Question and Answer Responses

View the file

Other files for this federal contract opportunity

Other files attached to Repair Chiller #5, newest first.
File Type Posted
FA8101-17-Q-001201_Amendment02.pdf PDF
FA8101-17-Q-001201_Amendment01.pdf PDF
Attachment_2.pdf PDF
Attachment_3.pdf PDF
Attachment_1.pdf PDF
FA8101-17-Q-0012.pdf PDF
Attachment_4.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

HEADQUARTERS AIR FORCE SUSTAINMENT CENTER (AFMC)

TINKER AIR FORCE BASE OKLAHOMA

31 August 2017

MEMORANDUM FOR POTENTIAL OFFERORS

FROM: AFSC/PZIOC

7858 5TH STREET, SUITE 1

TINKER AIR FORCE BASE OK 73145

SUBJECT: Questions and Answers (Q&A #1 - #5) from Site Visit for Project WO#57322 Repair Chiller, Bldg 9301 – FA8101-17-Q-0012

1. The following Q&A is offered and incorporated in the subject contract as follows:

Questions & Answers:

Q-1:Section-2.5 PWS mentions oil pump was replaced our inspection shows the oil heater disconnected. Does the oil heater need to be replaced?

A: CLINs have been restructure. CLIN 0001 will be for the system operational test results (PWS 2.14) of the chiller and CLIN 0002 will be for the repair. The Government stated that the oil pump has been replaced and the assumption is that the oil pump is operational. After the results of the system operational test and it has been determined that the oil pump has fail, a modification will be executed.

Q-2: Section-2.5 chiller has set for 3 years, do you want the shaft seal replaced? Or after test it and if leaking work a change order in needed?

A: CLINs have been restructure. CLIN 0001 will be for the system operational test of the chiller and CLIN 0002 will be for the repair. The shaft seal will need to be tested and evaluated for leaking. After the results of the system operational test and it has been determined that the shaft seal is leaking, a modification will be executed.

Q-3:Section-2.12 PWS states start up chiller and calibrate controls. Is it just the controls and sensors on the chiller proper or it is the additional controls system for the whole plant that’s need addressed and calibrated?

A: Only the controls and sensors on the chiller and not the control system for the whole plant.

Q-4:Section-5.1 PWS states the Government would not supply parts or the use of the overhead crane. The power plant personnel stated they would allow of use of crane and personnel if needed during normal business hours. 7-4. Can we get a clarification?

A: The Government will not supply parts and the contractor shall supply all parts for repair. The contractor may utilize the overhead crane and scheduling shall be coordinated with the plant facility staff.

Q-5:Section-13.1 PWS will this project require certified payroll?

A: Manpower Reporting is required for service contracts.

2. Any questions may be directed to Jason Perry at 739-7568 or via email at

(jason.perry.7@tinker.af.mil).

JASON PERRY

Contracting Officer mailto:jason.perry.7@tinker.af.mil

2017-08-31T09:59:35-0500
PERRY.JASON.MICHAEL.1245638791

File details come from the government source that posted it. Updated .