LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

C-1

COVER SHEET

A

A

A

A

P

P

R S

U

R S

O

P

A D

F

P

P

P

P

5 1

5 1

5 1

3 1

5 1

1 1

0 1

8 1

5 1

3 1

5 1

6 1

9 1

5 1

4 1

8 1

5 3

8 2

6 2

0 2

9 2

0 1

P

P

P

S E

N T

R Y

H

O U

S E

P

M A

C

M

A I N

T

S

H E

L T

E R

M A

C

M

A I N

T

S

H E

L T

E R

M A

C

M

A I N

T

S

H E

L T

E R

L O

C A

L I Z

E R

A N

T E

N N

A A

N T

E N

N A

L O

C A

L I Z

E R

T R

A I L E

R

L O

C A

L I Z

E R

I L S

M

N

T

P

P p

P

T R

A I N

I N

G

A

R E

A

S E

C U

R I T

Y

P

O L I C

E

P

P

S U

B S

T A

T I O

N

W T

U

N O

S T

A T

I O

N

S W

I T

C H

I N

G

S T

A T

I O

N

S W

I T

C H

I N

G

S U

B S

T A

T I O

N

P9018P9019

P

P

P

P

P

P

P

P

P

S

S

B U

N

P

I T

A R

E A

B U

R I A

L

O R

D N

A N

C E

P9009

P9008

P9007

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

S

S

P

S

S

P

P

P

P

P

P

P

P

P

P

P

P C

P B

P A

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

T

S

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P5001

P5004

P

S

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

S

P

S

S

S

S

P

P

P

S

P

P

P

P

P

P

P

P

P

P

P

T

P

P

P

P

P

P

W T

T A

P4128

P E

R M

I T

F A

A

P

P4125

P

P

P

P

P

P

P

P

P4002

P

P

P

P9003

P

P

P

P8050

P8054

P

P

S

S

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P7225

P

P

P

P

P

P

P

P8006

P

P

P

P

P

P

P8016

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

F A

C I L I T

Y

T R

A I N

I N

G

F A

C I L I T

Y

T R

A I N

I N

G

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P7420

P

P

P

P

P7313

P7312

P

P

P

P

P

P

P

P

P

P

T

T

P

P

B U

N K

E R

P

P

P

P

P

P

P

P

P

P

P

P

P

P 8P

P 6P

P

P

P

P

P

P

P

T

T11975

T11974

T11977

T

S11900

B

B

M E

M O

R I A

L

A R

E A

P I C

N I C

P A

V I L I O

N

P A

V I L I O

N

T

P

P

P

P

T

S T

A B

L E

S

T

T E

N N

I S

C T

S

TAXIWAY NO. 6

C

O

U

R

T

V

O

L

L

E

Y

B

A

L

L

B B

C T

S

T E

N N

I S

W

A

S

H

I N

G

T

O

N

M

I

S

S

I

S

S

I

P

P

I

T

E

N

N

E

S

S

E

E

P

E

N

N

S

Y

L

V

A

N

I

A

O

K

L

A

H

O

M

A

N

E

W

R

K

M

A

R

Y

L

A

N

D

K

E

N

TU

C

K

Y

IN

D

IAN

A

CO

LO

RADO

AR

IZO

N

A

V I R

G I N

I A

U T

A H

I S

L

A

N

D

R H

O D

E

D

R

I

V

E

N

E

B

R

A

S

K

A

M

A

I

N

E

O

R

E

G

O

N

T

E

X

A

S

KANSAS

ILLIN

O

IS

G

E

O

R

G

IA

F

L

O

R

I

D

A

D

E

L

A

W

A

R

E

C

A

L

I

F

O

R

N

I

A

A

L

A

B

A

M

A

LO

UISIANA

L

O

U

I S

I A

N

A

O V

E R

R U

X

R

I P

A S

S A

U

A

N D

I N

G

O V

E R

R U

N

J A

C K

R A

B B

I T

A

S S

A U

N

D I N

G

S

T R

D

I R

T

A

B

A

N

D

O

N

E

D

A

B

A

N

D

O

N

N

W

A

Y

O

R

F

I E

L

D

A

B

A

N

D

O

N

R

O

N

O V

E R

R U

N

NO. 1TAXIWAY

T A

X I W

TAXIWAY NO. 2

A B

A N

D O

N E

D

TAXIWAY NO 8

R U

N W

A Y

A B

A N

D O

N E

D

P A

R K

I N

G

A

P R

O N

O V

E R

R U

N

OVERRUN

T A

X I W

TAXIWAY NO. 5

TAXIWAY NO. 4

I N

S T

R U

M E

N

W A

Y

T R

B

A

R I

G

W

B

A

S

K

E

T

B

A

L

L

C O

U R

T

B B

P O

O L

P O

O L

C O

U R

T

V

O

L

L

E

Y

B

A

L

L

T R

A C

K

C

O

U

R

T

G O

F

C

U

R S

E

G

G

G

G

G

G

G

G

T

T

T

N O

G

G

G

G

T

T

T

T

G

N O

T

T

G

N O

N O

C O

U R

S E

G O

L F

G

T

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

G O

U

R S

E

G O

U

R S

E

G

N O

N O

N O

HERK DR.

H

I

G

H

W

A

Y

H

I

G

H

W

H

I G

H

W

H

I

G

H

W

A

Y

H I G

H W

H I G

H W

A Y

AVE. E-1

AVE. D-1

AVE. D-2

F I R

S T

AVENUE D

T A

X I W

AVE. A-2

S T

R E

E T

F I R

S T

S T

R E

E T

F I R

S T

AVE A-1

L

T W

C

B A

A

N S

I E

N T

A I R

C R

A F

T

A L E

R

K I N

G

A

R E

A

P A

R K

I N

G

A

P R

O N

AVENUE A

L

C

M

O

T

O

R

C

Y

C

A

I L

S T

R E

E T

S E

C O

N D

R

O

A

D

D

I

V

E

R

S

I

O

N

S T

R E

E T

T H

I R

D

AVENUE D

T H

I

R

E E

T

F O

U R

R

E E

T

AVENUE D

S E

C O

R

E E

T

AVENUE E

T H

I

R

E E

T

S T

R E

E T

T H

I R

D

S

T R

E E

T

F O

U R

R

E E

T

F O

U R

R

E E

T

AVENUE C

AVENUE B

AVENUE C

AVENUE B

S E

C O

N D

S T

R E

E T

S E

C O

N D

S T

R E

E T

F O

U R

T H

S T

R E

E T

S E

C O

N D

S T

R E

E T

T H

I R

D

ROAD

AMMO

AAVENUE

A

AVENUE

ROADRAPCON

S T

R E

E T

T H

I R

D

ROAD

RAPCON

T H

I R

D

S

T R

E E

T

R O

A D

D I V

E R

S I O

N

D

AVENUE

S T

R E

E T

F I F

T H

R

O

A

D

D

I

V

E

R

S

I

O

N

R

O

A

D

C

O

M

M

I

S

S

A

R

Y

THEATER ROAD

AVENUE C

F I F

R

E E

T

A

V

E

N

U

E

B

F I F

R

E E

T

ARNOLD BLVD.

ROAD

AMMO

ROAD

AMMO

A

AVENUE

D

R

I

V

E

T

E

X

A

S

D

I

V

E

R

S

I

A

D

B

L

V

D

A

R

N

O

L

D

A

R

N

O

L

D

B

L

V

D

R

O

A

D

H

O

S

P

I T

A

L

B

L

V

D

A

R

N

O

L

D

R

O

A

D

L

O

U

I S

I A

N

A

R

O

A

D

H

O

S

P

I

T

A

L

B

L

V

D

A

R

N

O

L

D

N

GENERAL NOTES:

1. PROSPECTIVE BIDDERS MAY CONTACT ONLY THE BASE CONTRACTING OFFICE - 7 CONS/LGCA, 381 3rd STREET, DYESS AFB, TX. 79607-1581; (325) 696-3865 FOR ANY AND ALL INFORMATION WITH

REGARDS TO THIS INVITATION FOR BIDS.

2. ALL WORK IS NEW UNLESS OTHERWISE INDICATED TO BE EXISTING, REUSED OR RELOCATED.

3. CONTRACTOR SHALL OBTAIN A COMPLETED AF FORM 103, "WORK CLEARANCE REQUEST" FROM

THE CONTRACTING OFFICER PRIOR TO PERFORMANCE OF ON-SITE WORK.

4. PROSPECTIVE BIDDERS ARE HIGHLY ENCOURAGED TO ATTEND THE SCHEDULED PRE-BID SITE

VISIT TO THOROUGHLY FAMILIARIZE THEMSELVES WITH ANY AND ALL EXISTING SITE AND

PROJECT LOCATION CONDITIONS WHICH MAY AFFECT THE WORK UNDER THIS CONTRACT. THE

GOVERNMENT WILL NOT BE RESPONSIBLE FOR CONTRACTOR ERRORS OR OMISSIONS WHICH

COULD BE MADE KNOWN BY ATTENDING A SCHEDULED SITE VISIT. FAILURE TO ATTEND

SCHEDULED SITE VISITS SHALL NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY TO

PROVIDE ALL REQUIRED WORK AS SPECIFIED AND/OR SHOWN UNDER ANY CONDITION WHICH

COULD BE READILY MADE KNOWN, SHOWN OR EVIDENCED THROUGH THE SITE VISIT.

5. EXISTING UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL

FIELD VERIFY EXACT LOCATIONS PRIOR TO EXCAVATION OR TRENCHING.

6. CONTRACTOR SHALL HAND DIG WITHIN 5 FEET EITHER SIDE OF UTILITY CROSSING UNTIL THE

UTILITY IS PHYSICALLY EXPOSED PRIOR TO EXCAVATION OR TRENCHING.

7. ANY BREACH OF POTABLE WATER LINES SHALL BE PREPARED IN ACCORDANCE WITH

SPECIFICATION SECTION 01510 UTILITIES (CONTRACTOR IDENTIFIED). BACTERIOLOGICAL

SAMPLING/TESTING OF THE WATER AFTER COMPLETION OF REPAIRS SHALL BE BY 7 CES/CEOI,

(325) 696-2056.

8. ANY ACCIDENTAL CUTTING OF FIBER OPTICS CABLE OR MULTI-PAIRED COMMUNICATIONS CABLE

SHALL BE REPAIRED IN A MANNER SATISFACTORY TO AND APPROVED BY 7CS/SCXP AT (325)

696-4433.

PROJECT LOCATION

SCALE: 1" = 2000'

FNWZ 09-0070B

7CES BLDG. 8006

710 3RD. ST.

PROJECT LOCATION

BLDG. 4201

1001 AVE. A-3

N

REPAIR FLIGHTLINE SECURITY CONTROL HVAC, BLDG. 4201

AREA MAP

SCALE: 1" = 2.5 MILES

NC

GAL

MTD

NOM

OCEW

HORIZ

ELECTRICAL

DETAIL

ELEVATION

DIAMETER

DEGREE

EXISTING

EQUIPMENT

EX, EXIST

ELEC

DET

EL

DIA

DEG OR °

EQUIP

OD

NO

NTS

OC

NIC

CONCRETE

AMERICAN WIRE GAUGE

COPPER

BUILDING

APPROXIMATE

CLEAR

CUBIC FEET PER MINUTE

CONC

CU

CLR

AWG

APPROX

BLDG

MIN

IAW

INV

FT

ASBESTOS CEMENT

ABOVE FINISHED FLOOR

AC

AFF

FL

OUTSIDE DIAMETER

NOT TO SCALE

NOT IN CONTRACT

NUMBER

NOMINAL

ON CENTER

ON CENTER EACH WAY

REQUIRED

THICK(-NESS)

POUNDS PER SQUARE INCH

PHASE, DIAMETER

OUTSIDE AIR

SIMILAR

Ø

NOISE CRITERIA

MINIMUM

MOUNTED

IN ACCORDANCE WITH

GALLONS

INVERT

FOOT OR FEET

HORIZONTAL

TYP

TK

SIM

SHT

TYPICAL

SHEET

REQ'D

REF

PSI

REFER

FLOW

OSA

COATED AND WRAPPED STEELC & WS

CFM

PE

POLYETHYLENE

DRAWING(S)DWG(S)

MAX MAXIMUM

SCHEDULESCH

DUCTILE IRONDI

M.J. MECHANICAL JOINT

POST INDICATOR VALVEPIV

SHEET SEQUENCE NUMBERSSN

ANTI-TERROST/FORCE PROTECTIONAT/FP

FTG FITTING

NRS NON-RISING STEM

GCO GRADE CLEANOUT

MH MANHOLE

OE OVERHEAD ELECTRIC

SWITCH GEAR

SWGR

UEP UNDERGROUND ELECTRICAL (PRIMARY)

ALTERNATING CURRENTAC

AIR-HANDLING UNITAHU

AMPERE (AMP, AMPS)AMP

CONCENTRIC DIFFUSER

CONDENSATE DRAIN (PIPE)

CONDUIT

CD

CD

C

CAST IRONCI

CONDENS (-ER, -ING)COND

CUBIC INCHCU IN

CUBIC FEETCU FT

DRY-BULB TEMPERATUREDBT

DECIBELDB

ENTERING AIR TEMPERATUREEAT

EASTE

ENTERING WATER TEMPERATUREEWT

FAHRENHEIT

FOR INFORMATION ONLY, NOT IN CONTRACT

FLOOR DRAIN (PLUMBING)

FIO

F

FD

FIRE DAMPER (MECH)FD

FEET PER MINUTEFPM

HZ HERTZ

HP HORSEPOWER

LWT

LAT LEAVING AIR TEMPERATURE

LEAVING WATER TEMPERATURE

KW KILOWATT

LBS POUNDS

KWH KILOWATT HOUR

MFD MOTORIZED FIRE DAMPER

N/A NOT APPLICABLE

NC NORMALLY CLOSED (CONTACT)

PERCENT%

RA

RETURN AIR

REVOLUTIONS PER MINUTERPM

S SOUTH

RELATIVE HUMIDITYRH

SUPPLY AIRSA

THERMOSTATT'STAT

WET-BULB TEMPERATURE

VENTILATION, VENT

XFMR

WBT

VENT

W

TRANSFORMER

WATT

VOLT AMPEREVA

WITHW/

WET BULBWB

Z ZONE

VOLTV

WATT-HOURWH

ABBREVIATIONS DRAWING INDEX

SYMBOL LEGENDS

SEQ. NO SHEET NO TITLE

1. C1 COVER SHEET

2. GC-1 REFLECTED CEILING PLAN

3. MPE-1 MECHANICAL & ELECTRICAL SITE PLAN

4. M-2 FLOOR PLAN - HVAC, DEMOLITION

5. M-3 FLOOR PLAN - HVAC, NEW

6. M-4 SECTIONS

7. M-5 SCHEDULES

8. M-6 DETAILS

9. M-7 DETAILS

10. M-8 DETAILS

11. M-9 DETAILS AND LEGEND

12. M-10 VRV SYSTEM POWER AND CONTROL ONE LINE WIRING DIAGRAM

13. P-2 FLOOR PLAN - PLUMBING

14. E-2 FLOOR PLAN - LIGHTING, DEMOLITION

15. E-3 FLOOR PLAN - LIGHTING, NEW

16. E-4 FLOOR PLAN - ELECTRICAL, POWER

17. E-5 SCHEDULES

18. E-6 ELECTRICAL RISER DIAGRAM

19. E-7 DETAILS

20. FA-1 FLOOR AND ATTIC PLANS - EXISTING FIRE ALARM SYSTEM

21. FA-2 FIRE ALARM RISER DIAGRAM

FINISHED FLOORFF

ELECTRICAL BREAKER BOX (PANEL)EBB

COMMUNICATIONSCOMM

ENCLOSUREENCL

FUSIBLE DISCONNECT SWITCHFDS

ABILENE

DYESS AFB

FIRE ALARM: REFER TO SHEET FA-2

MECHANICAL: REFER TO SHEET M-9

ELECTRICAL: REFER TO SHEET E-5

VARIABLE REFRIGERANT VOLUMEVRV

VARIABLE REFRIGERANT VOLUMEVRVI

INDOOR (UNIT)

VARIABLE REFRIGERANT VOLUMEVRVO

OUTDOOR (UNIT)

VENTILATION AIR RETURNVAR

VENTILATION AIR SUPPLYVAS

CENTRAL

SECURITY

CONTROL

REFLECTED CEILING PLAN

SCALE: 1/8" = 1' - 0"

NOTES INDICATED BY NUMBER IN :

1. REFER TO SHEET M-2 AND "ROOM FINISH SCHEDULE" NOTE 5 FOR EXISTING

CEILINGS TO BE DEMOLISHED.

2. EXISTING DRYWALL PARTITION EXTENDS TO BOTTOM OF ORIGINAL ROOF

DECK.

3. EXISTING MASONRY WALL EXTENDS TO BOTTOM OF ORIGINAL ROOF DECK.

4. ATTIC ACCESS HATCH.

LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

REFLECTED

CEILING PLAN

GC-1

ROOM FINISH SCHEDULE

107A

VESTIBULE

ASSEMBLY/WAITING

VESTIBULE

SUPPLY

OFFICE

CORRIDOR

ARMORY

ARMORY

CORRIDOR

FLIGHT OFFICER

VESTIBULE

MEN

BASE

RCB

WALLS

P

FLOORING

CT

CEILING

VCT

SC

- CONDUCTIVE TILE

- VINYL COMP. TILE

- SEALED CONCRETE

ABBREVIATIONS

- PAINT 2 COATS LATEX ENAMEL -

COLOR SELECTION BY OWNER

- RUBBER COVE BASE

CPT- CARPET

EXISTING

HEIGHT

NEW

HEIGHT

JANITOR

112 WOMEN

113 TELEPHONE EQUIP.

MECHANICAL

CENTRAL SECURITY CONTROL115

NO. ROOM

FLOOR

BASE FINISH NORTH EAST SOUTH

WALLS CEILING

REMARKS

WEST FIN.

7' - 10"

10' - 0"

8' - 0"

10' - 0"

10' - 0"

10' - 0"

10' - 0"

10' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

10' - 0"

9' - 0"

10' - 0"

EX (1)

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

(2)

ALL SURFACES

EX - EXISTING, NO WORK REQUIRED

NOTES:

1. CEILING SLOPES IN MECH. RM. 116.

2. EX. GYP. BD. CEILING TO REMAIN.

3. WHERE EXISTING FINISHES ARE SHOWN TO REMAIN,

REPAIR, PATCH, RE-FINISH, AND PAINT TO MATCH

EXISTING CONSTRUCTION OF ALL SURFACES

DISTURBED BY THE REPLACEMENT OF THE CEILING,

OR BY THE DEMOLITION OF THE EXISTING HVAC

SYSTEM OR THE REPLACEMENT OF THE HVAC

SYSTEM.

4. REPAIR, PATCH, RE-FINISH ALL SURFACES WITH

PENETRATIONS, DAMAGE, VOIDS, ETC. RESULTING

FROM THE REMOVAL OF ELECTRICAL AND

MECHANICAL EQUIPMENT IN MECH. 116.

5. DEMOLISH EXISTING LAY-IN CEILING.

6. PROVIDE 2 X 2 ARMSTRONG LAY-IN OPTIMA TILE &

GRID.

EX

EX

EX

EX

EX

EX EX EX EX EX EX

(2) (3)

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX

EX

EX

EX

EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX

EX

EX

EX

EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

EX EX EX EX EX

WEAPONS CLEANING ROOM117

EX

EX

EX

EX EX EX EX EX

EX P P P P

EX EX EX EX EX

C-1

EX

C-1

C-1

C-1

C-1

C-1

C-1

C-1

C-1

C-1

C-1

C-1

C-1

C-1

P

C-1

(3) (5) (6)

(3)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(3) (5) (6)

(4)

(2)

(3) (5) (6)

10' - 0" 9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

ALL FINISHES SHALL BE NEW UNLESS OTHERWISE

INDICATED AS EX, EXISTING NO WORK REQUIRED.

ARMORY

107A

WOMEN

MEN

MECH.

CORRIDOR

FLIGHT

OFFICER

CORRIDOR

VEST.

SUPPLY

ASSEMBLY/WAITING

VEST.

JANITOR

TEL. EQUIP.

VEST.

OFFICE

CENTRAL

SECURITY

CONTROL

ARMORY

WEAPONS

CLEANING

ROOM

COMM.

ROOM

CLOS.

PHASING PLAN

SCALE: 1/8" = 1' - 0"

PHASE 1

PHASE 1

PHASE 4

(NOTE 6)

PHASE 2

PHASE 3

NOTES:

1. THE WORK OF THE PROJECT SHALL BE PERFORMED BY AREAS IN THE

PHASE SEQUENCE INDICATED HEREON.

2. THE WORK OF ANY GIVEN PHASE SHALL BE COMPLETED BEFORE

PROCEEDING TO THE NEXT PHASE.

3. THE EXISTING HYDRONIC HVAC SYSTEM SHALL BE MAINTAINED

OPERATIONAL IN ALL AREAS WHERE WORK IS NOT BEING PERFORMED OR

HAS NOT YET BEEN PERFORMED.

4. FOR ALL AREAS RECEIVING THE NEW VRV HVAC SYSTEM, SAID VRV

SYSTEM SHALL BE OPERATIONAL IN ALL AREAS OF A PHASE UPON

COMPLETION OF THE WORK IN SAID PHASE.

5. ROOMS 107, 107A AND 115 ARE DESIGNATED AS CONTROLLED AREAS. A

FREE ZONE LETTER MUST BE ISSUED TO THE CONTRACTOR PRIOR TO

WORK IN THESE ROOMS. FREE ZONES MUST BE ESTABLISHED IN THESE

ROOMS. ALL CONTRACTORS MUST BE ESCORTED WHEN CONDUCTING

BUSINESS IN THESE ROOMS.

6. PHASE 1 WILL REQUIRE THE INSTALLATION OF REFRIGERANT LINES (REF.

SEQ. 5) AND ELECTRICAL POWER (REF. SEQ. 14) THRU WOMEN 112, MEN 111

AND OTHER PHASE 4 AREA ROOMS 108, 109, 113 AND 114. CONTRACTOR

SHALL REMOVE CEILINGS AND MAKE OTHER ALTERATIONS AS NECESSARY

IN AREAS SHOWN AS PHASE 4 TO ENERGIZE THE NEW VRVO #1-12, VRVI

#5-12, VRVI #6-12, VRVI #7-12 AND OSAMU #1-12 TO PROVIDE HEATING,

VENTILATION AND COOLING IN PHASE 1. LIKEWISE IN PHASE #2 & #3.

7. A PORTION OF THE BUILDING WILL BE OCCUPIED DURING CONSTRUCTION.

THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE USERS TO

MINIMIZE DISTURBANCE OF THE BUILDING FUNCTIONS AND TO MINIMIZE

THE HOURS OF OPERATION WITHOUT HVAC IN ALL OCCUPIED AREAS

DURING THE CONSTRUCTION PERFORMANCE PERIOD.

C-1 - 2X2 ARMSTRONG LAY-IN OPTIMA TILE & GRID

ARMORY

107A

WOMEN

MEN

MECH.

CORRIDOR

FLIGHT

OFFICER

CORRIDOR

VEST.

SUPPLY

ASSEMBLY/WAITING

VEST.

JANITOR

TEL. EQUIP.

VEST.

I.M.

OFFICE

ARMORY

WEAPONS

CLEANING

ROOM

COMM.

ROOM

LOCKERS

CLOS.

FLOOR PLAN - FIRE RATED WALLS

SCALE: 1/8" = 1' - 0"

CENTRAL

SECURITY

CONTROL

ARMORY

107A

WOMEN

MEN

MECH.

CORRIDOR

FLIGHT

OFFICER

CORRIDOR

VEST.

SUPPLY

ASSEMBLY/WAITING

VEST.

JANITOR

TEL. EQUIP.

VEST.

ARMORY

WEAPONS

CLEANING

ROOM

COMM.

ROOM

LEGEND

SYMBOL DESCRIPTION

EXISTING 1 HR. FIRE RATED WALL

107B

107B CLOSET

10' - 0" 9' - 0"EX EX EX EX EX EX C-1

(3) (5) (6)

SITE PLAN

SCALE: 1" = 10' - 0"

NOTES INDICATED BY NUMBER IN :

1. REFER TO SHEET M-3 FOR 1/4" = 1' - 0" PLAN OF THIS AREA.

2. EXISTING RECORD DRAWINGS SHOW A COMMUNICATIONS LINE

TO BE ROUTED THRU THE AREA WHERE THE OSAMU (AND

RELATED WORK) IS TO BE PROVIDED. REFER TO THE

"GENERAL NOTES", SHEET C-1 AND TO SECTION 01510 FOR

REQUIREMENTS RELATED TO THE LOCATING AND PROTECTION

OF EXISTING UTILITIES.

3. EXISTING LB'S IMMEDIATELY ABOVE GRADE WHERE EXISTING

COM LINES ARE STUBBED UP FOR ENTRY TO THE BUILDING.

4. COM LINES STUBBED UP FOR ENTRY TO THE BUILDING.

5. EXISTING MAKE-UP AIR HOOD ON ROOF WITH 12/12 DUCT

DOWN TO SPACE BELOW. REFER TO SH. M-2, HEX NOTE 2.

6. EXISTING RELIEF AIR HOOD ON ROOF WITH 12/12 DUCT UP

FROM SPACE BELOW. REFER TO SH. M-2, HEX NOTE 3.

7. DEMOLISH EXISTING HOOD, CURB AND RELATED

COMPONENTS. CLOSE ROOF OPENING WITH DECKING

MATCHING EXISTING DECKING. PROVIDE BLOCKING, BRACING,

ETC. ON UNDERSIDE OF DECKING AS REQUIRED TO

ADEQUATELY SUPPORT THE DECKING AND ANY LIVE LOAD

THAT MAY BE IMPOSED ON IT. COVER THE NEW DECKING WITH

ROOFING MATERIALS MATCHING THE EXISTING ROOFING

MATERIALS.

8. EX. CHILLER TO BE DEMOLISHED. REFER SH. M-2.

9. REFER TO SH. M-3.

10. REFER TO SHEETS M-2, M-3 AND E-4 FOR MECHANICAL AND

ELECTRICAL WORK IN THIS AREA.

11. 75 KVA 120/208 V, 3Ø, 4W POLE MOUNTED XFMR. BANK (3 - 25

KVA XFMRS.) ON THIS POLE.

12. EXISTING PITCHED ROOF CAPS FOR EXHAUST FANS IN MEN 111

AND WOMEN 112. DEMOLISH CAPS AND RELATED DUCT IN

ATTIC.

13. CLOSE ROOF OPENING WITH DECKING MATCHING EXISTING

DECKING. PROVIDE BLOCKING, BRACING, ETC. ON UNDERSIDE

OF DECKING AS REQUIRED TO ADEQUATELY SUPPORT THE

DECKING AND ANY LIVE LOAD THAT MAY BE IMPOSED ON IT.

COVER THE NEW DECKING WITH ROOFING MATERIALS

MATCHING THE EXISTING ROOFING MATERIALS.

14. EXISTING INACTIVE BOILER VENT AND CAP. REMOVE VENT,

CAP AND RELATED WORK.

15. EXISTING GAS FIRED WATER HEATER VENT THRU/ON ROOF TO

REMAIN; NO WORK REQUIRED.

16. CONCRETE PADS ON WHICH THE EXISTING GENERATOR,

CHILLER AND ACCU ARE LOCATED ARE EXISTING AND ARE TO

REMAIN.

17. EXISTING UNDERGROUND ELECTRIC SERVICE EXTENDS TO

MAIN PANEL "B" IN MECHANICAL ROOM.

18. SAW CUT AND DEMOLISH EXISTING PAVEMENT, EXCAVATE,

INSTALL 2W2 DUCTLINE, BACKFILL AND REPAIR PAVEMENT PER

DETAIL 3/E-7.

19. REFER TO DETAIL 6/E-7.

20. NEW TWO WAY DUCT LINE WITH TWO (2) 2" SCH. 40 PVC

CONDUITS AND NEW 120/208V, 3Ø, 4W SERVICE TO BLDG. 4201.

REFER TO "ELECTRICAL RISER DIAGRAM".

21. 1" CONDENSATE DRAIN LINE.

22. REFER TO SHEET M-3 FOR CONTINUATION.

23. TO PANEL "D". REFER TO SHEET E-4.

24. NEW ELECTRIC SERVICE FROM XFMR. TO DISCONNECT. REFER

TO "ELECTRICAL RISER DIAGRAM", SH. E-6.

LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

G

C

O

M

COM

G

G

S

8.00" AC

MPE-1

MECHANICAL &

ELECTRICAL SITE

PLAN

C O

M

C O

M

G

G

C

O

M

WAT

S

OEP

S

S

C O

M

C O

M

C O

M

AVENUE A-3

LINE OF ROOF OVERHANG

LINE OF BUILDING

EXTERIOR WALL

OSAMU

#1-12

WAT

WAT

W A

T

S

S

S

S

W A

T

EX. PKG'D. AIR

COOLED CHILLER

VRVO #1-129

EX. EMER. GEN.

6 7

W A

T

U

E

P

T4202, 225 KVA,

120/208V, 3Ø, 4W

U

E

P

U

E

P

XFMR. T4201

100 KVA, 7.2KV-

120/240V, 1Ø

OEP

O E

P

O E

P

O E

P

O

E

S

O

E

S

O E

S

C

O

M

#4 QUADRAFLEX CABLE

120/208 V, 3Ø, 4W

U

E

S

U E

S

U E

S

ANTENNA POLE

U E

P

TO PAD MTD. XFMR.

AT BLDG. 4225

EX. TURF, TYP.

13 14

12 13

BL-157

BL-

C

O

M

WAT

W

AT

W

AT

XFMR. T4112

KVA,

7.2KV-

120/240V, 1Ø

MPE

-1

M-

EX. GAS

METER

EX. GAS

RISER

O H

G

BL-

G

MPE

-1

E-

MPE

-1

E-

PULLBOX

NUES

N U

E S

NUES

N U

E S

BL-155

DRYWELL

MPE

-1

E-

AREA LIGHT

POLE

MPE

-1

E-

MPE

-1

E-

EXISTING

BITUMINOUS

PVMT.

MPE

-1

E-

G

19 20

POLE

POLE

POLE

POLE

POLE

DRYWELL

(TO BE DEMOLISHED)

DG

U E

S

TO BLDG. 4112

F, WP

19 20

C

O

M

C O

ARMORY

107A

WOMEN

MEN

MECH.

CORRIDOR

FLIGHT

OFFICER

CORRIDOR

VEST.

SUPPLY

ASSEMBLY/WAITING

VEST.

JANITOR

TEL. EQUIP.

VEST.

I.M.

OFFICE

CENTRAL

SECURITY

CONTROL

ARMORY

WEAPONS

CLEANING

ROOM

COMM.

ROOM

LOCKERS

CLOS.

107B

NOTES INDICATED BY NUMBER IN :

1. DEMOLISH EXISTING FAN COIL UNIT.

2. DEMOLISH 12X12 OUTSIDE AIR DUCT EXTENDING UP TO INTAKE AIR HOOD

ON ROOF. THERE IS A FIRE DAMPER IN THE DUCT AT THE PENETRATION OF

THE ORIGINAL ROOF.

3. DEMOLISH 12X12 RELIEF AIR DUCT EXTENDING UP TO RELIEF AIR HOOD ON

ROOF. THERE IS A FIRE DAMPER IN THE DUCT AT THE PENETRATION OF

THE ORIGINAL ROOF.

4. DEMOLISH THE 12X12 DUCT AND DAMPER. REFER TO SHEET MPE-1 FOR

HOOD REMOVAL AND RELATED WORK.

5. CUT OFF AND CAP EXISTING GAS LINE.

6. CUT OFF AND CAP EXISTING COLD WATER LINE.

7. THIS ACCU AND ITS ASSOCIATED D-X AIR HANDLING UNIT (IN CLOSET IN

ARMORY 107) PROVIDE BACK-UP/SUPPLEMENTAL COOLING FOR THE

ARMORY. DEMOLISH ACCU AND ALL RELATED APPURTENANCES.

8. THIS INDOOR D-X AHU AND ITS ASSOCIATED ACCU (REFER NOTE 7)

PROVIDE BACK-UP/SUPPLEMENTAL COOLING FOR THE ARMORY. DEMOLISH

INDOOR D-X AHU AND ALL DUCTWORK AND RELATED APPURTENANCES.

9. EXISTING 1" CONDENSATE DRAIN LINE CONNECTS TO SANITARY SEWER IN

CHASE. THE 1" CONDENSATE DRAIN LINE IS TO BE DEMOLISHED. THE

CONNECTION TO THE SEWER IS TO REMAIN AND BE RE-USED. REFER TO

SH. M-3.

10. DEMOLISH THERMOSTAT AND RELATED WIRING AND CONDUIT. PROVIDE

NEW BLANK COVERPLATE FOR OUTLET BOXES WHERE THERMOSTATS ARE

REMOVED.

11. REMOVE EXHAUST FAN AND ALL RELATED DUCTWORK, EXHAUST HOODS,

EXHAUST LOUVERS, ETC.

12. WHERE DUCTWORK, PIPING AND CONDUITS THRU WALLS ARE REMOVED,

PATCH THE RESULTING OPENINGS TO MATCH EXISTING CONSTRUCTION.

13. EXISTING HVAC PIPING SYSTEM IS A TWO-PIPE HYDRONIC SYSTEM; PIPING

CARRIES CHILLED WATER DURING COOLING SEASON AND HOT WATER

DURING THE HEATING SEASON.

14. DEMOLISH EXISTING CHILLED WATER PIPING.

15. DEMOLISH EXPANSION TANK AND RELATED PIPING.

16. DEMOLISH CONDENSING BOILER, ALL RELATED HYDRONIC PIPING AND ALL

RELATED GAS PIPING. THE PVC VENT FROM THE BOILER IS TERMINATED AT

THE INSIDE FACE OF THE LOUVER IN THE SOUTH WALL OF MECH. 116.

DEMOLISH THIS VENT.

17. DEMOLISH BOILER HOUSEKEEPING PAD.

18. DEMOLISH CHILLED WATER/HOT WATER CIRCULATING PUMP AND AND ALL

RELATED HYDRONIC PIPING.

19. DEMOLISH SHOT FEEDER AND ALL RELATED HYDRONIC PIPING.

20. EXISTING DOMESTIC COLD WATER AND DOMESTIC HOT WATER LINES ARE

LOCATED IMMEDIATELY BELOW THE C&HWS AND C&HWR LINES. SAID

DOMESTIC C.W. AND DOMESTIC H.W. LINES ARE TO REMAIN.

21. EXISTING DISCONNECT FOR PKG'D. AIR COOLED CHILLER. DISCONNECT TO

BE DEMOLISHED; REFER ELECTRICAL DRAWINGS.

22. DEMOLISH WINDOW UNIT AIR CONDITIONER. CLOSE/PATCH WINDOW

OPENING TO MATCH EXISTING CONSTRUCTION INSIDE AND OUTSIDE.

23. EXISTING (ORIGINAL) INACTIVE BOILER VENT THRU ROOF. DEMOLISH VENT

AND RELATED WORK; REFER SH. MPE-1.

24. EXISTING CONCRETE PAD/SLAB TO REMAIN.

25. DEMOLISH ALL PORTIONS OF EXISTING CONDENSATE DRAIN LINE IN

JANITOR 114.

26. DEMOLISH REFRIGERANT PIPING BETWEEN ACCU AND INDOOR D-X AHU.

FLOOR PLAN - HVAC, DEMOLITION

SCALE: 1/4" = 1' - 0"

LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

C D

C D

C D

C

H W

S

C

H W

R

C

H W

S

C

H W

R

C D

C D

C&HWS

C&HWR

D

CDCD

C&HWS

C&HWR

5/8"

1/2"

T

T

T

T

T

8/8

8/8

12/6

10/514/10

8/6

8/6

8/6

3/4"

5/8"

1-1/4"

1-1/2"

5/8"

5/8"

1-1/2"

3/4"

3/4"

M-2

FLOOR PLAN -

HVAC, DEMOLITION

DEMOLISH EX. PKG'D. AIR

COOLED CHILLER

EX. FCU

EX. FCU

3 4

EX. FCU

EX. FCU

2 4

EX. FCU

EX. FCU

EX. FCU

EX. EMERGENCY

GENERATOR

EX. TRANSFER

SWITCH

T

EX. ACCU

WTR. HTR.

SHOT FEEDER

PUMP

F.D.

EXP. TANK

F.A.C.P.

F.A.C.P. DISC.

MONACO PNL.

BOILER

PNL. "A"

PNL.

"B"

EXIT LT.

DISC.

MONACO

PNL.

EX. WINDOW

UNIT AIR

CONDITIONER

NOTES INDICATED BY NUMBER IN CONTINUED FROM SHEET M-3:

52. EXISTING COMMUNICATIONS LINES.

53. THE LOCATIONS OF COMMUNICATIONS LINES AS SHOWN HEREON ARE

BASED ON THE GOVERNMENT'S RECORD DRAWINGS. THE CONTRACTOR

SHALL TAKE ALL MEASURES REQUIRED TO LOCATE PROJECT AND MAINTAIN

SAID COMMUNICATIONS LINES. REFER TO "GENERAL NOTES" 5, 6 & 9, SHEET

C-1 AND TO SECTION 01510 UTILITIES (CONTRACTOR IDENTIFIED).

54. 10 X 10 DESIGN "D" GRILLE, 240 CFM.

55. EXTEND 1/2"Ø CONDENSATE DRAIN LINE THRU EXTERIOR WALL AND TURN

DOWN. TRANSITION TO 1"Ø; EXTEND DOWN WALL TO 12" BELOW GRADE AND

EXTEND TO DRYWELL.

ARMORY

107A

WOMEN

MEN

MECH.

CORRIDOR

FLIGHT

OFFICER

CORRIDOR

VEST.

SUPPLY

ASSEMBLY/WAITING

VEST.

JANITOR

TEL. EQUIP.

VEST.

OFFICE

CENTRAL

SECURITY

CONTROL

ARMORY

WEAPONS

CLEANING

ROOM

COMM.

ROOM

LOCKERS

CLOS.

107B

NOTES INDICATED BY NUMBER IN :

1. SURFACE MOUNT UNIT ON WALL 4" BELOW CEILING. INSTALLATION SHALL

BE SIMILAR TO DETAIL 3/M-8.

2. EXTEND REFRIGERANT PIPING DOWN FROM CEILING SPACE AND INTO LEFT

SIDE OF VRVI.

3. 3/4" CONDENSATE DRAIN LINE. PROVIDE CONTINUOUS WIREMOLD 6000

SERIES SURFACE RACEWAY (4-3/4" (H) X 3-9/16" (D)) TO HOUSE AND

CONCEAL THE DRAIN LINE IN MEN 114. PROVIDE ALL FITTINGS AND

RELATED COMPONENTS AS REQUIRED FOR THE RACEWAY INSTALLATION.

4. TURN DRAIN LINE DOWN WALL TO COUNTER TOP. EXTEND THRU COUNTER

TOP; EXTEND UNDER THE COUNTER TOP TO THE LAVATORY DRAIN

TAILPIECE; CONNECT CONDENSATE DRAIN TO THE TAILPIECE.

5. TEL. EQUIP. 113 HAS A 10' - 0" CEILING. MOUNT VRVI ON WALL ABOVE DOOR

AND 4" BELOW CEILING. EXTEND CONDENSATE DRAIN THRU NORTH WALL,

INTO JANITOR 114 CEILING. EXTEND LINE TO NEW 1-1/4" CD LINE. (REFER

NOTE 6) AND CONNECT.

6. TURN 1-1/4" CONDENSATE DRAIN LINE DOWN THRU CEILING AND EXTEND

DOWN WALL TO JANITOR'S SINK. TERMINATE LINE AT JANITOR'S SINK. ALL

PORTIONS OF THE LINE EXPOSED IN JANITOR 114 SHALL BE COVERED WITH

A METAL JACKET OVER THE INSULATION.

7. PIER AND SUPPORT STRUCTURE FOR INTAKE AIR DUCT.

8. PROVIDE 1-1/2" TK. EXTERNAL RIGID INSULATION ON ALL OUTDOOR DUCT.

(REFER SECTION 23 07 00). DUCT DESIGN SIZE IS 16/16. DUCT IS SHOWN

18/18 TO BE APPROXIMATE ACTUAL SIZE WITH 1-1/2" TK. EXTERN

INSULATION, WEATHER BARRIER MASTIC WITH MESH AND ALUMINUM

JACKET. PROVIDE SILICONE SEALANT AT ALL JACKET JOINTS/LAPS AND AT

ALL SCREW PENETRATIONS OF THE JACKET.

9. TRANSITION FROM EXTERIOR DUCT WITH RIGID INSULATION TO INTERIOR

DUCT WITH BLANKET INSULATION; REFER TO NOTE 8.

10. 4" CHANNEL BRACE; REFER SECTION 2/M-4.

11. 4" SQ. TS AND BASE PLATE; REFER SECTION 2/M-4.

12. 4" CHANNEL, TWO THUS; REFER SECTION 2/M-4.

13. 4 X 3 X 1/4 L'S; BOTTOM SUPPORTS FOR DUCT RISERS. REFER SECTION

2/M-4.

14. THE INDOOR D-X AHU (AND RELATED APPURTENANCES) LOCATED IN THIS

CLOSET IS TO BE DEMOLISHED; REFER TO SH. M-2. RE-FINISH ALL

SURFACES OF THE INTERIOR SUCH THAT THE CLOSET CAN BE USED FOR

STORAGE.

15. ATTIC ACCESS HATCH.

16. 1" CONDENSATE DRAIN LINE ON 5/8" UNISTRUT SUPPORTS AT 2' - 0" O.C.

FASTENED TO CONCRETE SLAB. PROVIDE SHIMS UNDER UNISTRUT AS

REQUIRED TO MAINTAIN 1% DOWNWARD SLOPE IN DRAIN FROM TRAP

OUTLET TO DISCHARGE.

17. PROVIDE TRAP IN CONDENSATE LINE AT DISCHARGE FROM OSAMU. REFER

TO DETAIL 6/M-7.

18. EXTEND 1"Ø CONDENSATE DRAIN LINE BELOW GRADE TO DRY WELL.

19. CONCRETE FOUNDATION/PAD SHALL BE PER THIS DETAIL. PROVIDE

CONSTANT 1% DOWNWARD SLOPE ACROSS PAD FROM NORTH TO SOUTH.

20. PROVIDE 4 PAIR CAT 5E CABLE FROM THE IP/LON ROUTER IN MECH. 116 TO

THE CISCO 2950-24 SWITCH IN THE COMM. ROOM. REFER TO "VRV SYSTEM

POWER AND CONTROL ONE LINE WIRING DIAGRAM", SHEET M-10.

21. 20 X 20 MARK "B" GRILLE.

22. EXTEND 1/2"Ø CONDENSATE DRAIN LINE DOWN WALL TO BUILDING

EXTERIOR.

23. TRANSITION FROM 1/2"Ø IN BLDG. TO 1"Ø. TURN DOWN TO 12" BELOW

GRADE AND EXTEND TO DRY WELL.

24. CONNECT NEW 1" CONDENSATE DRAIN LINE TO THE EXISTING SANITARY

SEWER IN CHASE WHERE THE PREVIOUS CONDENSATE DRAIN WAS

CONNECTED. REFER TO SHEET M-2.

25. VRVI INSTALLATION SHALL BE SIMILAR TO DETAIL 1/M-4.

26. PROVIDE FULL PORT ISOLATION VALVES IN THE REFRIGERANT LINES (2

LINES THUS) SERVING EACH VRVI, TYPICAL.

27. EXISTING ROOF JOIST(S), TYP. REFER TO SECT. 4/M-4.

28. FIRE DAMPER, TYPICAL. REFER TO DETAIL 1/M-8.

29. REFER TO DETAIL 1/M-4 FOR VRVI MOUNTING.

30. PROVIDE EMERGENCY SHUTOFF SWITCH FOR OSAMU #1-12. SWITCH SHALL

BE BRIGHT YELLOW W/CLEAR LEXAN COVER AND SHALL BE LABELED

"EMERGENCY SHUTOFF SWITCH FOR OSAMU #1-12".

31. EXISTING CHILLED WATER SUPPLY AND CHILLED WATER RETURN PIPING

TO BE DEMOLISHED. REFER TO SH. M-2.

32. REFER TO DETAIL 5/M-9, VRVI CONDENSATE DRAIN PIPING.

33. EXISTING DOMESTIC COLD WATER AND DOMESTIC HOT WATER LINES ARE

LOCATED IMMEDIATELY BELOW THESE LINES.

34. SUPPORT BRANCH SELECTOR BOX FROM THE STRUCTURE ABOVE WITH

FOUR (4) HANGER RODS IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

35. DUCT TYPE SMOKE DETECTOR IN OSAMU. (DETECTOR TO BE PROVIDED

WITH OSAMU). DETECTOR SHALL SHUT DOWN OSAMU UPON DETECTION OF

PARTICLES OF COMBUSTION IN THE RETURN AIR STREAM. DETECTOR

SHALL REPORT TO THE FIRE ALARM CONTROL PANEL THRU THE AUXILIARY

CONTACTS OF THE DETECTOR. REFER TO SHEET FA-1.

36. "RJ1" REFNET JOINTS, THREE (3) THUS. PROVIDE AS SCHEDULED IN

ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

37. REFNET JOINTS, THREE (3) THUS. PROVIDE AS SCHEDULED AND IN

ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

38. REFNET JOINTS, TWO (2) THUS. PROVIDE AS SCHEDULED AND IN

ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

39. VERIFY LOCATION OF EXISTING CISCO SWITCH IN COMM. ROOM. CONNECT

4 PAIR CAT 5E CABLE FROM THE IP/LON ROUTER TO THE SWITCH. REFER

TO NOTE 20.

40. PROVIDE BRANCH SELECTOR BOX AS SCHEDULED AND IN ACCORDANCE

WITH THE MANUFACTURER'S RECOMMENDATIONS.

41. FLOOR MOUNTED WEAPONS RACK. ALL MECHANICAL DEVICES IN THE

CEILING OR ABOVE THE CEILING IN ARMORY 107 SHALL BE LOCATED

BETWEEN THE WEAPONS RACK AISLES FOR ACCESS.

42. MAKE REFRIGERANT PIPING CONNECTIONS TO THE VRVI USING OUTDOOR

UNIT CONNECTION KITS PROVIDED BY THE VRV SYSTEM MANUFACTURER.

43. EXTEND TO DRY WELL. REFER SH. MPE-1 FOR CONTINUATION.

44. 30" (W) X 24" (H) X 3/4" PLYWOOD BACKBOARD.

45. REFER TO "VRV SYSTEM POWER AND CONTROL ONE LINE WIRING

DIAGRAM", SHEET M-10.

46. CENTRAL CONTROLLER; DAIKIN DCS302CA61.

FLOOR PLAN - HVAC, NEW

SCALE: 1/4" = 1' - 0"

M-

M-

LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

FLOOR PLAN - HVAC,

NEW

M-3

A270

10X10

A270

10X10

18/8

12/8

18/8

A165

8X8

A165

8X8

A165

8X8

A165

8X8

A240

9X9

A200

9X9

A200

9X9

A200

9X9

A125

8X8

A115

8X8

A180

8X8

A180

8X8

A180

8X8

A180

8X8

A180

8X8

12/8

A90

6X6

C225

16X16

A130

8X8

C115

8X8

10/6

10/6

12/6 10/6

18/8

6/6

20/6

8/6

10/6 10/6

M-

M-

M-

M-

M-

M-

C275

16X16

C75

6X6

EX. EMERGENCY

GENERATOR

C30

6X6

C75

6X6

C75

6X6

C30

6X6

C80

6X6

8/6

8/6

C20

6X6

8/4

10/10

14/8

8/6

18/6

8/6

8/6 18/6

14/8

10/12

A30

6X6

A20

6X6

8/4

8/6

10/6

6/6

12/12

8/6

10/12

8/6

8/10

6/6

6/6

8/6

12/10

8/8

VRVI #11-121

VRVI #6-12

VRVI #7-12

BFF

20X20

VRVI #8-12

VRVI #9-12

VAS

VRVI #5-12

BFF

20X20

(TYP.)

VRVI #10-12

VRVI #1-12

VRVI

#2-12

VRVI

#3-12

VRVI #4-12

MVD

8/6

MVD

MVD

MVD

MVD

MVD

8/6

MVD

30/10

12/6

VR2

VR2

VR2

VR2

V R

EX. TRANSFER

SWITCH

1"

1"

1"

8/6

12/612/6

1"

3/4"

1"

1"

3/4"

30/8

12/8

6/8

10/6 10/6

V R

BFF

20X20

A295

10X10

BS2

BFF

20X20

16/16

BS4

BS3

16/16

OSAMU

#1-12

18/18

18/18

16/16

BFF

20X20

(2 THUS)

BS1

BFF

20X20

VRVI #1-12

EXISTING PACKAGED AIR

COOLED CHILLER TO BE

DEMOLISHED. REFER TO SH. M-2

BFF

20X20

P

EX. MANUAL PULL STATION (FIRE ALARM SYS.)

REFER TO FLOOR PLAN - EXISTING FIRE

ALARM SYSTEM W/ALTERATIONS, SH. FA-1.

C8-12

FD

C 7-12

FD

FD28

C 9-12

FD

FD

FD

C 6-12

C 5-12

FD

FD

C10-12

C11-12

FD

FD FD

C2-12

C1-12

C 3-12

FD

C

4-12

31 33

VR3

VRV SYSTEM REFRIGERATION

PIPING NOTES:

1. REFRIGERANT PIPING SIZES AS

SHOWN HEREON ARE

PRELIMINARY. THE VRV SYSTEM

MANUFACTURER SHALL SIZE ALL

REFRIGERANT PIPING FOR THE

VRV SYSTEM. THE CONTRACTOR

SHALL SUBMIT A REFRIGERANT

PIPING SHOP DRAWING FOR

APPROVAL PRIOR TO INSTALLING

ANY REFRIGERANT PIPING. THE

SHOP DRAWINGS SHALL SHOW

THE VRVO, ALL VRVI'S, ALL

BRANCH SELECTOR BOXES, ALL

REFNET JOINTS, AND ALL

REFRIGERANT PIPING WITH SIZES

FOR EACH SECTION/SEGMENT AS

DETERMINED BY THE VRV SYSTEM

MANUFACTURER.

2. REFER TO DETAILS 1, 2 & 3, SH. M-9

FOR REFRIGERANT PIPING

SUPPORTS.

RJ5

34 40

34 40

RJ3

RJ4

RJ7 38

RJ6

34 40

RJ237

RJ1

L: 3/8"

S: 5/8"

DG: 1/2"

L: 1/4 "

S: 1/2"

VR2

A180

8X8

1" CD

L: 3/8"

S: 5/8"

DG: 1/2"

L: 1/4 "

S: 1/2"

L: 1/4 "

S: 1/2"

L: 1/2"

S: 1-1/8"

DG: 7/8"

RJ8

L: 1/4 "

S: 1/2"

L: 3/8 "

S: 5/8"

L: 1/4 "

S: 1/2"

RJ10

RJ9

NOTES INDICATED BY NUMBER IN CONTINUED:

47. LONWORKS INTERFACE; DAIKIN DMS504C71.

48. ILON 600 IP/LON ROUTER.

49. EXISTING CONCRETE SLAB.

50. PROVIDE NEW CONCRETE SLAB EXTENSION. SLAB SHALL

BE 6" THICK WITH #4 BARS AT 12" O.C.E.W.

51. CONNECT NEW CONCRETE SLAB EXTENSION TO EXISTING

SLAB WITH #4 X 18" DOWELS AT 12" O.C.

52. REFER TO SH. M-2 FOR NOTE 52 AND NOTES AFTER 52.

BS5

34 40

RJ1137

45 46

45 47

45 48

VRVI #12-12

C O

M

C

O

M

C

O

M

C

O

M

CD

18 53

C D

DRYWELL

1030 VAR

4/4

6/6

VAR 445 VAR

C170

14X14

L: 1/4 "

S: 1/2"

VAS

VAR

VAR

105 345 365 495

V A

S

VAR

C170

14X14

16/6

M-

M-

C

O

M

12/12

12/1012/8

8/6

NOTES INDICATED BY NUMBER IN :

1. 8" HIGH CURB TO BE FURNISHED WITH OSAMU.

2. 10" X 10" X 3/8" PLATE, GALVANIZED. PROVIDE FOUR (4) 5/8" X 24"

GALVANIZED ANCHOR BOLTS CAST IN PIER. FASTEN BASE PLATE TO

ANCHOR BOLTS. PROVIDE 1" (H) SPACE BETWEEN TOP OF PIER AND

BOTTOM OF PLATE. PACK SPACE WITH NON-SHRINK GROUT.

3. 1-5/8" GALVANIZED UNISTRUT. FASTEN UNISTRUT TO 4" TS; FASTEN DUCT

TO UNISTRUT.

4. 10" X 10" X 3/8" PLATE, GALVANIZED. PROVIDE FOUR (4) 1/2"Ø, EPOXY

EMBEDDED HILTI ANCHOR BOLTS TO FASTEN BASE TO SLAB. BOLTS SHALL

BE OF LENGTH REQUIRED FOR 6" DEEP EMBED. PROVIDE 1" SPACE

BETWEEN TOP OF SLAB AND BOTTOM OF PLATE. PACK SPACE WITH

NON-SHRINK GROUT.

5. CONTINUOUS 4" X 3" X 1/4" L (GALVANIZED) BETWEEN THE TWO 4 X 4 TS

VERTICAL SUPPORTS; TWO THUS.

6. CONTINUOUS 1" TK. EXPANSION JOINT BETWEEN EQUIPMENT

PAD/FOUNDATION AND BUILDING FOUNDATION.

7. GALVANIZED CHANNEL BRACE, 4" X 1-5/8" X LENGTH REQ'D.

8. PROVIDE 8" (H) X 4" (W) X 1/4" TK. PLATE WELDED TO END OF CHANNEL.

FASTEN PLATE TO BUILDING CMU WITH TWO (2) 1/2"Ø HILTI EPOXY

ANCHORS OF THE TYPE DESIGNED FOR HOLLOW CORE CMU.

9. SUPPORT FOR 4" CHANNEL. FABRICATE FROM 4" X 3" X 1/4" L, GALVANIZED.

FASTEN TO 4 X 4 TS AND TO CHANNEL.

10. GALVANIZED CHANNEL, 4" X 1-5/8" X LENGTH REQ'D. PROVIDE TWO THUS,

ONE EACH SIDE OF DUCTS. FASTEN TO THE DUCTS AND THE 4"

SUPPORTING CHANNEL.

11. NOT USED.

12. PROVIDE 1-1/2" TK. EXTERNAL RIGID INSULATION ON ALL OUTDOOR DUCT.

(REFER SECTION 23 07 00). DUCT DESIGN SIZE IS 16/16. DUCT IS SHOWN

18/18 TO BE APPROXIMATE ACTUAL SIZE WITH 1-1/2" TK. EXTERN

INSULATION, WEATHER BARRIER MASTIC WITH MESH AND ALUMINUM

JACKET. PROVIDE SILICONE SEALANT AT ALL JACKET JOINTS/LAPS AND AT

ALL SCREW PENETRATIONS OF THE JACKET.

13. REPAIR EFIS TO MATCH EXISTING ADJACENT SURFACES AFTER

INSTALLATION OF BRACE(S).

14. EXTERIOR WALL FINISH IS EFIS. BUILDING EXTERIOR WALL CONSTRUCTION

IS 8" TK. CMU.

15. REFER TO SH. M-3 FOR CONTINUATION.

16. EXTEND 1-1/4" CD LINE DOWN FROM CEILING SPACE INTO JANITOR 114.

17. CD LINE FROM VRVI #2-12. REFER TO SH. M-3 FOR CONTINUATION.

18. TERMINATE CD LINE AT JANITOR'S SINK.

LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

SECTIONS

M-4

SECTION

SCALE: 1/4" = 1' - 0"

SECTION

SCALE: 1/4" = 1' - 0"

M-

M-

VRVI #8-12

DETAIL

SCALE: 1/2" = 1' - 0"

M-

M-

ORIGINAL ROOF DECK

20X20

FFB

22/22

5/16"Ø HANGER

ROD

SPRING

ISOLATOR

L 3 X 2 X 3/16 X

LENGTH REQ'D

SECTION

SCALE: 1/4" = 1' - 0"

M-

M-

SUPPLY

ASSEMBLY/

WAITING

16/16

VRVI #7-12

VRVI #8-12

M-

M-

10X10

250 A

NEW LAY-IN

CEILING, TYP.

ORIGINAL BLDG. ROOF

ORIGINAL BLDG. ROOF

6/12

CONC. PIER

18"

30"

M

I N

FINISHED

GRADE

18/18

4 X 4 X 1/4"

TS, GALV.

18/18

OSAMU

#1-12

6"

4 X 4 X 1/4"

TS, GALV.

M-

M-

NOTES INDICATED BY NUMBER IN :

1. OPPOSED BLADE DAMPER (OBD) IN FILTER FRAME GRILLE FOR BALANCING

VENTILATION AIR TO VRVI.

2. FLEX DUCT CONNECTION, TYP.

3. REFER TO DETAIL 5/M-9 FOR CONDENSATE DRAIN PIPING AT VRVI'S.

4. ADJUST (OBD) IN MARK "B" GRILLE, THE MVD AT THE VRVI, AND THE VAR

RETURN AIR GRILLE IN THE SPACE TO PROVIDE THE SCHEDULED AMOUNT OF

VENTILATION AIR TO THE SPACE.

5. THIS DETAIL IS TYPICAL/SIMILAR FOR ALL ABOVE CEILING, DUCT MOUNTED

VRVI'S.

6. ISOLATION VALVES (2 THUS) IN REFRIGERANT PIPING.

SECTION

SCALE: 1/4" = 1' - 0"

SECTION

SCALE: 1/4" = 1' - 0"

CENTRAL

SECURITY

CONTROL

JANITOR

CORRIDOR

FLIGHT

OFFICER

OFFICE

SUPPLY

WEAPONS

CLEANING

ROOM

M-

M-

22/22

20X20

FF B

NEW LAY-IN

CEILING, TYP.

22/2222/2222/22

20X20

FF B

20X20

FF B

20X20

FF B

ORIGINAL BLDG. ROOF

18/8

VRVI #1-12

FD

10/6

8/4

10/4

16/6

FD

8/6

12/10

M.V.D.

F.D.

16/16

8/4

8/4

M.V.D.

6X6

C

6X6

21 C

6X6

95 A

6X6

75 A

6X6

70 A

6X6

70 C

20X20

FF B

8X8

170 A

A250

10X10

10/6

12/8

9X9

200 A

12/6

9X9

200 A

9X9

200 A

12/8

8/6

12/6

12/6

6/6

20X20

FF B

FD

8/6

6/18

MVD

6/8 (VAS)

VR2

CD

16/16

EX. JAN.

SINK

C D1-1/4"

3/4"

CD

CD

3/4"

DETAIL

WALL MTD. VRVI UNIT, TYPICAL

SCALE: NONE

NOTES INDICATED BY NUMBER IN :

1. 1" TK. ARMAFLEX INSULATION.

2. SQ. D LDB6 SERIES. PROVIDE WITHOUT KNOCKOUTS, WITH HINGE COVER AND

END CLOSING PLATE. PAINT WIREWAY TO MATCH WALL COLOR.

3. EXTEND REFRIGERANT LINES THRU KNOCKOUT IN SIDE OF VRVI. CONNECT

REFRIGERANT LINES TO CONNECTORS IN VRVI.

4. REFER TO SH. M-3 FOR CONTINUATION.

5. PROVIDE ALUMINUM JACKET OVER INSULATION EXCEPT WHERE INDICATED

OTHERWISE.

6. PROVIDE FRACTIONAL HORSEPOWER MOTOR STARTER IN SURFACE MTD.

SWITCH BOX. REFER TO ELECTRICAL DRAWINGS.

7. STRAIN RELIEF CONNECTOR.

8. 1/2" CONDUIT WITH 277V CIRCUIT CONDUCTORS. REFER TO SH. E-4 FOR

CONTINUATION.

9. MOUNT/FASTEN VRVI TO WALL IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

LGT

03-08-13

WTA 11078

BDW

REPAIR FLIGHTLINE

SECURITY CONTROL

HVAC, BLDG. 4201

FNWZ 09-0070B

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

08 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

OBTAINED PRIOR TO USING THIS

ANGLE REINFORCED POCKET LOCK

OF APPROXIMATELY 16" ON CENTER

METAL FASTENERS SHALL BE SPACED A MINIMUM

ANGLE REINFORCED STANDING SEAM

DAMPER SHALL BE INSTALLED WITHIN FIRE WALL OR FLOOR SLAB. DAMPER SHALL BE MOUNTED IN A SLEEVE, FACTOR APPLIED

SLEEVE SHALL NOT BE LESS THAN 16 GAUGE STEEL FOR SIZES 40 WIDTH OR 24 HEIGHT AND UNDER, AND MUST NOT BE LESS

DAMPER SHALL BE INSTALLED IN SLEEVE WITH #10X1/2 S.M. SCREWS OF 1/4X1/2 BOLTS AND NUTS. FASTENERS SHALL BE NO

MOUNTING AND EXPANSION CLEARANCE: WHEN SIZING MASONRY OPENING, TWO ADDITIONS HAVE TO BE MADE TO LISTED

DIMENSIONS. ALLOW 3/4" OVER BOTH LISTED WIDTH AND LISTED HEIGHT FOR SLEEVE METAL THICKNESS AND DAMPER FASTENER

CLEARANCE. PROVIDE AN ADDITIONAL 1/8 INCH FOR EACH 12 INCHES OF BOTH LISTED WIDTH FOR THERMAL EXPANSION. FOR

VERTICAL INSTALLATION, ALL VERTICAL CLEARANCE SHOULD BE ABOVE TOP OF SLEEVE. ALL HORIZONTAL CLEARANCE SHOULD

BE DIVIDED EQUALLY ON BOTH SIDES OF SLEEVE. FOR HORIZONTAL INSTALLATION, ALL CLEARANCES ARE DIVIDED EQUALLY

SLEEVE SHALL NOT BE ATTACHED TO WALL (OR SLAB), BUT RETAINED ON EACH SIDE BY A 1-1/2"X1/8" MOUNTING ANGLE

FRAME ATTACHED TO SLEEVE BY #10X1/2 S.M. SCREWS, OR 1/4X1/2 BOLTS - NOT OVER 8 INCHES ON CENTER. THIS ANGLE

FRAME ALSO CLOSES ALL CLEARANCE BETWEEN SLEEVE AND WALL (OR SLAB) AND SHALL OVERLAP WALL A MINIMUM OF 1" ON

A SUITABLE TIGHTLY COVERED, ACCESS TO THE DAMPER MUST BE PROVIDED IN THE DUCTING TO ALLOW INSPECTION AND

SLEEVE SHALL BE INSTALLED SO DAMPER BLADE LOCKS ARE UPPERMOST IN HORIZONTAL INSTALLATIONS AND TOWARD ACCESS

FOR INSTALLATION REQUIRING FLUSH MOUNTING, ANGLE FRAME MAY BE NOTCHED TO ALLOW IT TO BE MOUNTED FACING INTO

MAXIMUM SINGLE DAMPER OF MULTIPLE DAMPER ASSEMBLY SHALL BE 40"X40" IN VERTICAL MOUNTINGS, 42" HEIGHT X 40"

IN MULTIPLE DAMPER ASSEMBLIES, UNITS SHALL BE FASTENED TOGETHER USING MOUNTING HOLES AS PROVIDED.

WIDTH IN HORIZONTAL MOUNTINGS.

UL LABEL SHALL BE RIVETED TO FIRE DAMPER. MANUFACTURER SHALL INSTALL ALL UL TAGS AT THE FACTORY.

AS WITH ALL JOINTS, CONTRACTOR MUST SEAL SLEEVE, IN FIELD, AFTER INSULATION.

DOUBLE "S" SLIP

METHOD OF INSTALLATION.

THAN 14 GAUGE STEEL OVER 40 WIDTH OR 24 HEIGHT.

ALTERNATE BAR SLIP (STANDING SLIP)

OR FIELD FABRICATED WITH INSIDE DIMENSIONS EQUAL TO NOMINAL DUCT DIMENSIONS.

MORE THAN 9 INCHES ON CENTER, AND 2-3/4 INCHES FROM CORNERS.

THE FOLLOWING DUCT-SLEEVE CONNECTIONS MAY BE USED ON ALL SYSTEMS:

REINFORCED BAR SLIP (CLEAT)

THE WALL (OR SLAB).

PLAN "S" SLIP

HEMMED "S" SLIP

ANGLE SLIP

BAR SLIP

INSIDE SLIP

ALL FOUR SIDES.

DOOR IN ALL CASES.

MAINTENANCE.

ON ALL SIDES.

DRIVE SLIP

POCKET LOCK

CUP SLIP

COMPANION ANGLES

J.

M.

N.

O.

K.

L.

I.

TYPICAL FIRE DAMPER INSTALLATIONS

DAMPER

SLEEVE

MIN.

MAX.

12-1/2"

ENGINEER'S APPROVAL MUST BE

PARTITION

3"

MIN.

SLEEVE

DAMPER

FIRE

WALL OR

PARTITION PARTITION

12-1/2"

MIN.

3"

MIN.

3"

SLEEVE

MOUNTING

DUCT

ANGLE

FIRE

DAMPER

MAX. MIN.

3"

DUCT

3"

ANGLE

MOUNTING

FIRE

WALL OR

WALL OR

12-1/2"

MAX. MIN.

3"

DUCT

ANGLE

MOUNTING

FIRE DAMPER INSTALLATION DETAILS

11.

13.

12.

10.

NO SCALE

H.

9.

8.

7.

6.

B.

E.

F.

G.

C.

D.

A.

5.

4.

3.

2.

1.

MOUNTING

ANGLE

DUCT

MAX.

12-1/2"

FIRE

3" MIN.

SLEEVE

DAMPER

3" MIN.

FLOOR

FIRE DAMPER FOR FLOOR PENETRATION

THE DETAILS INDICATED HEREON ARE "TYPICAL". THE MANUFACTURER'S INSTALLATION REQUIREMENTS FOR THE DAMPERS14.

PROVIDED SHALL TAKE PRECEDENCE OVER THE DETAILS INDICATED HEREON.

FIRE DAMPERS SHALL BE DELIVERED FROM THE FACTORY WITH A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL),15.

SUCH AS UL OR FM SEAL AFFIXED TO THE DAMPER AT THE FACTORY. DO NOT INSTALL DAMPERS WHICH DO NOT HAVE

THIS SEAL ALREADY AFFIXED.

M-

M-

DETAILS

M-8

SCALE: 3/4" = 1'-0"

TYPCIAL DRY WELL DETAIL

DETAIL

EXISTING GRADE

FILL WITH CRUSHED

INLET PIPE-SIZE

AS SHOWN ON PLAN

AGGREGATE OR GRAVEL

CROWN BACKFILL

BACKFILL

ABOVE EXISTING GRADE

COPPER SCREEN

30" DIA.

M-

PLAN

ELEVATION "A - A"

M-

M-3

MPE

-1

TOGGLE

SWITCH

12/3 SO

CORD

CONDENSATE

DRAIN LINE

6" X 6" ELECTRIC

WIREWAY

CEILING

REFRIGERANT LIQUID

AND SUCTION LINES

WALL

LIQUID LINE

SUCTION LINE

VRVI

A A

VRVI

M-

LGT

03-28-13

WTA 12025

BDW

REPAIR VEHICLE

MAINTENANCE

SHOP HVAC,

BLDG. 8015

FNWZ 09-0070A

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLAGE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

28 MARCH, 2013. USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

LGT

SECTION

WHERE SHOWN

SHEET No.

WHERE TAKEN

SHEET No.

ELEVATIONDETAILSECTION

A

A

A

A

P

P

R S

U

R S

O

P

A D

F

P

P

P

P

5 1

5 1

5 1

3 1

5 1

1 1

0 1

8 1

5 1

3 1

5 1

6 1

9 1

5 1

4 1

8 1

5 3

8 2

6 2

0 2

9 2

0 1

P

P

P

S E

N T

U

S E

P

M A

C

M

A I N

T

S

H E

L T

E R

M A

C

M

A I N

T

S

H E

L T

E R

M A

C

M

A I N

T

S

H E

L T

E R

L O

C A

L I Z

E R

A N

T E

N N

A A

N T

E N

N A

L O

C A

L I Z

E R

T R

A I L E

R

L O

C A

L I Z

E R

I

N

T

P

P p

P

T R

A I N

I N

G

A

R E

A

S E

C U

R I T

Y

P

O L I C

E

P

P

S U

B S

T A

T I O

N

W T

U

N O

S T

A T

I O

N

S W

I T

C H

I N

G

S T

A T

I O

N

S W

I T

C H

I N

G

S U

B S

T A

T I O

N

P9018P9019

P

P

P

P

P

P

P

P

P

S

S

B U

T

A R

E A

B U

R I A

L

O R

D N

A N

C E

P9009

P9008

P9007

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

S

S

P

S

S

P

P

P

P

P

P

P

P

P

P

P

P C

P B

P A

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

T

S

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P5001

P5004

P

S

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

S

P

S

S

S

S

P

P

P

S

P

P

P

P

P

P

P

P

P

P

P

T

P

P

P

P

P

P

W T

A

P4128

P E

R M

I T

F A

A

P

P4125

P

P

P

P

P

P

P

P

P4002

P

P

P

P9003

P

P

P

P8050

P8054

P

P

S

S

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P7225

P

P

P

P

P

P

P

P8006

P

P

P

P

P

P

P8016

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

F A

C I L I T

Y

T R

A I N

I N

G

F A

C I L I T

Y

T R

A I N

I N

G

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P7420

P

P

P

P

P7313

P7312

P

P

P

P

P

P

P

P

P

P

T

T

P

P

B U

N K

E R

P

P

P

P

P

P

P

P

P

P

P

P

P

P 8P

P 6P

P

P

P

P

P

P

P

T

T11975

T11974

T11977

T

S11900

B

B

M E

M O

R I A

L

A R

E A

P I C

N I C

P A

V I L I O

N

P A

V I L I O

N

T

P

P

P

P

T

S T

A B

L E

S

T

T E

N N

I S

C T

S

TAXIWAY NO. 6

C

O

U

R

T

V

O

L

L

E

Y

B

A

L

L

B B

C T

S

T E

N N

I S

W

A

S

H

I N

G

T

O

N

M

I

S

S

I

S

S

I

P

P

I

T

E

N

N

E

S

S

E

E

P

E

N

N

S

Y

L

V

A

N

I

A

O

K

L

A

H

O

M

A

N

W

R

K

M

A

R

Y

L

A

N

D

K

E

N

TU

C

K

Y

IN

D

IAN

A

CO

LO

RADO

AR

IZO

N

A

V I R

G I N

I A

U T

A H

I S

L

A

N

D

R H

O D

E

D

R

I

V

E

N

E

B

R

A

S

K

A

M

A

I

N

E

O

R

E

G

O

N

T

E

X

A

S

KANSAS

ILLIN

O

IS

G

E

O

R

G

IA

F

L

O

R

I

D

A

D

E

L

A

W

A

R

E

C

A

L

I

F

O

R

N

I

A

A

L

A

B

A

M

A

LOUISIANA

L

O

U

I S

I A

N

A

O V

E R

R

R

I P

A S

S A

U

N D

I N

G

O V

E R

R U

N

J A

C K

R A

B B

I

S

A U

N

D I N

G

S

T R

I R

T

A

B

A

N

D

O

N

E

D

A

B

A

N

D

O

N

N

W

A

Y

O

R

F

I E

L

D

A

B

A

N

D

O

N

R

O

N

O V

E R

R U

N

NO. 1TAXIWAY

T A

X I W

TAXIWAY NO. 2

A B

A N

D O

N E

D

TAXIWAY NO 8

R U

N W

A Y

A B

A N

D O

N E

D

P A

R K

I N

G

A

P R

O N

O V

E R

R U

N

OVERRUN

T A

X I W

TAXIWAY NO. 5

TAXIWAY NO. 4

I N

S T

R U

M E

N

W A

Y

T R

B

A

R I

G

W

B

A

S

K

E

T

B

A

L

L

C O

U R

T

B B

P O

O L

P O

O L

C O

U R

T

V

O

L

L

E

Y

B

A

L

L

T R

A C

K

C

O

U

R

T

G O

U

R S

E

G

G

G

G

G

G

G

G

T

T

T

N O

G

G

G

G

T

T

T

T

G

N O

T

T

G

N O

N O

C O

U R

S E

G O

L F

G

T

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

G O

U

R S

E

G O

U

R S

E

G

N O

N O

N O

HERK DR.

H

I

G

H

W

A

Y

H

I

G

H

W

H

I G

H

W

H

I

G

H

W

A

Y

H I G

H W

H I G

H W

A Y

AVE. E-1

AVE. D-1

AVE. D-2

F I R

S T

AVENUE D

T A

X I W

AVE. A-2

S T

R E

E T

F I R

S T

S T

R E

E T

F I R

S T

AVE A-1

L

T W

C

B A

A

N S

I E

N T

A I R

C R

A F

T

A L

E R

T

P

A R

K I N

G

A

R E

A

P A

R K

I N

G

A

P R

O N

AVENUE A

L

C

M

O

T

O

R

C

Y

C

A

I L

S T

R E

E T

S E

C O

N D

R

O

A

D

D

I

V

E

R

S

I

O

N

S T

R E

E T

T H

I R

D

AVENUE D

T H

I

R

E E

T

F O

U R

R

E E

T

AVENUE D

S E

C O

R

E E

T

AVENUE E

T H

I

R

E E

T

S T

R E

E T

T H

I R

D

S

T R

E E

T

F O

U R

R

E E

T

F O

U R

R

E E

T

AVENUE C

AVENUE B

AVENUE C

AVENUE B

S E

C O

N D

S T

R E

E T

S E

C O

N D

S T

R E

E T

F O

U R

T H

S T

R E

E T

S E

C O

N D

S T

R E

E T

T H

I R

D

ROAD

AMMO

AAVENUE

A

AVENUE

ROADRAPCON

S T

R E

E T

T H

I R

D

ROAD

RAPCON

T H

I R

D

S

T R

E E

T

R O

A D

D I V

E R

S I O

N

D

AVENUE

S T

R E

E T

F I F

T H

R

O

A

D

D

I

V

E

R

S

I

O

N

R

O

A

D

C

O

M

M

I

S

S

A

R

Y

THEATER ROAD

AVENUE C

F I F

R

E E

T

A

V

E

N

U

E

B

F I F

R

E E

T

ARNOLD BLVD.

ROAD

AMMO

ROAD

AMMO

A

AVENUE

D

R

I

V

E

T

E

X

A

S

D

I

V

E

R

S

I

A

D

B

L

V

D

A

R

N

O

L

D

A

R

N

O

L

D

B

L

V

D

R

O

A

D

H

O

S

P

I T

A

L

B

L

V

D

A

R

N

O

L

D

R

O

A

D

L

O

U

I S

I A

N

A

R

O

A

D

H

O

S

P

I

T

A

L

B

L

V

D

A

R

N

O

L

D

N

NUMBER

CONTRACTING DIV.

BLDG. 7238

381 3rd ST.

MAIN GATE (NOT A

PROJECT ACCESS)

TRUCK ROUTE

TRUCK GATE (UTILIZE FOR

PROJECT ENTRANCE)

FIRE DEPT

BLDG. 5013

GENERAL NOTES:

1. PROSPECTIVE BIDDERS MAY CONTACT ONLY THE BASE CONTRACTING OFFICE - 7 CONS/LGCA, 381 3rd STREET, DYESS AFB, TX. 79607-1581;

(325) 696-3865 FOR ANY AND ALL INFORMATION WITH REGARDS TO THIS INVITATION FOR BIDS.

2. ALL WORK IS NEW UNLESS OTHERWISE INDICATED TO BE EXISTING, REUSED OR RELOCATED.

3. CONTRACTOR SHALL OBTAIN A COMPLETED AF FORM 103, "WORK CLEARANCE REQUEST" FROM THE CONTRACTING OFFICER PRIOR TO

PERFORMANCE OF ON-SITE WORK.

4. PROSPECTIVE BIDDERS ARE HIGHLY ENCOURAGED TO ATTEND THE SCHEDULED PRE-BID SITE VISIT TO THOROUGHLY FAMILIARIZE

THEMSELVES WITH ANY AND ALL EXISTING SITE AND PROJECT LOCATION CONDITIONS WHICH MAY AFFECT THE WORK UNDER THIS

CONTRACT. THE GOVERNMENT WILL NOT BE RESPONSIBLE FOR CONTRACTOR ERRORS OR OMISSIONS WHICH COULD BE MADE KNOWN BY

ATTENDING A SCHEDULED SITE VISIT. FAILURE TO ATTEND SCHEDULED SITE VISITS SHALL NOT RELIEVE THE CONTRACTOR OF HIS

RESPONSIBILITY TO PROVIDE ALL REQUIRED WORK AS SPECIFIED AND/OR SHOWN UNDER ANY CONDITION WHICH COULD BE READILY MADE

KNOWN, SHOWN OR EVIDENCED THROUGH THE SITE VISIT.

5. EXISTING UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS PRIOR TO

EXCAVATION OR TRENCHING.

6. CONTRACTOR SHALL HAND DIG WITHIN 5 FEET EITHER SIDE OF UTILITY CROSSING UNTIL THE UTILITY IS PHYSICALLY EXPOSED PRIOR TO

EXCAVATION OR TRENCHING.

7. ANY BREACH OF POTABLE WATER LINES SHALL BE PREPARED IN ACCORDANCE WITH SPECIFICATION SECTION 01510 UTILITIES

(CONTRACTOR IDENTIFIED). BACTERIOLOGICAL SAMPLING/TESTING OF THE WATER AFTER COMPLETION OF REPAIRS SHALL BE BY 7

CES/CEOI, (325) 696-2056.

8. ANY ACCIDENTAL CUTTING OF FIBER OPTICS CABLE OR MULTI-PAIRED COMMUNICATIONS CABLE SHALL BE REPAIRED IN A MANNER

SATISFACTORY TO AND APPROVED BY 7CS/SCXP AT (325) 696-4433.

9. FRIABLE ASBESTOS CONTAINING MATERIAL (ACM) WAS DETECTED IN 2001 SURVEY SAMPLES IN THE FOLLOWING AREAS: PIPE INSULATION, MECHANICAL EQUIPMENT INSULATION, WINDOW CAULKING, WINDOW GLAZING, FLOOR TILE, GYPSUM BOARD. SOME OF THE ABOVE

DETECTED ACM WAS REMOVED. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A SURVEY AND SAMPLING FOR ACM IN ALL AREAS OF

THE BUILDING AFFECTED BY THE PROPOSED WORK. PROVIDE ABATEMENT OF ASBESTOS-CONTAINING MATERIALS IN AREAS AFFECTED BY

THE WORK THAT IS DETERMINED TO HAVE ACM.

PROJECT LOCATION

SCALE: 1" = 2000'

FNWZ 09-0070A

7CES BLDG. 8006

710 3RD. ST.

PROJECT LOCATION

BLDG. 8015

698 AVE. E

N

REPAIR VEHICLE MAINTENANCE SHOP HVAC, BLDG. 8015

AREA MAP

SCALE: 1" = 2.5 MILES

COVER

SHEET

NC

GAL

MTD

NOM

OCEW

HORIZ

ELECTRICAL

DETAIL

ELEVATION

DIAMETER

DEGREE

EXISTING

EQUIPMENT

EX, EXIST

ELEC

DET

EL

DIA

DEG OR °

EQUIP

OD

NO

NTS

OC

NIC

CONCRETE

AMERICAN WIRE GAUGE

COPPER

BUILDING

APPROXIMATE

CLEAR

CUBIC FEET PER MINUTE

CONC

CU

CLR

AWG

APPROX

BLDG

MIN

IAW

INV

FT

ASBESTOS CEMENT

ABOVE FINISHED FLOOR

AC

AFF

FL

OUTSIDE DIAMETER

NOT TO SCALE

NOT IN CONTRACT

NUMBER

NOMINAL

ON CENTER

ON CENTER EACH WAY

REQUIRED

THICK(-NESS)

POUNDS PER SQUARE INCH

PHASE, DIAMETER

OUTSIDE AIR

SIMILAR

Ø

NOISE CRITERIA

MINIMUM

MOUNTED

IN ACCORDANCE WITH

GALLONS

INVERT

FOOT OR FEET

HORIZONTAL

TYP

TK

SIM

SHT

TYPICAL

SHEET

REQ'D

REF

PSI

REFER

FLOW

OSA

COATED AND WRAPPED STEELC & WS

CFM

PE

POLYETHYLENE

DRAWING(S)DWG(S)

MAX MAXIMUM

SCHEDULESCH

DUCTILE IRONDI

M.J. MECHANICAL JOINT

POST INDICATOR VALVEPIV

SHEET SEQUENCE NUMBERSSN

ANTI-TERROST/FORCE PROTECTIONAT/FP

FTG FITTING

NRS NON-RISING STEM

GCO GRADE CLEANOUT

MH MANHOLE

OE OVERHEAD ELECTRIC

SWITCH GEAR

SWGR

UEP UNDERGROUND ELECTRICAL (PRIMARY)

ALTERNATING CURRENTAC

AIR-HANDLING UNITAHU

AMPERE (AMP, AMPS)AMP

CONCENTRIC DIFFUSER

CONDENSATE DRAIN (PIPE)

CONDUIT

CD

CD

C

CAST IRONCI

CONDENS (-ER, -ING)COND

CUBIC INCHCU IN

CUBIC FEETCU FT

DRY-BULB TEMPERATUREDBT

DECIBELDB

ENTERING AIR TEMPERATUREEAT

EASTE

ENTERING WATER TEMPERATUREEWT

FAHRENHEIT

FOR INFORMATION ONLY, NOT IN CONTRACT

FLOOR DRAIN (PLUMBING)

FIO

F

FD

FIRE DAMPER (MECH)FD

FEET PER MINUTEFPM

HZ HERTZ

HP HORSEPOWER

LWT

LAT LEAVING AIR TEMPERATURE

LEAVING WATER TEMPERATURE

KW KILOWATT

LBS POUNDS

KWH KILOWATT HOUR

MFD MOTORIZED FIRE DAMPER

N/A NOT APPLICABLE

NC NORMALLY CLOSED (CONTACT)

PERCENT%

RA

RETURN AIR

REVOLUTIONS PER MINUTERPM

S SOUTH

RELATIVE HUMIDITYRH

SUPPLY AIRSA

THERMOSTATT'STAT

WET-BULB TEMPERATURE

VENTILATION, VENT

XFMR

WBT

VENT

W

TRANSFORMER

WATT

VENTILATION AIR (SUPPLY)VAS

WITHW/

WET BULBWB

Z ZONE

VOLTV

WATT-HOURWH

ABBREVIATIONS

DRAWING INDEX

SYMBOL LEGENDS

SEQ. NO SHEET NO TITLE

1. C-1 COVER SHEET

2. G-001 ABBREVIATIONS AND LEGENDS

3. A-101 AREAS A & C EXISTING/DEMO FLOOR PLAN

4. A-102 AREA B EXISTING/DEMO FLOOR PLAN

5. A-103 AREAS A & C FLOOR PLAN

6. A-104 EXISTING - REFLECTED CEILING PLAN - DEMOLITION

7. A-105 NEW - REFLECTED CEILING PLAN

8. A-601 DETAILS

9. A-602 CEILING SCHEDULE

10. ME-1.1 SITE PLAN

11. ME-1.2 ROOF PLAN AND PHASING PLAN

12. M-2.1 PARTIAL FLOOR PLAN - HVAC, EXISTING - DEMOLITION

13. M-2.2 PARTIAL FLOOR PLAN - HVAC, EXISTING - DEMOLITION

14. M-3.1 PARTIAL FLOOR PLAN - HVAC, NEW

15. M-3.2 PARTIAL FLOOR PLAN - HVAC, NEW

16. M-3.3 PARTIAL FLOOR PLAN - HVAC REFRIGERANT PIPING

17. M-3.4 FLOOR PLAN - AIR BALANCE

18. M-4.1 SECTIONS

19. M-4.2 ELEVATION AND SECTIONS

20. M-4.3 ELEVATION AND SECTION

21. M-4.4 SECTIONS

22. M-4.5 SECTIONS AND DETAILS

23. M-5.1 SCHEDULES

24. M-5.2 SCHEDULES

25. M-7.1 VRV SYSTEM POWER AND CONTROL ONE LINE WIRING DIAGRAMS

26. M-7.2 HVAC CONTROL DIAGRAMS

27. M-7.3 HVAC CONTROL DIAGRAMS

28. M-7.4 HVAC CONTROL DIAGRAMS

29. M-7.5 DDCS LEGEND AND SEQUENCE OF OPERATION

30. M-7.6 LON DDCS CONTROL PANEL

31. M-8.1 DETAILS

32. M-8.2 DETAILS

33. M-8.3 DETAILS

34. M-8.4 DETAILS

35. M-8.5 DETAILS AND MECHANICAL SYMBOL LEGEND

36. E-2.1 PARTIAL FLOOR PLAN - LIGHTING, EXISTING - DEMOLITION

37. E-2.2 PARTIAL FLOOR PLAN - LIGHTING, EXISTING - DEMOLITION

38. E-2.3 PARTIAL FLOOR PLAN - LIGHTING, NEW

39. E-2.4 PARTIAL FLOOR PLAN - LIGHTING, NEW

40. E-3.1 PARTIAL FLOOR PLAN - POWER

41. E-3.2 PARTIAL FLOOR PLAN - POWER

42. E-5.1 ELECTRICAL RISER DIAGRAM

43. E-6.1 EXISTING PANEL SCHEDULES

44. E-6.2 EXISTING PANEL SCHEDULES

45. E-6.3 PANEL SCHEDULES

SEQ. NO SHEET NO TITLE

46. FA-1 DEMOLISH PLAN FOR EXISTING FIRE ALARM

47. FA-2 NEW FIRE ALARM AND MASS NOTIFICATION PLAN

48. FA-3 FIRE ALARM/NEW MASS NOTIFICATION RISER DIAGRAMS

49. FS-1 EXISTING FIRE SUPPRESSION FLOOR PLAN

50. FS-2 EXISTING FIRE SUPPRESSION FLOOR PLAN

FINISHED FLOORFF

ELECTRICAL BREAKER BOX (PANEL)EBB

CEMENT MASONRY UNITCMU

ENCLOSUREENCL

FUSIBLE DISCONNECT SWITCHFDS

ABILENE

DYESS AFB

SECURITY FORCES

BLDG. 6117

390 4th AVE.

EXTERIOR FINISH INSULATION SYSTEMEFIS

VRVO

VARIABLE REFRIGERANTVRVI

VARIABLE REFRIGERANT VOLUMEVRV

VARIABLE REFRIGERANT

VOLUME INDOOR (UNIT)

VOLUME OUTDOOR (UNIT)

MECHANICAL: REFER TO SHEET M-8.5

ELECTRICAL: REFER TO SHEET E-2.2

FIRE ALARM & MASS

NOTIFICATION: REFER TO SHEET FS-4

COMMUNICATIONSCOMM

GYP GYPSUM

HM HOLLOW METAL

HR HOUR

VINYL COMPOSITION TILEVCT

C-1

DRAWING INDEX

VENTILATION AIR (RETURN)VAR

VOLT AMPEREVA

03-06-2013

REPAIR VEHICLE

MAINTENANCE

SHOP HVAC,

BLDG. 8015

FNWZ 09-007A

AREA A

AREA C

KEYPLAN

R E

G

I

S

T

E

R

E

D A

R

C

H

I

T

E

C

T

S

T

A

X

A

S

G

A

P

U

L

L

I

N

03-06-2013

A-104

EXISTING

REFLECTED

CEILING PLAN -

DEMOLITION

EXISTING REFLECTED CEILING PLAN - DEMOLITION

3/32"=1'-0"

A103 A103

0 20'4' 8'

NORTH

ALPHA BAY

MAINTENANCE

AREA

TRAINING

STORAGE

BAY

UPHOLSTERY

COMPUTER

LASER

CORRIDOR

TRAINING

BAY

CORR

MENS

TOILET &

LOCKER

JAN.

BREAK

MATERIAL

CONTROL

SUPPLY

CONTROL

CLOS

CLOS

MAINTENANCE

MANAGER

OFFICE

OFFICE

TIRE

SHOP

118A

MAINTENANCE

CONTROL

ANALYSIS

CUSTOMER

SERVICE

OFFICE

ALPHA

BAY

OFFICE

STORAGE

CUSTOMER

SERVICE

BRAVO

OFFICE

DRESSING

MECHANICAL

ROOM

WOMEN'S

TOILET

"MATCH LINE"

WELDING

DRIVE-THRU

PAINT

BOOTH

118B

SECOND FLOOR PLAN

FIRST FLOOR PLAN

PRODUCTION

SUPPORT

ALLIED

TRADES

STAIR

18B

AREA A

AREA C

1 1

KEYNOTES

1. DEMOLISH EXISTING LAY-IN CEILING

PANELS AND GRID

2. DEMOLISH EXISTING GYPSUM BOARD

CEILINGS IN THESE AREAS

3. REPAIR ALL EXISTING DAMAGED GYP

BOARD ABOVE LAY-IN CEILING

REQUIRED TO FIREPROOF THE METAL

ROOF STRUCTURE. PROVIDE NEW

TAPE AND BEDDING AT…