This document contains existing elevator drawings and specifications for Building 502 at Dover Air Force Base, as well as the related federal contract opportunity solicitation. The opportunity solicitation seeks a contractor to replace the roof snow retention system, one seven-story elevator, and repair tower HVAC components at Building 502 for the Department of the Air Force Air Mobility Command. The statement of work provides detailed requirements for the project scope, which includes all design, labor, materials, tools and equipment. The contractor must complete the work in accordance with the solicitation and attached documents.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELEVATOR NUMBER 1

ELEVATOR APPLICATION MACHINE ROOMLESS

CLASS OF LOADING PASSENGER

SEISMIC ZONE N/A

CAPACITY 2500 LB [1160 kg] SPEED, CONTRACT 350 FPM [1.75 m/s] CAB LIGHT 120 15 15 1 1

ROPING 2 : 1

LANDINGS / OPENINGS 4/4F CONTR SUPPLY 480 30 30 3 1 0

WEIGHT 2850LB[1292kg]

RAIL GUIDE TYPE SHOE

SAFETY TYPE DYNATECHPQ-3400-UD

WEIGHT ) 4100 LB [1859 kg]

OVER BALANCE 50%

STEEL BLOCKS QTY (1" TH'K) 100

RAIL GUIDE TYPE SHOE

CONSTRUCTION STEEL FRAME

CAR GUIDE RAIL SIZE 15 LB/FT[22.5 kg/m] CWT GUIDE RAIL SIZE 8 LB/FT[12 kg/m] GOVERNOR CABLE DIAMETER 1/4" [6.4 mm] GOVERNOR CABLE LENGTH 212 FT [65 m]

HOIST CABLE QUANTITY 6

HOIST CABLE DIAMETER 8 MM Drako 250T Steel Core HOIST CABLE LENGTH 235 FT [72 m] HOIST CABLE BREAKING STRENGTH 8723LB [38.8 kN] MAXIMUM RAIL BRACKET SPACING 12 FT [3658 mm]

CAR BUFFER TYPE OIL

CAR BUFFER LOAD RATING 2x6002AF2(1323-10000LB)[600-4535kg]

CWT BUFFER TYPE OIL

CWT BUFFER LOAD RATING 6002AF2(1323-10000LB)[600-4535kg] IND DRWN CHKD COMP. CHAIN//CABLE QTY x SIZE 1 x WF15 A OZ

MACHINE TYPE MAGIL MAG05-2535

MACHINE GEAR RATIO 1 : 1

DRIVE SHEAVE DIAMETER 15.75"[400 mm] IDLER SHEAVE DIAMETER 13" [330 mm] B MS

MOTOR SIZE 16.6 HP [12.4 kW]

DRIVE V.V.V.F

HEAT DISSIPATION IN MACHINERY SPACE 1x(2115Btu/h[0.61kW]) HEAT DISSIPATION IN CONTROL SPACE/ROOM 1x(11291Btu/h[3.31kW]) TWO HOIST HOOKS, EACH, STATIC 1.825KIPS [8kN]

R1 0.17KIPS [0.76 kN] R2 0.07 KIPS [0.31 kN] R1 N/A R2 N/A R1 0 KIPS [ 0 kN] R2 0.306 KIPS [1.36 kN]

R3U N/A R3D 10.1 KIPS [44.7 kN] R1 N/A R2 N/A

CAR BUFFER, EACH, DYNAMIC R4 11.66 KIPS [51.76kN] CWT BUFFER, EACH, DYNAMIC R5 17.87 KIPS [79.33kN] GOVERNOR, STATIC R6 0.4 KIPS [1.78 kN] GOVERNOR, DYNAMIC R6 1.5 KIPS [6.69 kN]

R7 10.38 KIPS [46.2 kN] R8 6.07 KIPS [27.0 kN] R9 3.22 KIPS [14.3 kN] R10 4.52 KIPS [20.1 kN]

CROSS HEAD SECTION 6"H x 2"W x 12GA UPRIGHT SECTION 8"Wx2.125"Hx1.1"WINGSx12GA SINGLE PLANK SECTION 7"H x 2.75"W x 10GA BOTTOM SHEAVE SUPPORT SECTION 7"Wx7"Hx2.5"WINGSx10GA JOB No. DWG. No.

DRAWN BY:C.CH

CHECKED BY:

DATE: 02/13/08

File: J082864L1B PAGE: 1 OF 4

PROVIDE VENTILATION IN 1) MACHINERY SPACE IN OVERHEAD; 2)

CONTROL SPACE OR ROOM IF PROVIDED, TO MAINTAIN TEMPERATURE

OF 41°F [5°C] TO 90°F [32°C]. FOR HEAT DISSIPATION AT 60% DUTY

CYCLE SEE GENERAL INFORMATION TABLE. HUMIDITY RANGE IS 0% TO

95% NON-CONDENSING.

DOVER AIR FORCE BASE

POCKETS FOR BEAMS AS SHOWN WHERE REQUIRED.

INFILL CAVITY AFTER BEAMS ARE SET IN PLACE.

ADDRESS:

DOVER, DELAWARE

DOVER AFB

ILLUMINATION AT SILL OF EVERY LANDING IS 100 LUX.

PROJECT:

AT OVERHEAD, PROVIDE 120V LIGHT FIXTURE, SWITCH AND

CONVENIENCE OUTLET. ILLUMINATION 200 LUX. MIN.

GENERAL INFORMATION

PREPARED FOR:

DELAWARE ELEVATOR INC.WIRE MESH PARTITION AS SHOWN WHERE REQUIRED.

PARTITION TO BE ABLE TO REJECT 2" [50 MM] DIA BALL AT

PIT LEVEL AND 1" [25 MM] AT HIGHER LEVELS. MINIMUM

PARTITION HEIGHT IS 6'-7" [2000 MM] OR OPENING HEIGHT

WHICHEVER IS LESS.

VOLTAGE & AMPERAGE DATA PROVISIONS BY OTHERS

PIT TO BE CONSTRUCTED PER ASME A17.1-2004 SECTION

2.2.2. PROVIDE DRAIN OR SUMP PUMP FOR ELEVATORS

WITH FIRE FIGHTER'S EMERGENCY OPERATION.

HOISTWAY AND CONTROL SPACE OR ROOM IN ACCORDANCE WITH

ELEVATOR SAFETY CODE REGULATIONS. HOISTWAY TO BE ERECTED

PLUMB 1/2" [±13 MM] THRUOUT.

NO CONDUIT WIRING OR PIPING OTHER THAN THAT

PERTAINING TO THIS ELEVATOR IS PERMITTED IN THE HOISTWAY AND

CONTROL SPACE OR ROOM.

DATE

24-Apr-08

REVISIONS

POCKETS FOR BEAMS AS SHOWN WHERE REQUIRED.

DO NOT INFILL CAVITY AFTER BEAMS ARE SET IN PLACE.

IN PIT PROVIDE 120 VOLT GUARDED LIGHT FIXTURES, SWITCH AND

CONVENIENCE OUTLET. SWITCH TO BE ON JAMB SIDE OF BOTTOM

LANDING DOOR.ILLUMINATION 100 LUX. MIN.

FOR JOBS ENGINEERED PER ASME A17.1 PROVIDE MEANS

OF ACCESS TO GOVERNOR(S) FOR INSPECTION AND

SERVICING (SECTION 2.1.3.1.2).

1-Aug-08

HOISTWAY SIZE WAS 8'-7"X 5'-9", CONTROLLER WAS

AT FRONT FLUSH MOUNTING, TRAVEL WAS 104'-9",

LANDING WAS 9, FLOOR HEIGHT REVISED, SHOW PIT

LADDER DETAIL WITH AND WITHOUT POCKET.

LANDINGS/OPENINGS WERE 7, FLOOR TO FLOOR HEIGHT

REVISED, TRANSFORMER DEL., RESISTOR AND POWER

UNIT RELOCATED IN CONTROLLER ROOM., HEAT

DISSIPATION REVISED

M A

X . R

A

IL

L O

AD

S

HOISTWAY ACCESS:

A) FOR SPEED 150 FPM [0.75 M/S] OR LESS PROVIDE H.I.S.

AT TOP LANDING WHEN DISTANCE FROM TOP OF CAR TO

TOP LANDING EXCEEDS 2'-11" [900 MM] WHEN CAR IS LEVEL

WITH LANDING BELOW TOP LANDING.

B) FOR SPEEDS MORE THAN 150 FPM [0.75 M/S] PROVIDE

H.I.S. AT TOP AND BOTTOM LANDINGS.

LOADING/

UNLOADING

SEISMIC

ACCESS TO CONTROL SPACE OR ROOM TO BE SAFE AND

CONVENIENT. IF A ROOM OR CLOSET IS PROVIDED, PROVIDE A DOOR

3'-0" [915 MM] WIDE x 6'-8" [2030 MM] HIGH MINIMUM. DOOR MUST BE

SELF CLOSING AND SELF LOCKING. GIVE KEYS TO AUTHORIZED

PERSONNEL ONLY. CLEAR HEAD ROOM NOT LESS THAN 7'-0"[2134 MM].

OPENINGS FOR ENTRANCES IN FRONT WALLS TO BE FILLED IN AFTER

ENTRANCE FRAMES HAVE BEEN INSTALLED. GROUT IN SILLS FULL

LENGTH.

NOTE: ENTRANCE FRAMES ARE NOT DESIGNED TO SUPPORT

OVERHEAD WALL LOADS. SUITABLE SUPPORTS FOR THESE LOADS

MUST BE PROVIDED BY OTHERS.

C A

R M

A C

H

IN

E C

W T

H O

IS

TW

AY

E

Q U

IP

M

EN

T

J082864L

CONTROL SYSTEM

C A

R S

LI

N

G

SAFETY APPL.

SEISMIC

C A

R C

W T

B U

IL

D

IN

G

R E

A C

TI

O

N S

MACHINE/ MACHINE BEAM, DYNAMIC

G E

N E

R A

L

1) ALWAYS PROVIDE AUXILIARY DISCONNECT SWITCH IN

OVERHEAD MACHINERY SPACE. SEE SCHEMATIC.

2) WHEN CONTROLLER IS IN PLACE ACCESSIBLE TO PUBLIC

PROVIDE LOCKABLE CIRCUIT BREAKERS IN CONTROL

CABINET.

Version: 0

ThyssenKrupp Elevator

J082864

SCALE: N.T.S.

B

HOIST HOOKS CAPABLE TO HANDLE MAXIMUM LOAD SHOWN ON

GENERAL INFORMATION TABLE.

FOR GROUPS OF ELEVATORS IN SAME HOISTWAY PROVIDE DIVIDER

BEAMS (I-BEAMS 4"[100 MM] WIDE MAX. WHERE SHOWN AT VERTICAL

INTERVALS NO GREATER THAN MAX. RAIL BRK'T SPACING PER

GENERAL INFORMATION TABLE. UPPER MOST BEAM AT DISTANCE

EQUALS CAB HEIGHT PLUS 3'-10"[1170 MM] ABOVE TOP LANDING.

ELEVATOR PIT LADDER TO COMPLY WITH

CAN/CSA B-44-04 OR ASME A17.1S-2004 (IF APPLY).

CWT RAIL, SMALLEST SIZE:

- 8 LB/FT [12 KG/M] FOR SEISMIC ZONE 1.

- 15 LB/FT [22.5 KG/M] FOR SEISMIC ZONES 2 OR GREATER.

REV.

DESIGNED PER ASME A17.1-2004 AND A17.1S-2005

PROPRIETARY RIGHTS OF THYSSENKRUPP NORTHERN ELEVATOR ARE INVOLVED IN THE

SUBJECT MATTER OF THIS MATERIAL AND ALL MANUFACTURING, REPRODUCTION, USE AND SALES RIGHTS PERTAINING TO SUCH SUBJECT MATTER ARE EXPRESSLY RESERVED. IT IS SUBMITTED IN CONFIDENCE FOR A SPECIFIED PURPOSE, AND THE RECIPIENT, BY ACCEPTING THIS MATERIAL, AGREES THAT THIS MATERIAL WILL NOT BE USED, COPIED OR REPRODUCED IN WHOLE OR IN PART, OR ITS CONTENTS REVEALED IN ANY MANNER, OR TO ANY PERSON, EXCEPT FOR THE PURPOSE

DELIVERED.

SUPPORT BEAMS WHERE REQUIRED AND AS SHOWN. MAXIMUM

DEFLECTION IS 1/1666 OF BEAM FREE SPAN.

ADEQUATE SUPPORTS FOR RAIL BRACKETS AT VERTICAL INTERVALS

NO GREATER THAN MAX. RAIL BRACKET SPACING SHOWN ON GENERAL

INFORMATION TABLE. HIGHEST SUPPORT AT DISTANCE EQUAL CAB

HEIGHT PLUS 3'-8"[1120 MM] ABOVE TOP LANDING. SUPPORTS TO BE

EITHER BUILDING BEAMS, INSERTS, OR BANDS MADE OF 3000 PSI [20

MPa] CONCRETE 8" [200 MM] X 6" [150 MM] MIN.

PIT LADDER, LOWEST LANDING HALL DOOR IS ALSO

PROVIDED WITH HAND GRIPS TO 48" [12220 MM] ABOVE

LANDING LEVEL.

TI

M

E D

E

LA

Y 'D

' F U

S E

(A M

P

P H

A S

E

PROVISIONS BY OTHERS

PROVIDE ONE COMPENSATION CHAIN IF REQUIRED.

MINIMUM PIT DEPTH IS 5 FT.

NOTES

PIT STOP SWITCH IS 1'-6' [450 MM] ABOVE BOTTOM

LANDING.

IF PIT DEPTH EXCEEDS 5'-7" [1700 MM], PROVIDE ONE MORE

SWITCH 3'-11" [1200 MM] ABOVE PIT FLOOR.

WHERE POWER IS AVAILABLE FROM MULTIPLE SOURCES, PROVIDE

POWER TRANSFER SWITCH(ES) WITH TIME DELAY OF APPROX. 10

SECONDS BETWEEN THE REMOVAL AND REAPPLICATION OF POWER

TO LOAD FROM ANY SOURCE.

CAR RAIL, SMALLEST SIZE:

- 15 LB/FT [22.5 KG/M] FOR SEISMIC ZONE 1

- FOR SEISMIC ZONES 2 OR GREATER T.B.A. BY

ENGINEERING

TOE GUARD:

2'-0" [610 MM] FOR PIT DEPTH LESS THAN 5'-0"[1524 mm], 4'-0" [1220 MM] FOR PIT DEPTH 5'-0"[1524 mm] AND MORE

A) WHEN CONTROLLER IS IN PLACE ACCESSIBLE TO PUBLIC PROVIDE

SEPARATE OPTIONAL SWITCHES IN BUILDING ELECTRICAL ROOM;

ELECTRICAL POWER SUPPLY TO TERMINATE AT THE CONTROLLER

CABINET; REFER TO CONTRACT FOR CABINET LOCATION.

B )WHEN CONTROLLER IS IN CONTROL ROOM OR CLOSET NOT

ACCESSIBLE TO PUBLIC PROVIDE LOCKABLE FUSED DISCONNECTS

SWITCHES OR CIRCUIT BREAKERS IN CONTROL ROOM OR CLOSET.

SEE VOLTAGE & AMPERAGE DATA IN TABLE ABOVE.

EQUIPMENT

LI

N

E V

O

LT

A G

E

D

IS

C O

N N

E C

T S

IZ

E

(A M

P

MIN. CLEARANCE REQ'D IN FRONT OF ELECTRICAL PANELS:

- 3'-3 1/2" [1000 MM] IN CANADA;

- 3'-6" [1070 MM] EXCEPT 4'-0" [1220 MM] WHEN FACING

EACH OTHER IN U.S.A.

IN THE CONTROL SPACE OR ROOM, PROVIDE 120 VOLT LIGHT

FIXTURES, SWITCH AND CONVENIENCE OUTLET. SWITCH TO BE INSIDE,

ON LOCK SIDE OF DOOR. ILLUMINATION 200 LUX. MIN.

Q

TY

R E

Q 'D

FU

S

E D

Q

TY

R E

Q 'D

U N

FU

S

E D

T I M E

A

FINAL

J082864L1B
J082864L2B
J082864L3B
J082864L4B
07-21-2008