Section_07_60_00_-_Flashing_and_Sheet_Metal.pdf
PDF 41 KB Posted
- Attached to
- Renovate Building 18-C Federal contract opportunity
- Solicitation number
- FA2823-18-R-4005
About this file
Flashing and Sheet Metal
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sanitary_Line.pdf | ||
| Q&A_-_2.pdf | ||
| FA282318R40050003.pdf | ||
| 18-R-4005_Amendment-2.pdf | ||
| 18-R-4005_Renovate_Bldg._18-C_Q&A.pdf | ||
| 18-R-4005_Attach_G_PPQ.pdf | ||
| Section_07_41_13_-_Metal_Roof_Panels.pdf | ||
| 18-R-4005_Attach_F_PPI.pdf | ||
| Section_09_29_00_-_Gypsum_Board.pdf | ||
| 18-R-4005_Amendment-1.pdf | ||
| 18-R-4005.pdf | ||
| 18-R-4005_Site_Visit_Sign-In_Sheet.pdf | ||
| Attch_E._FL262.pdf | ||
| 18-R-4005_Attach_F_PPI.pdf | ||
| 18-R-4005_Specifications.pdf | ||
| 18-R-4005_Attachment_I.xls | XLS spreadsheet | |
| 18-R-4005_Attach_H_FRQ.pdf | ||
| FA2823-18-R-4005.pdf | ||
| 18-R-4005_Attach_G_PPQ.pdf | ||
| 18-R-4005_Drawings.pdf | ||
| Technical-Specifications-SCIF-Construction.pdf | ||
| 18-R-4005_Statement_of_Work.pdf | ||
| 18-R-4005_Specs_Addendum-1.pdf | ||
| Attach_D_-_Eglin_Specific_Contract_Language.pdf |
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENOVATE BUILDING 18-C FTFA 16-1182
EGLIN AFB, FL SPEC NO.: 16BA
SECTION 07 60 00
FLASHING AND SHEET METAL
08/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM A653/A653M (2013) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B101 (2012) Standard Specification for Lead-Coated Copper Sheet and Strip for Building Construction
ASTM B370 (2012) Standard Specification for Copper Sheet and Strip for Building Construction
SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
(SMACNA)
SMACNA 1793 (2012) Architectural Sheet Metal Manual, 7th Edition
1.2 GENERAL REQUIREMENTS
Finished sheet metalwork will form a weathertight construction without waves, warps, buckles, fastening stresses or distortion, which allows for expansion and contraction. Sheet metal mechanic is responsible for cutting, fitting, drilling, and other operations in connection with sheet metal required to accommodate the work of other trades. Coordinate installation of sheet metal items used in conjunction with roofing with roofing work to permit continuous roofing operations.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
SECTION 07 60 00 Page 1
Covering on flat, sloped, or curved surfaces; G
Gutters; G
Downspouts; G
Expansion joints; G
Base flashing; G
Counterflashing; G
Flashing at roof penetrations; G
Drip edge; G\, Eave flashing; G
Indicate thicknesses, dimensions, fastenings and anchoring methods, expansion joints, and other provisions necessary for thermal expansion and contraction. Scaled manufacturer's catalog data may be submitted for factory fabricated items.
1.4 DELIVERY, HANDLING, AND STORAGE
Package and protect materials during shipment. Uncrate and inspect materials for damage, dampness, and wet-storage stains upon delivery to the job site. Remove from the site and replace damaged materials that cannot be restored to like-new condition. Handle sheet metal items to avoid damage to surfaces, edges, and ends. Store materials in dry, weather-tight, ventilated areas until immediately before installation.
PART 2 PRODUCTS
2.1 MATERIALS
Use any metal listed by SMACNA Arch. Manual for a particular item, unless otherwise specified or indicated. Conform to the requirements specified and to the thicknesses and configurations established in SMACNA Arch.
Manual for the materials. Different items need not be of the same metal, except that if copper is selected for any exposed item, all exposed items must be copper.
Furnish sheet metal items in 8 to 10 foot lengths. Single pieces less than 8 feet long may be used to connect to factory-fabricated inside and outside corners, and at ends of runs. Factory fabricate corner pieces with minimum 12 inch legs. Provide accessories and other items essential to complete the sheet metal installation. Provide accessories made of the same or compatible materials as the items to which they are applied. Fabricate sheet metal items of the materials specified below and to the gage, thickness, or weight shown in Table I at the end of this section. Provide sheet metal items with mill finish unless specified otherwise. Where more than one material is listed for a particular item in Table I, each is acceptable and may be used except as follows:
2.1.1 Exposed Sheet Metal Items
Must be of the same material. Consider the following as exposed sheet metal: gutters, including hangers; downspouts; fascias; cap, base, and
SECTION 07 60 00 Page 2 eave flashings and related accessories.
2.1.2 Drainage
Do not use copper for an exposed item if drainage from that item will pass over exposed masonry, stonework or other metal surfaces. In addition to the metals listed in Table I, lead-coated copper may be used for such items.
2.1.3 Copper, Sheet and Strip
ASTM B370, cold-rolled temper, H 00 (standard).
2.1.4 Lead-Coated Copper Sheet
ASTM B101.
2.1.5 Lead Sheet
Minimum weight 4 pounds per square foot.
2.1.6 Steel Sheet, Zinc-Coated (Galvanized)
ASTM A653/A653M.
2.1.6.1 Finish
Exposed exterior items of zinc-coated steel sheet must have a baked-on, factory-applied color coating of polyvinylidene fluoride or other equivalent fluorocarbon coating applied after metal substrates have been cleaned and pretreated. Provide finish coating dry-film thickness of 0.8 to 1.3 mils and color to match metal roof panels.
2.1.7 Stainless Steel
ASTM A167, Type 302 or 304, 2D Finish, fully annealed, dead-soft temper.
2.1.8 Fasteners
Use the same metal or a metal compatible with the item fastened. Use stainless steel fasteners to fasten dissimilar materials.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Workmanship
Make lines and angles sharp and true. Free exposed surfaces from visible wave, warp, buckle, and tool marks. Fold back exposed edges neatly to form a 1/2 inch hem on the concealed side. Make sheet metal exposed to the weather watertight with provisions for expansion and contraction.
Make surfaces to receive sheet metal plumb and true, clean, even, smooth, dry, and free of defects and projections. For installation of items not shown in detail or not covered by specifications conform to the applicable requirements of SMACNA 1793, Architectural Sheet Metal Manual. Provide sheet metal flashing in the angles formed where roof decks abut walls, curbs, ventilators, pipes, or other vertical surfaces and wherever indicated and necessary to make the work watertight. Join sheet metal
SECTION 07 60 00 Page 3 items together as shown in Table II.
3.1.2 Nailing
Confine nailing of sheet metal generally to sheet metal having a maximum width of 18 inch. Confine nailing of flashing to one edge only. Space nails evenly not over 3 inch on center and approximately 1/2 inch from edge unless otherwise specified or indicated. Face nailing will not be permitted. Where sheet metal is applied to other than wood surfaces, include in shop drawings, the locations for sleepers and nailing strips required to secure the work.
3.1.3 Cleats
Provide cleats for sheet metal 18 inch and over in width. Space cleats evenly not over 12 inch on center unless otherwise specified or indicated.
Unless otherwise specified, provide cleats of 2 inch wide by 3 inch long and of the same material and thickness as the sheet metal being installed.
Secure one end of the cleat with two nails and the cleat folded back over the nailheads. Lock the other end into the seam. Pretin cleats for soldered seams.
3.1.4 Bolts, Rivets, and Screws
Install bolts, rivets, and screws where indicated or required. Provide compatible washers where required to protect surface of sheet metal and to provide a watertight connection. Provide mechanically formed joints in aluminum sheets 0.040 inch or less in thickness.
3.1.5 Seams
Straight and uniform in width and height with no solder showing on the face.
3.1.5.1 Flat-lock Seams
Finish not less than 3/4 inch wide.
3.1.5.2 Lap Seams
Finish soldered seams not less than one inch wide. Overlap seams not soldered, not less than 3 inch.
3.1.5.3 Loose-Lock Expansion Seams
Not less than 3 inch wide; provide minimum one inch movement within the joint. Completely fill the joints with the specified sealant, applied at not less than 1/8 inch thick bed.
3.1.5.4 Standing Seams
Not less than one inch high, double locked without solder.
3.1.5.5 Flat Seams
Make seams in the direction of the flow.
3.1.6 Soldering
Where soldering is specified, apply to copper, zinc-coated steel, and
SECTION 07 60 00 Page 4 stainless steel items. Pretin edges of sheet metal before soldering is begun. Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.
3.1.6.1 Edges
Scrape or wire-brush the edges of lead-coated material to be soldered to produce a bright surface. Flux brush the seams in before soldering. Treat with soldering acid flux the edges of stainless steel to be pretinned.
Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.
3.1.7 Protection from Contact with Dissimilar Materials
3.1.7.1 Copper or Copper-bearing Alloys
Paint with heavy-bodied bituminous paint surfaces in contact with dissimilar metal, or separate the surfaces by means of moistureproof building felts.
3.1.7.2 Metal Surfaces
Paint surfaces in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.
3.1.7.3 Wood or Other Absorptive Materials
Paint surfaces that may become repeatedly wet and in contact with metal with two coats of aluminum paint or a coat of heavy-bodied bituminous paint.
3.1.8 Expansion and Contraction
Provide expansion and contraction joints at not more than 32 foot intervals for aluminum and at not more than 40 foot intervals for other metals.
Provide an additional joint where the distance between the last expansion joint and the end of the continuous run is more than half the required interval. Space joints evenly. Join extruded aluminum gravel stops and fascias by expansion and contraction joints spaced not more than 12 feet apart.
3.1.9 Base Flashing
Lay the base flashings with each course of the roof covering, shingle fashion, where practicable, where sloped roofs abut curbs, or other vertical surfaces. Extend up vertical surfaces of the flashing not less than 8 inch and not less than 4 inch under the roof covering. Where finish wall coverings form a counterflashing, extend the vertical leg of the flashing up behind the applied wall covering not less than 6 inch. Overlap the flashing strips with the previously laid flashing not less than 3 inch.
Fasten the strips at their upper edge to the deck. Horizontal flashing at vertical surfaces must extend vertically above the roof surface and fastened at their upper edge to the deck a minimum of 6 inch on center with a minimum of 2-inch lap of any surface. Solder end laps and provide for expansion and contraction. Extend the metal flashing over crickets at the up-slope side of curbs, and similar vertical surfaces extending through sloping roofs, the metal flashings. Extend the metal flashings onto the roof covering not less than 4.5 inch at the lower side of vertical surfaces extending through the roof decks. Install and fit the flashings so as to be completely weathertight. Provide factory-fabricated base flashing for
SECTION 07 60 00 Page 5 interior and exterior corners.
3.1.10 GFascias
Prefabricate in the shapes and sizes indicated and in lengths not less that 8 feet. Extend flange at least 4 inch onto roofing. Provide prefabricated, mitered corners internal and external corners. Nail flange securely to wood nailer with large-head, barbed-shank roofing nails 1.5 inch long spaced not more than 3 inch on center, in two staggered rows.
3.1.10.1 Edge Strip
Hook the lower edge of fascias at least 3/4 inch over a continuous strip of the same material bent outward at an angle not more than 45 degrees to form a drip. Nail hook strip to a wood nailer at 6 inchmaximum on center.
Where fastening is made to concrete or masonry, use screws spaced 12 inch on center driven in expansion shields set in the concrete or masonry.
Where horizontal wood nailers are slotted to provide for insulation venting, install strips to prevent obstruction of vent slots. Where necessary, install strips over 1/16 inch thick compatible spacer or washers.
3.1.10.2 Joints
Leave open the section ends of gravel stops and fascias 1/4 inch and backed with a formed flashing plate, mechanically fastened in place and lapping each section end a minimum of 4 inch set laps in plastic cement. Face nailing will not be permitted. Install prefabricated aluminum gravel stops and fascias in accordance with the manufacturer's printed instructions and details.
3.1.11 Gutters
The hung type of shape indicated and supported on underside by brackets that permit free thermal movement of the gutter. Provide gutters in sizes indicated complete with mitered corners, end caps, outlets, brackets, and other accessories necessary for installation. Bead with hemmed edge or reinforce the outer edge of gutter with a stiffening bar not less than 3/4 by 3/16 inch of material compatible with gutter. Fabricate gutters in sections not less than 8 feet. Lap the sections a minimum of one inch in the direction of flow or provide with concealed splice plate 6 inch minimum. Join the gutters, other than aluminum, by riveted and soldered joints. Join aluminum gutters with riveted sealed joints. Provide expansion-type slip joints midway between outlets. Install gutters below slope line of the roof so that snow and ice can slide clear. Support gutters on adjustable hangers spaced not more than 30 inch on center and by cleats spaced not less than 36 inch apart. Adjust gutters to slope uniformly to outlets, with high points occurring midway between outlets.
Fabricate hangers and fastenings from metals.
3.1.12 Downspouts
Space supports for downspouts according to the manufacturer's recommendation for the masonry or steel substrate. Types, shapes and sizes are indicated. Provide complete including elbows and offsets. Provide downspouts in approximately 10 foot lengths. Provide end joints to telescope not less than 1/2 inch and lock longitudinal joints. Keep downspouts not less than one inch away from walls. Fasten to the walls at top, bottom, and at an intermediate point not to exceed 5 feet on center with leader straps or concealed rack-and-pin type fasteners. Form straps
SECTION 07 60 00 Page 6 and fasteners of metal compatible with the downspouts.
3.1.12.1 Terminations
Neatly fit into the drainage connection the downspouts terminating in drainage lines and fill the joints with a portland cement mortar cap sloped away from the downspout. Provide downspouts terminating in splash blocks with elbow-type fittings. Provide splash pans as specified.
3.1.13 Eave Flashing
One piece in width, applied in 8 to 10 foot lengths with expansion joints spaced as specified in paragraph entitled "Expansion and Contraction."
Provide a 3/4 inch continuous fold in the upper edge of the sheet to engage cleats spaced not more than 10 inch on center. Locate the upper edge of flashing not less than 18 inch from the outside face of the building, measured along the roof slope. Fold lower edge of the flashing over and loose-lock into a continuous edge strip on the fascia.
3.1.14 Flashing at Roof Penetrations and Equipment Supports
Provide metal flashing for all pipes, ducts, and conduits projecting through the roof surface and for equipment supports, guy wire anchors, and similar items supported by or attached to the roof deck.
3.1.15 Single Pipe Vents
See Table I, footnote (d). Set flange of sleeve in bituminous plastic cement and nail 3 inch on center. Bend the top of sleeve over and extend down into the vent pipe a minimum of 2 inch. For long runs or long rises above the deck, where it is impractical to cover the vent pipe with lead, use a two-piece formed metal housing. Set metal housing with a metal sleeve having a 4 inch roof flange in bituminous plastic cement and nailed 3 inch on center. Extend sleeve a minimum of 8 inch above the roof deck and lapped a minimum of 3 inch by a metal hood secured to the vent pipe by a draw band. Seal the area of hood in contact with vent pipe with an approved sealant.
3.2 PAINTING
Field-paint sheet metal for separation of dissimilar materials.
3.3 CLEANING
Clean exposed sheet metal work at completion of installation. Remove grease and oil films, handling marks, contamination from steel wool, fittings and drilling debris, and scrub-clean. Free the exposed metal surfaces of dents, creases, waves, scratch marks, and solder or weld marks.
3.4 REPAIRS TO FINISH
Scratches, abrasions, and minor surface defects of finish may be repaired in accordance with the manufacturer's printed instructions and as approved.
Repair damaged surfaces caused by scratches, blemishes, and variations of color and surface texture. Replace items which cannot be repaired.
SECTION 07 60 00 Page 7
3.5 FIELD QUALITY CONTROL
3.5.1 Procedure
TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES
Sheet Metal Items
Stainless Steel, inch
Zinc-Coated Steel, U.S.
Std. Gage
Downspouts and leaders
.015 24
Downspout clips and anchors
- .040 clip .125 anchor
Downspout straps, 2-inch
48 (a) .060 .050 - -
Flashings:
Base .018 24
Eave .015 24
Pipe vent sleave (d)
Extrusions
Sheets, smooth .018 24
Edge strip .025 - -
Gutters:
Gutter section .015 24
Continuous cleat .015 24
Hangers, dimensions
1 inch by .
inch
Joint Cover plates (See Table II)
(a) Brass.
SECTION 07 60 00 Page 8
TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES
Sheet Metal Items
Stainless Steel, inch
Zinc-Coated Steel, U.S.
Std. Gage
(b) May be lead weighing 4 pounds per square foot.
(c) May be polyvinyl chloride.
(d) 2.5 pound minimum lead sleeve with 4 inch flange. Where lead sleeve is impractical, refer to paragraph entitled "Single Pipe Vents" for optional material.
TABLE II. SHEET METAL JOINTS
TYPE OF JOINT
Item Designation Zinc-Coated Steel and Stainless Steel
Remarks
Flashings
Base One inch 3 inch lap for expansion joint
Fill each metal expansion joint with a joint sealing compound compound.
Eave One inch flat locked, cleated.
One inch loose locked, sealed expansion joint, cleated.
Same as base flashing.
Edge strip Butt --
SECTION 07 60 00 Page 9
TABLE II. SHEET METAL JOINTS
TYPE OF JOINT
Item Designation Zinc-Coated Steel and Stainless Steel
Remarks
Extrusions -- Use sheet flashing beneath and a cover plate
Sheet, smooth Butt with 1/4 inch space
Use sheet flashing backup plate.
Gutters 1.5 inch lap, riveted and soldered
(a) Provide a 3 inch lap elastomeric flashing with manufacturer's recommended sealant.
(b) Seal Polyvinyl chloride reglet with manufacturer's recommended sealant.
-- End of Section --