Install Textile Brakes/BAK 15, F.7050 JBLE - Langley

25 August 2017

JBLE - Langley Contract Number: FA4890-11-D0003-F352 Project Number: MUHJ 10-4214 Project Title: Install Textile Brakes/BAK 15, F.7050

100% Design Submittal Manufacturer Product Cut Sheets

25 August 2017

Prepared for:

Department of the Air Force JBLE – Langley

Prepared by:

URS Group, Inc.

440 Monticello Avenue, Suite 1500 Norfolk, VA 23510 www.urscorp.com

Department of the Air Force 633 Civil Engineering Squadron 37 Sweeney Boulevard Langley AFB, VA 23665-2107

THIS PAGE INTENTIONALLY LEFT BLANK.

Table of Contents

A. Electrical Manufacturer Product Cut Sheets

Install Textile Brakes/BAK 15, F.7050 JBLE - LANGLEY

Langley AFB

A. Electrical Manufacturer Product Cut Sheets

Install Textile Brakes/BAK 15, F.7050 JBLE - LANGLEY

C - 20

APPROACH LIGHTING

2029 Rev. O I Manual No. 96A0293

IAML

Incandescent In-pavement ALSF and MALSR Approach Light

STYLE 2 HIGH-INTENSITY/MEDIUM-INTENSITY

Compliance with Standards FAA: ALSF ETL Verifi ed to FAA-E-2952 (Detail Specifi cation for Approach Light, Chemical Resistant, High Intensity, Semi-fl ush Steady Burning) MALSR ETL Verifi ed to FAA-E-2968 (Detail Specifi cation for Semi-fl ush Approach Light Units for Medium Intensity Approach Lighting System with Runway Alignment Indicator Lights)

Uses

• ALSF high-intensity approach centerline, crossbar, and side row barrettes in white, green, and red

• MALSR medium-intensity approach in white and threshold in green

Features

• FAA Style 2–Low protrusion above ground of ≤0.50 inch reduces vibrations caused by aircraft landing gear in both the light fi xture and the landing gear, increasing lamp life

• Provides numerous advantages– including lower weight, easier maintenance, and lower life cycle cost–than older style fi xtures

• Designed and built with simplicity and ease of maintenance in mind

• Light channel in front of prism windows protects prisms from damage and prevents rubber buildup thereby maintaining opti-mal light output

• Low-energy/long-life halogen lamps are 105 W (3 per fi xture) with a rated life of 1,000 hours at 6.6 A for ALSF applications.

For MALSR green threshold applications, the 62 W lamp (3 per fi xture) has a rated life of 1,000 hours at 6.6 A.

• For MALSR white approach applications, the 105 W lamp (1 per fi xture) has a rated life of 1,000 hours at 6.6 A. This fi xture meets the photometric requirements per FAA-E-2968 that pre-vioulsy used an L-850B 200 W fi xture. Provides a 48% reduction in power consumption and double the lamp life.

• Uses latest state-of-the-art in-pavement fi xture technology in order to retrofi t older FAA-E-2491, 20 A, 500 W ALSF fi xtures.

Provides a 37% reduction in power consumption and double the lamp life.

• Fixture uses aluminum alloy cover and inner cover, stainless steel hardware, and aluminum alloy and stainless steel optical assembly

• Includes a UL 467 rated ground lug, which accepts an AWG 6 earth ground wire

Optional Snow Plow Ring Depending on installation method and snow plowing technique used, a snow plow ring may be necessary. Snow plow rings are available for either standard or stainless steel adjustable Size B L-868 cans. Contact the ADB Sales Department for additional details.

ALSF Ordering Code 44A6148- 000 Color 1 = White (Style A) 2 = Green (Style B) 3 = Red (Style C)

Notes

• A Shorting Device is also available. If any lamp opens, the shorting device places a short on the secondary of the isolation transformer. This allows certain monitoring systems to detect a lamp out. The shorting device ordering code is 44A6143.

• To retrofi t into older FAA-E-2491 applications, a fl ange ring is required. The fl ange ring ordering code is 128A145-SS-G.

MALSR Green Ordering Code 44A6440-1000 Notes

• For FAA-E-2968 MALSR system, Style II, unidirectional green applications, this fi xture uses three 62 W lamps and is photometrically equivalent to the older style 200 W L-850E fi xtures that were used in this application. FAA-E-2968 MALSR applications are not toed.

• Encapsulated (FAA Style) isolation transformers are available for voltage-driven, medium-intensity approach lighting applications. For three 62 W lamp applications, a 186 W, 240 VAC to 28.2 VAC transformer is used (Part No. 35C0096).

MALSR White Ordering Code 44A6440-2000 Notes

• For FAA-E-2968 MALSR medium-intensity system, Style I, unidirectional white applications, this fi xture uses one 105 W lamp and is photometrically equivalent to the older style 200 W L-850B fi xtures that were used in this application.

FAA-E-2968 MALSR applications are not toed.

• Encapsulated (FAA Style) isolation transformers are available for voltage-driven, medium-intensity approach lighting applications. For 105 W, 240 VAC to 15.9 VAC applications, use transformer Part No. 35C0095.

ALSF White Shown

Product specifi cations may be subject to change, and specifi cations listed here are not binding.

Confi rm current specifi cations at time of order.

C - 21

ADB Airfi eld Solutions Leuvensesteenweg 585 B-1930 Zaventem Belgium

Telephone: +32 (0)2 722.17.11 www.adb-air.com

ADB Airfi eld Solutions, LLC 977 Gahanna Parkway Columbus, OH 43230

USA

Telephone: +1 614.861.1304 +1 800.545.4157

© ADB Airfi eld Solutions All rights reserved

2029 Rev. O I Manual No. 96A0293

APPROACH LIGHTING IAML I In-pavement ALSF & MALSR Approach Light

Inside View

1. High tensile strength screw with washer

2. Aluminum alloy cover

3. O-ring seal

4. Prism with retainer and gaskets

5. Cold mirror prefocus halogen lamp 105W - 6.6A

6. Optical assembly

7. Terminal block

8. Die cast aluminum inner cover

9. Wire clamp with grommets

10. FAA L-823 two-pole plug molded on heat-resistant wires

11. Pressure relief and test plug

12. Heat-resistant wire

Spare Components Description Part No.

Cable assembly, series jumper 44A5955 Cable clamp 4071.50.090 Cord set, L-823 73A0133-35 Cord set grommet 63A1014 Cord set terminal, female 6111.87.140 Filter spring clip 4071.50.160 Lamp retainer spring 4071.58.510 O-ring, pressure release screw 63B0267-011 O-ring, top cover 7080.90.710 Pressure release screw 60A2602 Prism clamp 4071.50.360 Prism gasket sleeve 4071.50.030 Prism keeper plate 4071.50.052 Seal, prism keeper plate 4071.50.041 Terminal block assembly w/o fi lm disc cutout 44A6112-1

ALSF Only Spare Components Description Part No.

Lamp, 105 W, 6.6 A 2990.40.900 Lamp holder assembly 1411.22.002 Lamp holder, left 44A6192-1 Lamp holder, right 44A6192-2 Prism 1428.00.300 Prism, green 1428.00.280 Prism, red 1428.00.270

MALSR Only Spare Components Description Part No.

Filter, MALSR green 63A0963-1 Lamp, 62 W, 6.6 A 48A0386 Lamp, 105 W, 6.6 A 2990.40.900 Lamp holder assembly 1411.22.001 Prism 63A0993-3

Packaging In cardboard box: 7 x 13 x 13 in (17.8 x 33 x 33 cm)

Weight with packing: 20 lb (9.07 kg)

Weight without packing: 17 lb (7.71 kg)

K - 2

INSTALLATION & MOUNTING

2012 Rev. L I No Manual

Light Bases

Compliance with Standards FAA: L-867 & L-868 AC 150/5345-42 (Current Edition)

Uses

FAA L-867 Applications subject to occasional light vehicular loads but no aircraft or other heavy vehicular loads. Some product applications are:

• Elevated Lights

• Navaids such as Precision Approach Path

Indicators (PAPI), Runway End Identifi er Lights (REIL), and ALSF/MALSR Approach Systems

• Signs

• Junction/Splice Box

FAA L-868 Applications subject to aircraft and other heavy vehicular loads. Some product applications are:

• Runway In-pavement Lights

• Taxiway In-pavement Lights

• Junction/Splice Box

Features

• One- and two-piece confi gurations

• Extensions and spacers available

• Manufactured in the USA by ETL-Certifi ed suppliers

• Supplied with 2-2” grommeted or threaded hub openings at 0-180° (standard). Optional locations and sizes available.

• All bases provided with an internal and external ground strap

• One copper ground lug kit provided with each base (standard).

A second ground lug kit can be provided as an option.

• Optional drain hole or hub in user-specifi ed sizes

• Standard bases provided as Class IA, galvanized steel unless otherwise specifi ed

• Optional Class IB available in stainless steel or internal epoxy coating. See ordering code for options.

Optional Replaceable Threaded Inserts Optional RTI (replaceable threaded insert) system facilitates:

• Replacement of failed threaded fi xture-mounting bolt holes

• Replacement of stripped, sheared, cross-threaded, frozen fi xture-mounting bolts

• Does not require changing the azimuth location of the base bolt circle

• Accommodates standard, non proprietary spacer rings and fl ange rings (with/without dam rings)

Optional Replaceable Threaded Inserts (Continued)

• Kit part numbers to add RTI to L-867/L-868 bases:

- L-867 Base – L867RTI06 (set of six inserts)

- L-868 Base – L868RTI12 (set of twelve inserts)

L-867 Light Base Notes

• Tapped holes in top fl ange rings are located on centerline of couplings. Tolerance: ±0.1875 inch (0.47 cm).

• Light bases available with either 2-inch (5.08 cm) NPT hub or 2-inch (5.08 cm) grommet openings. Couplings located 180° apart. Tolerance: ±1°.

• Threads inside couplings are protected with L.D.P.E. plugs

• All light bases provided with an Exterior Grade CC plywood shipping cover that is 0.5-inch (1.27 cm) thick grade CC with 0.4375-inch (1.11 cm) diameter bolt holes

• Six 3/8-inch-16 x 1-inch stainless steel machine screws secure the plywood shipping cover to the light base

• Optional second ground lug kit for grounding provision and/or drain coupling or weep hole must be specifi ed when ordering

• Finish is hot dip galvanized per ASTM A123/A123M-02 and A153 or material is 304 stainless steel

• Standard lengths for the 12-inch (30.48 cm) diameter light base are 20 inches (50.8 cm) and 24 inches (60.96 cm) with a tolerance of ±0.25 inch. Standard lengths for the 16-inch (40.64

cm) diameter light base are 20 inches (50.80 cm) and 24 inches (60.96 cm) with a tolerance of ±0.25 inch. Standard lengths for the 24-inch (60.96 cm) diameter light base are 20 inches (50.80

cm) and 24 inches (60.96 cm) with a tolerance of ±0.25 inch.

Custom heights available.

• Adjustable L-867 telescoping bases available. Please contact the ADB Sales Department for details.

Dimensions - L-867 Inches

Nom. Dia. “A” “B” “C” “D”

12.0 13.500 10.250 12.250 9.250

16.0 17.375 14.250 16.250 12.375

24.0 24.000 21.500 22.500 20.000

Centimeters

Nom. Dia. “A” “B” “C” “D”

30.5 34.290 26.035 31.115 23.495

40.6 44.133 36.195 41.275 31.433

61.0 60.960 54.610 57.150 50.800

L-868 Replaceable Insert

K - 3

INSTALLATION & MOUNTING LIGHT BASES

2012 Rev. L I No Manual

L-868 Light Base Notes

• Light bases available with either 2-inch (5.08 cm) NPT hub or

2-inch (5.08 cm) grommeted openings. Couplings or grommeted openings located 180° apart. Tolerance: ±1°

• Threads inside hubs are protected with L.D.P.E. plugs

• All light bases are provided with a nylon (standard) or plywood (optional) shipping cover:

8-in (20.3 cm) Nom. O.D.: 8.5-in dia. x 0.750-in thick (21.590 cm x 1.905 cm) 12-in (30.5 cm) Nom. O.D.: 12.5-in dia. x 0.750-in thick (31.75 cm x 1.905 cm) 15-in (38.1 cm) Nom. O.D.: 17.750-in dia. x 1.25-in thick (45.085 cm x 3.175 cm)

• Six 3/8-inch -16 x 1-inch stainless steel machine screws secure the plywood shipping cover to the light base

• Finish is hot dip galvanized per ASTM A123/A123M-02 and A153 or material is 304 stainless steel

• Optional Equipment – Second ground lug kit for grounding provision, drain coupling or opening. Anti-rotation bars must be specifi ed when ordering.

Typical L-868 - All dimensions shown in inches

Typical L-867D - All dimensions shown in inches

Dimensions - L-868 Inches

Nom. Dia. “A” “B” “C” “E” “F”

8.0 8.5000 7.250 6.500 9.000 10.000

12.0 12.500 11.25 10.000 13.000 14.000

15.0 15.500 14.25 13.000 16.000 17.000

Centimeters

Nom. Dia. “A” “B” “C” “E” “F”

25.4 21.590 18.415 16.510 22.860 25.400

30.5 31.750 28.575 25.400 33.020 35.560

38.1 39.370 36.195 33.020 40.640 43.180

Base Options Description Part No.

(4) side-mounted, anti-rotation fi ns in 90° pattern. ANTI-FIN Typically used with L-868 load bearing bases.

(6) bottom-mounted, anti-rotation hooks/bars in ANTI-HOOK 60° pattern. Typically used with shallow L-868 load bearing bases.

Copper Ground Lug Kit. (Each base supplied w/one). 0919

2012 Rev. L I No ManualK - 4

L-867 Base Plate and Gasket Notes

• Gasket suitable for locations where heat is not present, such as elevated edge lights, edge light extensions, transformer boxes, or junction boxes

• Base plate fi nish is oxide primer and aviation yellow enamel

• Base plate individually packed with neoprene gasket, steel cable clamp and screws for securing L-823 connector, and as-sembly instructions

• High-strength 1832RGL base plate is mandatory for FAA L-804 applications and should be used for ICAO applications.

L-867 Base Plate - All dimensions shown in inches

Dimensions - Base Plate

Inches

Nom. Dia. “A” “B” “C” “D”

12 12.000 10.250 7.875 0.625

16 16.000 14.250 11.125 0.750

Centimeters

Nom. Dia. “A” “B” “C” “D”

30.5 30.48 26.035 20.002 1.588

40.7 40.65 36.195 28.258 1.905

Ordering Code FAA Type & Size 867B = 12” diameter 867BT = Telescoping, 12” diameter 867D = 16” diameter 867DT = Telescoping, 16” diameter 867DD = 16” diameter with 0.5” dam 867E = 24” diameter 868A = 8” diameter 868AB = Bottom section, 8” diameter 868B = 12” diameter 868BB = Bottom section, 12” diameter 868C = 15” diameter 868CB = Bottom section, 15” diameter

Height 20 = 20 inches overall height 24 = 24 inches overall height XX = Customer specifi ed in inches

Type of Opening B = Mixed type and/or size1 C = 2-inch Coupling F = 2-inch Flex (Grommet) G = 3-inch Flex H = 3-inch Coupling S = 0.75-inch Coupling T = 0.75-inch Flex

Opening Quantity & Location 1 = One opening at 0°3

2 = Two openings at 0°, 180° 3 = Three openings at 0°, 90°, 180° 4 = Four openings at 0°, 90°, 180°, 270° 5 = Five openings at 0°, 0°, 90°, 180°, 180° 6 = Six openings - customer specifi ed 9 = Two openings at 0°, 90°3

A = Three 2” fl ex at 0°, 90°, 180°, one 2” coupling at 270°2

B = One 2” fl ex at 0°; one 3” fl ex at 180°2 C = One 2” coupling at 0°; one 3” coupling at 180°2

Drain Type C = Coupling F = Flex (Grommet) H = Hole N = None

Drain Size 0 = None 1 = 1 inch 2 = 2 inch 3 = 0.75 inch 4 = 0.5 inch 5 = 0.5 inch offset, 3.5 inches from center 6 = 0.75 inch offset, 3.5 inches from center 7 = 1 inch offset, 3.5 inches from center

Class IB or RWSL Options SS = Stainless steel PA = Potassium acetate resistant (PAR), internal coating;

external is galvanized 01 = With 48” 1/0 bare copper earth ground wire Z0 = RWSL copper clamp (PN AGNDSSASSY0_3125) w/out earth ground wire Z1 = RWSL copper clamp with externally attached 48” 1/0 bare copper earth ground wire

Notes 1 Only use with options A, B or C under Opening Qty & Location 2 Only use with option B under Type of Opening

L-867 Base Plate Ordering Code Base Plate 19 = 12 in, L-867B 29 = 16 in, L-867D

Thread Size 32 = 2 in TPI 35 = 1.5 in - 12 TPI

Material n/a = None G = With ground lug

Note: L-867 Base Plate includes gasket. See bullet 3 above.

Notes (Continued) 3 Base must have opening at 0° and 180° to allow for draining of the galvanizing materials. A solid grommet will be installed at 180°.

K- 5

Neoprene Gasket Ordering Code 52 Base Plate 20 = 12 in, L-867B 60 = 16 in, L-867D 70 = 24 in, L-867E

2012 Rev. L I No Manual

L-867 Base Plate and Gasket (Continued)

L-867 / L-868 Blank Steel Cover Notes

• “T” = thickness in sixteenths of an inch. Specify thickness when ordering.

• 7/16-inch (1.113 cm) diameter bolt holes have 1-1/8-inch (2.858

cm) diameter counter bore when cover thickness is 0.50 inch (1.27 cm) or greater

• Finish is hot dip galvanized per ASTM A123/A123M-02 and A153

• Blank steel covers do not include bolts or gaskets Blank Steel Cover - All dimensions shown in inches

Dimensions - L-867 / L-868 Blank Steel Cover

Inches

Dia.

Base

L-867

L-867

L-867

L-868

L-868

L-868

“X” O.D. 13.500 17.375 24.000 8.000 12.000 15.000

“Y” O.D. 10.250 14.250 21.500 7.250 11.250 14.250

“T” (Typ.) 0.375 0.375 0.500 0.750 0.750 1.250

Dimensions – Centimeters

Dia.

Base

30.5 L-867

40.6 L-867

L-867

20.3 L-868

30.5 L-868

38.1 L-868

“X” O.D. 34.290 44.133 60.960 20.320 30.480 38.100

“Y” O.D. 26.035 36.195 54.610 18.415 28.575 36.195

“T” (Typ.) 0.953 0.953 0.953 1.905 1.905 3.175

Steel Cover Ordering Code 000- - Diameter 1 = 13-1/2 in, L-867B 2 = 17-3/8 in, L-867D 4 = 12 in, L-868B 5 = 15 in, L-868C 7 = 24 in, L-867E 8 = 8 in, L-868A

Thickness 4 = 1/4 in (L-867B only) 6 = 3/8 in 8 = 1/2 in 10 = 5/8 in 12 = 3/4 in 14 = 7/8 in 16 = 1 in 18 = 1-1/8 in 20 = 1-1/4 in

Material (n/a) = Galvanized SS = Sta inless Steel PA = PAR Coated (Class 1B option)

Dimensions - Neoprene Gasket

Inches

Nom. Dia. “A” “B” “C”

12 11.938 10.250 9.312

16 15.938 14.250 12.438

24 23.750 21.500 20.000

Centimeters

Nom. Dia. “A” “B” “C”

30.5 30.232 26.035 23.652

40.7 40.483 36.195 31.593

60.96 60.325 54.610 50.800

Neoprene Gasket - All dimensions shown in inches

1832RGL Base Plate - All dimensions shown in inches

K - 6

Product specifi cations may be subject to change, and specifi cations listed here are not binding.

Confi rm current specifi cations at time of order.

ADB Airfi eld Solutions Leuvensesteenweg 585 B-1930 Zaventem Belgium

Telephone: +32 (0)2 722.17.11 www.adb-air.com

ADB Airfi eld Solutions, LLC 977 Gahanna Parkway Columbus, OH 43230

USA

Telephone: +1 614.861.1304 +1 800.545.4157

© ADB Airfi eld Solutions All rights reserved

INSTALLATION & MOUNTING LIGHT BASES

2012 Rev. L I No Manual

L-868 Flange Ring with Pavement Ring Notes

• “T” = thickness in sixteenths of an inch. Minimum thickness is 0.375 inch (0.953 cm) and maximum thickness is 0.75 inch (1.905 cm). Specify when ordering.

• Finish is hot dip galvanized per ASTM A123/A123M-02 and A153 for fl ange ring

• Six 3/8-16-inch x “T”-inch + 11/4-inch long stainless steel bolts.

3/8-inch locking washers and O-ring gasket shipped with fl ange ring. If fl ange ring is to be stacked over spacer ring, please consult ADB Airfi eld Solutions for a bolt chart to obtain the ap-propriate bolt length and ordering information.

Notes

• Nylon composite base plate designed for use in highly corrosive environments, such as coastal areas with high salt concentra-tions

• UV protectant and color are an integral part of nylon composite

• Base plate has a 12-inch diameter with six 7/16” diameter holes equally spaced on 10.25” bolt circle

• Base plate individually packed with:

- Neoprene gasket

- (6) 3/8” stainless steel washers

- One copper ground lug

- Steel cable clamp and screws for securing L-823 connector

- Assembly instructions

• Aluminum center hub and aluminum inserts in bolt holes

Ordering Code 127B015P

L-867 1.5-inch Nylon Composite Base Plate

Flange Ring with Pavement Ring All dimensions shown in inches

Dimensions - Flange Ring with Pavement Ring

Inches

Nom. Dia. “A” “B” “C” “H”

8” 8.160 7.250 6.500 6.645

12” 12.160 11.250 10.000 10.145

15” 15.160 14.250 13.000 13.145

Centimeters

Nom. Dia. “A” “B” “C” “H”

20.3 20.726 18.415 16.510 16.878

30.5 30.798 28.575 25.400 25.768

38.1 38.506 36.195 33.020 3 .388

Flange Ring Ordering Code 02- Y- Diameter 08 = 8 in 54 = 12 in 55 = 15 in

Thickness 4 = 1/4 in 6 = 3/8 in 8 = 1/2 in 12 = 3/4 in

Material (n/a) = Galvanized SS = Stainless Steel PA = PAR Coated (Class 1B option)

Okoguard is Okonite’s registered trade name for its exclusive medium voltage grade ethyl-ene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics.

Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance for long, prob-lem free service.

The Okolon TS-CPE jacket on this cable is a vulcanized chlorinated polyethylene based compound which is mechanically rugged, flame, and oil resistant.

Okoguard-Okolon TS-CPE cables are heavy duty nonshielded cables designed for use at up to 5kV in wet or dry airport lighting appli-cations.

Okoguard-Okolon TS-CPE nonshielded air-port lighting cables are recommended for use in series lighting circuits for runways and control systems. Cables can be installed in metallic or non-metallic conduit, directly bur-ied or aerial application.

Meets or exceeds the requirements of FAA Advisory Circular AC 150/5345-7F.

Annealed uncoated copper compact Class B stranded per ASTM B-496.

Extruded semiconduct-ing EPR strand screen. Meets or exceeds electrical and physical requirements of

ICEA S-96-659/NEMA WC71.

Meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71. Insulation thick-ness per Table 4-3 for wet or dry applications.

Meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71 for chlorinated polyethylene jackets.

• Resistant to runway and wing de-icers

• 90°C Continuous Rating, 130°C Emergency Overload Rating, 250°C Short Circuit Rating

• Exceptional resistance to surface tracking

• Superior Flexibility

• Constructed for “wet” location applications

• Excellent corona resistance

• Stress cones not required

• Resistant to most oils, acids, and alkalies

*Applications governed by the National Electrical Code limit non-shielded cable to 2.4kV

Okoguard®-Okolon® TS-CPE 5kV Airport Lighting Cable*

One Okopact (Compact Stranded) Copper Conductor/90°C Rating Wet or Dry

Uncoated, Okopact (Compact Stranded) Copper Conductor Strand Screen-Extruded Semiconducting EPR Insulation-Okoguard EPR Jacket-Okolon TS-CPE

� 114-24-2213 � 114-24-2217

8 8.4 6 13.3

125 3.18 125 3.18

80 2.03 80 2.03

0.60 15.1

0.63 16.0

� Available from our Customer Service Centers.

are available.

E/14080606 THE OKONITE COMPANY

Ramsey, New Jersey 07446

A

B

C

D

Bare Copper Wire and Cable

Bare Copper Conductor. Solid and Stranded .

APPLICATIONS

Solid and stranded (classes AA and A) bare copper are suitable for overhead transmission and distribution applications.

Stranded conductor of greater flexibility (classes B and C) are suitable for uninsulated hook up, jumpers, and grounds in electrical construction. Soft Drawn copper is unilay construction.

SPECIFICATIONS

Southwire's bare copper wire and cable meets or exceeds the following ASTM specifications:

• B-1 Hard-Drawn Copper Wire.

• B-2 Medium-Hard Copper Wire.

• B-3 Soft or Annealed Copper Wire.

• B-8 Concentric-Lay-Stranded Hard, Medium-Hard or Soft Copper Conductor.

• B-33 Tinned Conductors

• B-787 19 Wire Combination Unilay-Stranded Soft copper wire.

CONSTRUCTION

Bare copper, solid or stranded. Available in tempers hard, medium-hard, or soft. Stranded conductors are concentrically stranded in hard and medium-hard tempers and are Combination Unilay stranded in the soft-drawn temper.

Thu Mar 21 11:12:22 EDT 2013 Page 1 of 3

Size

(AWG)

Weight (lbs/1000 ft)

Diameter (mils)

Circular Mil Area (mils)

Hard Drawn Medium-Hard Drawn Soft-Drawn (Annealed) Allowable Ampacity+

Rated Strength>

(lbs)

DC

Resistance (ohms/1000

ft) @20°C

Rated Strength

(lbs)

DC

Resistance (ohms/1000

ft) @20°C

Rated Strength

(lbs)

DC

Resistance (ohms/1000

ft) @20°C

SOLID

14 12.4 64.1 4110 213.5 2.626 166.6 2.613 124.2 2.525 --

13 15.7 72 5180 268.0 2.083 208.8 2.072 156.6 2.003 --

12 19.8 80.8 6530 336.9 1.652 261.2 1.643 197.5 1.588 --

11 24.9 90.7 8230 422.9 1.310 327.6 1.303 249.0 1.260 --

10 31.4 101.9 10380 529.2 1.039 410.4 1.033 314.0 .999 --

9 39.6 114.4 13090 661.2 .824 514.2 .820 380.5 .792 --

8 50 128.5 16510 826.0 .653 643.9 .650 479.8 .628 95

7 63 144.3 20820 1030.0 .518 806.6 .515 605.0 .498 105

6 79.4 162 26240 1280.0 .411 1010.0 .409 762.9 .395 125

5 100.2 181.9 33090 1591.0 .326 1265.0 .324 961.9 .313 145

4 126.3 204.3 41740 1970.0 .258 1584.0 .257 1213.0 .249 170

3 159.3 229.4 52620 2439.0 .205 1984.0 .204 1530.0 .197 195

2 200.9 257.6 66360 3003.0 .163 2450.0 .162 1929.0 .156 225

1 253.3 289.3 83690 3688.0 .129 3024.0 .128 2432.0 .124 260

+Ampacity based on 75°C conductor temperature; 25°C ambient temperature; 2 ft./sec. wind in sun.

Thu Mar 21 11:12:22 EDT 2013 Page 2 of 3

Size

(AWG)

Stranding Stranding Class

Weight (lbs/1000 ft)

Diameter (mils) Hard Drawn Medium-Hard Drawn Soft-Drawn (Annealed) Allowable Ampacity+

Individual Wires

Complete Conductor

Rated Strength

(lbs)

DC

Resistance (ohms/1000

ft) @20°C

Rated Strength

(lbs)

DC

Resistance (ohms/1000

ft) @20°C

Rated Strength

(lbs)

DC

Resistance (ohms/1000

ft) @20°C

STRANDED

8 7 B 51 49 146 777 .6663 610 .6629 499 .6408 95

6 7 B 81 61 184 1228 .4191 959 .4169 794 .4030 130

4 7 A, B 128.9 77 232 1938 .2636 1505 .2622 1320 .2534 170

3 7 A, B 162.5 87 260 2433 .2090 1885 .2079 1670 .2010 200

2 7 A, B 204.9 97 292 3050 .1660 2360 .1650 2110 .1578 230

1 7 A 258.4 109 328 3801 .1316 2955 .1309 2552 .1252 265

1/0 7 A, AA 326.1 123 368 4752 .1042 3705 .1037 3221 .1002 310

2/0 7 A, AA 410.9 138 414 5926 .08267 4640 .08224 4062 .07949 355

2/0 19 B 410.9 84 418 6690 .08267 4765 .08224 4024 .07949 355

3/0 7 A, AA 518.1 155 464 7366 .06556 5812 .06522 5118 .06304 410

4/0 7 A, AA 653.3 174 522 9154 .05199 7278 .05172 6459 .04999 480

4/0 19 B 653.3 106 528 9617 .05199 7479 .05172 6453 .04999 480

250 19 A 771.9 115 574 11360 .04400 8836 .04378 7627 .04231 530

250 37 B 771.9 82 575 11600 .04400 8952 .04378 7940 .04231 530

300 19 A 926.2 126 628 13510 .03667 10530 .03648 9160 .03526 590

350 19 A 1080.6 136 679 15590 .03143 12200 .03127 10680 .03022 650

500 37 A, B 1543.8 116 814 22510 .02200 17550 .02189 15240 .02116 810

600 37 A, AA 1852.5 127 891 27020 .01834 21060 .01825 18300 .01763 910

750 61 A, B 2315.6 111 998 34090 .01467 26510 .01459 22890 .01410 1040

1000 61 A, B 3087.5 128 1152 45030 .01100 35100 .01094 30500 .01058 1240

+Ampacity based on 75°C conductor temperature; 25°C ambient temperature; 2 ft./sec. wind in sun.

Thu Mar 21 11:12:22 EDT 2013 Page 3 of 3

Eaton’s Cooper Power Systems manufactures a complete line of single-phase pad-mounted distribution transformers. They are available in standard ratings and configurations or can be customized to meet specific needs.

Single-phase transformers are available as Shrubline™, MaxiShrub™, and Ranch Runner™ transformers (shown above in order). All of these distribution transformers are oil-insulated, self-cooled, available in loop or radial feed, and are dead-front.

Both the Shrubline and MaxiShrub transformer versions are manufactured with ratings from10-167 kVA. All of these transformers meet or exceed ANSI®, IEEE® and NEMA® standards.

The Shrubline transformer from Eaton’s Cooper Power Systems is a Type-2 single-phase dead-front pad-mounted transformer. The low profile design blends visually with surroundings-shrubs, low hedges, and home air conditioners—making it ideal for residential applications.

The MaxiShrub transformer from Eaton’s Cooper Power Systems is an ANSI® and IEEE® Type-1 single-phase dead-front pad-mounted transformer.

The ANSI® and IEEE® Type-1 frontplate arrangement allows vertical feed to the primary and secondary bushings. It is ideal for single-phase industrial and residential applications where a wide range of kVAs or heavy cabling is required.

The Ranch Runner transformer is manufactured with ratings from 10-50 kVA. It is Rural Utilities Services (RUS) approved, and meets all ANSI® and IEEE® requirements except frontplate arrangements. The Ranch Runner transformer is a very compact pad-mounted transformer.

Its compact design makes it ideal for irrigation, oil field and residential applications. It offers an economical design which provides standard transformer capabilities in a very compact space.

This unit is shipped complete with its own poly-pad suitable for shipping and installation.

Eaton’s Cooper Power Systems offers poly-pads that are usable with most transformers conforming to ANSI® C57.12.25-1990 standard (Type-1 or Type- 2). This polymer pad serves as a shipping pallet as well as an installation pad.

Single-phase pad-mounted distribution transformers

General

Technical Data 201-20 Effective March 2014 Supersedes August 2012

Standard features

• Meet or exceeds ANSI®, IEEE® and NEMA® standards

• Meets DOE Energy Efficiency Standard 10 CFR Part 431 for distribution transformers

• Tank coating exceeds IEEE Std C57.12.28™-2005 and IEEE Std

C57.12.29™-2005 standards (stainless steel units only)

• Full compliance with IEEE Std C57.12.28™-2005 standard enclosure integrity requirements

• Laser engraved nameplate

• Recessed stainless steel lifting provisions

• Tank grounding provisions

• Automatic pressure relief device

• Electrical grade mineral oil

• Hinged door with stainless steel hinge pins and barrels

• Floating lock pocket for easy alignment

• Captive stainless steel pentahead door locking bolt

• Oil fill and drain provisions

• Removable sill

• Welded domed tank cover

• High-voltage bushing wells - 200 A

• Ground strap from X2 to tank ground

• Tamper strips of noncorrosive material

• Decal bushing designations

• Quality System ISO 9001 certified

Optional features

• Various multiple voltages or taps

• Externally-operable multiple voltage or tap changer switches for safe operation

• Stainless steel tank, tank bottom, sill, door, and/or hardware

• Service entrance in sill

• Various spades and terminals available for secondary bushings

• High efficiency transformers at 0.05% above DOE efficiency or higher

• Stencilled bushing designations

• Various other designations available, e.g., kVA, voltages, fuse number

• High-voltage bushing inserts

• Ground connectors

• Captive stainless steel hexhead door locking bolt

• RUS design

Figure 1. Shrubline single-phase pad-mounted transformer.

LIFTING PROVISION

BAY-O-NET FUSE

HIGH-VOLTAGE BUSHING

GROUNDING PROVISIONS

FLOATING LOCK POCKET

STRIPS FOR TAMPER

RESISTANCE

AUTOMATIC PRESSURE RE-

LIEF DEVICE

GROUNDING PROVISIONS

DUAL VOLTAGE

SWITCH

PARKING STAND LOW-VOLTAGE BUSHING

NAMEPLATE

REMOVABLE

SILL

DOOR

GROUNDING STRAP

Technical Data 201-20 Effective March 2014

Single-phase pad-mounted distribution transformers www.cooperpower.com

1 Add 3” for 150 kV BiL 2 Includes corrugate 3 Weights, gallons of fluid and dimensions are for reference only, and not for construction. Please contact Eaton’s Cooper Power Systems for exact dimensions.

Single-phase pad-mounted shrubline transformer Product Scope:

kVA: 10-167

Primary Voltage: 2400-19,920 V

Secondary Voltage: 120-600 V

Single-phase pad-mounted maxishrub transformer Product Scope:

kVA: 10-167

Primary Voltage: 2400-19,920 V

Secondary Voltage: 120-600 V

Single-phase pad-mounted ranch runner transformer Product Scope:

kVA: 10-50

Primary Voltage: 2400-14,400 V

Secondary Voltage: 120-600 V

CB

A

16" (19" for 150 kV BIL)

H1A

H1BH1B

X1

X2

X3

CB

30"

16" (19" for 150 kV BIL)

H1A H1B X1

X2

X3

Figure 2. Single-phase pad-mounted Shrubline.

Figure 3. Single-phase pad-mounted MaxiShrub.

Figure 4. Single-phase pad-mounted Ranch Runner.

1 Add 3” for 150 kV BiL 2 Includes corrugate 3 Weights, gallons of fluid and dimensions are for reference only, and not for construction. Please contact Eaton’s Cooper Power Systems for exact dimensions.

1 Weights, gallons of fluid and dimensions are for reference only, and not for construction. Please contact Eaton’s Cooper Power Systems for exact dimensions.

A

NP

16"

B C

Table 1. Typical Dimensions and Weights3 kVA

Dimensions (in.) Approx.

Weight (lbs.)“A” “B” “C”

10 24 291 33 600

15 24 291 33 625

25 24 291 33 650

37.5 24 301 33 700

50 24 321 33 750

75 24 341 33 1000

100 30 371 36 1150

167 30 471, 2 36 1650

Table 2. Typical Dimensions and Weights3 kVA

Dimensions (in.)

Approx.

Weight (lbs.)“B” “C”

10 281 33-36 700

15 381 33-36 700

25 281 33-36 700

37.5 281 33-36 750

50 301 33-36 800

75 321 33-36 1000

100 341 36 1150

167 461, 2 36 1650

Typical Dimensions and Weights1 kVA

Dimensions (in.) Approx.

Weight (lbs.)“A” “B” “C”

10 24 28.5 21 400

15 24 28.5 21 500

25 24 32.5 21 600

37.5 24 35.5 21 650

50 24 35.5 21 720

• One piece high-voltage bushings

• High-voltage bushing wells with removable studs

• Envirotemp™ FR3™ fluid where less-flammable fluid is required and where superior enviromental characteristics are desired

• Canadian Standards Association (CSA) and Consumer Electronics

Association (CEA) designs

• Special designs to meet international specifications are also available

• Loadbreak switches1

• Drain/sampling valve1

• Pressure vacuum gauge1

• Liquid level gauge1

• Temperature gauge1

• Combination shipping and installation poly-pad3

1 Not available with the Ranch Runner.

2 Only available with ANSI®and/or IEEE® Type -2 front plate configurations.

3 Standard with the Ranch Runner transformer.

Technical Data 201-20 Effective March 2014

Single-phase pad-mounted distribution transformers www.cooperpower.com

Protection options

• Bay-O-Net expulsion fuse with Flapper™ valve

• Bay-O-Net and partial range current-limiting fuses

• Weak link fuse

• Weak link and partial range current-limiting fuses

• Secondary breaker with weak link1

• MagneX™ interrupter with isolation link1

• MagneX interrupter with partial range current-limiting fuse1

• Under-oil high-voltage MOV arrester1

• Low-voltage distribution-class MOV arrester, internally or externally mounted

• Vacuum Fault Interrupter (VFI) for electronic breaker trip control2 1 Not available with the Ranch Runner.

2 Only available with ANSI® and/or IEEE® Type -2 front plate configurations.

Single-phase VFI transformer The VFI transformer combines a conventional Eaton’s Cooper Power Systems distribution transformer with the proven Vacuum Fault Interrupter (VFI). This combination provides both voltage transformation and overcurrent protection in one space-saving, money-saving package.

The single-phase pad-mounted VFI transformer with loop protection is designed to protect the loop or downstream section of a feeder, and provide proper coordination with upstream and downstream protective devices. In this configuration, when a fault occurs downstream, the VFI trips and isolates the fault, leaving the transformer load uninterrupted.

The VFI breaker has an interrupting rating that far exceeds standard riser pole fuses, enabling better fault clearing coordination and thereby minimizing outage area. Because it is resettable, fault locating is simplified and outage time is reduced.

Poly-pad Eaton’s Cooper Power Systems offers a poly-pad that is usable with most transformers conforming to ANSI® C57.12.25-1990 standard (Type-1 or Type-2). This polymer pad enables transformers to be shipped and installed on the same pad. Use of the poly-pad can eliminate the purchasing, inventory, and administrative costs associated with conventional concrete, polymer or fiberglass pads. Installation costs can also be significantly reduced since the transformer is pre-mounted to its pad. These forkliftable units can be transported damage free during shipping and handling.

Quality control Single-phase pad-mounted distribution transformers manufactured by Eaton’s Cooper Power Systems provide outstanding performance.

All transformers from Eaton’s Cooper Power Systems pass routine tests as prescribed per ANSI® and IEEE® prior to shipment.

MaxiShrub ANSI® and IEEE® Type-1, Shrubline ANSI® and IEEE® Type-2 and Ranch Runner designs are in full compliance with IEEE Std C57.12.28™-2005 standard security requirements.

Corrosion resistance is optimized with the utilization of a superior coating system, combined with the strategic use of stainless steel material, and a tank designed to reduce the retention of water. Our coating systems exceed IEEE Std C57.12.28™-2005 and IEEE Std C57.12.29™-2005 standards. Stainless steel components include door hinge pins and barrels, parking stands, mounting studs, and recessed lifting provisions.

Door and tank covers are permanently domed to eliminate retention of water. All external parts are full-welded to eliminate corrosion caused by moisture entrapment. Bumper pads on doors reduce shipping damage. Lifting provisions are recessed to reduce damage during handling.

The Quality System at Eaton’s Cooper Power Systems Transformer Products is ISO 9001 certified.

Fluid options Transformers can be filled with standard electrical grade mineral insulating oil, Envirotemp™ FR3™ fluid, or other dielectric coolants.

For fire-sensitive locations, Envirotemp™ FR3™ fluid, a fire resistant natural ester-based fluid is recommended. Envirotemp™ FR3™ fluid also offers the benefits of a soy oil-based dielectric coolant that is sustainable and has unique environmental and material properties in addition to increased fire safety over conventional mineral oil.

Check with Eaton’s Cooper Power Systems for the availability of other dielectric coolants in single-phase, pad-mounted transformers.

Eaton, Cooper Power Systems, MagneX, Ranch Runner, Shrubline, and MaxiShrub are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use the these trademarks without the prior written consent of Eaton.

IEEE Std C57.12.28™-2005 and Std C57.12.29™-2005 standards are trademarks of the Institute of Electrical and Electronics Engineers, Inc., (IEEE). This publication is not endorsed or approved by the IEEE.

IEEE® is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc.

ANSI® is a registered trademark of American National Standards Institute.

NEMA is a registered trademark of the National Electrical Manufacturers Association.

Envirotemp™ and FR3™ are licensed trademarks of Cargill, Incorporated.

Single-phase pad-mounted distribution transformers

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com

Eaton’s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53188 United States Cooperpower.com

© 2014 Eaton All Rights Reserved Printed in USA Publication No. 201-20 March 2014

Technical Data 201-20 Effective March 2014

For Eaton’s Cooper Power Systems single-phase pad-mounted transformer product information call 1-877-277-4636 or visit: www.cooperpower.

com.

36-7 19ET 1c, 35kV, 345 mil EPR (100%), TS, PVC

Simpull® 19ET 35kV or 25 kVU Type MV-105. Copper Conductor.

Thermosetting Conductor and Insulation Shield. EPR Insulation.

Copper Tape Shield. Simpull® PVC Jacket.

RoHS

APPLICATIONS

Southwire SIMpull 19ET Type MV-105 Cable is for use in aerial, direct burial, conduit, and underground duct installations as permitted by the National Electrical Code. These cables are capable of operating continuously at a conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions, and are rated at 25,000V, 133%, and 35,000V, 100% insulation level. Maximum sidewall pressure is 1000 lbs. This cable can be installed without the need for pulling lubricant.

SPECIFICATIONS

Southwire SIMpull 19ET Type MV-105 Cable is manufactured and tested in accordance with the latest revisions of the following standards and specification:

• UL 1072 - Medium Voltage Power Cables

• ICEA S-93-639 (NEMA WC 74)

• IEEE 1202/ FT4 - Flame Test (70,000 Btu/hr Vertical Tray Test) with CPE and Solonon jacket.

• ICEA S-97-682

• AEIC CS-8

• RoHS

CONSTRUCTION

Southwire SIMpull 19ET Type MV-105 Cable offers our patented SIM (Slikqwik ® Infused Membrane) Technology ® for easier pulling, flexible, easy bending insulation, easy cable preparation, fast stripping thermosetting insulation shield, 105°C continuous operating temperature, 100% shield coverage and it is triple extruded. Cable is sunlight resistant, suitable for direct burial. Also available listed for cable tray use upon request. SOLONON™ low smoke, non halogen polyolefin jackets and CPE jackets are available upon request.

Product Code Size Conductor Diameter

0.345” (8.76mm) Insulation Diameter

Extruded Insulation Shield

Diameter

Min. Point Jacket Thickness

Approximate Overall Diameter

Approximate Net Weight

Allowable Ampacities+

AWG or kcmil in* mm in** mm in*** mm in mm in mm lb./Mft. kg/km Duct Conduit In Air

19-ET-010 1/0 .362 9.19 1.098 27.88 1.153 29.27 .07 1.78 1.32 33.5 1071 1593 215 215

19-ET-020 2/0 .405 10.29 1.138 28.89 1.193 30.29 .07 1.78 1.36 34.5 1189 1769 245 255

19-ET-030 3/0 .456 11.58 1.188 30.16 1.243 31.56 .07 1.78 1.41 35.8 1340 1993 275 290

19-ET-040 4/0 .512 13 1.243 31.56 1.298 32.96 .07 1.78 1.465 37.2 1523 2266 315 330

19-ET-250 250 .558 14.17 1.298 32.96 1.353 34.35 .07 1.78 1.52 38.6 1688 2512 345 365

19-ET-350 350 .661 16.79 1.403 35.62 1.458 37.02 .07 1.78 1.625 41.3 2089 3108 415 440

19-ET-500 500 .79 20.07 1.528 38.8 1.583 40.2 .1 2.54 1.813 46 2761 4108 500 535

19-ET-750 750 .968 24.59 1.715 43.56 1.77 44.96 .1 2.54 2 50.8 3706 5514 610 655

19-ET-100 1000 1.117 28.37 1.86 47.24 1.915 48.64 .1 2.54 2.145 54.5 4607 6855 690 755

*Minimum diameter per ASTM Standards. ** **±0.030" ***±0.050" +Ampacities are based on the NEC, 2008 Edition. Duct ampacities are based on Table 310.77 three conductors in one underground duct, 105°C conductor, 20°C earth ambient temperature. Conduit in air ampacities are based on Table 310.73 three cables in isolated conduit in air, 105°C conductor, 40°C ambient temperature.

Scope: This specification covers single conductor EPR (ethylene propylene rubber) insulated, shielded, thermoplastic jacketed power cable for use in aerial, direct burial, conduit, and underground duct installations. This cable is capable of operating continuously at a conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions, and are rated at 25,000V, 133% insulation level, and 35,000V, 100% insulation level (grounded system).

Standards: The following standards shall form a part of this specification - UL Standard 1072 for Medium Voltage Power Cable and ICEA S-93-639 (NEMA WC 74) 5-46 kV Shielded Power Cable for Use in the Transmission & Distribution of Electric Energy.

Conductor: The conductor shall be Class B compressed soft or annealed copper in accordance with ASTM Specs B3 and B8 and ICEA Part 2, Section 2.1 and 2.5.

Conductor Shield: The conductor shall be shielded with an extruded semi-conducting thermosetting polymeric layer over the conductor, applied in tandem with and firmly bonded to the insulation.

Insulation: The insulation shall be EPR (ethylene propylene rubber) meeting the requirements of the referenced standards. The nominal thickness shall be 0.345".

Insulation Shield: The insulation shall be shielded with an extruded layer of semi-conducting thermosetting material which shall be identified as being semi-conducting. Over this layer shall be applied a helically wrapped 5-mil copper tape with 25% overlap.

Jacket: The cable shall be provided with a jacket of black sunlight resistant PVC conforming to the requirements specified for polyvinyl chloride jackets in ICEA. The average thickness shall be in accordance with Table 7-3 of ICEA. Optional SOLONON low smoke, non halogen polyolefin jackets and CPE jackets are available upon request.

Identification: Cable shall be identified by surface printing on the jacket.

Tests: Qualification tests shall be conducted in accordance with the requirements of AEIC.

Available Alternatives: Upon request, cable is available in sizes 1/0 AWG and larger listed for use in cable trays.

19ET 1c, 35kV, 345mil EPR, TS(100%), PVC

X-Olene is Okonite’s trade name for its chemically cross-linked polyethylene insulat-ing compound with outstanding electrical and physical properties. Its excellent chemical physical resistance permits X-Olene’s use in areas exposed to alcohol, ketones and dilute acids and bases, without additional cover-ings.

X-Olene Type RHH or RHW-2 or USE-2 600 Volt Power and Control Cables are recom-mended for general low voltage power and control applications. Where the National Electrical Code applies, Type RHH or RHW-2 or USE-2 may be used up to 90°C in dry or wet locations. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, directly buried in the earth, or lashed to a messenger for aerial installation.

Uncoated soft copper per ASTM B-3. Solid per ASTM B-3. Sizes smaller than #8 are compress stranded per ASTM B-8.

Sizes #8 and larger are compact stranded per ASTM B-496.

Meets or exceeds all require-ments of ICEA S-95-658, NEMA WC-70, and UL Standards 44 and 854.

Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2 or USE-2.

*Available with CSA RW90 rating on special request

• Outstanding heat resistance.

• Rated 90°C wet or dry.

• Mechanically rugged.

• Stable electrical properties.

• Low moisture absorption.

• Highly resistant to weather and most chemicals.

• UL Listed.

X-Olene®

Type RHH or RHW-2, or USE-2

Copper Conductor/90°C Wet or Dry

Bare Solid or Stranded Copper Conductor X-Olene Insulation

ULR

B

A

112-32-3061 112-32-3071 112-32-3101

1.14 1.14 1.14

0.16 0.17 0.18

4.06 4.32 4.57

112-32-3111 112-32-3141 112-32-3151

1.14 1.14 1.14

0.19 0.20 0.21

4.57 5.08 5.33

112-32-3231 112-32-3271 112-32-3311

1.52 1.52 1.52

0.26 0.30 0.34

6.60 7.62 8.64

112-32-3371 112-32-3401 112-32-3421

1/0

1.52 2.03 2.03

0.40 0.47 0.51

10.16 11.94 12.95

112-32-3441 112-32-3461 112-32-3481

2/0 3/0 4/0

2.03 2.03 2.03

0.55 0.60 0.65

21.10 23.01 24.93

112-32-3511 112-32-3521 112-32-3541

2.41 2.41 2.41

0.73 0.78 0.82

28.00 29.92 31.45

112-32-3581 112-32-3641 112-32-3701

2.41 2.79 2.79

0.94 1.13 1.28

36.05 43.34 49.09

Visit Okonite's web site, www.okonite.com, for the most up to date dimensions.

Ampacities are based on Table 310.16 of the National Electrical Code for these 90°C rated conductors at an ambient temperature of 30°C. The 75°C wet column is provided for additional information.

The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accor-dance with NEC Section 310.15.B.2.

Based on three (3) conductors in a single enclosed or exposed conduit. Ca-pacities based on 40°C air ambient using ICEA methods. For 30°C ambient multiply values by 1.10; for 50°C multiply by .90. For other ambients or installa-tion conditions refer to Engineering Data Book EHB.

*Available with CSA RW90 rating on special request.

A/10030304

X-Olene®

Type RHH or RHW-2 or USE-2 Copper Conductor/90°C Wet or Dry

To order a color other than black, change the last digit of the catalog number as follows:

White 2 Orange 5

Red 3 Blue 6

Green 4 Yellow 7

Example: To order #14/SOL - Red, the catalog number would be 112-32-3063.