Repair (R/M) Electrical Lines – 26 05 13-1 156-011
MSA/COMM SQ Areas – JFSD970342
(114009) Revised July 2013 2012 by FEI
SECTION 26 05 13 1
MEDIUM-VOLTAGE CABLES 2
A. GENERAL 4
RELATED DOCUMENTS 6
Drawings and general provisions of the Contract, including General and Supplementary Conditions and 8 Division 01 Specification Sections, apply to this Section. 9
SUMMARY 11
Section includes cables and related cable splices, terminations, and accessories for medium-voltage (2001 to 13 35,000 V) electrical distribution systems. 14
DEFINITIONS 16
Jacket: A continuous nonmetallic outer covering for conductors or cables. 18 NETA ATS: Acceptance Testing Specification. 20 Sheath: A continuous metallic covering for conductors or cables. 22
ACTION SUBMITTALS 24
Product Data: For each type of cable. Include splices and terminations for cables and cable accessories. 26 Samples: 16-inch lengths for each type of cable specified. 28
INFORMATIONAL SUBMITTALS 30
Qualification Data: For Installer. 32 Material Certificates: For each type of cable and accessory. 34 Source quality-control reports. 36 Field quality-control reports. 38
QUALITY ASSURANCE 40
Installer: Engage a cable splicer, trained and certified by splice material manufacturer, to install, splice, and 42 terminate medium-voltage cable. 43
FIELD CONDITIONS 45
Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by Owner or 47 others unless permitted under the following conditions and then only after arranging to provide temporary 48 electric service according to requirements indicated: 49
1. Notify Construction Manager no fewer than five days in advance of proposed interruption of electric 50 service. 51
2. Do not proceed with interruption of electric service without Construction Manager's written 52 permission. 53
Repair (R/M) Electrical Lines – 26 05 13-2 156-011
(114009) Revised July 2013 2012 by FEI
B. PRODUCTS 1
MANUFACTURERS 3
Manufacturers: Subject to compliance with requirements available manufacturers offering products that may 5 be incorporated into the Work include, but are not limited to, the following: 6
1. Cables: 7
a. Aetna Insulated Wire, Inc.; a Berkshire Hathaway company. 8
b. General Cable Technologies Corporation. 9
c. Kerite; a Marmon Wire & Cable/Berkshire Hathaway company. 10
d. Okonite Company (The). 11
e. Prysmian Cables & Systems. 12
f. Southwire Company. 13
2. Cable Splicing and Terminating Products and Accessories: 14
a. Adalet; a Scott Fetzer company. 15
b. DSG-Canusa; a Shawcor company. 16
c. Engineered Products Company. 17
d. G&W Electric Company. 18
e. MP Husky. 19
f. RTE Components; Cooper Power Systems, Inc. 20
g. Thomas & Betts Corporation. 21
h. Thomas & Betts Corporation/Elastimold. 22
i. 3M; Electrical Markets Division. 23
j. Tyco Electronics; Raychem Products. 24
Source Limitations: Obtain cables and accessories from single source from single manufacturer. 26
SYSTEM DESCRIPTION 28
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified 30 testing agency, and marked for intended location and application. 31 Comply with IEEE C2 and NFPA 70. 33
CABLES 35
Cable Type: Type MV 105. 37 Comply with UL 1072, AEIC CS8, and ICEA S-94-649. 39 Conductor: Aluminum. 41 Conductor Stranding: Compact round, concentric lay, Class B. 43 Conductor Insulation: Ethylene-propylene rubber. 45
1. Voltage Rating: 15 kV. 46
2. Insulation Thickness: 133 percent insulation level. 47 100% Copper Concentric Neutral. 49
Cable Jacket: Sunlight-resistant PVC. 51 http://www.specagent.com/LookUp/?ulid=1693&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456836318&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802845&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817805&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802846&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456836319&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802849&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1696&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456836320&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456836321&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802850&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802851&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802852&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817807&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802853&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802853&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817809&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456836322&mf=04&src=wd
Repair (R/M) Electrical Lines – 26 05 13-3 156-011
(114009) Revised July 2013 2012 by FEI
CONNECTORS 1
Comply with ANSI C119.4 for connectors between aluminum conductors or for connections between 3 aluminum to copper conductors. 4
SOLID TERMINATIONS 6
Shielded Cable Terminations: Comply with the following classes of IEEE 48. Insulation class is equivalent to 8 that of the cable. Include shield ground strap for shielded cables. 9
1. Class 1 Terminators: Modular type, furnished as a kit, with stress-relief tube; multiple, molded-10 silicone rubber, insulator modules; shield ground strap; and compression type connector. 11
2. Class 1 Terminators: Heat-shrink type with heat-shrink inner stress control and outer nontracking 12 tubes; multiple, molded, nontracking skirt modules; and compression type connector. 13
3. Class 1 terminators: Modular type, furnished as a kit, with stress relief shield terminator; Multiple-wet-14 process, porcelain modules: shield ground strap; and compression type connector. 15
SEPARABLE INSULATED CONNECTORS 18
Description: Modular system, complying with IEEE 386, with disconnecting, single-pole, cable terminators 20 and with matching, stationary, plug-in, dead-front terminals designed for cable voltage and for sealing against 21 moisture. 22 Terminations at Distribution Points: Modular type, consisting of terminators installed on cables and modular, 24 dead-front, terminal junctions for interconnecting cables. 25 Load-Break Cable Terminators: Elbow-type units with 200-A-load make/break and continuous-current rating; 27 coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test 28 point on terminator body that is capacitance coupled. 29 Dead-Front Terminal Junctions: Modular bracket-mounted groups of dead-front stationary terminals that 31 mate and match with above cable terminators. Two-, three-, or four-terminal units as indicated, with fully 32 rated, insulated, watertight conductor connection between terminals and complete with grounding lug, 33 manufacturer's standard accessory stands, stainless-steel mounting brackets, and attaching hardware. 34
1. Protective Cap: Insulating, electrostatic-shielding, water-sealing cap with drain wire. 35
2. Portable Feed-Through Accessory: Two-terminal, dead-front junction arranged for removable 36 mounting on accessory stand of stationary terminal junction. 37
3. Grounding Kit: Jumpered elbows, portable feed-through accessory units, protective caps, test rods 38 suitable for concurrently grounding three phases of feeders, and carrying case. 39
4. Standoff Insulator: Portable, single dead-front terminal for removable mounting on accessory stand 40 of stationary terminal junction. Insulators suitable for fully insulated isolation of energized cable-41 elbow terminator. 42
Test-Point Fault Indicators: Applicable current-trip ratings and arranged for installation in test points of load-44 break separable connectors, and complete with self-resetting indicators capable of being installed with 45 shotgun hot stick and tested with test tool. 46 Tool Set: Shotgun hot stick with energized terminal indicator, fault-indicator test tool, and carrying case. 48
MEDIUM-VOLTAGE TAPES 50
Ethylene/propylene rubber-based, 30-mil splicing tape, rated for 130 deg C operation. Minimum 3/4 inch 52 wide. 53
ARC-PROOFING MATERIALS 55
Repair (R/M) Electrical Lines – 26 05 13-4 156-011
(114009) Revised July 2013 2012 by FEI
Tape for First Course on Metal Objects: 10-mil- thick, corrosion-protective, moisture-resistant, PVC pipe-1 wrapping tape. 2 Arc-Proofing Tape: Fireproof tape, flexible, conformable, intumescent to 0.3 inch thick, and compatible with 4 cable jacket. 5 Glass-Cloth Tape: Pressure-sensitive adhesive type, 1 inch wide. 7
FAULT INDICATORS 9
Resetting Tool: Designed for use with fault indicators, with moisture-resistant storage and carrying case. 11
SOURCE QUALITY CONTROL 12
Test and inspect cables according to ICEA S-97-682 before shipping. 14
C. EXECUTION 16
INSTALLATION 18
Install cables according to IEEE 576. 20
Proof conduits prior to conductor installation by passing a wire brush mandrel and then a rubber duct swab 22 through the conduit. Separate the wire brush and the rubber swab by 48 to 72 inches on the pull rope. 23
1. Wire Brush Mandrel: Consists of a length of brush approximately the size of the conduit inner 24 diameter with stiff steel bristles and an eye on each end for attaching the pull ropes. If an obstruction 25 is felt, pull the brush back and forth repeatedly to break up the obstruction. 26
2. Rubber Duct Swab: Consists of a series of rubber discs approximately the size of the conduit inner 27 diameter on a length of steel cable with an eye on each end for attaching the pull ropes. Pull the 28 rubber duct swab through the duct to extract loose debris from the duct. 29
Pull Conductors: Do not exceed manufacturer's recommended maximum pulling tensions and sidewall 31 pressure values. 32
1. Where necessary, use manufacturer-approved pulling compound or lubricant that does not 33 deteriorate conductor or insulation. 34
2. Use pulling means, including fish tape, cable, rope, and basket-weave cable grips, that do not 35 damage cables and raceways. Do not use rope hitches for pulling attachment to cable. 36
3. Use pull-in guides, cable feeders, and draw-in protectors as required to protect cables during 37 installation. 38
4. Do not pull cables with ends unsealed. Seal cable ends with rubber tape. 39
Install "buried-cable" warning tape 12 inches above cables. 41
In handholes, pull boxes and junction boxes, train cables around walls by the longest route from entry to exit; 43 support cables at intervals adequate to prevent sag. 44 Install sufficient cable length to remove cable ends under pulling grips. Remove length of conductor damaged 46 during pulling. 47 Install cable splices at pull points and elsewhere as indicated; use standard kits. Use dead-front separable 49 watertight connectors in manholes and other locations subject to water infiltration. 50 Install terminations at ends of conductors. 52 Install separable insulated-connector components as follows: 54
1. Protective Cap: At each terminal junction, with one on each terminal to which no feeder is indicated 55 to be connected. 56
Repair (R/M) Electrical Lines – 26 05 13-5 156-011
(114009) Revised July 2013 2012 by FEI
2. Portable Feed-Through Accessory: At each terminal junction, with one on each terminal. 1
3. Standoff Insulator: At each terminal junction, with one on each terminal. 2
Arc Proofing: Unless otherwise indicated, arc proof medium-voltage cable at locations not protected by 4 conduit, cable tray, direct burial, or termination materials. In addition to arc-proofing tape manufacturer's 5 written instructions, apply arc proofing as follows: 6
1. Clean cable sheath. 7
2. Wrap metallic cable components with 10-mil pipe-wrapping tape. 8
3. Smooth surface contours with electrical insulation putty. 9
4. Apply arc-proofing tape in one half-lapped layer with coated side toward cable. 10
5. Band arc-proofing tape with two layers of 1-inch- wide half-lapped, adhesive, glass-cloth tape at each 11 end of the arc-proof tape. 12
Install fault indicators on each phase. 14
Ground shields of shielded cable at terminations, splices, and separable insulated connectors. Ground metal 16 bodies of terminators, splices, cable and separable insulated-connector fittings, and hardware. 17 Identify cables according to Section 26 05 53 "Identification for Electrical Systems." Identify phase and circuit 19 number of each conductor at each splice, termination, pull point, and junction box. Arrange identification so 20 that it is unnecessary to move the cable or conductor to read the identification. 21
FIELD QUALITY CONTROL 23
Testing Agency: Engage a qualified testing agency to perform tests and inspections. 25 Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect 27 components, assemblies, and equipment installations, including connections. 28
Perform the following tests and inspections: 30
1. Perform each visual and mechanical inspection and electrical test stated in NETA ATS. Certify 31 compliance with test parameters. 32
2. After installing medium-voltage cables and before electrical circuitry has been energized, test for 33 compliance with requirements. 34
3. Perform direct-current High Potential test of each new conductor according to NETA ATS, Ch. 7.3.3. 35
Do not exceed cable manufacturer's recommended maximum test voltage. 36 Medium-voltage cables will be considered defective if they do not pass tests and inspections. 38 Prepare test and inspection reports. 40
END OF SECTION 42