SF30 Amendment 0002.pdf
PDF 142 KB Posted
- Solicitation number
- FA462021QA211
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXCEPTION OF SF 30, APPROVED BY NARS 5/79
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
PAGE OF PAGES
2. AMENDMENT/MODIFICATION NO.
3. EFFECTIVE DATE
19 April 2021
4. REQUISITION/PURCHASE REQ. NO.
5. PROJECT NO. (If applicable)
6. ISSUED BY
CODE
7. ADMINISTERED BY (If other than Item 6)
CODE
92nd Contracting Sq./PKA 110 W Ent St., Suite 200 SAME AS BLOCK 6
Fairchild AFB, WA 99011 Attn: roy.nichols.1@us.af.mil and clifford.dockter@us.af.mil
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) () 9A. AMENDMENT OF SOLICITATION NO.
X
FA462021QA211
All Offerors 9B. DATED (SEE ITEM 11)
01 April 2021
10A. MODIFICATION OF CONTRACT/ORDER
NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
[X] The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers [ ] is extended, [X] is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing Items 8 and 15, and returning _1_ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c)
By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACT/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
() A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor [ ] is not, [X] is required to sign this document and return _1_ copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
SEE SUMMARY OF CHANGES
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10 A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA
BY
(Signature of Contracting Officer)
16C. DATE SIGNED
NSN 7540-01-152-8070 30-105-03 STANDARD FORM 30 (REV. 10-83)
PREVIOUS EDITION UNUSABLE Prescribed by GSA
FA462021QA211
Amendment 0002 Page 2
SUMMARY OF CHANGES
1. The purpose of this amendment is to add Q&A to the solicitation.
Q1: Please provide the GPM required on the pumps.
A1: 75 GPM @ Approximate 25 FT head min
Q2: Please provide Voltage & Phase.
A2: 230v/1ᴓ
Q3: Please provide TDH. TDH is required to make sure the new pumps will meet demand.
A3: 75 GPM @ Approximate 25 FT head min
Q4: Can the model number of the Control Panel be provided? If not, we may be able to quote off of the picture shown in appendix B.
A4: Control Panel to be NEMA rated for outdoor conditions, configurable for duplex operation, 230v/1ᴓ, UL approved and Digital Programmable w/ MOD-Buss or Telemetry output.
Q5: Can the serial number on the pumps be provided to see if they are in the data base for PACO.
FYI, PACO pumps was purchased by Grundfos pumps several years ago. So, the information in Appendix B is obsolete as they are not located in Spokane anymore. I am in contact with the rep and the old PACO rep works for them now and may be able to give some direction
A5: Model NO: 58-47015-5532
Serial NO: 96B01726-01 &96B01726-02
Order Number: 0513-96-1000
Conditions: 75 GPM@20 FT TDH | 5.3” Impeller Trim
Motor: 2HP, 1Phase, 230 V, 60 Hertz, 1750 RPM, Explosion Proof Motor.
Most all of the above information is in the SOW.
Please remember to complete Blocks 8 and 15a, 15b, and 15c of this amendment.
END SUMMARY OF CHANGES