Atch 02- Nellis-Creech IFS appendix Fire Protection Req.pdf

PDF 85 KB Posted

Attached to
Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation Federal contract opportunity
Solicitation number
FA486119RA001
Issued by
Department of the Air Force Air Combat Command

About this file

This document outlines fire protection requirements and standards for facilities at Nellis and Creech Air Force Bases. It includes details on design, plans, specifications, and testing requirements for fire alarm, mass notification, and suppression systems. Key requirements include using Monaco or Hochiki fire alarm panels; separate signaling, notification and initiating circuits; dedicated circuits for SCIFs and SAPFs; location of manual pull stations and fire extinguishers; and testing by a third party. Related federal contract opportunity Nellis/Creech AFB Multiple Award Construction Contract solicits for construction services at the bases, requiring adherence to the fire protection standards and specifications in the requirements document.

Not Listed

View the file

Other files for this federal contract opportunity

Other files attached to Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation, newest first.
File Type Posted
Solicitation_Amendment_FA486119RA0010008_SF_30.pdf PDF
Atch_00-_MACC_Attachment_Index.pdf PDF
Solicitation_Conformed.pdf PDF
Atch_00-_MACC_Attachment_Index.pdf PDF
Atch_00-_MACC_Attachment_Index.pdf PDF
Atch_48-_App_D_RKMF_17-0097_Electrical_REVISED_8-9-19.pdf PDF
Atch_52_Bid_Schedule,_RKMF_17-0097.pdf PDF
Atch_55-_19RA001_Preproposal_Site_Visit_(Slides_and_Sign-In_Sheet).pdf PDF
Atch_53-_RKMF_17-0097_VCC_SOW_Dated_11_July_19.pdf PDF
Atch 11- USAF Integrated Cultural Resources Mgmt Plan.pdf PDF
Atch 04- Nellis-Creech IFS appendix Electrical Req.pdf PDF
Atch 01- MACC SOW.pdf PDF
Atch 35- WD NV190001 20180001.pdf PDF
Atch 49- App E RKMF 17-0097 Site Contours.JPG JPG image
Atch 30- Progress Schedule Template.xls XLS spreadsheet
Atch 54- VCC Site Plan 2018-10-02.jpg JPG image
Atch 29- Cost Estimate Template.xlsx XLSX spreadsheet
Atch 24- VEA CONNECTION CHARGE AGREEMENT.docx DOCX document
Atch 13- UR2 S Primary and Secondary Trenching Requirements.pdf PDF
Atch 53- RKMF 17-0097 VCC SOW 20181203.pdf PDF
Atch 34- BUILDER inventory sheet.xls XLS spreadsheet
Atch 12- UM1-6C 3-Phase Pad and Vault.PDF PDF
Atch 17- Bulletin 1728F-806 UG Main VEA standard.pdf PDF
Atch 15- UM33 200 Amp 3-Phase CJE 4 inch Conduit Placement Standards.pdf PDF
Atch 32- Schedule of Vaules Template.xlsx XLSX spreadsheet
Atch 25- NTTR Visit Request.pdf PDF
19RA001_MACC_Attch_25-34.zip ZIP file
19RA001_MACC_Attch_12-24.zip ZIP file
Atch 14- UM3-14 1-Phase CJE Conduit Placement Standards.pdf PDF
Atch 00- MACC Attachment Index.pdf PDF
Atch 05- Nellis-Creech IFS appendix Lighting Req.pdf PDF
Atch 23- UM48-2 Multi-Grounds.pdf PDF
Atch 28- AF Form 103, Base Civil Engineering Work Clearance Request.pdf PDF
Atch 38- WD NV190012 20180012.pdf PDF
Atch 37- WD NV190024 20180061.pdf PDF
Atch 36- WD NV190038 20180075.pdf PDF
Atch 47- App C RKMF 17-0097 Elevations.pdf PDF
Atch 41- Past Peformance Information Sheet.pdf PDF
Atch 33- AIS Form 2015.pdf PDF
Atch 43- Sample Client Authorization Letter.pdf PDF
Atch 48- App D RKMF 17-0097 Electrical.pdf PDF
Atch 27- Nuclear Gauge Request Form 2.docx DOCX document
19RA001_MACC_Attch_00-11.zip ZIP file
19RA001_MACC_Attch_00-11.zip ZIP file
Atch 46- App B RKMF 17-0097 Floor Plan.pdf PDF
Atch 40- Teaming List.pdf PDF
Atch 39- Quality Control Plan.pdf PDF
Atch 20- UM3-14 VEA Standards.pdf PDF
Atch 50- App F RKMF 17-0097 Site Utilities.JPG JPG image
Atch 22- UM33 VEA Standards.pdf PDF
Show all 50

Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NELLIS AND CREECH AFB

INSTALLATION FACILITIES STANDARDS (IFS)

FIRE PROTECTION REQUIREMENTS

22 JAN 2019

This document is an appendix to Nellis & Creech Air Force Bases IFS which is located here:

https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs

1. DESIGN:

A. All facility design and construction shall comply with UFC 3-600-01 (Fire Protection Engineering), UFC 4-021-01, UFGS 28-31-76, and current edition of all National Fire Protection Association (NFPA) codes and standards to include the requirements called for in this document. The Fire Protection Engineer of record (FPEOR) shall ensure that the design meets the requirements of UFC 3-600-01 or stricter requirements noted herein. The FPEOR shall review all shop drawings for approval and shall witness all operational tests for acceptance of the fire protection systems.

FPEOR shall be identified at the beginning of the project. As required, the FPEOR shall be available to respond to design review comments.

B. All projects shall include building code analysis, life safety code analysis and a water supply analysis in accordance with UFC 3-600-01.

C. Base-level projects that do not involve full A-E services, the above requirements for the FPEOR still apply. If detailed designed documents are not being provided, the FPEOR shall prepare at a minimum a building code, life safety code, and water supply analysis as applicable to the statement of work, specifications, and a narrative description (performance specification) of the required systems.

D. These requirements supersede all previous Nellis-Creech Air Force Base Fire Protection Standards.

Fire protection for all facilities shall follow these requirements.

E. These requirements are not all inclusive and any disputed items shall be decided by the Authority Having Jurisdiction (AHJ), the Air Combat Command (ACC) Fire Protection Engineer. Nellis- Creech Fire Emergency Services Flight (Fire Department) and the Engineering Flight (Base EE) share the responsibility as the local AHJ. Both flights are part of Base Civil Engineer (BCE) office (99th Civil Engineer Squadron).

2. PLANS:

A. CODE ANALYSES:

Life Safety Code analysis and Building Code analysis shall be included as separate plans following the format shown above. The designer shall ensure that below values are shown on each project design and the final as-built for each particular project.

BUILDING CODE ANALYSIS:

1) Occupancy classification https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs

2) Required (or allowed) and designed

a. Building area

b. Building height

c. Construction type

d. Exterior exposure protection

e. Height/area increases (provide calculations)

f. Interior fire rated occupancy separation

g. Internal fire area separations

LIFE SAFETY CODE ANALYSIS:

1) Occupancy classification

2) Occupant load factor(s) (with calculations)

3) Required (or allowed) and designed

a. Common path of travel

b. Dead-end corridor

c. Egress capacity

d. Exit discharge

e. Flame spread/smoke development ratings for interior finishes

f. Horizontal exits

g. Number of exits

h. Remoteness of exits

i. Separation of exits and exit access

j. Separation of hazardous areas

k. Travel distance

4) Total calculated load (per floor and total for building)

5) Location of fire walls

6) Location of extinguishers:

a. The design must show that all fire extinguisher cabinets are sized to support a 20-lb ABC Dry chemical fire extinguisher. Provide a recessed or semi-recessed fire extinguisher cabinet.

b. The design must show that a 10-lb ABC Dry chemical fire extinguisher is being supplied and installed.

c. Fire extinguisher will be mounted on a hook inside cabinet IAW NFPA 10.

7) All exit door(s), including those in SCIF areas, shall not take more than one physical action to exit (open door); only one action is allowed IAW NFPA, LSC 101.

B. CIVIL PLANS:

1) Civil drawings shall show all fire water mains to include positive identification of test fire hydrants (both pressure and flow hydrants). Plans shall show water main from the test point to the building riser.

2) Show all fire hydrants and control valves. Provide dry barrel fire hydrants meeting all requirements stated in UFC 3-600-01. Fire hydrants at hangars shall also meet requirements of UFC 4-211-01 Aircraft Maintenance Hangars (Section 3-6.3).

3) Roads, parking lots, and access drives shall comply with UFC 3-600-01 and NFPA 1 for accessibility to building by emergency vehicles. Coordinate design with fire department.

C. ARCHITECTURAL PLANS:

1) Architectural plans and Life Safety Code plans shall both show fire walls and partitions and architectural plans shall identify the UL number or other standard such as FM for fire rated assemblies. Additionally, these plans shall show the location of the fire extinguishers.

2) Door Schedule shall identify fire rating of all fire doors. Fire doors shall be coordinated with fire walls.

D. MECHANICAL PLANS:

1) Mechanical plans shall positively identify all fire and/or smoke dampers and provide a detail for installation. Smoke dampers shall include a smoke detector for activation of the damper. Fire dampers shall be shown to comply with NFPA 90A and smoke dampers shall comply with

NFPA 101.

2) Mechanical plans shall include smoke detectors on the control diagram. Smoke detectors shall not activate the building evacuation alarm system but shall report as an alarm to the fire department as a separate zone on the fire alarm panel.

3) Duct smoke detectors shall be 24V and resettable through the Fire Alarm Control Panel.

4) An electrical control schematic and wiring detail shall be included in the fire alarm drawing set for each fire damper. Fire dampers shall be designed as failsafe.

E. FIRE ALARM / MASS NOTIFICATION SYSTEM (MNS) / ELECTRICAL PLANS:

1) Plans shall show exit signs and emergency lights. Exit signs shall be RED in color. Exit sign batteries shall be located in air-conditioned rooms or the battery lives (minimum of 7 years) are to be rated for the temperature seen at non-air conditioned location (usually 135degF).

2) Switchgear shall show power for the fire alarm system as a separate breaker.

3) Fire Alarm and MNS panels shall be in a climate controlled (air conditioned) room.

4) Mark each breaker for each fire alarm box, NAC panel etc.

5) Use of MONACO MAAP-X panels (combines FACP, MNS, and the Monaco transceiver into one unit, are point to point compatible, and is an addressable system) is required for the following: a) all facilities with MNS (including trailers), b) all facilities with fire pumps, c) all facilities with VESDA system, d) all facilities larger than 20,000 square feet, and e) all dormitories. This applies for Nellis, Creech, Point Bravo, and all other NTTR facilities.

Creech and Point Bravo require the use of Monaco panels for all smaller facilities with a separate MONACO BTXM radio with a minimum of 16 zones or use of MAAP-X or similar. Use of Hochiki Firenet panels with a minimum of two signaling/indicating circuits and other Monaco panels for the FACP and with a separate MONACO BTXM radio with a minimum of 16 zones is permitted at Nellis AFB. Monaco panels or Hochiki Firenet panels are required for FACP due to base operations and maintenance requirements.

Generally, all buildings shall have their own fire alarm panel with an exception for associated fire pump building and small storage buildings. Use of dialup phone systems for communication between fire alarm panel and fire department dispatch is not permitted at Nellis, Creech, and Point Bravo. Frequency for fire alarm system at Creech AFB is 138.9750 MHZ. Monaco # -86 is assigned to Creech AFB. Frequency for the fire alarm system at Nellis AFB is 138.250 MHZ.

Monaco # -01 is assigned to Nellis AFB. System shall use combination speaker/strobes and the strobes shall be as specified in UFC 4-021-0. Clear strobes shall be used fire and amber strobes shall be used for MNS.

6) Signaling and indicating circuits shall use Class A unless otherwise noted below. Notification circuits shall use Class B unless otherwise noted below. Separate dedicated signaling or indicating dedicated circuits shall be used for the following:

A. Devices detecting Ansul or similar type of kitchen hood fire suppression units have tripped. If

Ansuls are electrically operated, they shall also detect loss of electrical power.

B. Hangar bay IR fire detection systems interfaces to fire panels.

C. Hangar bay foam type fire suppression controller interfaces to fire panels including loss of power to foam controller. This may be combined with item B only if located in the same room.

D. Interfaces to fire pump controllers.

E. Interfaces to VESDA type or similar early smoke detection systems used principally in server rooms and in raised floor applications.

F. The base may waive in some applications the requirement for Class A circuits to have separate source and return conduits. For example: connections to two fire pump controllers located in the same fire pump room will require only one conduit from the FACP location to the fire pump room where it will split into two conduits. In this application the return lines will have separate different colored wires (different from the normal source wire color code) from the last interface unit back to the FACP.

G. SCIFs and SAPFs: All indicating and/or signaling circuits going into SCIFs and/or SAPFs shall be dedicated to that SCIF and/or SAPF with direct home runs to FACP and shall be class B circuits. If the only signaling devices inside the secured area is NAC and MNS fault contacts located immediately upon entry, the EOL resistors will be located inside the MNS or NAC amplifier unit. Signaling or indicating circuits shall not use the SCIF and/or SAPF as a passageway to a non-secured area.

Separate dedicated notification circuits shall be used for the following:

A. Notification circuits feeding NAC and MNS panels located at the entrance to SCIF and SAPF areas shall be fed directly with home runs from the FACP and shall be class B.

B. Notification circuits feeding NAC and MNS panels in locations other than SCIF and SAPF areas shall be fed in one of two ways:

1) Shall be fed directly with home runs from the FACP unless they are immediately adjacent to each other in which case 1 set of home runs is required. Class B may be used.

2) May be directly fed with a class A circuits for multiple locations of NACs and MNSs from the FACP with no other types of notification devices installed on these circuits.

7) SCIF and SAPF rooms and areas:

A. Small SCIFs and SAPFs consisting of only one room with small storage room using only one combination strobe(s) and speaker located therein immediately (less than 2” to the strobe mounting boxes) on the conduit entrance to the room: If room is large enough to require more than one combination strobe and speaker, then a NAC and a MNS amplifier unit shall be installed immediately upon conduit entry along with the necessary battery box.

B. Large SCIFs and SAPFs consisting of more than one room shall require a NAC and a MNS amplifier unit installed immediately upon conduit entry along with the necessary battery box.

Notification circuits shall not use the SCIF and/or SAPF areas as a passageway to a non-secured area. Exterior speakers shall not be connected to any notification circuit within the SCIF or SAPF.

C. LOCs shall not be located inside SCIFs or SAPFs.

8) Multi-floor buildings shall have at a minimum separate dedicated signaling or indicating circuit and notification circuits for each floor regardless of the number of devices on each floor. Large numbers of signaling or indicating devices (50 or more, dormitories 20 suites or more) on a floor shall require use of multiple dedicated signaling or indicating circuits. Large numbers of notification devices on a floor may require the use of multiple dedicated strobe or speaker circuits.

Number of devices on a strobe circuit may be limited by the number of speakers on the associated speaker circuit.

9) All strobe amplifiers (aka remote power supplies) shall be labelled “NACxx” or “NACx” where xx or x is a sequential number for a facility starting 01(for 10 or more) or 1 (for 9 or less). Each NAC unit shall have a unique number. All speaker amplifiers shall be labelled “MNSxx” or “MNSx” where xx or x is a sequential number for a facility starting at 01 (for 10 or more) or 1 (for 9 or less). Each MNS unit shall have a unique number.

Outgoing strobe circuits from NACs shall be numbered as follows: ASxxy or CSxxy where xx or x is the NAC number and y is the outgoing circuit number from that NAC. AS refers to amber (MNS) strobes and CS refers to clear (Fire) strobes. Outgoing speaker circuits from MNSs shall be numbered as follows: Sxxy where xx or x is the MNS number and y is the speaker output circuit number from that MNS unit.

Speaker circuits shall follow the conduit layout of the strobe circuits (ie a given speaker circuit shall NOT be shared with more than one fire strobe circuit or one amber strobe circuit). MNS amplifier panels may use splitter card(s) provided that if a splitter output is open or shorted it shall not affect the other splitter outputs and if a splitter output is open or shorted, it shall signal a fault to the main FACP panel. Speaker circuits fed from main FACP panel shall be labeled Sx where x is the circuit number. Clear strobe circuits fed from main FACP panel shall be labeled CSx where x is the circuit number. Amber strobe circuits fed from main FACP panel shall be labeled ASx where x is the circuit number. Amber and Clear strobe circuit numbers shall not overlap.

10) Mandatory use of separate conduits for initiating or signaling circuits from notification circuits is required.

11) White colored wire shall not be used for any positive data or power wire as this is reserved for negative signal or power wire.

12) Strobe and speaker locations: All offices having a space for a visitor to stand in or a space for a chair for a visitor are considered to be two-man offices and will require the installation of strobes and speakers therein. All offices separated by walls from other rooms having STC45 or STC50 ratings shall have strobes and speakers installed therein. Walk-in closets and other storage spaces such that a door may be closed with a person inside shall have strobes and speakers installed.

Janitor closets large enough such that a door may be closed with a person inside shall have strobes and speakers installed. Mechanical rooms, utility rooms, electrical rooms, comm. rooms, and riser rooms shall have strobes and speakers installed if large enough for 2 or more persons to be present in the room.

13) Plans shall show all fire alarm and mass notification devices. Visual devices shall show the candela rating of each device. Speakers will show power output setting. As-built drawings shall be revised to show the actual conduit locations and locations of all junction boxes employed.

14) Riser diagram shall show all power connections, initiating devices, alarm devices and any interconnections of shutdowns such as AHUs or door releases and the room numbers for the location of all devices and the sequential number of the device on that circuit.

Separate drawing shall show all external connections to the FACP including all strobe, speaker, indicating, signaling lines and how connected to the FACP (class A or class B), batteries, antenna, 120v power connections, and any required circuit termination resistors. This drawing shall contain a listing of all I/O slots and the cards inserted therein and the unused slots shall be listed as spares, along with all dip switch settings set in the normal operating mode. This drawing shall be used as a maintenance drawing allowing a base technician to see if all proper connections are made to the FACP panel.

A similar drawing shall be required for each NAC panel and each MNS panel.

AHU shutdowns shall be arranged such that any EMCS (JCI) controller located in that unit will NOT lose control power, will be able to detect shutdown of the AHU, and transmit that status to the base EMCS master station. An electrical detail will show the details of interconnection of how the shutdown of each AHU or each door release is accomplished. If not known at time of construction, the necessary details shall be incorporated into the as-built drawings.

As-built drawings shall show on the singleline or riser diagram all 120v. power sources for the fire alarm system by panel name and circuit number. Electrical drawing as-builts shall show the 120v conduit runs from electrical panel to fire equipment panels.

15) Provide a matrix showing what action each device will initiate.

16) Fire department shall approve all fire alarm panel locations. Panels shall be accessible to the fire department when the building is not occupied.

17) Nellis-Creech AFB fire alarm reporting system is a Monaco D-21 radio transceiver communication system using an addressable panel. Monaco radio transceivers (BTX, BTXM, or a transceiver card installed in a MAAP-X panel) shall be used in all fire alarm/MNS systems. Connections to Fire Alarm Control Panel(s) (FACP) to BTXM or BTX shall be by a serial port or Data line using Monaco communications protocol. No keying relays shall be used between the FACP and Monaco radio. Work shall be IAW manufacturer’s specifications for Nellis-Creech AFB transmission system.

18) Provide transmitter zone schedule. A minimum of 16 Zones shall be supplied with the capability to expand to 32 or 64 depending on the size of the facility. This is not required where point to point reporting is used with a MAAP-X panel and the transceiver is installed inside the MAAP-X panel. When point to point reporting is used, trouble and supervisory items shall give individual messages allowing the fire department and the alarm shop to see the remote messages before arrival at the building. The Monaco D-21 system is a point to point reporting system. MAAP-X panels shall utilize point to point reporting instead of zone reporting.

19) Connect any and all wiring in fire alarm systems with LEVER NUTS. However the use of any splices is to be limited and must be preapproved by the local AHJ.

20) The last device installed shall have an engraved sign stating the value and location of the end of line resistor if not located at this device.

21) All “J” box covers for fire alarm system shall be painted "RED" IAW NFPA and all couplings painted RED.

22) On all false ceiling grids, the cross tees shall be marked with a RED dot indicating the location of fire 'J' boxes.

23) Manual fire pull stations shall be key reset only (no other type reset will be allowed). Manual fire pull stations shall NOT have glass rods. Fire Pull stations to be single action. Pull stations will be installed at all MAJOR exits from a facility.

24) 'T' tapping is generally not permitted. In special situations the local AHJ may give approval to do so or where required to do so in the statement of work generated by BCE office.

25) All fire panels, associated panels, and fire pull stations shall be keyed the same. #415A key is recommended.

26) Antenna shall have direct line of sight and be 3 ft. above edge of roof line.

27) Smoke detector over fire alarm panel shall be no higher than 2 ft.

28) Supply certifications of all Installers, Testers, Certifiers, Fire Protection Engineers and other persons involved in the installation of Fire Alarm, Fire Suppression systems, or any item connected to Fire Protection system.

29) All NAC panels shall be individually zoned with trouble and battery fault conditions with a visual monitor module appropriate for the system.

30) All wires shall be clearly identified and labeled.

31) The AHJ shall be notified after conduit is installed for visual inspection. No panels shall be installed without coordination of location(s).

32) All fire alarm and MNS notification system panels and accessories panels shall reset on their own after a power bump or electrical outage.

33) Gutter systems shall be installed above and in between all fire alarm panels. In finished areas, the gutter and panels shall be flush mounted/recessed. Panels will not be flush mounted in SCIF and SAPF areas.

34) All devices shall be addressable and duct detectors will be 24 volt, resettable through the fire alarm panel.

35) Circuits operating at nominal 24 volts DC shall use 20.4 (85% of nominal battery voltage) as the starting point for voltage drop calculations. Total voltage calculated at any device shall not be less than 16.8Vdc provided that all devices will operate at 16.8Vdc on battery. Battery calculations, voltage drop calculations, and speaker db loss calculations shall be included in the fire alarm drawings.

F. FIRE SUPPRESSION PLANS:

1) Plans shall show the hazard classification for each area.

2) Provide a chart showing the density, area of application and hose stream demand for each hazard classification. The data shall comply with most current UFC 3-600-01.

3) Provide a riser diagram for the sprinkler system. Test connection for the backflow preventer shall be included. Air Force uses “shotgun" risers.

4) The inspector's test connection shall be located at the most remote end of the system. Install a large splash block on the outside discharge head for inspector test if the area is not concrete.

5) All fire sprinkler systems shall have a PIV shut off valve unless otherwise approved by Fire Department.

6) Provide a final inspection and acceptance checklist with the Material Register for each project.

The FPEOR shall attend the final inspection for the Fire Protection System and sign/certify all documents confirming to the Government that the systems were installed to meet the required standards. During final acceptance testing a check list shall be provided by the contractor IAW NFPA and/or UFC standards prior to the final inspection.

a. Each checklist shall provide procedures to test all installed Fire Protection systems.

b. This checklist shall comply with the current edition of the NFPA 72 and shall incorporate the procedures to test all aspects of the Fire Protection System: Fire Alarms, Fire Suppression, Mass Notification, and other systems as applicable.

c. If the contractor installs the Fire Protection system different from that shown in the design, a revised final inspection and acceptance checklist shall be submitted for review, two weeks prior to the final acceptance for the system. All checklists shall be approved by the local AHJ. Aircraft maintenance hangar foam system checklists require approval by the Air Force Fire Protection Engineer and the local AHJ.

7) Post a laminated schematic drawing next to the FACP/MNS panel and clearly mark on the drawing the location of all fire 'J' boxes.

8) All tamper switches arms on OS&Y valve stems shall be in the groove of the valve stem for proper alignment.

9) Fire suppression system shall have an external electric bell to indicate water flow. Install bell near fire riser room. Wiring detail of bell shall be incorporated into the fire alarm drawings.

G. TESTING:

1) Specifications must clearly indicate the testing of the fire protection systems and the A/E shall develop a commissioning plan that indicates how each system will be tested and who will witness the testing for acceptance, IAW NFPA 3, current edition. The FPEOR shall be the lead for the commissioning plan and the plan shall be approved by contracting officer prior to testing.

The FPEOR shall write a commissioning letter stating that the systems are in full compliance with the plans and specifications.

2) All batteries for the Fire Protection System shall provide 72 hours of backup power followed by 15 minutes of alarm operation and must also have 60 minutes of operation immediately after loss of 120v power unless otherwise approved by local AHJ for lower backup power. Mandatory system tests: All systems installed shall be tested on the battery backup power supply for the rated time of backup power provided IAW NFPA 72 or the times listed above whichever is longer. All systems must still be functional after testing.

3) A THIRD PARTY shall be used to perform all testing of installed Fire Protection System.

The FPEOR can be used as the third party if no conflict of interest exists.

3. SPECIFICATIONS:

A. CIVIL

1) Verify all fire protection devices such as fire hydrants, control valves, etc. greater than 5 feet from building are included in the civil design specifications.

B. FIRE SUPPRESSION / FOAM SYSTEMS

1) All requirements in UFC 3-600-01, UFGS, and applicable Fire and Life Safety codes shall be met. Aircraft maintenance hangars shall meet requirements of UFC 4-211-01 (Section 3- 6).

2) Designer must include the loss from the test connection to the base of the riser.

3) All sprinkler piping shall be schedule 40 for dry pipe and pre-action. No dyno flow piping.

4) Where fire pump(s) is required and the base power is determined to be reliable (see UFC

3- 600-01 paragraph 3-6.4), use electric motor driven pumps operated by variable frequency drives (VFD). BCE office has determined that base power at Nellis AFB is reliable.

5) If power is not reliable, use electric motor driven pumps operated by variable frequency drives (VFD) and supply a generator for starting and operating the fire pumps. DO NOT use diesel engines with direct connected pumps.

6) Base personnel (BCE maintenance shop and fire department) shall be trained on the operation, testing and maintenance of the FACP and devices, with a minimum of 4 each 2 hours training sessions. Four sessions are required to ensure all personnel can attend training. This training will be separate from the testing of the systems.

7) Contractor shall train and certify base personnel on newly installed systems that are not already installed on base. All software or materials needed by base personnel for maintenance and programming said systems shall be supplied to the Government.

8) Foam vertical bladder tanks are not permitted in new installations. Vertical bladder tanks may only be allowed in existing facilities with approval by the ACC FPE. Tanks will be located such that the bladder can be replaced without moving the tank.

9) Atmospheric tanks with concentrate pumps are preferred on all foam solution systems as the bladder tanks are often ruptured due to improper filling or over pressurization.

10) Test headers shall be provided for a permanent method of flow testing proportioner(s).

11) Deluge valves listed and approved for use with foam concentrate will be used for automatic foam concentrate control. When abort (dead-man) switches are provided, flow control valves shall be used. Fire alarm manual pull stations shall be at least 5 feet from the foam manual discharge station. Foam release pull station box will be yellow.

12) Isolation control valves shall be full port ball type with operating handle that indicates the on/off position of the valve. Unit shall be socket weld or flanged type. Valve body and ball shall be of 316 stainless steel complying with ASTM A351.

13) Foam tanks shall be provided with spill control, sized to contain the tank capacity.

14) Foam concentrate piping shall be stainless steel. Piping shall have either flanged joints and fittings, rolled groove fittings or welded joints and fittings. If welded joints and fittings are used, then flanged joints shall be provided for equipment maintenance.

15) The foam discharge panel shall be located in a climate controlled space in accordance with

NFPA 72 and per the manufacturer's recommendations.

C. UNIFIED FACILITIES GUIDE SPECIFICATION (UFGS SECTION 28 31 76):

1) Recommended practices stated in the manufacturer’s literature or documentation shall be considered as mandatory requirements.

2) Paint junction boxes and surface metal raceways RED in unfinished areas.

3) Contractor shall provide training records for all personnel involved with installation of fire protection system elements.

4) Control units shall be located in a climate controlled (air conditioned) space where the ambient temperature is maintained between 60 and 85degreesF.

5) Install control panel components in cabinets adequately sized to accommodate all components and to allow ample gutter space for interconnection of panels and field wiring.

6) Provide a recessed KNOX box (rapid entry system) in exterior wall near facility’s main entrance door. System shall be supervised and code is ML-03-0038-07-10.

7) On complex facilities provide the annunciator at a location IAW NFPA 72. Generally, annunciators shall be provided at all main entrances. If FACP is mounted near a main entrance, annunciators shall be provided at the other main entrances.

8) Include a color code schedule for all fire related wiring.

9) Contact the Fire Department or BCE office to determine what action is appropriate for the salvaging of existing fire alarm equipment. BTXs and BTXMs shall be provided to the BCE Alarm Shop.

10) New system transmitter shall be activated shortly before Pre-Final inspection.

11) Testing procedures shall be submitted NLT 30 days before testing and shall be signed by

Fire Protection Engineer of Record.

END OF FIRE PROTECTION REQUIREMENTS

2. PLANS:
3. SPECIFICATIONS:

File details come from the government source that posted it. Updated .