Attachment_3.pdf

PDF 5 MB Posted

Attached to
Repair Chiller #5 Federal contract opportunity
Solicitation number
FA8101-17-Q-0012
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

About this file

Tinker Air Force Base Facility Standard

View the file

Other files for this federal contract opportunity

Other files attached to Repair Chiller #5, newest first.
File Type Posted
FA8101-17-Q-001201_Amendment02.pdf PDF
FA8101-17-Q-0012_Q&A_Responses.pdf PDF
FA8101-17-Q-001201_Amendment01.pdf PDF
FA8101-17-Q-0012.pdf PDF
Attachment_4.pdf PDF
Attachment_2.pdf PDF
Attachment_1.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TINKER AIR FORCE BASE

FACILITY STANDARD

2016 Edition

Base Civil Engineer 72 ABW/CE 7535 5 th ST, Ste 101

Tinker Air Force Base, Oklahoma 73145-9010 Telephone 405-734-3451

Fax 405-734-5535

TABLE OF CONTENTS

Part 1: Project Procedures Chapter Page

1. EXECUTIVE SUMMARY……………………………………………………………………… 9

1.1. Introduction

1.2. Office of Primary Responsibility (OPR)

1.3. How to use the Standard:

1.4. TAFB 72 ABW/CE as the Authority-Having-Jurisdiction

1.5. BCE Project Submittal Requirements

1.6. BCE Function at TAFB

2. 72 ABW / CE RECORDS…………………………………………………………………….. 10

2.1 Base Maps:

2.2 CE Engineering Vault in B400

2.3 Vault Research Procedures

3. DESIGN CRITERIA……………………………………………………………………………. 11

3.1 Order of Project Requirements

3.2 Construction Documents - Signed/Sealed requirements

3.3 Design Publications incorporated by reference to the Standard

3.4 Model Building Codes and Construction Regulations

3.5 Occupational Safety and Health Act / OSHA Regulations

3.6 National Fire Protection Association

3.7 Americans with Disabilities Act

3.8 Sources of Technical and Procedural Requirements

3.9 Responsibilities of the Contractor

3.10 Variance from the Standard

3.11 Product Reference Disclaimer

4. COST ESTIMATING……………………………………………………………………………. 13

4.1 General

4.2 Change Order Documentation

5. DESIGN DOCUMENTATION FORMAT………………………………………………………. 13

5.1 CE Recordkeeping

5.2 Dual Records

5.3 Delivery Media

5.4 CADD File Formats

5.5 Documentation

5.6 Image Files

5.7 CADD File Formats

5.8 CADD Standards

5.9 Specifications Formatting

5.10 Base General Requirements TAFB

5.11 Additional Geographic Information Systems Data

Part 2: Base Infrastructure

6. UTILITY SYSTEMS AND INFRASTRUCTURE ON TAFB……………………………….. 16

6.1 Water Supply

6.2 Wastewater Treatment

6.3 Piping, Utilities, and Manholes

6.4 Sanitary Water Supply

6.5 Sanitary Sewer Collection Systems

6.6 Industrial Wastes

6.7 Oil Separators

6.8 Storm Drainage System

6.9 Natural Gas Delivery Systems

6.10 Liquid Fuel Supply Systems

7. EXTERIOR SIGNAGE………………………………………………………………………... 20

7.1 Standard Facility signs

7.2 Zip + 4 Program Implementation

7.3 Logos and Super Graphics

7.4 Highway Standards and Traffic Control

7.5 Identification of Hazardous Storage

8. TRAFFIC ENGINEERING……………………………………………………………………. 21

8.1 Traffic Considerations

8.2 Signage

8.3 Parking

8.4 Curbing Standards

9. ENVIRONMENTAL REGULATIONS COMPLIANCE……………………………………… 22

9.1 Mandatory publications

9.2 Asbestos Containing Materials (ACM)

9.3 Lead Based Paint

9.4 PCB Filled Ballast and Universal Waste Lamps

9.5 Solid Waste Tracking

9.6 Affirmative Procurement Plan for TAFB

Part 3: TAFB Facility Design on TAFB

10. LIFE SAFETY SYSTEMS………………………………………………………………….. 23

10.1 Identification of Hazardous Systems and Materials Storage

10.2 Color coding facility piping

10.3 ANSI standard and labels for piping

10.4 Antiterrorism and Force Protection at TAFB

10.5 Analytical Design for Projects with High Design Basis Threat and/or Level of Protection

11. FACILITY PROGRAMMING……………………………………………………………….. 24

11.1 Mandatory References

11.2 Facility Siting

11.3 Area Development Plans (ADP)

11.4 Air Installation Compatibility Use Zone (AICUZ)

11.5 Tenant Organization Responsibility

12. BARRIER FREE ACCESS………………………………………………………………… 25

12.1 Handicapped Accessibility

12.2 Uniform Federal Accessibility Standards (UFAS)

12.3 Maintenance and Repair

13. ARCHITECTURAL COMPATIBILITY PLAN……………………………………………… 27

13.1 Introduction

13.2 Architectural/Planning Districts

13.3 Building Design Standards

13.4 Wall Systems

13.5 Roof Systems

13.6 Entrances

13.7 Windows and Doors

13.8 Ancillary Structures

13.9 Landscaping

13.10 Screens and Enclosures

13.11 Roads

13.12 Parking

13.13 Walkways and Paths

13.14 Signs

13.15 Site Furnishings

13.16 Exterior Lighting

13.17 Site Utilities

13.18 Visual District Standards

13.19 Projects Checklist

13.20 Historic Structures

14. INTERIOR DESIGN…………………………………………………………………………. 55

14.1 Program Components

14.2 Specifications

14.3 Interior Finish Guidelines

14.4 Standard Restroom Finishes

14.5 Toilets in Industrial Areas

14.6 Toilet Room Accessories

14.7 Base-Wide Paint Scheme

14.8 Floor Coating Guidelines

14.9 Suspended Ceiling Systems

14.10 Carpet Policy

14.11 Air Force Facility Guidelines for Interior Design

14.11.1 Facility Group 1 – High Visibility Buildings

14.11.2 Facility Group 2 – Professional Image Buildings

14.11.3 Facility Group 3 – Highly Durable Buildings

14.12 Facility Group 4 – Residential Housing

14.13 Design Proposals

14.14 Color Boards

14.15 Installation Artwork and Signage

15. SYSTEMS FURNITURE ………………………………………………….. 69

15.1 TAFB Systems Furniture Policy

15.2 Factors to Consider

15.3 Responsibilities

15.4 CID Manager

15.5 Workstation Costs

15.6 Space Criteria

15.7 Terminology

15.8 Space Allowances

15.9 Project Development

15.10 Materials and Color

15.11 Life Safety

15.12 Electrical Requirements

15.13 Standard Operating Policy for Systems Furniture

15.14 Construction Submittal Requirements

15.15 Maintenance

15.16 Circular Systems

15.17 Panels

15.18 Lighting

15.19 Acoustics

15.20 Power and Communications

15.21 Ergonomics

15.22 Accessibility

15.23 Typical Workstations and Components

15.24 The basics of each workstation

15.25 Loose Furniture

15.26 Additional items

15.27 Sample Workstation Layouts and Clearances

15.28 Department Questionnaire Instructions

15.29 Individual Questionnaire Instructions

16. ENERGY CONSERVATION REQUIREMENTS…………………………………………. 80

16.1 Metering

16.2 Controls Considerations

16.3 Computer Analysis

16.4 Life Cycle Cost Analysis

16.5 Solar Heating System Requirements

Part 4: Engineering Systems Requirements for Facilities

17. CIVIL ENGINEERING REQUIREMENTS………………………………………………….. 81

17.1 Traffic Control

17.2 POV Parking Spaces

17.3 Curb and Gutter

17.4 Pavements

18. LANDSCAPE REQUIREMENTS…………………………………………………………….. 82

18.1 Sustainable Land Design

18.2 Regulatory Bases of Design

18.3 The preliminary stone material working list

18.4 Field Stone

18.5 Accent stone

18.6 Boulders of various sizes

18.7 Others previously used

18.8 Recommended Plantings

18.9 Hard Landscape Features

18.10 Protection and Re-Use of Existing Vegetation

18.11 Retained Trees

18.12 Transplantable Trees

18.13 Cut-Down Trees

18.14 Landscape Maintenance

18.15 Additional objectives of Project Planting Schemes

19. STRUCTURAL ENGINEERING REQUIREMENTS……………………………………..… 85

19.1 Design Load Calculations

19.2 TAFB Minimum Values in Structural Analysis

19.3 Foundation Design

19.4 Geo-technical Investigation

19.5 Structural Economy

19.6 Facility Hardening

19.7 Roof Design

19.8 Seismic Design

20. ARCHITECTURAL SYSTEMS REQUIREMENTS………………………………………… 88

20.1 Excellence in Design

20.2 Quality Architecture

20.3 Integration of Programming, Design, Engineering, and Construction Excellence

20.4 Sustainable Design of AF Facilities

20.5 Contracting Officer Primer on Green Procurement

20.6 Tinker AFB Policy

21. INTERIORS SYSTEMS……………………………………………………………………… 91

21.1 Elements of TAFB Interior Systems

21.2 Safety

21.3 Access

21.4 Function

21.5 Lighting

21.6 Acoustics

21.7 Comfort

21.8 Indoor Air Quality

21.9 Security

21.10 Interior Signage

21.11 Aesthetics

22. CATEGORIES OF EQUIPMENT…………..……………………………………………….. 92

22.1 Office Equipment

22.2 Building Equipment

22.3 Process Equipment

22.4 Project Equipment Schedules

23. FIRE PROTECTION ENGINEERING………………………………………………………. 93

23.1 Base Standardization of Building/Utility Mechanical Systems

23.2 System Design

23.3 Firewalls and Fire Area Limitations

24. PLUMBING REQUIREMENTS.……………………….………………………………….…. 93

24.1 Base Standardization of Building/Utility Mechanical Systems

25. MECHANICAL ENGINEERING…………………………….…………………………….…. 93

25.1 Base Standardization of Building/Utility Mechanical Systems

26. ELECTRICAL ENGINEERING REQUIREMENTS…………………………………………. 93

26.1 Base Standardization of Building/Utility Electrical Distribution Systems

26.2 Related Requirements found elsewhere within the Standard

27. TELECOMMUNICATION SYSTEMS REQUIRMENTS……………………………………. 94

27.1 Utility domain of the 72 ABW/SC

27.2 Civil Provisions

27.3 Telephone and Cable

27.4 Contractor Responsibilities

27.5 General Specifications for New Base Facilities

27.6 Communication Equipment Room

27.7 Primary Network Equipment Rooms

27.8 Secondary Network Equipment Rooms

Part 5: Project Construction and Installation Procedures

28. SAFETY REQUIREMENTS…………………………………………………………………… 95

28.1 General Health and Safety Work Practices on Base

28.2 Site Practices specific to TAFB

29. SPECIAL BASE PROCEDURES……………………………………………………………… 97

29.1 Requirements for all demolition and construction contracts on TAFB

29.2 Demolition, Excavation, and Construction Permits

29.3 Master keying and locks

29.4 Procedures for non-standard work days

29.5 Utility outages and road closings

29.6 Contractor Identification credentials while on TAFB

29.7 Soil and Foundation Conditions

29.8 Construction Facilities and Job Site Standard

29.9 MILCON Requirements

30. CONTRACTOR USE OF AVAILABLE UTILITIES……………………..……………………. 98

30.1 Electrical Service

30.2 Water

30.3 Sewage

30.4 Trash Disposal and Construction Debris

30.5 Maps

31. PROPERTY MAINTAINABILITY………………………………………………………………. 99

31.1 Mandatory references

31.2 Re-use of Existing Materials

31.3 Manufacturer’s name plate, parts, and maintenance manuals

31.4 Construction over Buried Utilities

31.5 Refuse Collection

31.6 Termite Control

Part 6: Links and Documents in Attachment to the Facility Standard https://org.eis.afmc.af.mil/sites/72ABWCE/CEO/TSS/Eng/STANDARDS/Forms/AllItems.aspx General Requirements for Construction on Tinker Air Force Base

Tinker Base Facility Standards

ATTACHMENT A Schedule of Native Plantings Recommended for TAFB……………………. 100

ATTACHMENT B Base Standards for Building/Utility Electrical Distribution Systems/Tele-Data

Communications…………………………………………………………….…. 106

ATTACHMENT C Base Standardization of Building/Utility Mechanical Systems………….…. 107

ATTACHMENT D Base Standardization for Sustainability Guidelines…………………….…. 107

ATTACHMENT E Pavement Trench Detail………………………………………………….…. 108

Part I: Project Procedures

Defense Information Systems Agency: Building 3900

1. Executive Summary

1.1. Introduction

The Tinker AFB Facility Standard (referenced hereafter simply as the Standard) identifies the minimum requirements for construction quality and life safety features for all real property improvements and for all equipment installation projects executed on Tinker Air Force Base.

All projects which permanently attach equipment to real property via hard-wired electrical connections and/or structural anchorage, such as systems furniture installation, hydraulically-operated crane assembly, or repair of existing similar components shall also be subject to compliance with this Standard.

All work encompassed within these categories shall be identified hereafter by the word project or projects as appropriate to the context.

All individuals or companies who provide design and/or construction services for execution of projects on the Base shall be identified hereafter by the word contractor.

1.2. Office of Primary Responsibility (OPR):

The Standard is maintained and annually updated under the authority of the Base Civil Engineer. All questions and recommendations for improvement to this document shall be directed to the 72 ABW/CE.

1.3. Application of the Standard

The Standard applies to Military Construction projects (MCP or MILCON), Simplified Acquisition of Base Engineering Requirements (SABER) projects; Multiple Award Construction Contract (MACC); Indefinite Delivery/Indefinite Quantity (IDIQ) contracts; Utility Energy Service Contract (UESC) delivery orders, Service contracts, Performance Oriented Construction Activity (POCA) projects, Contract By Requestor (CBR) projects, Self Help projects, and AFCEC GSA Contracts. Requirements contained herein shall be applied to all design and/or construction services affecting real property and/or equipment within TAFB, whether designed by 72 ABW/CE, the US Army Corps of Engineers, DLA, HPO, AAFES, NAVFAC, private design consultants, private construction companies, or any other person or business.

1.4. How to use the Standard:

Requirements of the Standard shall be incorporated to design documentation beginning with pre-design and pre-construction services including programming, design analyses, and site planning phases of project designs. The Standard shall be the basis by which all CE approval of projects for Base execution shall be granted or denied.

1.5. TAFB 72 ABW/CE as the Authority-Having-Jurisdiction

All design and construction services executed for the US Air Force and/or any of the Federal organizations residing within TAFB are subject to the review, approval, and inspection of the Base Civil Engineer (BCE) as the local Authority-Having-Jurisdiction. The TAFB Facilities Standard is the principal information source by which BCE project requirements are defined and administered.

1.6. BCE Project Submittal Requirements

As part of the project review process, both hardcopy and electronic documents shall be provided to the BCE by project designers for review prior to the completion of each design stage. All BCE review comments communicated to the project designer which implement requirements of the TAFB Facility Standard shall be incorporated to the Project design prior to the next design phase submittal and prior to issue of any/all drawings and specifications issued for construction.

1.6.1. All Project Drawings and Specifications, for each phase of design required for submittal, shall be delivered in digital format using AutoCAD and MS Word for Windows software for Specifications as identified in Chapter 11, CADD Requirements. The designer shall provide an unbound hard copy suitable for reproduction.

1.6.2. The schedule and number of design submittals shall be in accordance with the design documentation requirements of the project’s contract for construction.

1.7. BCE Function at TAFB

Located within a Federal military installation, the BCE performs the functions of capital improvement programming, urban planning, environmental management, civil and facilities maintenance, maintenance of roads and grounds, air field pavements, air field related lighting, barriers, provision and repair of municipal utilities and community services, and fire protection.

2. TAFB Civil Engineering Records

2.1. Base Maps: TAFB maps in paper format (scale 1 inch to 100 feet are available from the following office:

Engineering Support Division

72 ABW/CE

Second Floor, Building 400 7535 5 th Street

TAFB, OK 73145-9010

2.1.1. Electronic media records of base infrastructure and facility improvements are also available upon written request to the Office of 72 ABW/CE, also at the above street address.

2.2. CE Engineering Vault in B400

2.2.1. The CE Vault is the repository for hardcopy “as-built” drawings for all constructed improvements on base. The Vault, being at full capacity, does not contain all as-built record drawings, since many are in digital format. The archived “Vault” data is the starting point from which 72 ABW/CE personnel plan the continuing program of base maintenance and improvement projects.

Construction contractors use the Vault to find information about utilities and their locations, whereas design consultants use the vault at the beginning of project’s development for determining project proximities to airfield zoning, site constraints, and utility rights-of-way.

2.2.2. Currently, the vault houses approximately 50,000 drawings. Some 30,000 of those are associated with specific facilities while approximately 20,000 are associated with groups of facilities and the overall grounds of Tinker. This inventory includes the runways, aprons, taxiways, and utility services such as electrical, liquid fuel, natural gas, industrial waste, water, and waste water. All Vaulted drawings have been scanned, and are stored on a secure file-server. Available files formats include a mix of AutoCAD, MicroStation, and TIF or PDF files. Customers must present a request to Engineering Support for copies of these files.

2.2.3. Located on the Second Floor in the northwest corner of Building 400, the Vault is open business days 0715-1600 hours to all TAFB personnel and their visitors.

2.3. Vault Research Procedures

2.3.1. First-time visitors please check in at the Customer Support Desk located near the Vault entrance.

Customers must present their requests to Engineering Support, and then allow support personnel time to research the desired information. Typically, Engineering Support provides files to the customer on CD. Hardcopies may be printed upon request. Before entering the Vault, sign-in on the Logbook located just outside the door. This maintains security and accountability for Vault drawings.

2.3.2. After drawings have been selected for copying or scanning to digital files, please ask assistance of Engineering Support personnel on the use of scanner/copier equipment. In most cases this step will not be needed since all drawings have already been scanned. The designer shall be responsible to field verify as-built drawings as the Government does not guarantee their accuracy.

3. Design Criteria

3.1. Order of Project Requirements:

3.1.1. All projects shall comply with this Standard. All projects which permanently attach equipment to real property via hard-wired electrical connections and/or structural anchorage, such as systems furniture installation or hydraulically-operated crane assembly, are also subject to compliance with the Standard.

3.1.2. The term “standard” shall be taken to mean both the body of requirements stated here as well as stated in the attachments and publications incorporated –by-reference.

3.1.3. The primary Building Code reference for Tinker AFB is the Unified Facilities Criteria –Fire Protection Engineering for Facilities (UFC 3-600-01 latest. Edition. UFC 3-600-01 defines the portions of the International Building Code that are to be used in conjunction with the related UFC publications.

3.1.4. The BCE (Base Civil Engineer) is the AHJ (Authority Having Jurisdiction) for this Standard.

Omit UFC 3-600-01, Chapter 1-3.6, Authority Having Jurisdiction (AHJ) that identifies the component office of U.S. Air Force, HQ AFCESA/CEO as AHJ.

3.1.5. Refer to Part 2, 3, 4 and 5 of this Standard for specific and additional design requirements for applicable projects.

3.1.6. Where mandatory references cite differing provisions for similar construction or life safety features, the Project shall then meet the most stringent requirement.

3.2. Construction Documents - Signed/Sealed requirements

3.2.1 All Contractors shall be required to have final construction documents signed/seal by a Registered Architect, registered in the State of Oklahoma, unless the Code Use Group by size/stories/capacity is specifically exempt from the provisions of the State Architectural and Registered Interior Designers Act. Reference the July 1, 2010 Oklahoma State Architectural and Interior Designers Act (OS 59-46 .1, Paragraph 46 .21b) which requires final construction documents to be signed/seal by a Registered Architect.

3.3 Design Publications incorporated by reference to the Standard

Project designers shall prepare design and construction documents in accordance with (IAW) the most current editions of the following publications as they apply to the project: Refer to the mandatory and advisory requirements incorporated-by-reference to the standard as listed below.

3.3.1 Code of Federal Regulations (CFR)

3.3.2 AF Military Handbook Series (MILHDBK)

3.3.3 AF Instruction Series (AFI)

3.3.4 AF Regulation Series (AFR)

3.3.5 AF Manual Series (AFM, AFMAN)

3.3.6 Handbook Series (AFH)

3.3.7 AF Pamphlet Series (AFP, AFPAM)

3.3.8 AF Engineering Technical Letter Series (ETL)

3.3.9 AF Engineering Guidance Letter Series (EGL)

3.3.10 AF Construction Technical Letter Series (CTL)

3.3.11 Department of Defense Design Guide Series (DOD)

3.3.12 Unified Facilities Guide Specifications (UFGS)

3.3.13 USACE Engineering Manual Series (EM)

3.3.14 Unified Facilities Criteria Series (UFC)

3.3.15 Airfield Striping, ETL 04-2 Standard Airfield Marking Schemes

3.3.16 Airfield and Heliport Planning and Design, UFC 3-260-1

3.3.17 UFC 3-530-01 Interior and Exterior Lighting Systems and Controls

Most of the publications can be found at the following links:

http://www.wbdg.org http://www.e-publishing.af.mil/

3.4 Model Building Codes and Construction Regulations

The most current edition of the International Code Council publications is hereby incorporated by reference to the Standard:

3.4.1 International Building Code

3.4.2 Uniform Plumbing Code; (Backflow Prevention)

3.4.3 International Plumbing Code

3.4.4 International Mechanical Code

3.4.5 International Fuel Gas Code

3.4.6 International Maintenance Code

3.5 Occupational Safety and Health Act / OSHA Regulations

OSHA Safety and Health Standards, as published in the CFR, USACE EM 385-1-1 Safety and Health Requirements Manual, and the Air Force Policy on Ozone Depleting Chemicals (ODC) regulate all construction practices, systems operation, and maintenance on base.

3.6 National Fire Protection Association

All current National Fire Code, including NFPA 101 Life Safety Code, as published by the National Fire

Protection Association (NFPA), apply to base projects.

3.7 Americans with Disabilities Act

The Architectural Barriers Act (ABA) and the Uniform Federal Accessibility Standards (UFAS) is mandatory on all projects.

3.8 Sources of Technical and Procedural Requirements

The United States Government has many agencies of technical support. The following list directs the project designers and engineers to access design and construction publications which may be incorporated-by-reference to the standard.

http://www.wbdg.org/ http://www.e-publishing.af.mil/

Acronym Federal Internet Abbreviation Agency Address

USAF United States Air Force http://www.e-publishing.af.mil/

DOD United States Department of Defense http://www.dtic.mil/whs/directives/index.html

USACE United States Army Corps of Engineers http://www.usace.army.mil

AFCEC Air Force Civil Engineer Center http://www.afcec.af.mil

USGPO United States Government Printing Office http://www.access.gpo.gov

NAVFAC US Naval Facilities Engineering Command http://www.navfac.navy.mil

Whole Building Design Guide http://www.wbdg.org/

3.9 Responsibilities of the Contractor:

The contractor shall be responsible for accessing or obtaining all required publications referenced above that are recommended, mandatory, or applicable to the project’s design and engineering.

3.10 Variance from the Standard:

During the design and construction phases of TAFB projects, the contractor shall each be responsible, during their respective phases, to notify the project’s Contracting Office (CO) immediately of all project deficiencies relative to compliance with the TAFB Facility Standard and all other publications incorporated by reference hereto. The CO shall review the impact of all deficiencies to the original project scope and determine if a change in scope is warranted. Should a change in requirements be desirable on the part of the Government due to project limitations, written permission from the Office of the BCE is required.

3.11 Product Reference Disclaimer:

The use of a manufacture’s registered product name and model number within this Base Facility Standard, is to establish a standard of acceptable quality and is not an endorsement for use.

4. Cost Estimating

4.1. General:

All cost estimates submitted in support of design and/or construction contracts for TAFB shall be based on costs of materials, equipment, and labor rates appropriate to the Oklahoma City area and shall be in full compliance with the current rule of the Federal Acquisition Regulations. All cost estimates shall be developed IAW UFC-3-740.

4.2. Change Order Documentation

All estimates for change orders and the 8A Small Business Set Aside Program shall be prepared on AF Form 3052, and shall include labor hours, material, and bonding costs. The cost estimates for change orders and the 8A Program shall be presented in considerable detail.

5. Design Documentation Formats

5.1. CE Recordkeeping

Drawings, specifications, renderings, and graphics which are provided in fulfillment of design and construction contracts shall meet the following requirements:

5.1.1. GIS (Geographical information systems) information files shall be included for full design contracts which substantially change a facility footprint or install/replace substantial portions of utilities.

http://www.e-publishing.af.mil/ http://www.dtic.mil/whs/directives/index.html http://www.usace.army.mil/ http://www.afcec.af.mil/ http://www.access.gpo.gov/ http://www.navfac.navy.mil/ http://www.wbdg.org/

GIS Systems files shall include either data tags or geo-spatial databases.

5.1.2. Data dictionary(s) shall follow the current version of the Tri-Services GIS Standard. Preferred Datum is North American Datum 1983, Grid Oklahoma North #3501. Units shall be measured in International Feet. If other data is used, the contractor shall furnish a “read-me” file indicating datum. Grid and working units. Utilities information shall include, at a minimum, the installation date, pipe sizes and pipe materials.

5.2. Dual Records

The Contractor shall furnish digital design files and image files of final drawings along with the hard copy final design plans.

When the contractor requirement calls for as-constructed drawings, all hard copies, design sheet files and image files shall so state “AS-BUILT” and date(s) of revision.

Additionally, an electronic listing of drawings which detail Sheet Number, Sheet Sequence Number, Sheet Title, CADD file name, and Image File Name shall be provided in both hardcopy and electronic copy.

5.3. Delivery Media

Complete copies of all CADD data and files developed shall be delivered to the Government on electronic digital media at both construction-issue and as-built phases of the project. For projects with electronic digital files the electronic digital data and files shall be provided on either Read/Write optical disk (CDRW), or compact disc read-only memory (CD-ROM). CDRW and CD-ROM are the preferred media. The electronic digital media shall be in a format which can be read and processed by the Government’s target CADD system. See CADD file formats below.

5.3.1 The external label for each electronic digital media shall contain, at a minimum, the following information:

5.3.1.1 AF Project Number, Contract Number, Delivery Order Number (if applicable), and date of submission:

5.3.1.2 Type of submission (i.e. preliminary design, final design, or as-built);

5.3.1.3 Format and version of operating system software; i.e. WIN XP.

5.3.1.4 Name and version of utility software used for preparation (e.g.

compression/decompression) and copying files to the media; i.e. WIN ZIP.

5.3.1.5 Sequence number of the digital media;

5.3.1.6 Schedule of filenames (to be contained in a “text“ file on CD).

5.4. CADD File Formats

Before a CADD file is placed on electronic digital media to be submitted to 72 ABW/CE, the following procedures shall be performed;

5.4.1. Remove all extraneous graphics outside the border area and set the active parameters to a standard setting or to those in the government-furnished seed file.

5.4.2. Make sure all reference files are attached without device or directory specifications.

5.4.3. Where compression is required, compress and reduce all design files using “PKZip” or other compatible file compression/decompression software approved by the Contracting Officer. If the file compression/decompression software is different from that specified above, then electronic digital media copy of the file compression/decompression software shall be purchased for 72 ABW/CE by the submitting consultant/contractor and provided with the submitted media.

5.4.4. Include all files, both graphic and non-graphic, required for the project (i.e. color tables, pen tables, font libraries, line style files, cell libraries, user command files, plot files, etc.).

5.4.5. Make sure that all support files such as those listed above are in the same directory and that reference to those files does not include device or directory specifications.

5.4.6. Include all standard sheets (i.e., abbreviation sheets, standard symbol sheets, etc.) that are necessary to completely describe the project.

5.5. Documentation.

Document any fonts, tables, etc. developed by the A-E or not provided among the Government-furnished materials. The contractor shall obtain Government approval before using anything other than the Government’s standard fonts, line-types, tables or cells/blocks.

5.6. Image Files.

Each finished drawing (sheet) shall have its own separate image file. The image file for each finished drawing (sheet) shall have its own separate image file. The image file for each finished drawing shall be provided to the Government in Portable Document File (PDF).

5.7. CADD File Formats

Due to the fact many file formats are proprietary and not completely interchangeable; flexibility is required for file formats used. The following CAD file types may be furnished with the idea that context of information is maintained. The electronic format of all shall be in Autodesk AutoCAD 2004 or later.

5.7.1. AUTOCAD (DWG): Files in AutoCAD format shall NOT include XREFs or shape files as separate files, but rather be included in the drawing furnished. Specific font files (shx) used by any add-on software shall be included with the text file mentioning their inclusion.

5.8. CADD Standards

When submitting drawings, designers shall follow the Tri-Services A/E/C CADD Standards (Release 3.0 or later) as published in the National CADD Standard. Also, the standards can be found at the web site https://cadbim.usace.army.mil. The Tri-Services standard is an implementation of the National CADD Standard and thus, the National CADD Standard is also satisfactory. File structure, nomenclature, and assignment of layers, levels, and/or entities shall conform to those of the requesting organization. This information is to be provided by the Technical Representative of the Contracting Officer/TRCO.

5.8.1. Text index must be included on the media of the drawings as well as a description of the method of composition (attachment information).

5.8.2. Standard borders and cover sheets are provided to firms upon request. Border sheets are available in ANSI Standard A through D. D size borders are the preferred siz

5.9. Specifications Formatting

Project designers shall submit all technical specifications to the 72 ABW/CE for review and compliance with project requirements. All specifications shall be formatted for desktop publishing in MS Word for Windows electronic format using the US Army Corps of Engineers Guide Specifications (CEGS) or SPECSINTACT.

5.10. Base General Requirements TAFB

Standard Specifications Section 00 70 00 (General Requirements) and Section 00 72 00 (Environmental Requirements) shall be incorporated without amendment to all minor Construction and all Repair Projects’ construction specifications. Military Construction Projects shall also incorporate Sections 00 70 00 and 00 72 00 with amendments as approved by 72 ABW/CE.

5.11. Additional Geographic Information Systems Data

For contract deliverables that also require/include Geographical information System (GIS) data and printed materials as part of the product, the Tri-Services Spatial Data Standards for Facilities, Infrastructure and Environment SDSFIE (release 2.0 or later) shall be the minimum standard to which the delivered product must comply.

5.11.1. GIS products must include a hardcopy and an electric copy using the following format: ESRI ArcGIS (release 9.1 or later), ESRI Arc View (release 9.1 or later).

5.11.2. Any file structure and naming convention that falls outside the current SDSFIE specifications must be in accordance with, and be defined by, the requesting organization. This information should be provided by the Technical Representative of the Contracting Officer/TRCO.

Geographic Datum, Projection System, and Working Units should also be provided by the

TRCO.

5.11.3. If not otherwise indicated in the contract, any database material should be done in MS https://cadbim.usace.army.mil./

Access 2003 or later version. All products should be done in accordance with the current Operating System of Tinker AFB, i.e. MS Windows XP.

Part 2: Base Infrastructure

Satellite Image of Tinker Air Force Base

6. Utility Systems and Infrastructure on TAFB

6.1. Water Supply

The Tinker AFB domestic water distribution system is supplied by both groundwater wells and by connections to the Oklahoma City municipal system.

6.1.1. For most situations on TAFB, new fire hydrants and automatic fire protection sprinkler systems shall be served by the base domestic water distribution system.

6.1.2. Three important exceptions to the above requirement are in the provision of fire protection systems to Base hangar facilities which serve aircraft maintenance, paint-stripping, and painting. For facilities which serve these missions, those fire sprinkler systems which use water shall be served by separately piped/pumped, high pressure non-potable water systems.

6.1.3. Well water is chlorinated at the pump or at the end of collection lines. Chemical analysis of the water may be obtained from the Base Environmental Management office upon request.

6.1.4. Corrosion control for all new water supply lines shall be provided as part of a project’s scope.

6.1.5. Water usage shall be metered in accordance with 3-400-01 ENERGY CONSERVATION Section

2-5 METERS.

6.1.6. New meters and replacement of existing analog meters shall as a minimum be provided with pulse counter which can communicate with AMRS system at Tinker. Daily data is required for a minimum of 90 days. Contractor shall consult with and comply with the requirements of the TAFB Meter Management Group before installation of meter(s).

6.1.7. All Base equipment connections shall be designed and constructed to eliminate cross-connection and/or backflow hazards. Such connections include Heating Ventilating and Air Conditioning (HVAC) systems and automatic fire sprinkler systems. Construct backflow prevention components respective of the degree of hazard. Follow the Uniform Plumbing Code/UPC and AFI 32-1066 Backflow Prevention Program for design, installation, and maintenance requirements. (**Should obtain a copy for reference)

6.1.8. All landscape irrigation systems design and construction served by potable water systems shall include back flow prevention to protect the potable water supply.

6.1.9. All buildings or facilities equipped with a Siamese fire department water connection shall incorporate a reduced pressure principle back flow prevention to protect the potable water supply.

Project specifications shall call for "approved" back flow prevention devices as required by AFI 32-1066 and the UPC

6.2. Wastewater Treatment

Industrial wastewater is piped to one of the two treatment facilities located in Districts 2 and 5.

Industrial wastewater is then treated by filtration and clarification processing. For projects which are large producers of industrial wastewater, the designer shall verify that the capacities of both the collection system and the treatment plant are adequate to respectively transport and treat the discharge. All base sanitary sewer wastewater is channeled to the Oklahoma City municipal system for treatment. .

6.2.1. Design contribution to existing sanitary sewer system shall be estimated at 30 gallons per capita per day.

6.2.2. Wastewater collection systems shall be designed in accordance with the Water Environment Federation and American Society of Civil Engineers Manual of Practice MOP FD-5/ASCE MOP 60 Gravity Sanitary Sewer Design and Construction.

6.2.3. Design requirements for drinking fountains, water closets, lavatories, showers, and laundry washers shall be based on building occupancy.

6.3. Piping, Utilities, and Manholes

No physical connections shall exist between sewer and water supply systems. Minimum construction precautions and separation distances to ensure against utility cross-contamination between water and sewer utility lines shall be maintained as identified below. Where these minimum practices cannot be provided, the 72 ABW / CE may prescribe additional construction measures to provide an equivalent measure of utility integrity and maintainability.

6.3.1. Sewer and water lines shall be located at least 10 feet apart horizontally. In utility projects where the bottom of the water pipe is at least 12 inches above the top of the sewer, the horizontal spacing may be a minimum of 6 feet.

6.3.2. Where conditions require a sewer to cross above a water line, the sewer shall be constructed of cast iron, steel or other pressure pipe for a distance of 10 feet in both directions from the crossing.

Within these distances there shall be no occurrence of sewer pipe joints.

6.3.3. The earth cover for sanitary sewers shall be at least 30 inches deep to protect the pipe from superimposed live loads of ordinary traffic.

6.4. Sanitary Water Supply

All Base equipment connections shall be designed and constructed to eliminate cross-connection and/or backflow hazards. Such connections include Heating Ventilating and Air Conditioning (HVAC) systems and automatic fire sprinkler systems. Construct backflow prevention components respective of the degree of hazard. Follow the Uniform Plumbing Code/UPC and AFI 32-1066 Backflow Prevention Program for design, installation, and maintenance requirements. (**Should obtain a copy for reference)

6.4.1. All landscape irrigation systems design and construction shall include served by potable water systems shall include back flow prevention to protect the potable water supply.

6.4.2. All buildings or facilities equipped with a Siamese fire department water connection shall incorporate a reduced pressure principle back flow prevention to protect the potable water supply.

6.4.3. Project specifications shall call for "approved" back flow prevention devices as required by AFI 32- 1066 and the UPC.

6.5. Sanitary Sewer Collection Systems

6.5.1. To ensure maintainability, the minimum size pipe allowed for base facilities shall be six inches diameter for housing connections and eight inches for all other facility connections.

6.5.2. Adequate manholes and clean-outs shall be provided for all collection piping for maintainability.

Sanitary sewer manholes shall be provided at all changes in direction and at maximum intervals of 500 feet.

6.5.3. All sanitary collection systems shall be designed for gravity collection. Pressurized force main and lift station design for base sanitary sewers are prohibitive without the consent in writing of the 72ABW/CE. Where lift stations are permitted their construction shall feature dual ejectors pumps fitted with controls for alternate cycling of lead pump function. Manual override of automatic cycling control shall be included.

6.5.4. Lift stations shall be designed to preclude bypass/overflow. Provide adequate sump storage for short power outages. Provide an electrical outlet and transfer switch to permit connection of an emergency power generator on large lift stations or where overflow/bypass can create a health hazard or pollution problem.

6.5.5. Crossing potable water lines and sewage lines shall be installed in accordance with Water Environment Federation publication Gravity Sanitary Sewer Design and Construction.

6.6. Industrial Wastes

6.6.1. All facilities generating wastewater (other than sanitary sewage waste) shall be connected to the industrial waste sewer system (IW). All new industrial wastewater connections which connect to a dual-wall IW collection main or to an existing lift station shall be dual-wall polypropylene pipe with a leak detection system compatible with the existing system. Wastes shall be identified, both in characteristics and quantities, in project design analysis, and compared to the capabilities of the receiving treatment plant.

6.6.2. Materials for industrial waste drains, sewers, tanks, pumps, and other features shall be carefully selected for suitability based on worst case expected waste characteristics. Once selected, these materials shall be clearly and thoroughly specified in project specifications. Material substitutions shall be avoided to the greatest extent possible.

6.6.3. Where necessary, pretreatment at the source should be provided. This may include physical, chemical, or a combination pretreatment. Flammables and troublesome solids shall be removed at the source.

6.6.4. For projects which are large producers of industrial wastewater, the designer shall verify that the capacities of both the collection system and the treatment plant are adequate to respectively transport and treat the discharge.

6.7. Oil Separators

Many small, proprietary oil/grease separators on the market do not provide adequate detention times nor have sufficient volumetric capacities to function properly. These devises shall not be used for base construction.

6.7.1. All oil separators shall have a submerged tee (or other submerged feature) as an outlet. This feature allows the separator function as a two-stage separator, thereby preventing discharge of oils which pass to the outlet chamber. A tee may not be required if the two-stage-effect is provided by other means.

6.8. Storm Drainage System

All new facilities shall be designed so that the finished floor elevation (FFE) is above the 100-year flood elevation. Rainfall intensity shall be based on local intensity-duration-frequency data. The designer shall analyze the project’s effects of increased watershed runoff before tying into an existing system at any particular location. If post-project runoff is projected to be greater than previously recorded, then post construction storm water controls shall be constructed to prevent increase of flood potential downstream.

6.9. Natural Gas Delivery Systems

All natural gas systems shall be installed in accordance with Unified Facility Criteria, International Fuel Gas Code, and American Gas Association standard.

6.9.1. All underground natural gas pipes buried at a minimum of 60” cover.

6.9.2. Preferred material for underground gas pipe are steel pipe or highly congested areas or High Density Polyethylene Pipe.

6.9.3. All underground natural gas pipes shall be provided with trace wire.

6.9.4. All underground pipes shall be provided with location tape at least 12” above pipe.

6.9.5. All natural gas lines that pass under roadways shall be sleeved. All sleeves shall be installed and vented in accordance with ODOT (Oklahoma Department of Transportation) requirements.

6.9.6. Natural gas usage shall be metered in accordance with 3-400-01 ENERGY CONSERVATION Section 2-5 METERS.

6.9.7. New meters and replacement of existing analog meters shall as a minimum be provided with pulse counter which can communicate with AMRS system at Tinker. Daily data is required for a minimum of 90 days. Contractor shall consult with and comply with the requirements of the TAFB Meter Management Group before installation of meter(s).

6.10. Liquid Fuel Supply Systems

6.10.1. Pipelines and Hydrant Systems: All designs shall ensure that maintenance personnel shall be able to physically perform routine tasks with tools and equipment readily available on base. Items of consideration include:

6.10.1.1 Ensuring that parallel or crossing pipelines are at least one foot apart to permit repair and/or equipment use in-between the pipes. Large diameter pipes require greater separation.

6.10.1.2 Providing hydrant outlet pits or equipment pits large enough for tool use in the pit while replacing or maintaining valves, flanges, pumps, nuts and bolts, and flange gasket replacement.

6.10.1.3 Assuring that sufficient flanges are installed to permit ease of pipe and equipment repair or replacement. For example, because pipe cutting or welding is not permitted in a pump house, flanges are required.

6.10.1.4 Providing sectionalizing valves in piping systems to shut down piping sections for repair, maintenance, and pressure testing.

6.10.2. Fuel Storage Tanks and Welding:

6.10.2.1 Dikes or basins around storage tanks shall be designed so that tank cleaning, maintenance, and repair equipment can be easily transported into the diked area. This includes providing clear access to the tank manholes without climbing over or under pipelines. Provide cathodic protection (CP) inserts in the concrete basin of the dike for CP testing.

6.10.2.2 Clearance shall be provided between parallel buried tank structures and between other structures to allow individual tank excavation and removal. Separation of adjacent tank installations shall accommodate the use of mechanized equipment in tank excavation, maintenance, removal, and replacement. Also, cathodic protection systems for a given tank structure shall be shielded from adjacent tanks where sufficient clearance is not provided.

6.10.2.3 All welding shall be performed by a welder certified in accordance with ANSI B31.1 or API 1104 codes. Welds shall be made and inspected on accordance with ANSI B31.8 requirements

7. Exterior Signage

A consistent system of signage not only encourages smooth navigation of the base and is an important tool in establishing unifying visual images for the precinct of the specific facility, for its larger planning district, and for the base overall.

7.1. Standard Facility signs

7.1.1 All exterior signage shall be developed and designed in accordance with the Unified Facilities Criteria UFC 3-120-01 Air Force Sign Standard. This document is accessible via the following hyperlink: http://www.wbdg.org/ccb/DOD/UFC/ufc_3_120_01.pdf

7.1.2 Design sign panel thickness and support columns as required to resist all imposed wind forces.

Reflective sheathing shall conform to the requirements of Federal Specification LS300C, Type I, Table III, Reflectivity II and the Manual of Uniform Traffic Control Devices (MUTCD).

7.1.3 All exterior signs, except traffic control, shall be Spectrum Paint Cleveland Brown MP#80YR09/163 with reflective white letters. The building number sign shall be Type B4 sign as stated in UFC 3-120-01

7.1.4 Exception: In the Navy Area Machine Blue shall be used for all sign fields. Reflective numbers and letters shall meet Federal Specification LS300C, Type I, Table III, Reflectively II and be Helvetica medium style.

7.1.5 All painted frames shall match as closely as possible 3M Company, Scotchlite, #3680-29, Russet Brown.

7.1.6 Exception: In the Navy Area sign frames shall be painted Machine Blue to match sign fields.

7.1.7 Existing exterior signage that does not comply with base standards shall be replaced as needed, due to wear.

7.1.8 The AFMC logo and shield shall be used to establish corporate identity; however, use shall be limited to gate signs, selected towers, billeting, base operations and headquarters buildings.

Placement of the logo and shield on exterior signage shall be is accordance with AFPAM 32- 1099.

http://www.wbdg.org/ccb/DOD/UFC/ufc_3_120_01.pdf

7.2. Zip + 4 Program Implementation

7.2.1 The Zip + 4 program is a DOD directive mandating that bases such as Tinker shall develop street addresses for all base Facilities in addition to the long -time standard facility numbers. Questions about the program shall be directed to the Base Comprehensive Planner.

Office of the Base Planner

72 ABW/CEAO

7535 5th Street, Building

400 TINKER AFB OK

73145-9010 (405) 734-

7.3. Logos and Super Graphics

Painted logos, super graphics, and racing stripes are prohibited Base wide. All exterior signage proposals shall be submitted to the Base Architectural Compatibility Board and be subject to its review and approval.

7.4. Highway Standards and Traffic Control

The Air Force Sign Standard recognizes the importance of signage consistency between base rights of way and those in the community to which they connect.

7.4.1. Highway Standards are defined as that group of signs which regulate base traffic.

7.4.2. For design and construction of these types of signs refer to the Federal Highway Administration’s Standard Highway Signs and Manual of Uniform Traffic Control Devices. These publications can be accessed at the following hyperlinks:

http://mutcd.fhwa.dot.gov/ (Manual of Uniform Traffic Control Devices) http://mutcd.fhwa.dot.gov/ser-shs_millennium.htm (Standard Highway Signs)

7.5. Identification of Hazardous Storage

7.5.1 See Chapter 10 Life Safety, Paragraph 10.4.1 for the special signage requirements of hazardous materials storage occupancies.

8. Traffic Engineering

8.1. Traffic Considerations

The vehicle circulation system at TAFB provides primary means of movement of both people and materials throughout the Base. The infrastructure of roads, pedestrian systems, and open spaces links the individual structures on Base into a complete and functioning military installation.

8.1.1. Pedestrian and vehicle occupant safety are the first priorities in all roadway, parking lot, and sidewalk projects.

8.1.2. All sidewalks interrupted by vehicle rights-of-way shall feature barrier-free pedestrian crosswalk design and pavement marking and signage as recommended by the MUTCD.

8.1.3. Projects which include parking lot pavements shall also include traffic control signage, stall striping, crosswalk marking, and directional lane markers as part of the project scope of work.

8.1.4. Circulation and parking facilities shall conform to UFC 3-210-02.

8.2. Signage

All facility signs shall comply with UFC 3-120-01 Air Force Sign Standard.

All traffic signage shall comply with those standards set forth in the Manual of Uniform Traffic Control Devices (MUTCD) as published by the U.S. Department of Transportation and the Federal Highway http://mutcd.fhwa.dot.gov/ http://mutcd.fhwa.dot.gov/ser-shs_millennium.htm http://mutcd.fhwa.dot.gov/ser-shs_millennium.htm

Administration.

8.3. Parking

The Office of 72 ABW/CE is the authority for assigning reserved parking spaces. Parking requirements for new facilities shall be in accordance with AFI 3-218, Tinker Supplement.

8.3.1. A standard parking space is 9 feet wide by 18 feet long.

8.3.2. A standard motorcycle parking space is 4.5 feet wide by 12 feet long.

8.3.3. Parking accommodations for all Base facilities shall include an appropriate number of spaces designed and constructed in compliance with the Architectural Barriers Act (ABA)…