JA-5_Site_Map_and_Drawings.pdf
PDF 6 MB Posted
- Attached to
- Lightning and Surge Protection Federal contract opportunity
- Solicitation number
- FA5004-17-B-C001
About this file
JA-5 Site Map and Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_and_Answers__2.pdf | ||
| Questions_and_Answers.pdf | ||
| Bldg_1227_photos.pdf | ||
| Bldg_1228_photos.pdf | ||
| Bldg_1338_photos.pdf | ||
| Site_Visit_Sign_In.pdf | ||
| Bldg_1338_Extension_photos.pdf | ||
| Bldg_4371_photos.pdf | ||
| FA5004-17-B-C001-0002.pdf | ||
| JA-5_Site_Map_and_Drawings.pdf | ||
| JA-2_Specifications.pdf | ||
| JA-6_Asbestos_Surveys.pdf | ||
| JA-1_Other_Contract_Requirements.pdf | ||
| JA-3_Wage_Determination.pdf | ||
| FA5004-17-B-C001-0001.pdf | ||
| JA-4_AF_Form_66.pdf | ||
| JA-5_Site_Map_and_Drawings.pdf | ||
| JA-2_Specifications.pdf | ||
| JA-4_AF_Form_66.pdf | ||
| JA-1_Other_Contract_Requirements.pdf | ||
| FA5004-17-B-C001.pdf | ||
| JA-6_Asbestos_Surveys.pdf | ||
| JA-3_Wage_Determination.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
NORTH ARROWS
ROOM NUMBER
SCALE
TITLE
SHEET LOCATION
DETAIL NUMBER
A
E110
SHEET LOCATION
SECTION NUMBER
DETAIL NUMBER
OFFICE
SHEET LOCATION
A
E110
G001 GENERAL INFORMATION
GOVERNING CODES:
2012 INTERNATIONAL BUILDING CODE - IBC
2012 INTERNATIONAL FIRE CODE - IFC
2014 NFPA 70 - NATIONAL ELECTRICAL CODE - NEC
2013 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE
2015 NFPA 101 LIFE SAFETY CODE
2014 NFPA 780 - STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS
UFC 3-575-01 - LIGHTNING AND STATIC ELECTRICITY PROTECTION SYSTEMS
UFC 3-550-01 - EXTERIOR ELECTRICAL POWER DISTRIBUTION
AUTHORITY HAVING JURISDICTION
EAFB FIRE DEPARTMENT
E001 LEGEND AND OVERVIEW
E110 BUILDING 1227 ELECTRICAL PLANS AND DETAILS
E120 BUILDING 1228 ELECTRICAL PLANS AND DETAILS
E130 BUILDING 1300 ELECTRICAL PLANS AND DETAILS
E140 BUILDING 1324 LIGHTNING PROTECTION PLAN
E150 BUILDING 1326 LIGHTNING PROTECTION PLAN
E160 BUILDING 1335 ELECTRICAL PLAN
E170 BUILDING 1338 ELECTRICAL PLAN
E180 BUILDING 4371 LIGHTNING PROTECTION PLAN
E200 DETAILS
E201 DETAILS
BLDG 1227 & 1228
BLDG
BLDG 1300
BLDG 1324 & 1326
BLDG 1335
& 1338
A
E110
DRAWING TITLE
SCALE
Robert S. Gras
No. EE7352
13-Jan-2017
FA5004-17-B-C001 EIELSON AFB, AK JA-5 SITE MAPS AND DRAWINGS
B
C
D
1/ 2" X 24" GENTLY TAPERED SOLID COPPER AIR
TERMINAL WITH BRONZE SWIVEL AIR TERMINAL
BASE SET IN ADHESIVE
LEGEND
5/8" X 24" GENTLY TAPERED SOLID ALUMINUM AIR
TERMINAL WITH ALUMINUM UNIVERSAL BASE
MOUNTED HORIZONTALLY SET IN ADHESIVE
1/2" X 12" GENTLY TAPERED SOLID ALUMINUM AIR
TERMINAL WITH ALUMINUM UNIVERSAL BASE
MOUNTED HORIZONTALLY SET IN ADHESIVE
MOUNTED ON TOP OF HIGHEST LIGHT FIXTURE
5/8" X 24" GENTLY TAPERED SOLID ALUMINUM AIR
TERMINAL WITH ALUMINUM PIPE RAILING BASE
3/4" X 10'-0" COPPER CLAD GROUND ROD WITH
U-BOLT GROUND ROD CLAMP
G
CLASS 1 COPPER LIGHTNING CONDUCTOR (29
STRANDS OF 16 AWG WIRE) SECURE TO
BUILDING EVERY THREE FEET MAXIMUM.
T THRU ROOF CONNECTOR ASSEMBLY WITH
CLASS 1 DOWN CONDUCTOR
THRU WALL CONNECTOR ASSEMBLY WITH CLASS
1 DOWN CONDUCTOR
TYPICAL BODIES OF CONDUCTANCE AS NOTED BELOW. USE FULL SIZE
CONDUCTOR AND APPROPRIATE FITTING SHOWN FOR CONNECTION.
(PLUMBING STACK) REQUIRES BONDING WITH MAIN SIZE CABLE ONLY
IF WITHIN 6'-0" OF LIGHTNING PROTECTION SYSTEM.
TYPICAL BODIES OF INDUCTANCE AS NOTED BELOW. USE
SECONDARY SIZE (SMALLER) CONDUCTOR AND APPROPRIATE FITTING
SHOWN FOR CONNECTION.
BONDING CONNECTIONS AND FITTINGS SHOWN ARE TYPICAL
EXAMPLES. MAKE ALL CONNECTIONS REQUIRED TO MEET CODES AS
NOTED. ADJUST FITTING TYPE AS REQUIRED TO SUIT FIELD
CONDITIONS.
D
C
C
A
C
B
GENERAL INSTALLATION NOTES
LOCATE AIR TERMINALS AS SHOWN. TAKE CARE TO INSURE THAT ALL
POINTS ARE WITHIN 2'-0" OF OUTSIDE BUILDING EDGE, OUTSIDE CORNERS,
RIDGE ENDS, AND THAT MAX SPACING DOES NOT EXCEED 20'-0", AND
THAT MIN PROJECTION ABOVE OBJECT PROTECTED IS 10"; POINTS
PROJECTING 24" MAY BE SPACED @ 25'-0" MAX
MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN CONDUCTOR.
INSURE THAT ALL BENDS HAVE AT LEAST AN 8" RADIUS AND DO NOT
EXCEED 90 DEGREES.
ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING CABLES AT 3'-0"
ON CENTER MAX. VERIFY COMPATIBILITY OF ADHESIVE ON MEMBRANE
ROOF APPLICATION PRIOR TO INSTALLATION.
GROUND ELECTRODES SHALL BE INSTALLED AS SHOWN, BUT IN NO
INSTANCE SHALL THEY BE LESS THAN 1'-0" BELOW GRADE AND 2'-0" FROM
FOUNDATION WALL. DRIVEN RODS SHALL PENETRATE THE EARTH AT
LEAST 10'-0".
BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS SHOWN AND
AS REQUIRED BY CODE.
MAIN SIZE LIGHTNING CONDUCTOR BONDED TO MAIN GROUND
BUS FIELD VERIFY LOCATION 1 1/4" CONDUIT FOR ACCESS, INSTALLED BY
OTHERS. INTERCONNECT LIGHTNING PROTECTION GROUND TO
TELEPHONE AND OTHER BUILDING GROUND SYSTEMS LOCATION FIELD
DETERMINED OR AS REQUIRED BY CODE.
LB'S AND SIMILAR CONDUIT BODIES MAY NOT BE USED IN THE
INSTALLATION OF DOWNLEAD CONDUITS, AS THEY DO NOT ADHERE TO
THE REQUIRED 8" MINIMUM BEND RADIUS.
SYSTEM SHALL BE INSTALLED AS SHOWN TO INSURE PROPER CODE
COMPLIANCE AND SYSTEM CERTIFICATION. ANY MAJOR VARIANCE SHALL
BE RESUBMITTED FOR APPROVAL.
ALL MATERIALS TO BE UNDERWRITER'S LABORATORIES APPROVED WITH
"A" LABELS ON CONDUCTORS @ 10'-0" INTERVALS AND "B" LABELS ON ALL
AIR TERMINALS.
FINAL SYSTEM INSPECTION AND QUALITY CONTROL
A. THE CONTRACTOR SHALL FURNISH AN LPI-IP CERTIFICATE OR A UL
CERTIFICATE UPON COMPLETION OF THE INSTALLATION.
B. LPI CERTIFICATION IF REQUIRED, REQUIRES SIGNATURE BY A
REPRESENTATIVE OF THE OWNER AT MULTIPLE STAGES OF
INSTALLATION & BY THEIR THIRD PARTY FIELD STAFF. UL
CERTIFICATION IF REQUIRED, REQUIRES INSPECTION BY THEIR
THIRD-PARTY FIELD STAFF AFTER COMPLETION OF THE
INSTALLATION.
C. AS-BUILT DRAWINGS SHALL BE COMPLETED AND STAMPED BY AN LPI
CERTIFIED MASTER DESIGNER - INSTALLER OF LIGHTNING
PROTECTION SYSTEMS.
D. FINAL INSPECTION REPORT - A FINAL INSPECTION AND INSPECTION
REPORT SHALL BE COMPLETED BASED ON ANSI/TIA/EIA 607, NEC,
NFPA 780, AND UL96A INDUSTRY STANDARDS AS APPLICABLE. THE
SCOPE OF THE INSPECTION AND REPORT SHALL INCLUDE;
a. TEST AND EVALUATION THE GROUNDING SYSTEM. RECORD
FINAL SYSTEMS TO GROUND RESISTANCE LEVEL.
b. EVALUATION AND TESTING OF THE INTERNAL
BONDING AND GROUNDING SYSTEMS.
c. EVALUATION AND TESTING OF EQUIPMENT
GROUNDING.
d. EVALUATION OF AC SURGE SUPPRESSION INSTALLATION.
e. EVALUATION OF TELCO SURGE SUPPRESSION INSTALLATION.
f. COPY OF THE LPI-IP OR UL LIGHTNING PROTECTION
CERTIFICATION.
g. FINAL AS-BUILT REVIEW AND SUBMISSION.
E. REPORT SHALL INCLUDE DETAILED REPORTING AND TEST RESULTS
WITH CORRESPONDING PHOTOS OF EACH EVALUATION CATEGORY.
SYSTEM DESIGNED UTILIZING UL LISTED T&B/FURSE MATERIALS.
MECHANICAL CONNECTION
EXISTING AIR TERMINAL
EXISTING LIGHTNING PROTECTION CONDUCTOR
CLASS 2 COPPER LIGHTNING CONDUCTOR
A
AA
A
A
A
A
A
B
C
C
E001
GENERAL BONDING NOTES
NOT TO SCALE
E 12"X 12" GENTLY TAPERED SOLID ALUMINUM AIR
TERMINAL MOUNTED VERTICALLY ALONG WOOD
POLE USING CAST BRONZE CROSS-RUN CLAMP
F 12" X 12" GENTLY TAPERED SOLID ALUMINUM AIR
TERMINAL WITH ALUMINUM UNIVERSAL BASE
MOUNTED ON TOP OF LIGHT POLE
EX
GENERAL BONDING NOTES
AERIAL ANTENNA - ROOF MOUNTED
TEST WELL
Robert S. Gras
No. EE7352
1 2 3 4 5 6 7 8 9
E
4 5 6
A
E110
BUILDING 1227 ELECTRICAL PLAN
SCALE: 1/32" = 1'-0"
EXISTING 200 AMP, 480Y/277 VOLT, 4 POLE AUTO TRANSFER SWITCH
WITH CONNECTION TO EXISTING MCCE FROM 200/3 BREAKERS IN THE
MDP'S OF BOTH BUILDING 1227 AND 1228. PROVIDE NEW TYPE 2 SURGE
PROTECTIVE DEVICE (SPD) ADJACENT TO EXISTING TRANSFER SWITCH.
CONNECT TO NEW 50/3 ENCLOSED BREAKER MOUNTED ADJACENT TO
TRANSFER SWITCH AND CONNECT WITH 4 #6, (1) #10 GND, IN 1" C. MIN.
65,000 AIC.
EXISTING 500 KVA PAD
MOUNTED TRANSFORMER
G
EXISTING DATA/NETWORK
CABINET
EXISTING TELEPHONE SERVICE
PRIMARY PROTECTORS.
EXISTING FIRE ALARM SYSTEM
CONTROL PANEL & MONACO
RADIO TRANSMITTER
E110
BUILDING 1227 ELECTRICAL ROOM PLAN
SCALE: 1/8" = 1'-0"
EXISTING 500 KVA
PAD MOUNTED
TRANSFORMER
EXISTING 800 AMP, 480Y/277 VOLT MAIN
DISTRIBUTION PANEL "MDP". PROVIDE NEW TYPE 1
SURGE PROTECTIVE DEVICE (SPD), ADJACENT TO
EXISTING MDP. CONNECT TO NEW 50/3 BREAKER IN
EXISTING MDP SPACE AND CONNECT WITH 4 #6, (1)
#10 GND, IN 1" C. MIN. 65,000 AIC.
EXISTING FIRE ALARM
CONTROL PANEL
EXISTING ELECTRICAL
ROOM. SEE DETAIL 2/E110EXISTING VAULT ROOM.
SEE DETAIL 2/E110
Robert S. Gras
No. EE7352 29-Mar-2017
1 2 3 4 5 6 7 8 9
E
4 5 6
E
E120
BUILDING 1228 ELECTRICAL PLAN
SCALE: 1/32" = 1'-0"
EXISTING FIRE SUPPRESSION
SYSTEM CONTROL PANEL &
MONACO RADIO TRANSMITTER
EXISTING 500 KVA PAD
MOUNTED TRANSFORMER
G
EXISTING 800 AMP, 480Y/277 VOLT MAIN
DISTRIBUTION PANEL "MDP". PROVIDE NEW TYPE 1
SURGE PROTECTIVE DEVICE (SPD) ADJACENT TO
EXISTING MDP. CONNECT TO NEW 50/3 BREAKER IN
EXISTING MDP SPACE AND CONNECT WITH 4 #6, (1)
#10 GND, IN 1" C. MIN. 65,000 AIC.
EXISTING 200 AMP, 480Y/277 VOLT, 4 POLE AUTO TRANSFER SWITCH
WITH CONNECTION TO EXISTING MCCE FROM 200 3 BREAKERS IN THE
MDP'S OF BOTH BUILDING 1227 AND 1228. PROVIDE NEW TYPE 2 SURGE
PROTECTIVE DEVICE (SPD) ADJACENT TO EXISTING TRANSFER SWITCH.
CONNECT TO NEW 50/3 ENCLOSED BREAKER MOUNTED ADJACENT TO
TRANSFER SWITCH AND CONNECT WITH 4 #6, (1) #10 GND, IN 1" C. MIN.
65,000 AIC.
EXISTING 500 KVA PAD
MOUNTED
TRANSFORMER
EXISTING TELEPHONE SERVICE
PRIMARY PROTECTORS.
EXISTING FIRE ALARM
CONTROL PANEL
EXISTING DATA/NETWORK
CABINET
EXISTING ELECTRICAL
ROOM. SEE DETAIL 2/E120
EXISTING VAULT ROOM.
SEE DETAIL 2/E120
E120
BUILDING 1228 ELECTRICAL ROOM PLAN
SCALE: 1/8" = 1'-0"
Robert S. Gras
No. EE7352
E130
BUILDING 1300 ROOF ELECTRICAL PLAN
SCALE: 1/16" = 1'-0"
ROOF MOUNTED AERIAL ANTENNA (TYPICAL OF 12
ANTENNAS). PROVIDE AN ANTENNA DISCHARGE UNIT
(RF SPD) AND CONNECT TO THE GROUNDING
ELECTRODE SYSTEM WITH A MIN. #6 CU. SYSTEM
BONDING OR GROUNDING ELECTRODE CONDUCTOR.
BOND ANTENNA MAST TO THE GROUNDING
ELECTRODE SYSTEM (TYPICAL FOR EACH ANTENNA).
PROVIDE GROUNDING IN ACCORDANCE WITH NEC
CHAPTER 8 AND NFPA 780.
E130
BUILDING 1300 FIRST FLOOR ELECTRICAL PLAN
SCALE: 1/16" = 1'-0"
EXISTING UNIT SUBSTATION WITH 500KVA DRY TYPE
TRANSFORMER WITH 208Y/120 VOLT SERVICE. PROVIDE
NEW TYPE 1 SURGE PROTECTIVE DEVICE (SPD)
ADJACENT TO EXISTING DRY TYPE TRANSFORMER.
CONNECT TO NEW 50/3 ENCLOSED BREAKER MOUNTED
ADJACENT TO EXISTING TRANSFORMERS AND CONNECT
WITH 4 #6, (1) #10 GND, IN 1" C. MIN. 65,000 AIC. PROVIDE
NEW LUGS ON EXISTING TRANSFORMER BUSING AS
REQUIRED TO CONNECT NEW CONDUCTORS.
INSTALL THE NEW BREAKER AND SPD IN ACCORDANCE
WITH NEC 285.23 AND AS PERMITTED IN NEC 230.82(4).
COMPLY WITH THE LOCATION REQUIREMENTS OF NEC
230.72(B). PROVIDE LABEL FOR NEW SPD BREAKER AND
REPLACE ALL EXISTING SERVICE DISCONNECT LABELS
TO COMPLY WITH NEC 230.2.
INTERCEPT EXISTING #4/0 BARE GROUNDING ELECTRODE
CONDUCTOR WHICH HAS BEEN CUT OFF IN EXISTING
CONDUIT STUB UP IN EXISTING DRY TYPE TRANSFORMER
SECONDARY COMPARTMENT. REMOVE CONCRETE AROUND
EXISTING CONDUCTOR AND CONNECT NEW #4/0 BARE
COPPER CONDUCTOR WITH EXOTHERMIC WELD OR CRIMP
CONNECTION. EXTEND NEW GROUNDING ELECTRODE
CONDUCTOR TO EXISTING NEUTRAL TERMINAL ON
TRANSFORMER AND BOND TO TRANSFORMER NEUTRAL.
PROVIDE NEW LUGS ON TRANSFORMER BUSING AS
REQUIRED TO CONNECT NEW CONDUCTORS.
EXISTING #4/0 BARE GROUNDING ELECTRODE CONDUCTOR
CONNECTED TO GENERATOR SKID WHICH ORIGINATES
BELOW GRADE AND IS FRAYED WITH BROKE STRANDS.
INTERCEPT EXISTING CONDUCTOR AND CONNECT NEW #4/0
BARE CONDUCTOR TO EXISTING GROUNDING ELECTRODE
SYSTEM WITH EXOTHERMIC WELD OR CRIMPED
CONNECTIONS. RECONNECT TO EXISTING GENERATOR
SKID.
EXISTING EMERGENCY GENERATOR
EXISTING TELEPHONE SERVICE PRIMARY
PROTECTORS.
EXISTING FIRE
ALARM SYSTEM
CONTROL PANEL &
MONACO RADIO
TRANSMITTER
Robert S. Gras
No. EE7352 29-Mar-2017
EXISTING 400 AMP, 208Y/120 VOLT FUSED DISCONNECT
SWITCH FOR MAIN BUILDING SERVICE.
GENERAL NOTE:
POTENTIAL EXISTS FOR ASBESTOS
AND LEAD-BASED PAINT IN AREAS
AFFECTED BY NEW WORK. REPORT
IS AVAILABLE FROM CONTRACTING
OFFICER UPON REQUEST.
RELOCATE EXISTING MID-ROOF
AIR TERMINAL
INSTALL NEW MID-ROOF AIR
TERMINAL
FASTEN CONDUCTOR TO ROOF
EVERY 36" MAXIMUM BRACE AIR TERMINAL
AT MID-POINT
BURY 2'-6" MIN. BELOW
FINISHED GRADE & 3'-0" MIN.
FROM FOUNDATION WALL, TYP.
REPLACE GROUNDING
RING ELECTRODE
SYSTEM AROUND
BUILDING
INSTALL COUNTERPOISE, BOND TO
BOLLARDS AND TANK
BOND TO BOLLARDS,
(TYP. OF 4)
DISTANCE SHOWN FOR
CLARITY, EXACT ROUTING
OF COUNTERPOISE TO BE
FIELD DETERMINED
GG
G
GGG
A
G
G
EXISTING METER AND 400 AMP, 480Y/277 VOLT
FUSED MAIN DISCONNECT SWITCH. PROVIDE NEW
TYPE 1 SURGE PROTECTIVE DEVICE (SPD),
ADJACENT TO EXISTING SWITCH. PROVIDE NEW
50/3 ENCLOSED BREAKER MOUNTED ADJACENT TO
EXISTING DISCONNECT SWITCH. CONNNECT SPD
FROM LUGS OF EXISTING SWITCH THROUGH
ENCLOSED BREAKER WITH 4 #6, (1) #10 GND, IN 1"
C. MIN. 65,000 AIC.
E140
BUILDING 1324 LIGHTNING PROTECTION PLAN
1/8"=1'-0"
Robert S. Gras
No. EE7352
INSTALL COUTERPOISE,
BOND TO BOLLARDS AND
TANK
BURY 2'-6" MIN. BELOW
FINISHED GRADE, TYP.
INSTALL GROUNDING
ELECTRODE SYSTEM
BOND TO
TRANSFORMER
SEE DETAIL "E", TYP. AT
ALL CATENARY MASTS
SEE DETAIL "F", TYP. AT
ALL LIGHT POLES
G
GG
G F FFF F
F F F F F F
F
F
F F
F
E E E
EEE
G
G
E150
BUILDING 1326 LIGHTNING PROTECTION PLAN
3/32" = 1'-0"
Robert S. Gras
No. EE7352 29-Mar-2017
EXISTING METER AND 400 AMP, 480Y/277 VOLT FUSED MAIN
DISCONNECT SWITCH (FIELD VERIFY VOLTAGE). PROVIDE NEW
TYPE 1 SURGE PROTECTIVE DEVICE (SPD), ADJACENT TO
EXISTING SWITCH. PROVIDE NEW 50/3 ENCLOSED BREAKER
MOUNTED ADJACENT TO EXISTING DISCONNECT SWITCH.
CONNNECT SPD FROM LUGS OF EXISTING SWITCH THROUGH
ENCLOSED BREAKER WITH 4 #6, (1) #10 GND, IN 1" C. MIN.
65,000 AIC.
BOND THE GATE POSTS TO THE GROUND RING WITH
A CLASS 1 COPPER CONDUCTOR WITH EXOTHERMIC
CONNNECTORS BELOW GRADE AND CLAMPS. BOX
THE GATE TO THE GATE POST USING FLEXIBLE #6
AWG CONDUCTOR. PROVIDE A 3 /4 IN. X 10 FT.
GROUND ROD BY EACH POST AND BOND TO THE
GROUND RING USING A CLASS 1 COPPER
CONDUCTOR. TOP OF GROUND ROD SHALL BE
WITHIN 6 IN. OF THE GROUND RING'S DEPTH
E160
BUILDING 1335 ELECTRICAL PLAN
SCALE: 1/16" = 1'-0"
EXISTING UNIT SUBSTATION WITH HIGH VOLTAGE
SWITCH, 500KVA DRY TYPE TRANSFORMER AND
800 AMP, 480Y/277 VOLT MAIN DISTRIBUTION PANEL
"MDP". PROVIDE NEW TYPE 2 SURGE PROTECTIVE
DEVICE (SPD) ADJACENT TO EXISTING MDP.
CONNECT TO EXISTING SPARE 50/3 BREAKER IN
EXISTING MDP AND CONNECT WITH 4 #6, (1) #10
GND, IN 1" C. MIN. 65,000 AIC.
EXISTING TELEPHONE
SERVICE CABLE &
TERMINATION BLOCKS
EXISTING FIRE ALARM SYSTEM
CONTROL PANEL & MONACO
RADIO TRANSMITTER
EXISTING ELECTRICAL ROOM
EXISTING DATA/NETWORK
CABINET
WALL MOUNTED AERIAL FIRE ALARM ANTENNA
EXTENDING ABOVE ROOF. PROVIDE A NEW
ANTENNA DISCHARGE UNIT (RF SPD) AND CONNECT
TO THE GROUNDING ELECTRODE SYSTEM WITH A
MIN. #6 CU. SYSTEM BONDING OR GROUNDING
ELECTRODE CONDUCTOR. BOND ANTENNA MAST.
PROVIDE GROUNDING IN ACCORDANCE WITH NEC
CHAPTER 8 AND NFPA 780.
Robert S. Gras
No. EE7352
E170
BUILDING 1338 ELECTRICAL PLAN
SCALE: 1/32" = 1'-0"
EXISTING UNIT SUBSTATION WITH HV SWITCH,
750KVA DRY TYPE TRANSFORMER AND 1,200 AMP,
480Y/277 VOLT MAIN DISTRIBUTION PANEL "MDP".
PROVIDE NEW TYPE 2 SURGE PROTECTIVE DEVICE
(SPD) ADJACENT TO EXISTING MDP. CONNECT TO
NEW 50/3 BREAKER IN EXISTING MDP SPACE AND
CONNECT WITH 4 #6, (1) #10 GND, IN 1" C. MIN.
65,000 AIC.
EXISTING TELEPHONE
SERVICE CABLE &
TERMINATION BLOCKS
EXISTING FIRE ALARM SYSTEM
CONTROL PANEL & MONACO
RADIO TRANSMITTER
EXISTING 200 AMP METER/MAIN
DISCONNECT FOR 208Y/120 VOLT
SERVICE TO EXISTING
MAINTENANCE SHOP ADDITION.
EXISTING 200 AMP 208Y/120 VOLT PANEL
"A" IN EXISTING MAINTENANCE SHOP
ADDITION. PROVIDE NEW TYPE 2 SURGE
PROTECTIVE DEVICE (SPD) ADJACENT TO
EXISTING PANEL "A" AND CONNECT TO
NEW 30/3 BREAKER IN EXISTING SPACE IN
PANEL "A". CONNECT WITH 4 #10, (1) #10
GND, IN 3/4" C.
WALL MOUNTED AERIAL FIRE ALARM ANTENNA
EXTENDING ABOVE ROOF. PROVIDE AN ANTENNA
DISCHARGE UNIT (RF SPD) AND CONNECT TO THE
GROUNDING ELECTRODE SYSTEM WITH A MIN. #6 CU.
SYSTEM BONDING OR GROUNDING ELECTRODE
CONDUCTOR. BOND ANTENNA MAST. PROVIDE
GROUNDING IN ACCORDANCE WITH NEC CHAPTER 8
AND NFPA 780.
ROOF MOUNTED AERIAL ANTENNA (TYPICAL OF 4
ANTENNAS). VERIFY ANTENNA IS STILL IN
OPERATION. FOR OPERATIONAL ANTENNAS,
PROVIDE AN ANTENNA DISCHARGE UNIT (RF SPD)
AND CONNECT TO THE GROUNDING ELECTRODE
SYSTEM WITH A MIN. #6 CU. SYSTEM BONDING OR
GROUNDING ELECTRODE CONDUCTOR. BOND
ANTENNA MAST TO THE GROUNDING ELECTRODE
SYSTEM (TYPICAL FOR EACH ANTENNA). PROVIDE
GROUNDING IN ACCORDANCE WITH NEC CHAPTER 8
AND NFPA 780.
Robert S. Gras
No. EE7352
AA
AA
AA A
A
A A
A
A
D
PROVIDE NEW
MID-ROOF
AIR TERMINAL
SYSTEM
BOND VENT TO LIGHTNING
PROTECTION SYSTEM
PROVIDE NEW MID-ROOF
AIR TERMINAL SYSTEM
INSTALL ADDITIONAL PERIMETER
AIR TERMINALS TO MEET 100'
ROLLING SPHERE REQUIREMENTS,
(TYP. OF 4)
AA
AA
FASTENERS FOR ALL PERIMETER AND
CROSS RUN CONDUCTORS SHALL NOT
EXCEED A SPACING OF 36 IN. PROVIDE
ADDITIONAL FASTENERS AS REQUIRED
TO MAINTAIN MAXIMUM 36" SPACING
FOR ALL CONDUCTORS.
FASTENERS FOR ALL PERIMETER AND
CROSS RUN CONDUCTORS SHALL NOT
EXCEED A SPACING OF 36 IN. PROVIDE
ADDITIONAL FASTENERS AS REQUIRED
TO MAINTAIN MAXIMUM 36" SPACING
FOR ALL CONDUCTORS.
PROVIDE NEW MID-ROOF
AIR TERMINAL SYSTEM
REMOVE EXISTING
MID-ROOF AIR
TERMINAL SYSTEM
REMOVE EXISTING
MID-ROOF AIR
TERMINAL SYSTEM
REMOVE EXISTING
MID-ROOF AIR
TERMINAL SYSTEM
PROVIDE NEW MID-ROOF
AIR TERMINAL SYSTEM
EXISTING FA
ANTENNA
PROVIDE 24 IN. AIR TERMINAL ON
TOP OF EXISTING ANTENNA POLE
AND BOND THE POLE TO THE
LOWER DECK LPS USING CLASS II
ALUMINUM CONDUCTOR AND
BI-METALLIC CONNECTIONS.
PROVIDE 24 IN. AIR TERMINAL ON TOP
OF EXISTING ANTENNA POLE AND
BOND THE POLE TO THE LOWER DECK
LPS USING CLASS II ALUMINUM
CONDUCTOR AND BI-METALLIC
CONNECTIONS. REMOVE THE #12 AWG
CONNECTION TO THE UPPER DECK LPS
REMOVE EXISTING
MID-ROOF AIR
TERMINAL SYSTEM
EXISTING MAIN SERVICE DISCONNECT
AND DISTRIBUTION PANEL ON FLOOR
BELOW WITH SQUARE D SURLOGIC CAT.
FC4XGA24CD SPD. INVESTIGATE
EXISITNG SPD AND ENSURE THAT SPD IS
IN GOOD WORKING ORDER. REPAIR OR
REPLACE PARTS AND/OR MODULES AS
REQUIRED TO PLACE SPD IN GOOD
WORKING ORDER.
E180
BUILDING 4371 LIGHTNING PROTECTION PLAN
3/32" = 1'-0"
Robert S. Gras
No. EE7352
NOTE:
NO BEND OF A CONDUCTOR SHALL FORM AN INCLUDED ANGLE
OF LESS THAN 90 DEGREES, NOR SHALL IT HAVE A RADIUS
OF BEND LESS THAN 8".
CONDUCTOR SHALL INTERCONNECT ALL AIR
TERMINALS AND SHALL FORM A TWO-WAY PATH
FROM EACH AIR TERMINAL HORIZONTALLY,
DOWNWARD OR RISING AT A RATE NOT EXCEEDING
3" PER FOOT TO CONNECTIONS WITH GROUND
TERMINALS
FASTEN CABLE 3'-0" O.C.
MAX, WITH APPROPRIATE
CABLE FASTENER.
NOTE: BONDING IS FOR EXTERIOR METAL DOORS
& WINDOWS WHEN REQUIRED AND WILL BE
COURSED EXPOSED ON EXTERIOR WALL
TYPICAL EXTERIOR DOOR AND WINDOW BONDING
BONDING LUG
BONDING
CONDUCTOR
ADHESIVE
CABLE HOLDER
EXPOSED BONDING
CONDUCTOR, COURSE
IN PVC CONDUIT
CU/AL GENTLY
TAPERED AIR TERMINAL
ALUMINUM PIPE RAILING BASE.
PLUMB AIR TERMINAL AFTER
INSTALLATION
COPPER OR ALUMINUM, CLASS I
OR CLASS II LIGHTNING
PROTECTION CONDUCTOR
CU/AL GENTLY TAPERED
AIR TERMINAL
UNIVERSAL SWIVEL AIR
TERMINAL BASE
ADHESIVE CABLE FASTENER
ROOF MOUNTED LIGHT
ROOF PARAPET
BI-METALLIC
ONE-BOLT
CONNECTOR
BONDING
LUG
1/2" X 12" COPPER
AIR TERMINAL
1/2" COPPER BASE
(UNIVERSAL MOUNT)
CLASS II COPPER MAIN
CONDUCTOR, CONNECT
TO GROUND RING
TYPICAL AIR TERMINAL MOUNT ON TOP OF LIGHT POLE DETAIL
CLASS II COPPER MAIN
CONDUCTOR
BI-METALLIC ONE-BOLT
CONNECTOR
STRAIN
CLAMP
GUY WIRE
CAST BRONZE
CROSS-RUN CLAMP
CLASS II COPPER MAIN
CONDUCTOR
POLE
BI-METALLIC
ONE-BOLT
CONNECTOR
CATENARY WOOD POLE DETAIL
ALUMINUM CABLE CLIP
3/8" COPPER BASE (UNIVERSAL
MOUNT), SECURE WITH ADHESIVE
COPPER ADHESIVE
CABLE HOLDER
CONDUCTOR
BONDING
CONDUCTOR
SECURE TO LIGHTING CONDUIT
NO. ATTKUBC38 (**US
NP. PATENT 9,263,864) ,
3/8" COPPER BASE
(UNIVERSAL MOUNT),
SECURE WITH ADHESIVE
1/2" X 12" COPPER AIR TERMINAL
PVC CABLE GUARD. SUPPORT
PER NEC REQUIREMENTS OR
EVERY 3'-0"
E200
AIR TERMINAL 'B'
NOT TO SCALE
E200
AIR TERMINAL 'C'
NOT TO SCALE
E200
AIR TERMINAL 'D'
NOT TO SCALE
E200
AIR TERMINAL 'E'
NOT TO SCALE
E200
AIR TERMINAL 'F'
NOT TO SCALE
E200
BEND RADIUS DETAIL
NOT TO SCALE
E200
4 TO 1 CONDUCTOR DETAIL
NOT TO SCALE
E200
EXTERIOR STEEL FRAME BONDING
NOT TO SCALE
E200
AIR TERMINAL 'A'
NOT TO SCALE
Robert S. Gras
No. EE7352
" M
IN
B E
LO
W
F
IN
IS
H
G R
A D
E
6' -0
" M
IN
CLASS I COPPER
MAIN CONDUCTOR
1 1/4, PVC CABLE GUARD,
SUPPORT PER NEC
REQUIREMENTS OR
EVERY 3'-0"
CLASS I COPPER
MAIN CONDUCTOR
PROVIDE PVC CONDUIT
FOR PROTECTION
MAINTAIN A RADIUS BEND OF 8"
MINIMUM AND AN ANGLE BEND
OF 90° OR GREATER (TYPICAL
FOR ALL CONDUCTOR BENDS)
THRU WALL PENETRATION
CONNECT TO GROUND ROD
THRU ROOF PENETRATION (TRIM RISER
AND SLEEVE AS NECESSARY SO AS
NOT TO EXCEED 9" ABOVE ROOF)
AIR TERMINAL 'A'
CLASS 1 COPPER LIGHTNING CONDUCTOR
(TYPICAL FOR ALL CONDUCTOR SHOWN)
GROUND BUILDING FLOOR
COPPER OR ALUMINUM, CLASS I
OR CLASS II LIGHTNING
PROTECTION CONDUCTOR
THRU-ROOF CONNECTOR
COPPER OR ALUMINUM, CLASS I
OR CLASS II LIGHTNING
PROTECTION CONDUCTOR
COPPER OR ALUMINUM, CLASS I
OR CLASS II LIGHTNING
PROTECTION CONDUCTOR
COPPER OR ALUMINUM, CLASS I
OR CLASS II LIGHTNING
PROTECTION CONDUCTOR
THRU-WALL CONNECTOR
EXOTHERMIC WELD
CABLE TO GROUND
ROD CONNECTION
3/4" X 10' COPPER
CLAD GROUND ROD
CLASS II BARE
COPPER CONDUCTOR
ALTERNATE COPPER
GROUND PLATE
BOND TO STRUCTURAL STEEL
BOND TO STRUCTURAL STEEL
E201
WALL SECTION
NOT TO SCALE
E201
GROUNDING ROD DETAIL
NOT TO SCALE
E201
PVC CABLE GUARD
NOT TO SCALE
E201
THRU-ROOF PENETRATION
NOT TO SCALE
E201
THRU-WALL PENETRATION
NOT TO SCALE
Robert S. Gras
No. EE7352
| G001 |
| E001 |
| E110 |
| E120 |
| E130 |
| E140 |
| E150 |
| E160 |
| E170 |
| E180 |
| E200 |
| E201 |