AF Form 332 Additional Remarks from 502 CES/CEI

WO # 11549 , B83, Inspect and Abate, Demo Building and replace 06/24/2014

INSPECT AND ABATE MODULAR BUILDING INSIDE HANGAR 83

DEMO RENOVATE OR REPLACE MODULAR BUILDING INSlDE HANGAR Element Chief/CEAN Alvin Brown

Insure all Environmental Specifications are included in all contract documents

Toxics Edward Vogel

08/11/2014 - Work Order 11549 - All sheetrock, HDUCT Mastic is NAD, (No Asbestos Detected) for Asbestos Containing Materials. A Demolition Notification is required to be filed with the State 10 days prior to demol;ition.

Notify CEIE for demolition Notification submission. 652-3685.

PCB

All light fixtures must be checked for PCB Ballasts. If ballasts are not marked “NO PCBs” then ballasts must be handled as PCB Waste, or recycled at an approved EPA PCB Recycling Facility . PCB’s must be packaged IAW DOT regulations and Manifested. Recycling Certificate Required if Recycled

Light Bulbs, All fluorescent lamps are known to contain Mercury in small amounts. All lamps must be removed from fixture packaged IAW DOT regulations and manifested to an approved EPA recycling facility or handled as Universal Waste in the State of Texas.

08/11/2014 - Work Order 11549 - All areas related to the demolition of the portable building inside Hangar 83 is Negative for Lead Based Paint.

Recycling Coordinator AST/USTs Vacant no issues regarding the Tanks Program...

PCB

All light fixtures must be checked for PCB Ballasts. If ballasts are not marked “NO PCBs” then ballasts must be handled as PCB Waste, or recycled at an approved EPA PCB Recycling Facility . PCB’s must be packaged IAW DOT regulations and Manifested. Recycling Certificate Required if Recycled

Light Bulbs, All fluorescent lamps are known to contain Mercury in small amounts. All lamps must be removed from fixture packaged IAW DOT regulations and manifested to an approved EPA recycling facility or handled as Universal Waste in the State of Texas.

Drinking Water -- Wastewater Storm water Bryan Harvey

Ensure that storm drains near this construction are properly protected to prevent sediment from entering system. Sweep sediment from pavement periodically. If soil disturbance is 1 acre or greater site must comply with the TPDES TXR150000 construction general permit, which requires development of a Storm Water Pollution Prevention Plan (SWPPP). SWPPP must be submitted to Water Quality Manager for review prior to start of construction. 27 Jun 2014

Hazardous Materials Jordan Palombo Adrian Scott

Please provide all MSDS associated with this project to HazMat Manager, Jordan Palombo or Adrian Scott @ 652‐3062.

Katherine Mehaffey

IRP

Location is near closed IRP site, SS-22. Any suspect contaminated soil removed needs to be sampled and disposed of properly and CEIE Restoration Program Mgr must be contacted. KAM- 25Jun14

Green Procurement Vacant

"Green"/energy efficient materials/equipment must be considered first and foremost. Complete AETC Form 47 and/or 51 as applicable."

Historical David Brigham

No effect. Work may proceed

Air Katherine Mehaffey

Minimize nuisance dust emissions. Any painting or staining operations must use LOW VOC coating materials. KAM-25Jun14

Natural Resources Shannon Carrasco

11549- No Natural Resource issues

Real Estate Specialist Yvette Sampson

Send all closed work orders thru ACESRP for capitalization if project exceeds $20K or changes the square footage -YDS-06/24/2014

By Polarized Light Microscopy EPA Method: 600/R-93/116 and 600/M4-82-020

LAB #173190

1415166Lab Order ID:

83_11549_693_Chiller Loop Project_63_Roof Project

Project:

8/7/2014Date Received:

8/8/2014Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Edward VogelAttn:

1415166_PLMAnalysis ID:

Customer: 502 CES/CEIE 1651 5th Street West IBSA Randolph TX 78150

None Detected

83-HMAS-

001-B-001

South side of Portable Building; HDUCT Mastic

White Non Fibrous Heterogeneous

Dissolved1415166PLM_1

Other100%

None Detected

83-HMAS-

001-B-002

South side of Portable Building; HDUCT Mastic

White Non Fibrous Heterogeneous

Dissolved1415166PLM_2

Other100%

None Detected

83-HMAS-

001-B-003

South side of Portable Building; HDUCT Mastic

White Non Fibrous Heterogeneous

Dissolved1415166PLM_3

Other100%

None Detected

83-WLSH-

001-B-004

Portable Building; Sheetrock;

North;Out

White Non Fibrous Heterogeneous

Teased1415166PLM_4

Cellulose Other5% 95%

None Detected

83-WLSH-

001-B-005

Portable Building; Sheetrock;

East;Out

White Non Fibrous Heterogeneous

Teased1415166PLM_5

Cellulose Other10% 90%

None Detected

83-WLSH-

001-B-006

Portable Building; Sheetrock;

South;Out

White Non Fibrous Heterogeneous

Teased1415166PLM_6

Cellulose Other5% 95%

None Detected

83-WLSH-

001-B-007

Portable Building; Sheetrock;

North;In

White Non Fibrous Heterogeneous

Teased1415166PLM_7

Cellulose Other10% 90%

None Detected

83-WLSH-

001-B-008

Portable Building; Sheetrock;

East In

White Non Fibrous Heterogeneous

Teased1415166PLM_8

Cellulose Other10% 90%

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Byron Stroble (43) plm_3.3.009

All sheetrock, HDUCT Mastic is NAD, (NoAsbestos Detected) for Asbestos Containing Materials. A Demolition Notification is required to be filed with the State 10 days prior to demol;ition.Notify CEIE for demolition Notification submission. 652-3685.

1150049179C Cert

LAB #173190

1415166Lab Order ID:

83_11549_693_Chiller Loop Project_63_Roof Project

Project:

8/7/2014Date Received:

8/8/2014Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Edward VogelAttn:

1415166_PLMAnalysis ID:

Customer: 502 CES/CEIE 1651 5th Street West IBSA Randolph TX 78150

None Detected

83-WLSH-

001-B-009

Portable Building; Sheetrock;

West;In

White Non Fibrous Heterogeneous

Teased1415166PLM_9

Cellulose Other5% 95%

None Detected

693-CLSH-

001-B-001

Mechanical; Ceiling Sheetrock Brown, White Non Fibrous Heterogeneous

Teased1415166PLM_10

Cellulose Other5% 95%

None Detected

693-CLSH-

001-B-002

Mechanical; Ceiling Sheetrock Brown, White Non Fibrous Heterogeneous

Teased1415166PLM_11

Cellulose Other10% 90%

None Detected

693-CLSH-

001-B-003

Mechanical; Ceiling Sheetrock Brown, White Non Fibrous Heterogeneous

Teased1415166PLM_12

Cellulose Other10% 90%

None Detected

693-HMAS-

001-B-004

Mechanical; HDUCT Mastic;

AHU1

mixed mastic

White, Black Non Fibrous Heterogeneous

Dissolved1415166PLM_13

Cellulose Other10% 90%

None Detected

693-HMAS-

001-B-005

Mechanical; HDUCT Mastic;

AHU1

White Non Fibrous Heterogeneous

Dissolved1415166PLM_14

Cellulose Other5% 95%

None Detected

693-HMAS-

001-B-006

Mechanical; HDUCT Mastic;

AHU1

White Non Fibrous Heterogeneous

Dissolved1415166PLM_15

Cellulose Other5% 95%

None Detected

693-WLJ-

001-B-007

Mechanical; Wall Joint Compound; South

White Non Fibrous Heterogeneous

Teased1415166PLM_16

Other100%

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Byron Stroble (43) plm_3.3.009

LAB #173190

1415166Lab Order ID:

83_11549_693_Chiller Loop Project_63_Roof Project

Project:

8/7/2014Date Received:

8/8/2014Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Edward VogelAttn:

1415166_PLMAnalysis ID:

Customer: 502 CES/CEIE 1651 5th Street West IBSA Randolph TX 78150

None Detected

693-WLJ-

001-B-008

Mechanical; Wall Joint Compound; West

White Non Fibrous Heterogeneous

Teased1415166PLM_17

Other100%

None Detected

693-WLJ-

001-B-009

Mechanical; Wall Joint Compound; West

White Non Fibrous Heterogeneous

Teased1415166PLM_18

Other100%

None Detected

693-PWRP-

001-B-0010

Mechanical Room; Pipe Wrap;

White; 1

White, Tan Non Fibrous Heterogeneous

Dissolved1415166PLM_19

Fiber Glass Cellulose

Other 20% 20%

60%

None Detected

693-PWRP-

001-B-0011

Mechanical Room; Pipe Wrap;

White; 2

White, Tan Non Fibrous Heterogeneous

Dissolved1415166PLM_20

Fiber Glass Cellulose

Other 20% 20%

60%

None Detected

693-PWRP-

001-B-0012

Mechanical Room; Pipe Wrap;

White; 3

Tan, White Non Fibrous Heterogeneous

Dissolved1415166PLM_21

Fiber Glass Cellulose

Other 20% 20%

60%

5% Chrysotile

693-HMAS-

001-B-0013

Mechanical Room;HDUCT Mastic;Black

Black Non Fibrous Heterogeneous

Dissolved1415166PLM_22

Other95%

Not Analyzed

693-HMAS-

001-B-0014

Mechanical Room;HDUCT Mastic;Black

1415166PLM_23

Not Analyzed

693-HMAS-

001-B-0015

Mechanical Room;HDUCT Mastic;Black

1415166PLM_24

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

LAB #173190

1415166Lab Order ID:

83_11549_693_Chiller Loop Project_63_Roof Project

Project:

8/7/2014Date Received:

8/8/2014Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Edward VogelAttn:

1415166_PLMAnalysis ID:

Customer: 502 CES/CEIE 1651 5th Street West IBSA Randolph TX 78150

None Detected

63-RFROLL-0012-

B-001 - A

Roof; Roll Roofing Felt and Tar; Lean Too 1 tar

Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_25

Cellulose Other10% 90%

None Detected

63-RFROLL-0012-

B-001 - B

Roof; Roll Roofing Felt and Tar; Lean Too 1 felt

Black Fibrous Heterogeneous

Teased, Dissolved1415166PLM_39

Fiber Glass Other70% 30%

None Detected

63-RFROLL-0012-

B-002 - A

Roof; Roll Roofing Felt and Tar; Lean Too 1 tar

Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_26

Cellulose Other10% 90%

None Detected

63-RFROLL-0012-

B-002 - B

Roof; Roll Roofing Felt and Tar; Lean Too 1 felt

Black Fibrous Heterogeneous

Teased, Dissolved1415166PLM_40

Fiber Glass Other70% 30%

None Detected

63-RFROLL-0012-

B-003 - A

Roof; Roll Roofing Felt and Tar; Lean Too 2 tar

Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_27

Cellulose Other10% 90%

None Detected

63-RFROLL-0012-

B-003 - B

Roof; Roll Roofing Felt and Tar; Lean Too 2 felt

Black Fibrous Heterogeneous

Teased, Dissolved1415166PLM_41

Fiber Glass Other70% 30%

None Detected

63-RFROLL-0012-

B-004 - A

Roof; Roll Roofing Felt and Tar; Lean Too 3 tar

Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_28

Cellulose Other10% 90%

None Detected

63-RFROLL-0012-

B-004 - B

Roof; Roll Roofing Felt and Tar; Lean Too 3 felt

Black Fibrous Heterogeneous

Teased, Dissolved1415166PLM_42

Fiber Glass Other70% 30%

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

LAB #173190

1415166Lab Order ID:

83_11549_693_Chiller Loop Project_63_Roof Project

Project:

8/7/2014Date Received:

8/8/2014Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Edward VogelAttn:

1415166_PLMAnalysis ID:

Customer: 502 CES/CEIE 1651 5th Street West IBSA Randolph TX 78150

None Detected

63-RFSLR-

0012-B-005

Roof Sealer;Black; Lean Too

Black Non Fibrous Heterogeneous

Dissolved1415166PLM_29

Other100%

None Detected

63-RFSLR-

0012-B-006

Roof Sealer; /Black; Lean Too

Black Non Fibrous Heterogeneous

Dissolved1415166PLM_30

Other100%

None Detected

63-RFSLR-

0012-B-007

Roof Sealer; /Black; Lean Too

Black Non Fibrous Heterogeneous

Dissolved1415166PLM_31

Other100%

None Detected

63-RFSLR-

0012-B-008

Roof Sealer; Gray/Black;

Around Vent

Gray, Black Non Fibrous Heterogeneous

Dissolved1415166PLM_32

Cellulose Other5% 95%

None Detected

63-RFSLR-

0012-B-009

Roof Sealer; Gray/Black; Lean Too 2

Gray, Black Non Fibrous Heterogeneous

Dissolved1415166PLM_33

Other100%

None Detected

63-RFSLR-

0012-B-010

Roof Sealer; Gray/Black; Lean Too 3

Gray, Black Non Fibrous Heterogeneous

Dissolved1415166PLM_34

Cellulose Other5% 95%

None Detected

63-RFSLR-

0012-B-011

Roof Sealer; Red/Black; Lean Too Drain

Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_35

Cellulose Other10% 90%

None Detected

63-RFSLR-

0012-B-012

Roof Sealer; Red/Black;Wall Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_36

Cellulose Other5% 95%

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

LAB #173190

1415166Lab Order ID:

83_11549_693_Chiller Loop Project_63_Roof Project

Project:

8/7/2014Date Received:

8/8/2014Date Reported:

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos Fibrous

Components Non-Fibrous Components

Attributes

Treatment

Edward VogelAttn:

1415166_PLMAnalysis ID:

Customer: 502 CES/CEIE 1651 5th Street West IBSA Randolph TX 78150

None Detected

63-RFSLR-

0012-B-013

Roof Sealer; Red/Black; Pipe Black, Red Non Fibrous Heterogeneous

Dissolved1415166PLM_37

Cellulose Other10% 90%

None Detected

63-WLFLT-0012-

B-0014 - A

Roof; Wall Felt; Parapet tar

Black Non Fibrous Heterogeneous

Dissolved1415166PLM_38

Cellulose Other15% 85%

None Detected

63-WLFLT-0012-

B-0014 - B

Roof; Wall Felt; Parapet felt

Black Fibrous Heterogeneous

Teased, Dissolved1415166PLM_43

Fiber Glass Other60% 40%

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.1%.

Approved SignatoryAnalyst

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Scientific Analytical Institute 4604 Dundas Dr. Greensboro, He 27407

Phone: 336.292.3888 Fax: 336.292.3313 www.sailab.comlab@sailab.com f:: ~~~n~: /';15/ ~b Client Code: _______

Contact: 3 Hours 0 72 Hours

Address: 6 Hours 0 96 Hours

12 Hours 0 120Hours 0 24 Hours IX] 144'Hours 0

PO Number: FA3089-14-P-0031

ProjectNamelNumber: 83 11549 693 Chiller Loop Project 63 RoofProiect

PLM Point Count 400 (PT4)

• PLM Point Count 1000 (PTM)

PCM NIOSH 7400-A Rules (PCM) 0 B Rules (PCB) 0 TWA (PTA) 0

· TEM AHERA (AHE) OJ

· TEM Level II (LII) o

TEM NIOSH 7402 (TNI) o

· TEM Bulk Qualitative (TBL) o

TEM Bulk Chatfield (TBS) o TEM Bulk Quantitative (TBQ) o TEM Wipe ASTM D6480-05 o TEM Microvac ASTM D5755-09 0 TEMWaterEPA 100.2 (TWI) 0 Other: 0

83-HMAS-OOI-B-002 South side ofPortable Building; HDUCT Mastic

83-HMAS-001-B-003 South side ofPortable Building; HDUCT Mastic

83-WLSH-OOl-B-004 Portable Building; Sheetrock; North; Out

. 83-WLSH-OOI-B-005 Portable Building; Sheetrock; East; Out

83-WLSH-OOI-B-006 Portable Building; Sheetrock; South; Out

83-WLSH-OOI-B-007 Portable Building; Sheetrock; North;In

83-WLSH-OOI-B-008 Portable Building; Sheetrock; East;In

.83-WLSH-OOI-B-009 Portable Building; Sheetrock; West;In

693-CLSH-OOI-B-OOl Mechanical; Ceiling Sheetrock

693-CLSH-OOI-B-002 Mechanical; Ceiling Sheetrock

Positive Stop

A-F-Ol1 EXP: 12-1-13 mailto:www.sailab.comlab@sailab.com

Scientific Analytical Institute 4604 Dundas Dr. Greensboro, He 27407

Phone: 336.292.3888 Fax: 336.292.3313 www.sailab.comlab@sailab.com

~::~~~nfn: 1t//5:( b~ Client Code: ______

693-CLSH-001-B-OO3 Mechanical; Ceiling Sheetrock

I 693-HMA<: 001 -B-004 Mechanical; HDUCT Mastic; AHU1

693-HMAS-OOI-B-OO5 Mechanical; HDUCT Mastic; AHUI

693-HMAS-00I-B-006 • Mechanical; HDUCT Mastic; AHU1

.693-WLJ -001-B-007 Mechanical; Wall Joint Compound; South

693-WLJ-001-B-008 M, -I.. .1 Wall Toint rnmnrl11ni!; West .693-WLJ-001-B-009 Mechanical; Wall Joint r. 'r'~_.ld; West

693-PWRP-001-B-OOI0 Mechanical Room; Pipe Wrap; White; 1

693-PWRP-001-B-OO11 Mechanical Room; Pipe Wrap; White; 2

693-PWRP-OOl-B-0012 Mechanical Room; Pipe Wrap; White; 3

693-BMA<:-001-B-0013 Mechanical Room;HDUCT M .D1 -le

• 693-HMAS-001-B-0014 M Room;HDUCT Ma<~tic:Rlack

693-HMAS-00I-B-001S Mechanical Room;HDUCT Mastic;Black t'l"i-RFROU Roof; Roll Roofing Felt and Tar; Lean Too 1

.63-RFROLL-0012-B-002 Roof; Roll Roofing Felt and Tar; Lean Too 1

63-l{FROLL-0012-B-OO"i Roof; Roll Roofing Felt and Tar; Lean Too 2

63-RFROLL-0012-B-OO4i Roof; Roll Roofing Felt and Tar; Lean Too 3

63 -RF';;a <R-0012-B-00t; RoofSealer;Black; Lean Too 1 it'l~-RF<:LR -00 12-B-006 Roof<:p~lpr-Ri"rlc Lean Too

63-RFSLR -0012-B-007 Roof Sealer;Black; Lean Too 2

63-RFSLR-0012-B-008 Roof Sealer; Gray/Black; Around Vent

63-RFSLR-0012-B-009 Roof Sealer; Gray/Black; Lean Too 2

.63-RF<:LR-0012-B-OO I0 • Roof Sealer; Gray/Black; Lean Tc 3 i63-RFSLR-0012-B-0011 Roof Sealer; Red/Black; Lean Too Drain

63· • ..FC::' lL0012-B-0012 Roof Sealer; Red/Black;Wall

• 63·RFSLR-0017-R-0013 Roof Sealer; Rpi!IR]"rk·, Pipe

63-WLFLT -0012-B-OO141 Roof; Wall Felt; Parapet i Positive Stop

Positive Stop

Positive Stop

Positive Stop

Positive Stop

I

Positive Stop

Positive Stop

Positive Stop

Page~of ..2.

A-F-017 EXP. 12-1-13

mailto:www.sailab.comlab@sailab.com

Lead Based Paint Detected:

Acft Maintenance

Randolph AFB LBP Inventory

Square Footage: 0

Number of Floors: 0

None.tif

Drawing File Name:

Facility Status Manned

83.jpg

Photo File Name

Date Constructed: 1991

Facility Number: Facility Name:83 Acft Maintenance/AFMC

Facility Owner: 902 CES

Facility Type

Facility Address: Base

Facility Summary Report:

08/11/2014 - Work Order 11549 - All areas related to the demolition of the portable building inside Hangar 83 is Negative for Lead Based Paint.

The Yellow line that currently exists in the NDI section on the floor is Positive for Lead Based Paint. Do not disturb any areas that are POS for LBP by any abrasive means such as sanding, scraping blasting, drilling or any brazing/welding operations.etc.

OSHA 29 CFR 1926.62 rules will apply for this project. All work must be done by a Lead Certified Firm. The OSHA requirement for these rules apply for any amount of LBP .1 mg/cm2 or greater. A negative determination will be required for this project by a certified Lead Firm before anyone other than a Lead certified worker can disturb the existing LBPpaint by any chemical or abrasive means.

2/15/2012 - WO#10829 Install four outlets in bay, areas tested are Negative for LBP.

07/22/2011 - NIPRNET Upgrade - The exterior of this facility on the West side is constructed of a corrugated metal which is Negative at 0.00mg/cm square

83Lead Based Paint Samples for Facility Sample Date Room Side Quadrant Component Substrate Color Condition Pb PbErr Result

0 0 0N/A N/A N/A N/A N/A N/A N/A Neg

2 8/6/2014 0.01 0In Office A Upper Ceiling etal Coorrugate Grey Intact Negati

2 7/22/2011 0 0Exterior B Upper Wall etal Coorrugate Off White Intact Negati

3 8/6/2014 0 0In Office A Middle Wall etal Coorrugate Off White Intact Negati

4 8/6/2014 0 0In Office B Middle Wall etal Coorrugate Off White Intact Negati

5 8/6/2014 0 0In Office C Middle Wall etal Coorrugate Off White Intact Negati

6 8/6/2014 0 0In Office D Middle Wall etal Coorrugate Off White Intact Negati

7 8/6/2014 0.02 0.01In Office Partitopn A Middle Wall etal Coorrugate Tan Intact Negati

8 8/6/2014 1.73 0.17In Office Partitopn A Middle Divided Line Concrete Yellow Intact Positiv

16 2/15/2012 0 0interior B Middle Wall Support Column Metal Brown Intact Neg

17 2/15/2012 0 0interior B Upper Wall Support Column Metal Brown Intact Neg

18 2/15/2012 0 0interior D Lower Wall Support Column Metal Brown Intact Neg

19 2/15/2012 0 0interior D Upper Wall Support Column Metal Brown Intact Neg

Randolph AFB Asbestos Inventory

Facility Type

Facility Site: BASE

Administrative

Square Footage: 0Number of Floors: 0

B83.tifDrawing File Name:

Facility Status Manned

83.jpgPhoto File Name

Date Constructed: 1991

Facility Number: Facility Name:83 TNG AID SHP

Facility Owner: 12 MSG/CE

Facility Address: 171617 TNG AID SHP Asbestos:

Facility Summary Report:

08/11/2014 - Work Order 11549 - All sheetrock, HDUCT Mastic is NAD, (No Asbestos Detected) for Asbestos Containing Materials. A Demolition Notification is required to be filed with the State 10 days prior to demol;ition. Notify CEIE for demolition Notification submission. 652-3685.

PCB

All light fixtures must be checked for PCB Ballasts. If ballasts are not marked “NO PCBs” then ballasts must be handled as PCB Waste, or recycled at an approved EPA PCB Recycling Facility . PCB’s must be packaged IAW DOT regulations and Manifested. Recycling Certificate Required if Recycled

Light Bulbs, All fluorescent lamps are known to contain Mercury in small amounts. All lamps must be removed from fixture packaged IAW DOT regulations and manifested to an approved EPA recycling facility or handled as Universal Waste in the State of Texas.

07/22/2011 - NIPRNET Upgrade - This facility is constructed with corrugated metal and a non-suspect foam type core for insualtion. There are no known suspect asbestos materials that will be disturbed during this project

2 Mar 11, Project TYMX366550, Install dedicated curcuits.West wall in fire supression room is NAD (no Asbestos Detected)

Asbestos Containing Material (ACM) Results: Dimension:

AsbestosHSA DescriptionHSA Type Sample # Year ID Location(s) Floor Floor Area:

Sample Area:

Original Sample IDSample ID

0NAD, Non-Fibrous 100%

2014 1

Off White; Adhesive type mateirial;Brown paper;Silver Foil

Duct System Joint Mastic 1 LF

Office 01 SF83-HMAS-002-B-001

0NAD, Non-Fibrous 100%

2014 1

Off White; Adhesive type mateirial;Brown paper;Silver Foil

Duct System Joint Mastic 2 LF

Office 01 SF83-HMAS-002-B-002

0NAD, Non-Fibrous 100%

2014 1

Off White; Adhesive type mateirial;Brown paper;Silver Foil

Duct System Joint Mastic 3 LF

Office 01 SF83-HMAS-002-B-003

0NAD, Cellulose 5%, Non-fibrous 95%

2014 1

North; Off White;Chalky;Gran;OutWall - Sheetrock 4 SF

Office 01 SF83-WLSH-001-B-004

0NAD, Cellulose 10%, Non-fibrous 90%

2014 1

East; Off White;Chalky;Gran;OutWall - Sheetrock 5 SF

Office 01 SF83-WLSH-001-B-005

0NAD, Cellulose 5%, Non-fibrous 95%

2014 1

South; Off White;Chalky;Gran;OutWall - Sheetrock 6 SF

Office 01 SF83-WLSH-001-B-006

0NAD, Cellulose 10%, Non-fibrous 90%

2014 1

North; Off White;Chalky;Gran;InWall - Sheetrock 7 SF

Office 01 SF83-WLSH-001-B-007

0NAD, Cellulose 10%, Non-fibrous 90%

2014 1

East; Off White;Chalky;Gran;InWall - Sheetrock 8 SF

Office 01 SF83-WLSH-001-B-008

0NAD, Cellulose 5%, Non-fibrous 95%

2014 1

West; Off White;Chalky;Gran;InWall - Sheetrock 9 SF

Office 01 SF83-WLSH-001-B-009

2014-08-11T17:50:13-0500