FA3010-16-R-0010 Repair/Replace SFS HVAC Bldg 3501 Questions and Answers 1-2

Question 1: "What are you calling " Tight Fit Vinyl Wrap " used over the duct board in the mechanical rooms ?"

Answer 1: In lieu of the following: "...2" rigid insulation. Cover insulation with tight fit vinyl wrap. (TYP.)" Use "Glass Fiber Board Insulation: Glass fibers bonded with a thermosetting resin. Comply with ASTM C612, Type IA. Provide with factory applied FSK jacket." Certainteed CertaPro Commercial Board or equal.

Question 2:"Also the specifications call for duct wrap and the drawings call for duct board. Please clarify what you would require."

Answer 2: Duct wrap on all new ductwork. Glass Fiber Board Insulation (duct board) where indicated on drawing sheet M4. Duct liner where shown on drawing sheet M2.