or serviceability. Parts that are subject to corrosion in a marine environment shall be aluminum flame sprayed, zinc galvanized, or constructed of stainless steel, brass, bronze, or other corrosion resistant material. Unless protected against electrolytic corrosion, dissimilar metals, as defined in MIL-STD-889, shall not be used in intimate contact with each other. Alternate materials, such as composites, polymers, etc., may be used if suitable for the intended use and environmental extremes. All materials used in the system shall be new, without defects, and free of repairs. The contractor shall not use nonstandard or proprietary materials and processes without prior government approval.
3.1.5 Recovered materials. Unless otherwise specified herein, all equipment, material, and articles incorporated in the products covered by this specification shall be new and may be fabricated using materials produced from recovered materials to the maximum extent practical without jeopardizing the intended use. The term “recovered materials” means materials, which have been collected or recovered from solid waste and reprocessed to become a source of raw materials, as opposed to virgin raw materials. None of the above shall be interpreted to mean that the use of used or rebuilt products is allowed under this specification unless otherwise specifically specified.
3.1.6 Prohibited materials. The use of asbestos and cadmium/cadmium plating is prohibited. The use of Ozone Depleting Substances (ODCs) and the 17 hazardous materials in the EPA-17 listing are prohibited from use in any operation, maintenance, repair, overhaul, and/or troubleshooting action required of the government by any technical order of any kind, whether it be a commercial or government format. No technical manual shall contain any of these prohibited materials for either use or information. Toxic products and formulations used or generated by the system shall meet the requirements of AFOSH STD 48-8 and all other applicable environmental, occupational safety and health standards. Personnel shall not be exposed to unsafe amounts of chemicals or other health and safety threatening agents in producing, using, maintaining, storing, disposing, or servicing of the cart or its components.
3.1.7 Corrosion prevention. All parts or materials used in the design and construction of the water system’s major components shall be corrosive resistant in accordance with best commercial practice to support worldwide deployment scenarios. Composite and plastic materials shall be utilized to the maximum extent possible without compromising the structural integrity or life expectancy of the unit. A Corrosion Prevention and Control Plan is required and shall be in accordance with the requirements of Data Item Description DI-MFFP-81403.
3.1.8 Protective treatments. All parts or materials used in the design and construction of the unit that are subject to deterioration when exposed to the climatic, environmental, UV, and/or operational conditions shall be adequately protected in accordance with best commercial practices in a manner that will in no way prevent compliance with the performance requirements of this specification. Protective coatings that will chip, crack, or scale with age or extremes of climatic conditions shall not be used.
3.1.9 Fungus proof materials. Where possible, materials which are nutrients for fungi shall not be used. Materials treated for fungus resistance shall retain their original electronic, physical, or other properties sufficiently to remain entirely suitable for the purpose, and shall not present toxic hazards for personnel or have corrosive effects on adjacent materials. The period of effectiveness of such treatment shall be at least equivalent to the service life of the part or component on which it is used.
3.1.10 Finish. All finishing processes utilized in the design and construction of the unit shall result in a durable, non-fading, long lasting finish. Finish warranty shall be equivalent to best commercial warranty offered or a minimum of 5 years, whichever is greater. Warranty is not to include damage caused by common maintenance activities. Exterior surfaces shall be painted desert tan Color 33446 per FED-STD-595 to the maximum extent practical.
3.1.11 Dimensions. The primary system for which components shall be manufactured to is the U.S. Customary or Foot-Pound-Second system. Any component manufactured to metric dimensions will have to first be approved by the respective government procurement office and its associated engineers.
3.2 Subsystems.
3.2.1 Source Run. PD07WRGBGBLC48-1 (See Fig. 2 for typical layout.) The Source Run will consist of a series of pumping, piping, fluid control, and storage equipment. It shall be capable of drawing water from a natural water source (i.e. pond, lake, stream, sea, or ocean) up to 100 feet away and 20 feet below the pumping station. The system shall be capable of pumping this water 6000 feet to a height of 150 feet and deliver 400 GPM at its outlet for storage in a water bladder. All of the associated fittings and valves shall be provided to deliver the water from the source to the storage bladder 6000 feet away. The system shall be designed so that the Source Run can be connected in series (pump-to-source run line-to-pump-to-source run line). The possibility exists that this system may have to go over or under a roadway containing heavy vehicular traffic. Hose protecting ramps and/or PVC piping with associated Quick Disconnect hose connecting adapters shall be required components in order to allow the operator to either bury the pipe or run it atop the roadway.
NOTE: The Source Run Subsystem shall interface with the existing BEAR WATER SYSTEM (Ref. Fig. 1) and the components shall be form, fit, and functionally interchangeable with the existing Source Run Subsystem. The existing Source Run Subsystem consists of the following components:
· 1 ea- Strainer and Float Buoy Assembly, Raw Water (CAGE 61125, P/N 3010120 or equivalent) consisting of:
1 ea - 4” Steel Suction Strainer (Strainer openings shall be ½-inch diameter maximum). The strainer shall have a 4” Male QD fitting.
1 ea - Cable, Wire Rope, 15’ in length 2 ea - Clamp, Cable 1 ea - Float Buoy (The Float Buoy shall have buoyancy rating of 240 pounds.)
1 ea - Pump, Air, Hand
· 2 ea - Hose Assy, Suction, Raw Water, 4” X 25’ (CAGE 61125, P/N 3011070 or equivalent)
· 5 ea - Adapter, Raw Water, 4” Male QD X Male NPT(CAGE 33813, P/N 40F or equivalent)
· 2 ea - Hose Assy, Suction, Raw Water, 4” X 50’ (CAGE 61125, P/N 3011080 or equivalent)
· 8 ea - Hose Assy, Suction, Raw Water, 4” x 15’ (CAGE 61125, P/N 3011060 or equivalent)
· PD07WRGBGBLC48-6 1 ea - Pump, Diesel, Raw Water, 400 GPM, W/4” Female QD (Suction) X 4” Male QD, (Discharge). (CAGE 0AK83, P/N 701-1033 or equivalent)
· 3 ea - Valve, Swing Check, Raw Water, 4” Female QD X 4” Male QD (CAGE 61125, P/N 3010175-2 or equivalent)
· 1 ea - Reducer, Raw Water, 6” Male QD X 4” Female QD (CAGE 61125, P/N 3010301 or equivalent)
· 42 ea - Hose Assy, Discharge, Raw Water, 6” X 150’ (CAGE 61125, P/N 3011010 or equivalent)
· 40 ea - Hose Assy, Discharge, Raw Water, 4” X 150’ (CAGE 61125, P/N 3015030 or equivalent)
· 10 ea - Hose Assy, Discharge, Raw Water, 6” X 50’ (CAGE 61125 P/N 3011000 or equivalent)
· 1 ea - Reducer, Raw Water, 6” Female QD X 4” Male QD (CAGE 61125, P/N 3010230 or equivalent)
· 4 ea - Hose Assy, Discharge, Raw Water, 4” X 50’ (CAGE 61125 P/N 3011020 or equivalent)
· 4 ea - Hose Assy, Discharge, Raw Water, 4” X 25’ (CAGE 61125, P/N 3011030 or equivalent)
· 3 ea - Tee Assy, Raw Water, 4’, (PVC), W/4” Female QD X 4” Male QD X 4” Male QD (CAGE 61125, P/N 3020250-2 or equivalent)
· 6 ea - Valve, Ball, Raw Water, 4” Female QD X 4” Male QD (CAGE 61125, P/N 3010163-2 or equivalent)
· 1 ea - Bladder, Raw Water, 20,000 Gallon, W/accessories per MIL-T-53029 or equivalent, plus 1 ea - Adapter, 2” Male QD X 2” NPT per bladder. (CAGE 61125, P/N 3010100-2 or equivalent)
· 1 ea - Hose Assy, Suction, Raw Water, 2” X 8’ (CAGE 61125, P/N 3011090 or equivalent)
· 1 ea - Valve, Ball, Raw Water, 2” Female QD X 2” Female NPT (CAGE 61125 P/N 3010173-2 or equivalent)
· 2 ea - Coupler, Raw Water, 4”, Male QD X Male QD (CAGE 33813, P/N SA40X40 or equivalent)
· 2 ea - Coupler, Raw Water 4”, Female QD X Female QD (CAGE 33813, P/N 40CX40C or equivalent)
· 2 ea - Coupler, Raw Water, 6”, Male QD X Male QD (CAGE 58536, P/N AA59326/3A-10-A or equivalent)
· 2 ea - Coupler, Raw Water, 6”, Female QD X Female QD (CAGE 33813, P/N 60CX60C or equivalent)
· 1 ea - Kit, Transition, Raw Water, (CAGE 61125, P/N 3010140 or equivalent) Consisting of:
· 3 ea - Coupling, PVC, 6” X 150mm (CAGE 61125, P/N 3010141 or equivalent)
· 3 ea - Adapter, Male, PVC, 6” Slip X 6” Male NPT (CAGE 61125, P/N 3010142 or equivalent)
· 3 ea - Adapter, Female, PVC, 6” Slip X 6”Female NPT (CAGE 61125, P/N 3010143 or equivalent)
· 6 ea - Coupling, PVC, 4” X 100mm (CAGE 61125, P/N 3010144 or equivalent)
· 6 ea - Adapter, Male, PVC, 4” Slip X 4” Male NPT (CAGE 61125, P/N 3010145 or equivalent)
· 1 ea - Kit, PVC Adhesive (CAGE 44135, P/N 30244 or equivalent)
· 6 ea - Adapter, PVC, 4” Female, PVC, 4” Slip X 4” Female NPT (CAGE 61125, P/N 3010146 or equivalent)
· 4 ea - Pipe, PVC, 6” X 5’ (CAGE 61125, P/N 3010147 or equivalent)
· 4 ea - Pipe, PVC, 4” X 5’ (CAGE 61125, P/N 3010148 or equivalent)
· 3 ea - Adapter, Raw Water, 4” Female QD X Male NPT (CAGE 33813, P/N 40B or equivalent)
· 4 ea - Adapter, Raw Water, 6” Female QD X Female NPT (CAGE 58536, P/N AA59326/5A-10-A-2 or equivalent)
· 2 ea - Adapter, Raw Water, 6” Male QD X Female NPT (CAGE 58536, P/N AA59326/1A-10-A or equivalent)
· 3 ea - Mender, Hose, 6” (USA Blue Book, Stock # 60598 or equivalent)
· 2 ea - Adapter, Raw Water 6’ Male QD X Male NPT (CAGE 58536, P/N AA5936/3A-10-A or equivalent)
· 8 ea - Hose Bridge System, 6.5” (CAGE 032T9, P/N UHB5060 or equivalent) Consisting of:
16 ea - Ramp
8 ea - Tunnel Connector
· 10 ea - Flaking Box (CAGE 97403, P/N 13227E9787 or equivalent)
· 25 ea - Worm Gear Hose Clamps, ½” (or wider) band width, slotted hex screw, range 5 ¾” to 7 ¾” (USA Blue Book, Stock # 44645 or equivalent)
· 25 ea - Worm Gear Hose Clamps, ½” band width, slotted hex screw, range 3 ½” to 5”, (USA Blue Book, Stock # 67820 or equivalent)
· 2 ea - Ratchet Torque Wrench (USA Blue Book, Stock # 44790 or equivalent)
· 50 - Teflon Tape, 1” wide, (MIL-T-27730 or equivalent)
3.2.1.1 Source Run Pump. PD07WRGBGBLC48-6 The pump shall be trailer mounted, diesel-driven, and capable of running continuously for 24 hours off of JP-8 fuel. It shall be continuous self-priming and capable of producing a 300 ft maximum head in order to push water 6000 ft to an elevation of at least 150 ft and deliver water at its termination point at 400 GPM.
3.2.1.1.1 Source Run Engine. PD07WRGBGBLC48-6 The multi-fuel diesel engine used in conjunction with the source run pump shall meet or exceed the specifications of the John Deere 4045D engine.
Cylinders
Displacement ....................................................... 276 cubic inches
Power @ RPM.................................. 62 SAE net hp @ 1800 RPM
Fuel Consumption ............................3.2-3.4 Gallons per hour (Full Load) Electrical System .....................24 volt DC with 95 amp alternator Equivalent engines must be fully interchangeable in terms of form, fit, and function and shall require the use of minimal adapters. The engine must meet the strictest environmental requirements promulgated by commercial standards, the state of California, or the EPA for the applicable size. The engine shall be provided with appropriate gages and instruments such as a starter control, tachometer, hourmeter, oil pressure gage, temperature indicator, and ammeter. The engine shall be equipped with all mechanical and electrical controls and devices necessary for safe and efficient operation.
3.2.1.1.2 Trailer. PD07WRGBGBLC48-6 A towbar, at the front of unit, is required to provide a means of attaching the unit to a tow vehicle for movement. The towbar shall be 48 inches long and shall be equipped with a 2 3/8 inch minimum ID lunette with a load rating of 90,000 pounds. The unit shall be capable of being towed at speeds of up to 20 mph. A pintle hook per A-A-52550, Type L .Class 2 or equivalent shall be on the rear of the unit, attached to the main structural frame, for towing additional units of similar weight. Tie-down rings conforming to MIL-STD-209 shall be installed to provide for security of cart during air shipment and for lifting. Unit shall be capable of being lifted by 10K forklift. The trailer shall have two forklift tine pockets on each side extending completely through to the other side. The pockets shall be designed to allow the trailer, at maximum weight, to be lifted and carried by a forklift from any side. Each pocket shall be a minimum of 4.00 inches high by 10.00 inches wide. Each pocket shall be lined to prevent excessive wear when meeting the requirements in this specification
3.2.1.1.3 Transition kit. Conversion kits shall be required for long-term operations where commercially available rigid-walled piping is substituted for hose. This kit will consist of metric fittings and pipe sizes due to international local availability and American Standard fittings and pipe sizes.
3.2.2 ROWPU Water Production PD07WRGBGBLC48-2 (See Fig. 4 for typical layout.) The ROWPU Water Production package will consist of a series of pumping, piping, fluid control, and storage equipment. The subsystem shall be capable of moving water from a source 500 feet away using a 2” diesel pump and 3” hose/piping and delivering it to a 20K water preprocessing bladder. The water from the 20K water preprocessing bladder shall be distributed through a series of hoses and fittings arranged to interface with three (3) 600 Reverse Osmosis Water Purification Units (ROWPUs) setup in a parallel configuration or two (2) 1500 ROWPUs setup in a parallel configuration (Note: The 600 ROWPUs and 1500 ROWPUs are supplied separately and are NOT to be furnished with the water production package). The potable water provided by the ROWPUs will be fed through another series of hoses and fittings and will be stored in a 20K potable water storage bladder. The byproducts from the treatment process will enter a 20K pillow bladder (Waste) and a 3K pillow bladder (Waste water) for reuse and/or disposal. A pump and hose system will carry this byproduct away from the water production area. Two pumps shall be required in the package for disposing of the waste from the water production site. Both pumps shall be 2” pumps capable of pushing wastewater 500 feet through a 3” collapsible hose. One pump shall be diesel (in the event that prime power is not available or inadequate) and the other pump shall be electric (in the event that prime power is available and adequate).
NOTE: The ROWPU Water Production Subsystem shall interface with the existing BEAR WATER SYSTEM (Ref. Fig. 1) and the components shall be form, fit, and functionally interchangeable with the existing ROWPU Water Production Subsystem. The existing ROWPU Water Production Subsystem consists of the following components:
· 4 ea – Reducer, 2” Male X 1 ½” Female QD’s, Waste Water, (Purple Stripe) (CAGE 61125, P/N 3020268-3 or equivalent)
· 2 ea – Tee Assembly, 2” PVC, Potable Water W/Female X Male X Female QD’s, (White Stripe) (CAGE 61125, P/N 3020252-1)
· 4 ea - Reducer, Raw Water, 4" Female QD X 2" Male QD (CAGE 61125, P/N 3020269-2 or equivalent)
· 4 ea - Hose Assy, Suction, Raw Water, 2" X 25' (CAGE 61125, P/N 3022060 or equivalent)
· PD07WRGBGBLC48-8 - 1 ea - Pump, Diesel, 125 GPM, Raw Water,W/ 2" Female QD(Suction) X 2" Male QD (Discharge) (CAGE 61125, P/N 3020220-2 or equivalent)
· 1 ea - Reducer, Raw Water,3" Male QD X 2" Female QD (CAGE 61125, P/N 3020247-2 or equivalent)
· 5 ea- Hose Assy, Discharge, Raw Water, 3" X 100' (CAGE 61125, P/N 3021060 or equivalent)
· 1 ea - Valve Assy, Swing Check, PVC, Raw Water,W/ 3" Female QD X 3" Male QD (CAGE 61125, P/N 3030129-2 or equivalent)
· 2 ea - Reducer, Raw Water, 4" Male QD X 3" Female QD (CAGE61125, P/N 3020246-2 or equivalent)
· 2 ea - Hose Assy, Suction. Raw Water, 4" X 50' (CAGE 61125, P/N 3011080 or equivalent)
· 7 ea - Tee Assy, 4”, PVC, Raw Water, W/4" Female QD X 4" Male QD X 4" Male QD (CAGE 61125, P/N 3020250-2 or equivalent)
· 8 ea - Valve Assy, Ball, Raw Water,W/ 4" Female QD X 4" Male QD (CAGE 61125, P/N 3010163-2 or equivalent)
· 8 ea - Hose Assy, Suction, Raw Water, 4" X 15' (CAGE 61125, P/N 3011060 or equivalent)
· 1 ea - Bladder, 20,000 Gallon, Raw Water,W/accessories per MIL-T-53029 or equivalent, plus 1 ea - Adapter, 2" Male QD x 2" Male NPT per bladder. (CAGE 61125, P/N 3010100-2 or equivalent)
· 1 ea - Hose Assy, Suction, Raw Water, 2" X 8' (CAGE 61125, P/N 3011090 or equivalent)
· 1 ea - Valve Assy, Ball, Raw Water,W/ 2" Female QD X 2" Female NPT (CAGE 61125, P/N 3010173-2 or equivalent)
· 2 ea - Tee Assy, Raw Water, 4”, PVC, W/4"Male QD X 4"Male QD X 4"Female QD (CAGE 61125, P/N 3020285-2 or equivalent)
· 4 ea - Valve Assy, Ball, Raw Water W/ 2" Female QD X 2" Female QD (CAGE 61125, P/N 3020280-2 or equivalent)
· 2 ea - Water Purification Unit, 1500 GPH (ROWPU) (THIS PART NUMBER IS PROCURED ON A SEPARATE CLIN ITEM )
· 4 ea – Reducer, Raw Water, 2” Male X 1-1/2” Female QD, Raw (CAGE 61125, P/N 3020268-2 or equivalent)
· 4 ea - Reducer, Potable Water, 2” Male X 1-1/2" Female QD (CAGE 61125, P/N 3020268-1 or equivalent)
· 4 ea - Valve Assy, Swing Check, Potable Water,2" Male QD (CAGE 61125, P/N 3020245-1 or equivalent)
· 4 ea - Hose Assy, Suction, Potable Water, 61125, P/N 3021050 or equivalent)
· 2 ea - Tee Assy, Potable Water, Female QD X 2"Female QD X 2"Male QD (CAGE 61125, P/N 3020254-1 or equivalent)
· 1 ea - Reducer, Potable Water, 4” Male QD X 2” Female QD (CAGE 61125, P/N3020270-1 or equivalent)
· 3 ea - Tee Assy, Potable Water, 4”, PVC, W/4"Female QD X 4"Male QD X 4"Male QD (CAGE 61125, P/N 3020250-1 or equivalent)
· 7 ea - Valve Assy, Ball, Potable Water, 4" Female QD X 4" Male QD (CAGE 61125, P/N 3010163-1 or equivalent)
· 8 ea - Hose Assy, Suction, Potable Water, 4" X 15' (CAGE 61125, P/N 3021130 or equivalent)
· 1 ea - Bladder, Potable Water, 20,000 Gallon, W/accessories per MIL-T-53029 or equivalent, plus 1 ea - Adapter, 2" Male QD x 2" Male NPT per bladder. (CAGE 61125, P/N 3010100-1 or equivalent)
· 1 ea - Hose Assy, Suction, Potable Water, 2" X 8' (CAGE 61125, P/N 3022090 or equivalent)
· 1 ea - Valve Assy, Ball, Potable Water, W/2" Female QD X 2" NPT (CAGE 61125, P/N 3010173-1 or equivalent)
· 10 ea - Valve Assy, Ball, Waste, W/ 2" Female QD X 2" Male QD (CAGE 61125, P/N 3020240-3 or equivalent)
· 10 ea - Tee Assy, Waste, 2” PVC, W/2"Female QD X 2"Male QD X 2"Female QD (CAGE 61125, P/N 3020252-3 or equivalent)
· 6 ea - Hose Assy, Discharge, Waste, 2" X 25' (CAGE 61125, P/N 3021030 or equivalent)
· 3 ea - Hose Assy, Discharge, Waste, 2" X 50' (CAGE 61125, P/N 3021020 or equivalent)
· 8 ea - Hose Assy, Suction, Waste, 2" X 25' (CAGE 61125, P/N 3022050 or equivalent)
· 8 ea - Valve Assy, Swing Check, Waste, PVC,W/2" Female QD X 2" Male QD (CAGE 61125, P/N 3020245-3 or equivalent)
· 4 ea - Tee Assy, Waste, PVC, W/ 2"Female QD X 2"Male QD X 2"Male QD (CAGE 61125, P/N 3020256-3 or equivalent)
· 5 ea - Tee Assy, Waste, 2” PVC, W/2"Female QD X 2"Female QD X 2"Male QD (CAGE 61125, P/N 3020254-3 or equivalent)
· 5 ea - Reducer, Waste, 4" Male QD X 2" Female QD CAGE 61125, P/N 3020270-3 or equivalent)
· 4 ea - Tee Assy, Waste, 4”, PVC, W/ 4"Female QD X 4"Male QD X 4"Female QD (CAGE 61125, P/N 3020286-3 or equivalent)
· 4 ea - Hose Assy, Suction, Waste, 4" X 25' (CAGE 61125, P/N 3022110 or equivalent)
· 2 ea - Tee Assy, Waste, 4”, W/ 4"Female QD X 4"Male QD X 4"Male QD (CAGE 61125, P/N 3020250-3 or equivalent)
· 5 ea - Valve Assy, Ball, Waste, 4”, W/4" Female QD X 4" Male QD (CAGE 61125, P/N 3010163-3 or equivalent)
· 5 ea - Hose Assy, Suction, Waste, 4" X 15' (CAGE 61125, P/N 3022100 or equivalent)
· 2 ea - Reducer, Waste, 4" Female QD X 2" Male QD (CAGE 61125, P/N 3020269- 3 or equivalent)
· 1 ea - Bladder, Waste, 20,000 Gallon, W/accessories per MIL-T-53029 or equivalent, plus
1 ea - Adapter, 2" Male QD x 2" Male NPT (CAGE 61125, P/N 3020100-3 or equivalent)
· 1 ea - Hose Assy, Suction, Waste, 2" X 8', (CAGE 61125, P/N 3022080 or equivalent)
· 1 ea - Valve Assy, Ball, Waste, 2”, W/ 2" Female QD X 2" NPT (CAGE 61125, P/N 3010173-3 or equivalent)
· 1 ea - Bladder, Waste Water, (Red Stripe) 3,000 Gallon, W/accessories per MIL-T-53029, W/2”Female QD X 2” Male QD (CAGE 61125, P/N 3020300-4 or equivalent)
· 1 ea - Hose Assy, Suction, Waste Water (Red Stripe), 2" X 8' (CAGE 61125, P/N 3022120 or equivalent)
· 1 ea - Valve Assy, Ball, Waste Water, 2", W/ Female QD X 2" NPT (CAGE 61125, P/N 3010173-4 or equivalent)
· 1 ea - Pump Assy, Waste, Electric, 35 GPM, W/ 2"Female QD (Suction) X 2"Male QD (Discharge) (CAGE 61125, P/N 3020131-3 or equivalent)
· 1 ea - Pump Assy, Waste, Diesel, 125 GPM, W/ 2" Female QD (Suction) X 2" Male QD (Discharge) (CAGE 61125, P/N 3020220-3 or equivalent)
· 2 ea - Reducer, Waste, 3" Male QD X 2" Female QD,(CAGE 61125,P/N 3020247-3 or equivalent)
· 5 ea - Hose Assy, Discharge, Waste, 3" X 100' (CAGE 61125, P/N 3021010 or equivalent)
· 1 ea - Strainer and Float Buoy Assembly, Raw Water, (CAGE 61125, P/N 3020120-2 or equivalent),Consisting of:
1 ea - 2” Steel Suction Strainer (Strainer openings shall be ½” maximum). The strainer shall have a 2” Male QD fitting.
1 ea - Cable, Wire Rope, 15'
1 ea - Clamp, Cable
1 ea - Float Buoy (The Float Buoy shall have buoyancy rating of 240 pounds.)
1 ea - Pump, Air, Hand
· 1 ea - Hose Assy, Suction, Raw Water, 2" X 50' (CAGE 61125, P/N 3022070 or equivalent)
· 1 ea - Hose Assy, Suction, Raw Water, 4" X 25' (CAGE 61125, P/N 3011070 or equivalent)
· 1 ea - Hose Assy, Discharge, Waste, 3" X 25' (CAGE 61125, P/N 3022040 or equivalent)
· 2 ea - Hose Assy, Discharge, Waste, 3" X 50' (CAGE 61125, P/N 3021000 or equivalent)
· 1 ea - Adapter, Swivel, 2-1/2" Female NST X 3" Male NPT (CAGE 61125, P/N 3020230 or equivalent)
· 1 ea - Adapter, Swivel, 2-1/2" Female NST X 3" Female NPT (CAGE 61125, P/N 3020158 or equivalent)
· 1 ea - Adapter, Swivel, 2-1/2" Female NST X 2" Female NPT (CAGE 61125, P/N 3020159 or equivalent)
· 25 ea - Clamp, Hose, Worm Gear, 1/2" Band Width, Slotted Hex Screw, 3 ½” to 5" Range
· 25 ea - Clamp, Hose, Worm Gear, 1/2" Band Width, Slotted Hex Screw, 1 ¾” to 8 9/16” Range
· 2 ea - Ratchet Torque Wrench (USA Blue Book, Stock # 44790 or equivalent)
· 10 ea - Tape, Teflon, 1/2" or wider (MIL-T-27730 or equivalent)
· 1 ea - QD Adapter Kit Consisting of:
1 ea - Adapter, 4" Male QD x 4" Male QD (CAGE 33813, P/N SA40X40 or equivalent)
1 ea - Coupler, 4" Female QD x 4" Female QD (CAGE 33813, P/N 40CX40C or equivalent)
2 ea - Adapter, 2" Male QD x 2" Male QD (CAGE 33813, P/N SA20X20 or equivalent)
2 ea - Coupler, 2" Female QD x 2" Female QD (CAGE 33813, P/N 20CX20C or equivalent)
1 ea - Adapter, 1 ½” Male QD X 1 ½” Male QD (CAGE 33813, P/N SA15X15 or equivalent)
1 ea - Coupler, 1 ½” Female QD X 1 ½” Female QD (CAGE 33813, P/N 15CX15C or equivalent)
3.2.2.1 Reverse-Osmosis Water Purification Unit (ROWPU). PD07WRGBGBLC48-9 ROWPU shall be capable of producing potable water from natural water sources (i.e. pond, lake, stream, sea, or ocean). The ROWPUs shall be capable of operating in conjunction as well as independently. The ROWPUs shall also be capable of being isolated from one another in order to conduct repair, maintenance, and replacement of one ROWPU while maintaining water purification with the remaining operational ROWPU. The ROWPU shall operate at design capacity without leaks, malfunctions, or permanent deformation, and shall meet the overall design, material, temperature, transportability, reliability, maintainability, and safety requirements of the water system specified herein.
Each ROWPU shall have a capacity of no less than 1500 gallons per hour (GPH) when using a source that contains 27,000 ppm total dissolved solids (TDS) with a turbidity of 12.5 NTU, normalized at 77°F. The water produced shall be in full accordance with Tri-Service Field Water Quality Standards for long term consumption. The ROWPU shall be capable of obtaining not less than 99% decontamination of water in Nuclear, Biological, and Chemical (NBC) environments through routine operation (without the aid of additional components or external processes). The ROWPU shall be capable of achieving 99.9% decontamination of NBC contaminants in the water for not less than 100 operating hours. This additional purification capability may be achieved through the use of a post-treatment section and shall be considered part of the basic ROWPU unit. (CAGE Code OAK83, Part No. 701-1500 - 1500 ROWPU or equivalent)
The maximum operating pressure shall not exceed 1,000 psi. The ROWPU shall fit directly on a single 463L Pallet and shall be fully air transportable. The combined weight of the pallet and the unit shall not exceed 10,000 lbs. The use of commercial/military specification components and fittings in lieu of specialty components shall be maximized. The unit shall utilize standard off-the-shelf membranes and filters and shall have a minimum replacement/service time of 1500 hours. Design shall not require removal of other major components to access and service/replace subassemblies and filters. Unless otherwise specified, a sample shall be subjected to first article inspection.
NOTE: The 1500 ROWPU shall interface with the existing BEAR Water System and shall be form, fit, and functionally interchangeable with the existing 1500 ROWPU. (CAGE Code OAK83, P/N 701-1500, or equivalent)
3.2.2.2 Electric pump. Self-priming centrifugal pump, minimum flow of 35 gpm at 40 psi. Electric motor shall be a 2 HP, single-phase, 60 Hz, wired for 208volts. Any fans or other moving parts capable of causing injury shall be totally enclosed or protected by a guard and clearly labeled with warning. Electrical inlet fitting shall be a military or commercial version of MS90558C32412P. Pump assembly shall be fitted with an accumulator tank and a pressure switch set at on-20 psi and off-40 psi. Pressure switch shall contain a manual on-off switch. Pump inlet fitting shall be 2" female adapter quick disconnect and outlet fitting shall be 2” male adapter quick disconnect per A-A-59326/1A. The hose sections at the inlet and outlet of the pump shall be configured to prevent the hoses from becoming kinked. A check valve and pressure gage shall be mounted on the discharge of the pump. The outer perimeter of the assembly shall be contained in an aluminum cage.
3.2.3 550 Initial. PD07WRGBGBLC48-3 (See Fig. 5 for typical layout.) The 550-initial water distribution package is the backbone of the BEAR water system. The system shall be designed for added expansion, reliability, built-in redundancy, ease-of-installation/maintenance, and build-up. This system requires three 20K water bladders for front-end storage capacity, and five 3K (pillow-type) bladders for facility storage capacity and redundancy. The bladders shall be in accordance with MIL-T-53029 or equivalent. The 20K bladders are the starting point of the system and shall be configured in such a way, to accommodate tank farm expansion. These bladders shall be connected to a 4” header line feeding into a variable speed dual pumping station designed to feed the water-using facilities throughout the distribution line. The two pumps shall be capable of interacting with each other, alternating, and controlling the water flow within the distribution line that can be looped and connected together to form a pressurized feed line. The distribution line size shall be 3” collapsible hose. The pumps shall be powerful enough to handle pumping and feeding water to 12 continuously running 2” feeder branches off of the 3” distribution line (estimated feeding capacity is 300 GPM over 3,000 feet in two directions from pumping station or 6,000 feet of total “looped” distribution). The normal continuous pressure supplied throughout the distribution line shall be no less than 45 ± 5 PSI. Maximum continuous water pressure within the distribution line shall not exceed 80 PSI. Ball valves shall be placed on the distribution line at each feed branch to allow isolation capabilities. The water feed line coming directly off of the pump station shall go into a tee that contains a valve on each side to allow for shutting down the continuous loop. One ball valve shall be required at each feed branch on the distribution line, and all valves on the distribution line shall be spaced on the same side of each branch feeder tee in order to isolate each branch from the distribution line. All facility feed lines shall be 2” hose and shall contain a ball valve coming directly from the distribution line to allow for isolation. The possibility also exists that 3” feed lines will be placed on the system for operations like tanker truck filling stations and remote area feed line runs. The feeder branch tees shall be the same uniform, standard size and not specially made for the system. (Example: If 3” hose is selected as the distribution loop, 3x3x3” tees could be selected at each branch and reduced/bushed down to the 2” feeder line connections. This allows the maintainer and operator to be more flexible when setting up their system.) Each 2” feeder hose shall feed a 3K pillow bladder. Ball valves shall be connected on the 2” threaded inlet and outlet ports on each side of the bladder. The outlet side ball valve shall be 2” and the inlet shall be no smaller than 2”. The water entering the bladder from the distribution loop will be under pressure and shall be regulated. The pillow bladders are not designed to handle pressure and therefore, a bladder fill-level control device will be necessary to control the amount of water in the bladder. This subsystem shall also contain a wastewater collection system that will be capable of carrying wastewater away from the water-using facilities to a centralized collection/treatment area. The water system shall contain all the necessary interface components required to supply water to and remove wastewater from the following facilities: latrines, showers, laundries, and kitchens. Normal camp setup consists of latrines, showers, and laundries placed along the outside edges of the encampment. BEAR camps are placed on somewhat level ground making wastewater disposal collection lines by gravity-feed unfeasible. Forced wastewater lines are the only alternative and shall be part of this system design.
NOTE: The 550 Initial Subsystem shall interface with the existing BEAR WATER SYSTEM (Ref. Fig. 1) and the components shall be form, fit, and functionally interchangeable with the existing 550 Initial Subsystem. The existing 550 Initial Subsystem consists of the following components:
1 ea - Strainer and Float Buoy Assembly, Raw Water, (CAGE 61125, P/N 3020120 or equivalent), Consisting of:
1 ea - 2” Steel Suction Strainer (Strainer openings shall be ½” maximum). The strainer shall have a 2” Male QD fitting.
1 ea - Cable, Wire Rope, 15'
2 ea - Clamp, Cable
1 ea - Float Buoy (The Float Buoy shall have buoyancy rating of 240 pounds.)
1 ea - Pump, Air, Hand
· 1 ea - Adapter, Assy, Raw Water, Hydrant, 2 1/2" NST x 2" Female QD (CAGE 61125, P/N 3030337 or equivalent)
· 1 ea - Coupler, Raw Water, 2 in. Male NPT x 2 in. Female QD (CAGE 33813, P/N 20B or equivalent)
· 5 ea - Hose Assy, Suction, Potable Water, 2" X 25', Potable Water (CAGE 61125, P/N 3021050 or equivalent)
· PD07WRGBGBLC48-8 - 1 ea - Pump Assy, Diesel, Potable Water,125 GPM,W/ 2" Female QD(Suction) X 2" Male QD (Discharge) (CAGE 61125, P/N 3020220-1 or equivalent)
· 1 ea - Reducer, 3" Male QD X 2" Female QD, Potable Water (CAGE 61125, P/N 3020247-1 or equivalent)
· 15 ea - Hose Assy, Discharge, 3" X 100', Potable Water (CAGE 61125, P/N 3031020 or equivalent)
· 1 ea - Valve Assy, Swing Check, 3", PVC, Potable Water, W/3” Female QD X 3" Male QD (CAGE 61125, P/N 3030129-1 or equivalent)
· 1 ea - Reducer,4" Male QD X 3" Female QD, Potable Water (CAGE 61125, P/N 3020246-1 or equivalent)
· 4 ea - Reducer, 4” Male QD X 3” Female QD, Waste (CAGE 61125, P/N 3020246-3 or equivalent)
· 20 ea - Hose Assy, Suction, Potable Water, 4" X 15' (CAGE 61125, P/N 3021130 or equivalent)
· 5 ea - Tee Assy, 4”, PVC, Potable Water, W/ 4"Female QD X 4"Male QD X 4"Male QD (CAGE 61125, P/N 3020250-1 or equivalent)
· 10 ea - Valve Assy, Ball, 4", Potable Water, W/4” Female QD X 4" Male QD (CAGE 61125, P/N 3010163-1 or equivalent)
· 3 ea - Bladder, 20,000 Gallon, Potable Water, W/accessories per MIL-T-53029 or equivalent, plus
1 ea - Adapter, 2" Male QD x 2" Male NPT per bladder. (CAGE 61125, P/N 3010100-1 or equivalent).
· 8 ea - Hose Assy, Suction, Potable Water, 2" X 8' (CAGE 61125, P/N 3022090 or equivalent)
· 8 ea - Valve Assy, Ball, 2", Potable Water, W/2” Female QD X 2" NPT (CAGE 61125, P/N 3010173-1 or equivalent)
· 5 ea - Tee Assy, 4”, PVC, Potable Water, W/ 4"Male QD X 4"Female QD X 4"Female QD (CAGE 61125, P/N 3030345-1 or equivalent)
· PD07WRGBGBLC48-7 - 1 ea - Pump Station, Variable Speed, Dual, Potable Water (CAGE 0AK83, P/N 701-1037 or equivalent)
· 7 ea - Hose Assy, Discharge, Potable Water, 3" X 25' (CAGE 61125, P/N 3031010 or equivalent)
· 3 ea - Tee Assy,3”, Potable Water, W/3"Male QD X 3"Male QD X 3"Female QD (CAGE 61125, P/N 3030320-1 or equivalent)
· 6 ea - Valve Assy, Ball,3”, Potable Water, W3" Female QD X 3" Male QD (CAGE 61125, P/N 3030131-1 or equivalent)
· 14 ea - Hose Assy, Discharge, Potable Water, 3" X 50' (CAGE 61125, P/N 3031000 or equivalent)
· 7 ea - Tee Assy, 3” X 3” X 2”, PVC, Potable Water, W/3"Female QD X 3"Male QD X 2"Male QD (CAGE 61125, P/N 3030310-1 or equivalent)
· 15 ea - Valve Assy, Ball, 2”, Potable Water, W/2" Female QD X 2" Male QD (CAGE 61125, P/N 3020240-1 or equivalent)
· 10 ea - Hose Assy, Discharge, Potable Water, 2" X 25' (CAGE 61125, P/N 3032000 or equivalent)
· 4 ea - Bladder Water Level Control Valve, 2" Electric, W/ 2" Female QD X 2" Female QD, W/25 ft. Outdoor Extension Cord (CAGE 61125, P/N 3030121- 1 or equivalent)
· 5 ea - Bladder, 3,000 Gallon, Potable Water, W/accessories per MIL-T-53029 or equivalent. (CAGE 61125, P/N 3020200-1 or equivalent)
· 5 ea - Tee Assy, 2”, PVC, Potable Water,W/2"Male QD X 2"Male QD X 2"Female QD (CAGE 61125, P/N 3030300-1 or equivalent)
· 3 ea - Reducer, Potable Water, 2" Female QD X 1-1/2" Female QD (CAGE 61125, P/N 3030333-1 or equivalent)
· 4 ea - Reducer, Potable Water, 2" Female QD X 3/4" Male QD (CAGE 61125, P/N 3030332-1 or equivalent)
· 3 ea - Reducer, Potable Water, 2" Female QD X 1" Female QD (CAGE 61125, P/N 3030261-1 or equivalent)
· 3 ea - Reducer, Potable Water, 2" Female QD X 1" Male QD (CAGE 61125, P/N 3030331-1 or equivalent)
· 3 ea - Adapter, Waste, 4" Male QD X 4" Victaulic/Grooved (CAGE 61125, P/N 3030338-3 or equivalent)
· 2 ea - Lift Station, Sewage, Pump 1 HP, Ejector, Basin, Polyethylene, 30"W x 36"H, 208V, 1 ph W /power panel P/N 22060E02, W/ 4" Female QD Inlet X 2" Male QD Outlet W/Check Valve, Plus 2" NPT 90 Degree Elbow (detached) (CAGE 61125, P/N 3030350-3 or equivalent)
· 3 ea - Hose Assy, Discharge, Waste, 2" X 25' (CAGE 61125, P/N 3021030 or equivalent)
· 10 ea - Hose Assy, Discharge, Waste, 2" X 50' (CAGE 61125, P/N 3021020 or equivalent)
· 8 ea - Valve Assy, Swing Check 2”, Waste. PVC, W/2" Female QD X 2" Male QD (CAGE 61125, P/N 3020245-3 or equivalent)
· 8 ea - Wye Assy, PVC, Waste Water, W/3"Female QD X 3"Male QD X 2"F QD (CAGE 61125, P/N 3030330-3 or equivalent)
· 10 ea - Hose Assy, Discharge, Waste Water, 3" X 25' (CAGE 61125, P/N 3022040 or equivalent)
· 8 ea - Hose Assy, Discharge, Waste Water, 3" X 50' (CAGE 61125, P/N 3021000 or equivalent)
· 2 ea - Reducer, Waste Water, 3" Male QD X 2" Female QD (CAGE 61125, P/N 3020247-3 or equivalent)
· 5 ea - Valve, Swing Check, 3”, PVC, Waste Water, W/3" Female QD X 3" Male QD (CAGE 61125, P/N 3030129-3 or equivalent)
· 1 ea - Lift Station Assy, Macerator, Waste Water, W/3” Female QD X 3” Male QD (CAGE 61125, P/N 3030190-3 or equivalent)
· 5 ea - Hose Assy, Discharge, Waste Water, 3" X 100' (CAGE 61125, P/N 3021010 or equivalent)
· 1 ea - Sewage Lift Station, Assembly, Dual Pump, Waste Water, W/ 3" Female Inlet QD x 3" Male Outlet QD (CAGE 61125, P/N 3030170-3 or equivalent)
· 3 ea - Adapter, Waste, 4" Male QD X 4" Male NPT (CAGE 33813, P/N 40F or equivalent)
· 1 ea - 25,000 Gallon Tank Assy, Waste Water (CAGE 0AK83, P/N 701-1036 or equivalent). Consisting of:
10 ea - Section, Wall
12 ea - Rod, Connecting
1 ea - Liner, Tank
2 ea - Section, Wall, Bulkhead
1 ea - Cloth, Ground
8 ea - Kit, Bulk Head
2 ea – Ladder 1 ea – Wrench
1 ea – Knife
· 1 ea - System, Mixing, Wastewater(CAGE 0AK83, P/N 701-1045 or equivalent) Consisting of:
1 ea - Aerator, Assembly (CAGE 0AK83, P/N 701-1045-12 or equivalent) 1 ea - Pump, Assembly, Skid (CAGE 0AK83, P/N 701-1045-13 or equivalent) 3 ea - Hose Assembly, Discharge, 1-1/2" X 15' (CAGE 0AK83, P/N 701 1045-7 or equivalent) 2 ea - Hose Assembly, Suction, 3" X 30' (CAGE 0AK83, P/N 701- 1045-5 or equivalent) 1 ea - Hose Assembly, Suction, 3" X 5' (CAGE 0AK83, P/N 701-1045- 6 or equivalent) 1 ea - Hose Assembly, Discharge, 2" X 5' CAGE 0AK83, P/N 701- 1045-8 or equivalent) 2 ea - Strainer, 3" W/Positioning Cable CAGE 0AK83, P/N 701-1045- 14 or equivalent) 1 ea - Discharge Manifold Assembly (CAGE 0AK83, P/N 701-1045-15 or equivalent) 1 ea - Intake Manifold Assembly (CAGE 0AK83, P/N 701-1045-16 or equivalent)
1 ea – Ground Rod Assembly (CAGE 0AK83, P/N 701-W-R-550 or equivalent)
· 8 ea - Hose Assy, Discharge, Waste Water, 4" X 50' CAGE 61125, P/N 3031070 or equivalent)
· 1 ea - Hose Assy, Discharge, Potable Water, 2" X 100' (CAGE 61125, P/N 3031030 or equivalent)
· 1 ea - Hose Assy, Suction, Potable Water, 2" X 50' (CAGE 61125, P/N 3031140 or equivalent)
· 1 ea - Valve Assy, Swing Check, 2”,W/2" Female QD X 2" Male QD (CAGE 61125, P/N 3020245-1 or equivalent)
· 20 ea - 4" Hose Bridge System (CAGE 032T9, P/N UHB4045 or equivalent) Consisting of:
40 ea - Ramp 20 ea - Tunnel Connector
· 10 ea - 4" Tunnel Connector (CAGE 032T9, P/N UHB4045TC or equivalent)
· 10 ea - 4" Tunnel (CAGE 032T9, P/N UHB4045T or equivalent)
· 1 ea - Reducer, Potable Water, 4" Female QD X 2" Male QD (CAGE 61125, P/N 3020269-1 or equivalent)
· 1 ea - Reducer, Potable Water, 4" Male QD X 2" Female QD (CAGE 61125, P/N 3020270-1 or equivalent)
· 1 ea - Reducer, Potable Water, 4" Female QD X 3" Male QD (CAGE 61125, P/N 3030230-1 or equivalent)
· 2 ea - Ratchet Torque Wrench (USA Blue Book, Stock # 44790 or equivalent)
· 25 ea - Clamp, Hose, Worm Gear, 1/2" Band Width, Slotted Hex Screw, 3 ½” to 5" Range
· 25 ea - Clamp, Hose, Worm Gear, 1/2" Band Width, Slotted Hex Screw, 1 ¾” to 8 9/16” Range
· 1 ea - QD Adapter Kit Consisting of:
2 ea - Coupler, 2" Female QD x 2" Female QD (Cage 33813, P/N 20CX20C or equivalent) 1 ea - Adapter, 1 1/2" Male QD x 1 1/2" Male QD (CAGE 33813, P/N SA15X15 or equivalent) 1 ea - Coupler, 1 1/2" Female QD x 1 1/2" Female QD (CAGE 33813, P/N 15CX15C or equivalent) 2 ea - Adapter, 3" Male QD x 3" Male QD (CAGE 33813, P/N SA30X30 or equivalent) 2 ea - Coupler, 3" Female QD x 3" Female QD (CAGE 33813, P/N 30CX30C or equivalent) 2 ea – Adapter, 1" Male QD x 1" Male QD (CAGE 33813, P/N SA10X10 or equivalent) 2 ea - Coupler, 1" Female QD x 1" Female QD (CAGE 61125, P/N 3030336-1 or equivalent) 1 ea - Adapter, 3/4" Male QD x 3/4" Male QD (33813, P/N SA07X07 or equivalent) 1 ea - Coupler, 3/4" Female QD x 3/4" Female QD (CAGE61125, P/N 3030334-1 or equivalent) 2 ea - Coupler, 3/4" Female QD X 3/4" Female NPT (CAGE 33813, P/N 3/4D or equivalent)
· 2 ea - Faucet, 3/4" Hose bib X 3/4" Male NPT (COMM)
· 1 ea - Hose, Garden, 3/4", 50 ft. roll
· 1 ea - Tool, BAND-IT (CAGE 70847, P/N C001 or equivalent)
· 1 ea - Band,…