FA461019RA027
Attachment 7
PADMOUNT TRANSFORMER SPECIFICATIONS
(Typical)
In Accordance With UFGS 33 70 02-00.10 and UFC 3-550-01
• All stainless steel (Alloy 316) construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.)
• “Pentahead” Cabinet Locking Mechanism/Device
• Dead Front Construction (HV - 200A load break elbows with shield adapters)
• Externally clamped LV bushings with threaded copper stud for full load current below 2,100 amperes - NEMA spades shall be provided per ANSI hole requirements
• Radial Feed
• KVA: As Required
• Primary Voltage: 12kV Delta
• Secondary Voltage: As Required
• 3- Phase Transformer
• Frequency: 60Hz
• Windings: Copper
• Mineral Oil-Filled (Non-PCB): Type FR-3 Fluid
• Standard Impedance
• Mild steel high-voltage/low-voltage compartment barriers
• Metal Oxide Varistor (MOV) surge arresters
• Cooling Fins
• Proper grounding provisions
• Dial type gauges for oil temperature, liquid level, and pressure/vacuum
• Bay-O-Net Fuses & Current-Limiting Fuses: Properly-sized - Additionally, the transformer will include 3 spare fuses
• Two-Position “ON/OFF” Load Break Primary Switch
• 5-Position Tap Changer: (-5%, -2½%. 0, +2½%, +5%)
• Automatic pressure relief device mounted in the terminal compartment
• Oil drain valve with sampling device, and an oil fill/oil level plug
• Nameplate and NEMA Safety Labels: Include a “UL Listed” symbol on ratings label and nameplate
• Compliant with 2016 DOE Efficiency Standard
• Four (4) lifting lugs
• Entire exterior of the pad-mount transformer and terminal compartments shall be painted with a munsell green, outdoor finish
• Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient air temperature of 30°C when operated at rated voltage and load conditions
FA461019RA001
Attachment 7
Series of transformer tests (includes DGA) used to verify conformance to performance requirements as outlined in the latest revisions of ANSI C57.12.00 and ANSI C57.12.90. A report outlining successful test results must be completed and submitted to the Contracting Officer prior to final equipment acceptance