Attachment_QA_1_Carcom_filter.pdf

PDF 372 KB Posted

Attached to
Replace Halon & Electrical at GWEF Federal contract opportunity
Solicitation number
FA2823-19-R-A005
Issued by
Department of the Air Force Materiel Command Test Center

About this file

Filter Attachment for Q & A 1

View the file

Other files for this federal contract opportunity

Other files attached to Replace Halon & Electrical at GWEF, newest first.
File Type Posted
GWEF_BLDG_374_CEILING_HEIGHTS.PDF PDF
Q_and_A_03_May.pdf PDF
Q_and_A_02_May.pdf PDF
Q_and_A_26_Apr.pdf PDF
Amendment_FA282319RA0050002.pdf PDF
Conformed_FA282319RA0050002.pdf PDF
Q_and_A__2_25_Apr.pdf PDF
Conformed_FA282319RA0050001.pdf PDF
FA282319RA0050001_SF_30.pdf PDF
Q_and_A_1_19_Apr.pdf PDF
Attachment_QA_1_pictures.pdf PDF
Attachment_A_-_Specs_02Nov2018.pdf PDF
FA282319RA005_GWEF_FINAL.pdf PDF
Attachment_B_-_Drawings_02Nov2018.pdf PDF
50_Div_Cost.xls XLS spreadsheet
Wage_Determination_FL190217.pdf PDF
Attachment_F_-_Base_Access_Memo.docx DOCX document
Attachment_D_-_PPQ.pdf PDF
Attachment_E_-_FRQ.pdf PDF
Attachment_C_-_SOW_02Nov2018.pdf PDF
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECUL Series

TECUL Series - Extended Range Buffer Networks (Inductive Input)

Corcom Facility EMI Filters Product Guide Catalog: 1654986

Issue Date: 06.2011

Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric USA Cust. Svc.: 1-800-468-2023 equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. Corcom Prods: 1-847-680-7400 te.com corcom.com

Filter Cabinet

• Modified NEMA I, constructed of not less than #14 gauge CRS with galvanized bulkhead

• WHITE epoxy finish to all non-conductive surfaces

• Brush-plated electro-tin on all conductive surfaces

• R.F. Radiation of the shielded (load) compartment greater than 100 dB from 14 kHz to 10 GHz

• Front cover access, dual cover design

• Filter inserts pre-wired to standoffs and lugs

• Lifting hooks and mounting tabs

• Legs for floor mount available (see page 24)

Individual Filters

• Sealed components with welded seams

• Constructed of not less than #16 gauge steel with corrosion resistant plating

• Bleeder resistor to eliminate shock hazard provided

• HEMP Surge arrestors provided upon request‡

Electrical Characteristics

Voltage Drop:

Less than 1% @ unity power factor

Overload:

140% of rated current for 15 minutes

Harmonic Distortion:

Less than 2% @ full rated current

Dielectric Withstanding Voltage:

Per MIL-PRF-15733 and UL1283

D.C. Insulation Resistance:

Per MIL-STD-202, Method 302

Terminal Strength:

Per MIL-STD-202, Method 211, Condition E

Temperature Rise:

Per MIL-PRF-15733 and UL1283

R.F. Radiation:

100 dB minimum shielding effectiveness

Insertion Loss:

100 dB from 14 kHz - 10 GHz per MIL-STD-220B, under load condition, using extended range buffer networks over the frequency range of 14 kHZ - 20 MHz

Applicable Publications:

MIL-PRF-15733 — Filters, radio interference MIL-STD-202 — Test methods for Components MIL-STD-220B — Test method of Insertion Loss

MIL-STD-188-125-1 — HEMP

MIL-STD-285 — Test method for Shielding Effectiveness NFPA 70-1987 — National Electric Code 486A - 1983 — Wire Connectors and Lug UL1283 — UL standard for EMI Filters

How to Order:

TECUL 4 01000 A6 U -S -L

Voltage/Frequency A6 - 120/208V, 60Hz B6 - 277/480V, 60Hz

Legs Surge Arrestors (optional)

Orientation Blank - Shielded compartment on top U - Shielded compartment on bottom

Current Rating

# of Filtered Phases Series

Examples:

TECUL401000A6-S-L =

4 phases 1000A (each consisting of 3, 400A TECUL 120/208V filters) in a cabinet with surge arrestors and legs

TECUL300225B6 =

3 phases 225A TECUL, 277/480V filters in cabinet

Note 1: Surge Arrestor for A6 Models: V251BA60

Surge Arrestor for B6 Models: V481BA60

Note 2: Current rating always listed as 5 digits with leading zeros

‡ Intended for HEMP applications >225A. For filters rated <150A refer to the CDEUL Series on page 12.

Shown with optional legs Center mounting bracket not installed on all sizes

Intertek Listed Filter Panel

UL Recognized Filters

TECUL Series - ERBN (Inductive Input) (continued)

Corcom Facility EMI Filters Product Guide Catalog: 1654986

Issue Date: 06.2011

Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric USA Cust. Svc.: 1-800-468-2023 equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. Corcom Prods: 1-847-680-7400 te.com corcom.com

A E C

D B

R em ov ab le In d iv id ua l P ha se

F ilt er s

Mounting Brackets

Area for Conduit Penetration

Removable Cover

Removable Cover

RF

Gasket

Max. Operating Voltage A6: 120/208V, 60 Hz B6: 277/480V, 60 Hz

C o rco m Facility E

M I F ilters — N E M A C ab inet Style

For optional legs, refer to page 24

Recommended torque for fasteners on removable cover: 25 in. lb. ± 3 in. lb.

Center mounting bracket not installed on all sizes

# Filtered phases Dimensions Weight @ rated current A B C D E (Pounds/KG) 2 @ 225A 16.0 54.0 14.0 42.0 18.0 380

406.4 1371.6 355.6 1066.8 457.2 172.4 3 @ 225A 23.0 54.0 14.0 42.0 25.0 520

584.2 1371.6 355.6 1066.8 635.0 235.9 4 @ 225A 30.0 54.0 14.0 42.0 32.0 700

762.0 1371.6 355.5 1066.8 812.8 317.5 2 @ 400A 22.0 64.0 26.0 61.5 24.0 800

558.8 1625.6 660.4 1562.1 609.6 362.9 3 @ 400A 30.0 64.0 26.0 61.5 32.0 1100

762.0 1625.6 660.4 1562.1 812.8 498.9 4 @ 400A 38.0 64.0 26.0 61.5 40.0 1400

965.2 1625.6 660.4 1562.1 1016.0 635.0 2 @ 800A 38.0 70.0 26.0 67.5 40.0 1400

965.2 1778.0 660.4 1714.5 1016.0 635.0 3 @ 800A 56.0 70.0 26.0 67.5 58.0 2100

1422.4 1778.0 660.4 1714.5 1473.2 952.5 4 @ 800A 72.0 70.0 26.0 67.5 74.0 2600

1828.8 1778.0 660.4 1714.5 1879.6 1179.3

2 @ 1000 or 1200A 56.0 70.0 26.0 67.5 58.0 2000

1422.4 1778.0 660.4 1714.5 1473.2 907.2

3 @ 1000 or 1200A 82.0 70.0 26.0 67.5 84.0 3000

2082.8 1778.0 660.4 1714.5 2133.6 1360.8

4 @ 1000 or 1200A 106.0 70.0 26.0 67.5 108.0 3800

2692.4 1778.0 660.4 1714.5 2743.2 1723.6 david Highlight david Highlight david Highlight

File details come from the government source that posted it.