Amendment_3_19Q0075_Q&A_12_June_19.pdf
PDF 254 KB Posted
- Attached to
- B2 Wing Maintenance Stand Federal contract opportunity
- Solicitation number
- FA462519Q0075
About this file
Amendment 3: FA462519Q0075 Q&A dtd 12 June 19 Cabinet renderings for reference use only. Contractor-created cabinet drawings must be included with Specification Drawings as stated in the Combined Synopsis/Solicitation dtd 22 May 19.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA462519Q0075_Q&A_5_June_2019.pdf | ||
| Q&A_Amendment_Acknowledgement.docx | DOCX document | |
| FA462519Q0075_Q&A_30_May_2019.pdf | ||
| FA462519Q0075_Combo_22May19.pdf | ||
| FA462519Q0075_Atch_2_Bid_Schedule.xlsx | XLSX spreadsheet | |
| FA462519Q0075_Atch_3_PPQ.pdf | ||
| FA462519Q0075_Atch_1_SOW_21May19.pdf | ||
| FA462519Q0075_Atch_4_Clauses_dtd_22May19.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B2 Wing Maintenance Stand
FA462519Q0075
13 June 2019
Q & A
Q: – Ref: #9 Drawers, Work stand specifications.
Please confirm, drawers will be 3” deep (total 9” for 3 drawer assembly)
What is the preferred height from the working deck for the top drawer?
Is it the design intent that the drawers & cabinet units be independently mobile from the stand modules?
A: The lip on the each drawer will be 3”. The 3 drawers need to be at least 6” from the ground and at least 6” below the bottom of the decking. If the working deck height is 35” (ref Q&A dtd 30 May 19) then subtracting the 12” listed previously in the question gives 23” of usable space. Each drawer front will have a 3” lip. Evenly dividing the 23” of usable space leaves roughly 7.6” of height per drawer.
Drawers are made to be permanently installed. (See Attached Rendering)
Q: Ref: #2, Q&A responses June 5.
Please clarify access requirements, per Q&A response May 30 a total of 6 access stairways are required, please clarify if additional ladder type access is required and its location.
A: The ladder will be on the aft portion of the center module.
Q: Ref: #14, Q&A responses June 5.
Are cabinets required to be open on one side or would doors be preferred/desirable?
A: Cabinets shall not have doors on the front. The cabinets shall be enclosed on the 3 sides that overhang the stand.
Rendering is For Reference Use Only. The image below depicts a Left Wing Maintenance Stand. The dimensions listed shall be followed for the Right Wing Stand as well. Contractor-created cabinet drawings shall be included in Specification Drawings as required by the Combined Synopsis/Solicitation dated
22 May 19.