JA-5_Site_Map_and_Drawings.pdf

PDF 6 MB Posted

Attached to
Lightning and Surge Protection Federal contract opportunity
Solicitation number
FA5004-17-B-C001
Issued by
Department of the Air Force Pacific Air Forces

About this file

JA-5 Site Map and Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Lightning and Surge Protection, newest first.
File Type Posted
Questions_and_Answers__2.pdf PDF
Questions_and_Answers.pdf PDF
Bldg_1227_photos.pdf PDF
Bldg_1228_photos.pdf PDF
Bldg_1338_photos.pdf PDF
Site_Visit_Sign_In.pdf PDF
Bldg_1338_Extension_photos.pdf PDF
Bldg_4371_photos.pdf PDF
FA5004-17-B-C001-0002.pdf PDF
JA-5_Site_Map_and_Drawings.pdf PDF
JA-2_Specifications.pdf PDF
JA-6_Asbestos_Surveys.pdf PDF
JA-1_Other_Contract_Requirements.pdf PDF
JA-3_Wage_Determination.pdf PDF
FA5004-17-B-C001-0001.pdf PDF
JA-4_AF_Form_66.pdf PDF
JA-5_Site_Map_and_Drawings.pdf PDF
JA-2_Specifications.pdf PDF
JA-4_AF_Form_66.pdf PDF
JA-1_Other_Contract_Requirements.pdf PDF
FA5004-17-B-C001.pdf PDF
JA-6_Asbestos_Surveys.pdf PDF
JA-3_Wage_Determination.pdf PDF
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

NORTH ARROWS

ROOM NUMBER

SCALE

TITLE

SHEET LOCATION

DETAIL NUMBER

A

E110

SHEET LOCATION

SECTION NUMBER

DETAIL NUMBER

OFFICE

SHEET LOCATION

A

E110

G001 GENERAL INFORMATION

GOVERNING CODES:

2012 INTERNATIONAL BUILDING CODE - IBC

2012 INTERNATIONAL FIRE CODE - IFC

2014 NFPA 70 - NATIONAL ELECTRICAL CODE - NEC

2013 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE

2015 NFPA 101 LIFE SAFETY CODE

2014 NFPA 780 - STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS

UFC 3-575-01 - LIGHTNING AND STATIC ELECTRICITY PROTECTION SYSTEMS

UFC 3-550-01 - EXTERIOR ELECTRICAL POWER DISTRIBUTION

AUTHORITY HAVING JURISDICTION

EAFB FIRE DEPARTMENT

E001 LEGEND AND OVERVIEW

E110 BUILDING 1227 ELECTRICAL PLANS AND DETAILS

E120 BUILDING 1228 ELECTRICAL PLANS AND DETAILS

E130 BUILDING 1300 ELECTRICAL PLANS AND DETAILS

E140 BUILDING 1324 LIGHTNING PROTECTION PLAN

E150 BUILDING 1326 LIGHTNING PROTECTION PLAN

E160 BUILDING 1335 ELECTRICAL PLAN

E170 BUILDING 1338 ELECTRICAL PLAN

E180 BUILDING 4371 LIGHTNING PROTECTION PLAN

E200 DETAILS

E201 DETAILS

BLDG 1227 & 1228

BLDG

BLDG 1300

BLDG 1324 & 1326

BLDG 1335

& 1338

A

E110

DRAWING TITLE

SCALE

Robert S. Gras

No. EE7352

13-Jan-2017

FA5004-17-B-C001 EIELSON AFB, AK JA-5 SITE MAPS AND DRAWINGS

B

C

D

1/ 2" X 24" GENTLY TAPERED SOLID COPPER AIR

TERMINAL WITH BRONZE SWIVEL AIR TERMINAL

BASE SET IN ADHESIVE

LEGEND

5/8" X 24" GENTLY TAPERED SOLID ALUMINUM AIR

TERMINAL WITH ALUMINUM UNIVERSAL BASE

MOUNTED HORIZONTALLY SET IN ADHESIVE

1/2" X 12" GENTLY TAPERED SOLID ALUMINUM AIR

TERMINAL WITH ALUMINUM UNIVERSAL BASE

MOUNTED HORIZONTALLY SET IN ADHESIVE

MOUNTED ON TOP OF HIGHEST LIGHT FIXTURE

5/8" X 24" GENTLY TAPERED SOLID ALUMINUM AIR

TERMINAL WITH ALUMINUM PIPE RAILING BASE

3/4" X 10'-0" COPPER CLAD GROUND ROD WITH

U-BOLT GROUND ROD CLAMP

G

CLASS 1 COPPER LIGHTNING CONDUCTOR (29

STRANDS OF 16 AWG WIRE) SECURE TO

BUILDING EVERY THREE FEET MAXIMUM.

T THRU ROOF CONNECTOR ASSEMBLY WITH

CLASS 1 DOWN CONDUCTOR

THRU WALL CONNECTOR ASSEMBLY WITH CLASS

1 DOWN CONDUCTOR

TYPICAL BODIES OF CONDUCTANCE AS NOTED BELOW. USE FULL SIZE

CONDUCTOR AND APPROPRIATE FITTING SHOWN FOR CONNECTION.

(PLUMBING STACK) REQUIRES BONDING WITH MAIN SIZE CABLE ONLY

IF WITHIN 6'-0" OF LIGHTNING PROTECTION SYSTEM.

TYPICAL BODIES OF INDUCTANCE AS NOTED BELOW. USE

SECONDARY SIZE (SMALLER) CONDUCTOR AND APPROPRIATE FITTING

SHOWN FOR CONNECTION.

BONDING CONNECTIONS AND FITTINGS SHOWN ARE TYPICAL

EXAMPLES. MAKE ALL CONNECTIONS REQUIRED TO MEET CODES AS

NOTED. ADJUST FITTING TYPE AS REQUIRED TO SUIT FIELD

CONDITIONS.

D

C

C

A

C

B

GENERAL INSTALLATION NOTES

LOCATE AIR TERMINALS AS SHOWN. TAKE CARE TO INSURE THAT ALL

POINTS ARE WITHIN 2'-0" OF OUTSIDE BUILDING EDGE, OUTSIDE CORNERS,

RIDGE ENDS, AND THAT MAX SPACING DOES NOT EXCEED 20'-0", AND

THAT MIN PROJECTION ABOVE OBJECT PROTECTED IS 10"; POINTS

PROJECTING 24" MAY BE SPACED @ 25'-0" MAX

MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN CONDUCTOR.

INSURE THAT ALL BENDS HAVE AT LEAST AN 8" RADIUS AND DO NOT

EXCEED 90 DEGREES.

ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING CABLES AT 3'-0"

ON CENTER MAX. VERIFY COMPATIBILITY OF ADHESIVE ON MEMBRANE

ROOF APPLICATION PRIOR TO INSTALLATION.

GROUND ELECTRODES SHALL BE INSTALLED AS SHOWN, BUT IN NO

INSTANCE SHALL THEY BE LESS THAN 1'-0" BELOW GRADE AND 2'-0" FROM

FOUNDATION WALL. DRIVEN RODS SHALL PENETRATE THE EARTH AT

LEAST 10'-0".

BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS SHOWN AND

AS REQUIRED BY CODE.

MAIN SIZE LIGHTNING CONDUCTOR BONDED TO MAIN GROUND

BUS FIELD VERIFY LOCATION 1 1/4" CONDUIT FOR ACCESS, INSTALLED BY

OTHERS. INTERCONNECT LIGHTNING PROTECTION GROUND TO

TELEPHONE AND OTHER BUILDING GROUND SYSTEMS LOCATION FIELD

DETERMINED OR AS REQUIRED BY CODE.

LB'S AND SIMILAR CONDUIT BODIES MAY NOT BE USED IN THE

INSTALLATION OF DOWNLEAD CONDUITS, AS THEY DO NOT ADHERE TO

THE REQUIRED 8" MINIMUM BEND RADIUS.

SYSTEM SHALL BE INSTALLED AS SHOWN TO INSURE PROPER CODE

COMPLIANCE AND SYSTEM CERTIFICATION. ANY MAJOR VARIANCE SHALL

BE RESUBMITTED FOR APPROVAL.

ALL MATERIALS TO BE UNDERWRITER'S LABORATORIES APPROVED WITH

"A" LABELS ON CONDUCTORS @ 10'-0" INTERVALS AND "B" LABELS ON ALL

AIR TERMINALS.

FINAL SYSTEM INSPECTION AND QUALITY CONTROL

A. THE CONTRACTOR SHALL FURNISH AN LPI-IP CERTIFICATE OR A UL

CERTIFICATE UPON COMPLETION OF THE INSTALLATION.

B. LPI CERTIFICATION IF REQUIRED, REQUIRES SIGNATURE BY A

REPRESENTATIVE OF THE OWNER AT MULTIPLE STAGES OF

INSTALLATION & BY THEIR THIRD PARTY FIELD STAFF. UL

CERTIFICATION IF REQUIRED, REQUIRES INSPECTION BY THEIR

THIRD-PARTY FIELD STAFF AFTER COMPLETION OF THE

INSTALLATION.

C. AS-BUILT DRAWINGS SHALL BE COMPLETED AND STAMPED BY AN LPI

CERTIFIED MASTER DESIGNER - INSTALLER OF LIGHTNING

PROTECTION SYSTEMS.

D. FINAL INSPECTION REPORT - A FINAL INSPECTION AND INSPECTION

REPORT SHALL BE COMPLETED BASED ON ANSI/TIA/EIA 607, NEC,

NFPA 780, AND UL96A INDUSTRY STANDARDS AS APPLICABLE. THE

SCOPE OF THE INSPECTION AND REPORT SHALL INCLUDE;

a. TEST AND EVALUATION THE GROUNDING SYSTEM. RECORD

FINAL SYSTEMS TO GROUND RESISTANCE LEVEL.

b. EVALUATION AND TESTING OF THE INTERNAL

BONDING AND GROUNDING SYSTEMS.

c. EVALUATION AND TESTING OF EQUIPMENT

GROUNDING.

d. EVALUATION OF AC SURGE SUPPRESSION INSTALLATION.

e. EVALUATION OF TELCO SURGE SUPPRESSION INSTALLATION.

f. COPY OF THE LPI-IP OR UL LIGHTNING PROTECTION

CERTIFICATION.

g. FINAL AS-BUILT REVIEW AND SUBMISSION.

E. REPORT SHALL INCLUDE DETAILED REPORTING AND TEST RESULTS

WITH CORRESPONDING PHOTOS OF EACH EVALUATION CATEGORY.

SYSTEM DESIGNED UTILIZING UL LISTED T&B/FURSE MATERIALS.

MECHANICAL CONNECTION

EXISTING AIR TERMINAL

EXISTING LIGHTNING PROTECTION CONDUCTOR

CLASS 2 COPPER LIGHTNING CONDUCTOR

A

AA

A

A

A

A

A

B

C

C

E001

GENERAL BONDING NOTES

NOT TO SCALE

E 12"X 12" GENTLY TAPERED SOLID ALUMINUM AIR

TERMINAL MOUNTED VERTICALLY ALONG WOOD

POLE USING CAST BRONZE CROSS-RUN CLAMP

F 12" X 12" GENTLY TAPERED SOLID ALUMINUM AIR

TERMINAL WITH ALUMINUM UNIVERSAL BASE

MOUNTED ON TOP OF LIGHT POLE

EX

GENERAL BONDING NOTES

AERIAL ANTENNA - ROOF MOUNTED

TEST WELL

Robert S. Gras

No. EE7352

1 2 3 4 5 6 7 8 9

E

4 5 6

A

E110

BUILDING 1227 ELECTRICAL PLAN

SCALE: 1/32" = 1'-0"

EXISTING 200 AMP, 480Y/277 VOLT, 4 POLE AUTO TRANSFER SWITCH

WITH CONNECTION TO EXISTING MCCE FROM 200/3 BREAKERS IN THE

MDP'S OF BOTH BUILDING 1227 AND 1228. PROVIDE NEW TYPE 2 SURGE

PROTECTIVE DEVICE (SPD) ADJACENT TO EXISTING TRANSFER SWITCH.

CONNECT TO NEW 50/3 ENCLOSED BREAKER MOUNTED ADJACENT TO

TRANSFER SWITCH AND CONNECT WITH 4 #6, (1) #10 GND, IN 1" C. MIN.

65,000 AIC.

EXISTING 500 KVA PAD

MOUNTED TRANSFORMER

G

EXISTING DATA/NETWORK

CABINET

EXISTING TELEPHONE SERVICE

PRIMARY PROTECTORS.

EXISTING FIRE ALARM SYSTEM

CONTROL PANEL & MONACO

RADIO TRANSMITTER

E110

BUILDING 1227 ELECTRICAL ROOM PLAN

SCALE: 1/8" = 1'-0"

EXISTING 500 KVA

PAD MOUNTED

TRANSFORMER

EXISTING 800 AMP, 480Y/277 VOLT MAIN

DISTRIBUTION PANEL "MDP". PROVIDE NEW TYPE 1

SURGE PROTECTIVE DEVICE (SPD), ADJACENT TO

EXISTING MDP. CONNECT TO NEW 50/3 BREAKER IN

EXISTING MDP SPACE AND CONNECT WITH 4 #6, (1)

#10 GND, IN 1" C. MIN. 65,000 AIC.

EXISTING FIRE ALARM

CONTROL PANEL

EXISTING ELECTRICAL

ROOM. SEE DETAIL 2/E110EXISTING VAULT ROOM.

SEE DETAIL 2/E110

Robert S. Gras

No. EE7352 29-Mar-2017

1 2 3 4 5 6 7 8 9

E

4 5 6

E

E120

BUILDING 1228 ELECTRICAL PLAN

SCALE: 1/32" = 1'-0"

EXISTING FIRE SUPPRESSION

SYSTEM CONTROL PANEL &

MONACO RADIO TRANSMITTER

EXISTING 500 KVA PAD

MOUNTED TRANSFORMER

G

EXISTING 800 AMP, 480Y/277 VOLT MAIN

DISTRIBUTION PANEL "MDP". PROVIDE NEW TYPE 1

SURGE PROTECTIVE DEVICE (SPD) ADJACENT TO

EXISTING MDP. CONNECT TO NEW 50/3 BREAKER IN

EXISTING MDP SPACE AND CONNECT WITH 4 #6, (1)

#10 GND, IN 1" C. MIN. 65,000 AIC.

EXISTING 200 AMP, 480Y/277 VOLT, 4 POLE AUTO TRANSFER SWITCH

WITH CONNECTION TO EXISTING MCCE FROM 200 3 BREAKERS IN THE

MDP'S OF BOTH BUILDING 1227 AND 1228. PROVIDE NEW TYPE 2 SURGE

PROTECTIVE DEVICE (SPD) ADJACENT TO EXISTING TRANSFER SWITCH.

CONNECT TO NEW 50/3 ENCLOSED BREAKER MOUNTED ADJACENT TO

TRANSFER SWITCH AND CONNECT WITH 4 #6, (1) #10 GND, IN 1" C. MIN.

65,000 AIC.

EXISTING 500 KVA PAD

MOUNTED

TRANSFORMER

EXISTING TELEPHONE SERVICE

PRIMARY PROTECTORS.

EXISTING FIRE ALARM

CONTROL PANEL

EXISTING DATA/NETWORK

CABINET

EXISTING ELECTRICAL

ROOM. SEE DETAIL 2/E120

EXISTING VAULT ROOM.

SEE DETAIL 2/E120

E120

BUILDING 1228 ELECTRICAL ROOM PLAN

SCALE: 1/8" = 1'-0"

Robert S. Gras

No. EE7352

E130

BUILDING 1300 ROOF ELECTRICAL PLAN

SCALE: 1/16" = 1'-0"

ROOF MOUNTED AERIAL ANTENNA (TYPICAL OF 12

ANTENNAS). PROVIDE AN ANTENNA DISCHARGE UNIT

(RF SPD) AND CONNECT TO THE GROUNDING

ELECTRODE SYSTEM WITH A MIN. #6 CU. SYSTEM

BONDING OR GROUNDING ELECTRODE CONDUCTOR.

BOND ANTENNA MAST TO THE GROUNDING

ELECTRODE SYSTEM (TYPICAL FOR EACH ANTENNA).

PROVIDE GROUNDING IN ACCORDANCE WITH NEC

CHAPTER 8 AND NFPA 780.

E130

BUILDING 1300 FIRST FLOOR ELECTRICAL PLAN

SCALE: 1/16" = 1'-0"

EXISTING UNIT SUBSTATION WITH 500KVA DRY TYPE

TRANSFORMER WITH 208Y/120 VOLT SERVICE. PROVIDE

NEW TYPE 1 SURGE PROTECTIVE DEVICE (SPD)

ADJACENT TO EXISTING DRY TYPE TRANSFORMER.

CONNECT TO NEW 50/3 ENCLOSED BREAKER MOUNTED

ADJACENT TO EXISTING TRANSFORMERS AND CONNECT

WITH 4 #6, (1) #10 GND, IN 1" C. MIN. 65,000 AIC. PROVIDE

NEW LUGS ON EXISTING TRANSFORMER BUSING AS

REQUIRED TO CONNECT NEW CONDUCTORS.

INSTALL THE NEW BREAKER AND SPD IN ACCORDANCE

WITH NEC 285.23 AND AS PERMITTED IN NEC 230.82(4).

COMPLY WITH THE LOCATION REQUIREMENTS OF NEC

230.72(B). PROVIDE LABEL FOR NEW SPD BREAKER AND

REPLACE ALL EXISTING SERVICE DISCONNECT LABELS

TO COMPLY WITH NEC 230.2.

INTERCEPT EXISTING #4/0 BARE GROUNDING ELECTRODE

CONDUCTOR WHICH HAS BEEN CUT OFF IN EXISTING

CONDUIT STUB UP IN EXISTING DRY TYPE TRANSFORMER

SECONDARY COMPARTMENT. REMOVE CONCRETE AROUND

EXISTING CONDUCTOR AND CONNECT NEW #4/0 BARE

COPPER CONDUCTOR WITH EXOTHERMIC WELD OR CRIMP

CONNECTION. EXTEND NEW GROUNDING ELECTRODE

CONDUCTOR TO EXISTING NEUTRAL TERMINAL ON

TRANSFORMER AND BOND TO TRANSFORMER NEUTRAL.

PROVIDE NEW LUGS ON TRANSFORMER BUSING AS

REQUIRED TO CONNECT NEW CONDUCTORS.

EXISTING #4/0 BARE GROUNDING ELECTRODE CONDUCTOR

CONNECTED TO GENERATOR SKID WHICH ORIGINATES

BELOW GRADE AND IS FRAYED WITH BROKE STRANDS.

INTERCEPT EXISTING CONDUCTOR AND CONNECT NEW #4/0

BARE CONDUCTOR TO EXISTING GROUNDING ELECTRODE

SYSTEM WITH EXOTHERMIC WELD OR CRIMPED

CONNECTIONS. RECONNECT TO EXISTING GENERATOR

SKID.

EXISTING EMERGENCY GENERATOR

EXISTING TELEPHONE SERVICE PRIMARY

PROTECTORS.

EXISTING FIRE

ALARM SYSTEM

CONTROL PANEL &

MONACO RADIO

TRANSMITTER

Robert S. Gras

No. EE7352 29-Mar-2017

EXISTING 400 AMP, 208Y/120 VOLT FUSED DISCONNECT

SWITCH FOR MAIN BUILDING SERVICE.

GENERAL NOTE:

POTENTIAL EXISTS FOR ASBESTOS

AND LEAD-BASED PAINT IN AREAS

AFFECTED BY NEW WORK. REPORT

IS AVAILABLE FROM CONTRACTING

OFFICER UPON REQUEST.

RELOCATE EXISTING MID-ROOF

AIR TERMINAL

INSTALL NEW MID-ROOF AIR

TERMINAL

FASTEN CONDUCTOR TO ROOF

EVERY 36" MAXIMUM BRACE AIR TERMINAL

AT MID-POINT

BURY 2'-6" MIN. BELOW

FINISHED GRADE & 3'-0" MIN.

FROM FOUNDATION WALL, TYP.

REPLACE GROUNDING

RING ELECTRODE

SYSTEM AROUND

BUILDING

INSTALL COUNTERPOISE, BOND TO

BOLLARDS AND TANK

BOND TO BOLLARDS,

(TYP. OF 4)

DISTANCE SHOWN FOR

CLARITY, EXACT ROUTING

OF COUNTERPOISE TO BE

FIELD DETERMINED

GG

G

GGG

A

G

G

EXISTING METER AND 400 AMP, 480Y/277 VOLT

FUSED MAIN DISCONNECT SWITCH. PROVIDE NEW

TYPE 1 SURGE PROTECTIVE DEVICE (SPD),

ADJACENT TO EXISTING SWITCH. PROVIDE NEW

50/3 ENCLOSED BREAKER MOUNTED ADJACENT TO

EXISTING DISCONNECT SWITCH. CONNNECT SPD

FROM LUGS OF EXISTING SWITCH THROUGH

ENCLOSED BREAKER WITH 4 #6, (1) #10 GND, IN 1"

C. MIN. 65,000 AIC.

E140

BUILDING 1324 LIGHTNING PROTECTION PLAN

1/8"=1'-0"

Robert S. Gras

No. EE7352

INSTALL COUTERPOISE,

BOND TO BOLLARDS AND

TANK

BURY 2'-6" MIN. BELOW

FINISHED GRADE, TYP.

INSTALL GROUNDING

ELECTRODE SYSTEM

BOND TO

TRANSFORMER

SEE DETAIL "E", TYP. AT

ALL CATENARY MASTS

SEE DETAIL "F", TYP. AT

ALL LIGHT POLES

G

GG

G F FFF F

F F F F F F

F

F

F F

F

E E E

EEE

G

G

E150

BUILDING 1326 LIGHTNING PROTECTION PLAN

3/32" = 1'-0"

Robert S. Gras

No. EE7352 29-Mar-2017

EXISTING METER AND 400 AMP, 480Y/277 VOLT FUSED MAIN

DISCONNECT SWITCH (FIELD VERIFY VOLTAGE). PROVIDE NEW

TYPE 1 SURGE PROTECTIVE DEVICE (SPD), ADJACENT TO

EXISTING SWITCH. PROVIDE NEW 50/3 ENCLOSED BREAKER

MOUNTED ADJACENT TO EXISTING DISCONNECT SWITCH.

CONNNECT SPD FROM LUGS OF EXISTING SWITCH THROUGH

ENCLOSED BREAKER WITH 4 #6, (1) #10 GND, IN 1" C. MIN.

65,000 AIC.

BOND THE GATE POSTS TO THE GROUND RING WITH

A CLASS 1 COPPER CONDUCTOR WITH EXOTHERMIC

CONNNECTORS BELOW GRADE AND CLAMPS. BOX

THE GATE TO THE GATE POST USING FLEXIBLE #6

AWG CONDUCTOR. PROVIDE A 3 /4 IN. X 10 FT.

GROUND ROD BY EACH POST AND BOND TO THE

GROUND RING USING A CLASS 1 COPPER

CONDUCTOR. TOP OF GROUND ROD SHALL BE

WITHIN 6 IN. OF THE GROUND RING'S DEPTH

E160

BUILDING 1335 ELECTRICAL PLAN

SCALE: 1/16" = 1'-0"

EXISTING UNIT SUBSTATION WITH HIGH VOLTAGE

SWITCH, 500KVA DRY TYPE TRANSFORMER AND

800 AMP, 480Y/277 VOLT MAIN DISTRIBUTION PANEL

"MDP". PROVIDE NEW TYPE 2 SURGE PROTECTIVE

DEVICE (SPD) ADJACENT TO EXISTING MDP.

CONNECT TO EXISTING SPARE 50/3 BREAKER IN

EXISTING MDP AND CONNECT WITH 4 #6, (1) #10

GND, IN 1" C. MIN. 65,000 AIC.

EXISTING TELEPHONE

SERVICE CABLE &

TERMINATION BLOCKS

EXISTING FIRE ALARM SYSTEM

CONTROL PANEL & MONACO

RADIO TRANSMITTER

EXISTING ELECTRICAL ROOM

EXISTING DATA/NETWORK

CABINET

WALL MOUNTED AERIAL FIRE ALARM ANTENNA

EXTENDING ABOVE ROOF. PROVIDE A NEW

ANTENNA DISCHARGE UNIT (RF SPD) AND CONNECT

TO THE GROUNDING ELECTRODE SYSTEM WITH A

MIN. #6 CU. SYSTEM BONDING OR GROUNDING

ELECTRODE CONDUCTOR. BOND ANTENNA MAST.

PROVIDE GROUNDING IN ACCORDANCE WITH NEC

CHAPTER 8 AND NFPA 780.

Robert S. Gras

No. EE7352

E170

BUILDING 1338 ELECTRICAL PLAN

SCALE: 1/32" = 1'-0"

EXISTING UNIT SUBSTATION WITH HV SWITCH,

750KVA DRY TYPE TRANSFORMER AND 1,200 AMP,

480Y/277 VOLT MAIN DISTRIBUTION PANEL "MDP".

PROVIDE NEW TYPE 2 SURGE PROTECTIVE DEVICE

(SPD) ADJACENT TO EXISTING MDP. CONNECT TO

NEW 50/3 BREAKER IN EXISTING MDP SPACE AND

CONNECT WITH 4 #6, (1) #10 GND, IN 1" C. MIN.

65,000 AIC.

EXISTING TELEPHONE

SERVICE CABLE &

TERMINATION BLOCKS

EXISTING FIRE ALARM SYSTEM

CONTROL PANEL & MONACO

RADIO TRANSMITTER

EXISTING 200 AMP METER/MAIN

DISCONNECT FOR 208Y/120 VOLT

SERVICE TO EXISTING

MAINTENANCE SHOP ADDITION.

EXISTING 200 AMP 208Y/120 VOLT PANEL

"A" IN EXISTING MAINTENANCE SHOP

ADDITION. PROVIDE NEW TYPE 2 SURGE

PROTECTIVE DEVICE (SPD) ADJACENT TO

EXISTING PANEL "A" AND CONNECT TO

NEW 30/3 BREAKER IN EXISTING SPACE IN

PANEL "A". CONNECT WITH 4 #10, (1) #10

GND, IN 3/4" C.

WALL MOUNTED AERIAL FIRE ALARM ANTENNA

EXTENDING ABOVE ROOF. PROVIDE AN ANTENNA

DISCHARGE UNIT (RF SPD) AND CONNECT TO THE

GROUNDING ELECTRODE SYSTEM WITH A MIN. #6 CU.

SYSTEM BONDING OR GROUNDING ELECTRODE

CONDUCTOR. BOND ANTENNA MAST. PROVIDE

GROUNDING IN ACCORDANCE WITH NEC CHAPTER 8

AND NFPA 780.

ROOF MOUNTED AERIAL ANTENNA (TYPICAL OF 4

ANTENNAS). VERIFY ANTENNA IS STILL IN

OPERATION. FOR OPERATIONAL ANTENNAS,

PROVIDE AN ANTENNA DISCHARGE UNIT (RF SPD)

AND CONNECT TO THE GROUNDING ELECTRODE

SYSTEM WITH A MIN. #6 CU. SYSTEM BONDING OR

GROUNDING ELECTRODE CONDUCTOR. BOND

ANTENNA MAST TO THE GROUNDING ELECTRODE

SYSTEM (TYPICAL FOR EACH ANTENNA). PROVIDE

GROUNDING IN ACCORDANCE WITH NEC CHAPTER 8

AND NFPA 780.

Robert S. Gras

No. EE7352

AA

AA

AA A

A

A A

A

A

D

PROVIDE NEW

MID-ROOF

AIR TERMINAL

SYSTEM

BOND VENT TO LIGHTNING

PROTECTION SYSTEM

PROVIDE NEW MID-ROOF

AIR TERMINAL SYSTEM

INSTALL ADDITIONAL PERIMETER

AIR TERMINALS TO MEET 100'

ROLLING SPHERE REQUIREMENTS,

(TYP. OF 4)

AA

AA

FASTENERS FOR ALL PERIMETER AND

CROSS RUN CONDUCTORS SHALL NOT

EXCEED A SPACING OF 36 IN. PROVIDE

ADDITIONAL FASTENERS AS REQUIRED

TO MAINTAIN MAXIMUM 36" SPACING

FOR ALL CONDUCTORS.

FASTENERS FOR ALL PERIMETER AND

CROSS RUN CONDUCTORS SHALL NOT

EXCEED A SPACING OF 36 IN. PROVIDE

ADDITIONAL FASTENERS AS REQUIRED

TO MAINTAIN MAXIMUM 36" SPACING

FOR ALL CONDUCTORS.

PROVIDE NEW MID-ROOF

AIR TERMINAL SYSTEM

REMOVE EXISTING

MID-ROOF AIR

TERMINAL SYSTEM

REMOVE EXISTING

MID-ROOF AIR

TERMINAL SYSTEM

REMOVE EXISTING

MID-ROOF AIR

TERMINAL SYSTEM

PROVIDE NEW MID-ROOF

AIR TERMINAL SYSTEM

EXISTING FA

ANTENNA

PROVIDE 24 IN. AIR TERMINAL ON

TOP OF EXISTING ANTENNA POLE

AND BOND THE POLE TO THE

LOWER DECK LPS USING CLASS II

ALUMINUM CONDUCTOR AND

BI-METALLIC CONNECTIONS.

PROVIDE 24 IN. AIR TERMINAL ON TOP

OF EXISTING ANTENNA POLE AND

BOND THE POLE TO THE LOWER DECK

LPS USING CLASS II ALUMINUM

CONDUCTOR AND BI-METALLIC

CONNECTIONS. REMOVE THE #12 AWG

CONNECTION TO THE UPPER DECK LPS

REMOVE EXISTING

MID-ROOF AIR

TERMINAL SYSTEM

EXISTING MAIN SERVICE DISCONNECT

AND DISTRIBUTION PANEL ON FLOOR

BELOW WITH SQUARE D SURLOGIC CAT.

FC4XGA24CD SPD. INVESTIGATE

EXISITNG SPD AND ENSURE THAT SPD IS

IN GOOD WORKING ORDER. REPAIR OR

REPLACE PARTS AND/OR MODULES AS

REQUIRED TO PLACE SPD IN GOOD

WORKING ORDER.

E180

BUILDING 4371 LIGHTNING PROTECTION PLAN

3/32" = 1'-0"

Robert S. Gras

No. EE7352

NOTE:

NO BEND OF A CONDUCTOR SHALL FORM AN INCLUDED ANGLE

OF LESS THAN 90 DEGREES, NOR SHALL IT HAVE A RADIUS

OF BEND LESS THAN 8".

CONDUCTOR SHALL INTERCONNECT ALL AIR

TERMINALS AND SHALL FORM A TWO-WAY PATH

FROM EACH AIR TERMINAL HORIZONTALLY,

DOWNWARD OR RISING AT A RATE NOT EXCEEDING

3" PER FOOT TO CONNECTIONS WITH GROUND

TERMINALS

FASTEN CABLE 3'-0" O.C.

MAX, WITH APPROPRIATE

CABLE FASTENER.

NOTE: BONDING IS FOR EXTERIOR METAL DOORS

& WINDOWS WHEN REQUIRED AND WILL BE

COURSED EXPOSED ON EXTERIOR WALL

TYPICAL EXTERIOR DOOR AND WINDOW BONDING

BONDING LUG

BONDING

CONDUCTOR

ADHESIVE

CABLE HOLDER

EXPOSED BONDING

CONDUCTOR, COURSE

IN PVC CONDUIT

CU/AL GENTLY

TAPERED AIR TERMINAL

ALUMINUM PIPE RAILING BASE.

PLUMB AIR TERMINAL AFTER

INSTALLATION

COPPER OR ALUMINUM, CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

CU/AL GENTLY TAPERED

AIR TERMINAL

UNIVERSAL SWIVEL AIR

TERMINAL BASE

ADHESIVE CABLE FASTENER

ROOF MOUNTED LIGHT

ROOF PARAPET

BI-METALLIC

ONE-BOLT

CONNECTOR

BONDING

LUG

1/2" X 12" COPPER

AIR TERMINAL

1/2" COPPER BASE

(UNIVERSAL MOUNT)

CLASS II COPPER MAIN

CONDUCTOR, CONNECT

TO GROUND RING

TYPICAL AIR TERMINAL MOUNT ON TOP OF LIGHT POLE DETAIL

CLASS II COPPER MAIN

CONDUCTOR

BI-METALLIC ONE-BOLT

CONNECTOR

STRAIN

CLAMP

GUY WIRE

CAST BRONZE

CROSS-RUN CLAMP

CLASS II COPPER MAIN

CONDUCTOR

POLE

BI-METALLIC

ONE-BOLT

CONNECTOR

CATENARY WOOD POLE DETAIL

ALUMINUM CABLE CLIP

3/8" COPPER BASE (UNIVERSAL

MOUNT), SECURE WITH ADHESIVE

COPPER ADHESIVE

CABLE HOLDER

CONDUCTOR

BONDING

CONDUCTOR

SECURE TO LIGHTING CONDUIT

NO. ATTKUBC38 (**US

NP. PATENT 9,263,864) ,

3/8" COPPER BASE

(UNIVERSAL MOUNT),

SECURE WITH ADHESIVE

1/2" X 12" COPPER AIR TERMINAL

PVC CABLE GUARD. SUPPORT

PER NEC REQUIREMENTS OR

EVERY 3'-0"

E200

AIR TERMINAL 'B'

NOT TO SCALE

E200

AIR TERMINAL 'C'

NOT TO SCALE

E200

AIR TERMINAL 'D'

NOT TO SCALE

E200

AIR TERMINAL 'E'

NOT TO SCALE

E200

AIR TERMINAL 'F'

NOT TO SCALE

E200

BEND RADIUS DETAIL

NOT TO SCALE

E200

4 TO 1 CONDUCTOR DETAIL

NOT TO SCALE

E200

EXTERIOR STEEL FRAME BONDING

NOT TO SCALE

E200

AIR TERMINAL 'A'

NOT TO SCALE

Robert S. Gras

No. EE7352

" M

IN

B E

LO

W

F

IN

IS

H

G R

A D

E

6' -0

" M

IN

CLASS I COPPER

MAIN CONDUCTOR

1 1/4, PVC CABLE GUARD,

SUPPORT PER NEC

REQUIREMENTS OR

EVERY 3'-0"

CLASS I COPPER

MAIN CONDUCTOR

PROVIDE PVC CONDUIT

FOR PROTECTION

MAINTAIN A RADIUS BEND OF 8"

MINIMUM AND AN ANGLE BEND

OF 90° OR GREATER (TYPICAL

FOR ALL CONDUCTOR BENDS)

THRU WALL PENETRATION

CONNECT TO GROUND ROD

THRU ROOF PENETRATION (TRIM RISER

AND SLEEVE AS NECESSARY SO AS

NOT TO EXCEED 9" ABOVE ROOF)

AIR TERMINAL 'A'

CLASS 1 COPPER LIGHTNING CONDUCTOR

(TYPICAL FOR ALL CONDUCTOR SHOWN)

GROUND BUILDING FLOOR

COPPER OR ALUMINUM, CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

THRU-ROOF CONNECTOR

COPPER OR ALUMINUM, CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

COPPER OR ALUMINUM, CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

COPPER OR ALUMINUM, CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

THRU-WALL CONNECTOR

EXOTHERMIC WELD

CABLE TO GROUND

ROD CONNECTION

3/4" X 10' COPPER

CLAD GROUND ROD

CLASS II BARE

COPPER CONDUCTOR

ALTERNATE COPPER

GROUND PLATE

BOND TO STRUCTURAL STEEL

BOND TO STRUCTURAL STEEL

E201

WALL SECTION

NOT TO SCALE

E201

GROUNDING ROD DETAIL

NOT TO SCALE

E201

PVC CABLE GUARD

NOT TO SCALE

E201

THRU-ROOF PENETRATION

NOT TO SCALE

E201

THRU-WALL PENETRATION

NOT TO SCALE

Robert S. Gras

No. EE7352

G001
E001
E110
E120
E130
E140
E150
E160
E170
E180
E200
E201