RUNWAY DIRECTION

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

(850) 434-0513

FINAL SUBMITTAL

RUNWAY DIRECTION

STRUCTURE D1 D2

MG-30 6'-0" 4'-0"

MG-40 9'-0" 5'-6"

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

SCALE: 1" = 100'-0"

OVERALL ELECTRICAL SITE PLAN - APPROACH 18

GRAPHIC SCALE

100'100' 0 300'200'

1" = 100'-0"

GENERAL NOTES AND WORK PHASING:

1. THE CONTRACTOR SHALL PROVIDE A PHASED CONSTRUCTION SCHEDULE AND ASSOCIATED DRAWINGS NECESSARY TO OBTAIN AN AIRFIELD CONSTRUCTION WAIVER AT LEAST 60 DAYS PRIOR TO

ON-SITE MOBILIZATION. THE PHASING PLAN SHALL REFLECT ANY CONDITIONS THAT MAY ADVERSELY AFFECT OPERATIONS ON THE AIRFIELD DURING CONSTRUCTION. THE CONTRACTOR SHALL

PARTICIPATE IN THE AIRFIELD WAIVER AND OPERATIONAL RISK MANAGEMENT (ORM) PROCESS WITH AIRFIELD PERSONNEL. THE CONTRACTOR WILL ATTEND MEETINGS AT BASE OPERATIONS TO

PLAN AND DISCUSS THE ORM PROCEDURE WITH AIRFIELD PERSONNEL. NORMAL HOURS OF AIRFIELD OPERATION ARE 0900-2400 MONDAY THRU FRIDAY. THE CONTRACTOR MAY HAVE TO PERFORM

WORK ON NIGHTS AND WEEKENDS UNDER THIS CONTRACT. ANY OUTAGES TO THE EXISTING AIRFIELD LIGHTING SYSTEMS MUST OCCUR ON NIGHTS OR WEEKENDS. ALL OUTAGES WILL BE

COORDINATED WITH THE CONTRACTING OFFICER. IF WORK IS PERFORMED ON NIGHTS AND WEEKENDS, THE CONTRACTOR'S NIGHTLY WORKING HOURS SHALL BE 0030-0800 MONDAY THRU FRIDAY, AND WEEKEND HOURS WILL BE 0030 FRIDAY-0800 MONDAY.

2. THE EXISTING FOREIGN OBJECT DEBRIS (FOD) CHECKPOINTS ON THE AIRFIELD WILL BE STRICTLY OBSERVED BY THE CONTRACTOR.

3. A TEMPORARILY DISPLACED THRESHOLD WILL BE REQUIRED ON THIS PROJECT.

4. CONSTRUCTION ACTIVITIES ON THE AIRFIELD, IN PROXIMITY TO, OR AFFECTING AIRCRAFT OPERATIONAL AREAS OR NAVIGABLE AIRSPACE, MUST BE COORDINATED WITH ALL AIRFIELD USERS

BEFORE INITIATING SUCH ACTIVITIES. THE QUALITY ASSURANCE PERSONNEL, AIRFIELD MANAGER, AND CONTRACT ADMINISTRATOR SHALL CLOSELY MONITOR CONSTRUCTION ACTIVITY

THROUGHOUT ITS DURATION TO ENSURE CONTINUAL COMPLIANCE WITH SAFETY REQUIREMENTS. TEMPORARY OBSTRUCTIONS MUST BE MARKED AND LIGHTED IN ACCORDANCE WITH FAA AC

70/7460-1. ALL HAZARDOUS AREAS ON THE AIRFIELD (SUCH AS EXCAVATIONS AND STOCKPILED MATERIALS) MUST BE DELINEATED WITH LIGHTED BARRICADES ON ALL VISIBLE OR ACCESSIBLE SIDES.

RUNWAYS: ACTIVITIES WITHIN THE GRADED AREAS OF THE CLEAR ZONE MAY REQUIRE MARKED AND LIGHTED THRESHOLD DISPLACEMENT SUFFICIENT TO PROTECT THE APPROACH-DEPARTURE

CLEARANCE SURFACE AND TO PROVIDE A MINIMUM 1000 FOOT OVERRUN SAFETY AREA BETWEEN THE STOP END OF THE RUNWAY AND CONSTRUCTION ACTIVITIES. CONSTRUCTION ACTIVITIES

MUST NOT BE CONDUCTED WITHIN A DISTANCE EQUAL TO THE NORMAL VFR HOLDING POSITION DISTANCE FROM THE NEAR EDGE OF ANY ACTIVE RUNWAY.

TAXIWAYS: CONSTRUCTION ACTIVITY SETBACK LINES MUST BE LOCATED AT A DISTANCE TO PROVIDE THE MINIMUM WINGTIP CLEARANCE FOR THE LARGEST AIRCRAFT THAT WILL USE THE

TAXIWAY. CLOSED TAXIWAYS MUST BE BE MARKED OR BARRICADED AND NORMAL LIGHTING CIRCUITS DISABLED.

JET BLAST: THE EFFECTS OF JET BLAST ON PERSONNEL, EQUIPMENT, FACILITIES MUST BE CONSIDERED. MAINTAIN A DISTANCE BEHIND AIRCRAFT SUFFICIENT TO DISSIPATE JET BLAST TO 35

MILES PER HOUR AND TEMPERATURES TO A MAXIMUM OF 100 DEGREES FAHRENHEIT, OR AMBIENT, WHICHEVER IS MORE. WHERE THESE CONDITIONS CANNOT BE MET, PROVIDE JET BLAST

PROTECTION WITH A DEFLECTOR.

5. PRIOR TO BEGINNING CONSTRUCTION, AND DURING CONSTRUCTION, THE CONTRACTOR WILL CLOSELY COORDINATE CONSTRUCTION OPERATIONS WITH THE CONTRACTING OFFICER AND AIRFIELD

MANAGEMENT PERSONNEL. THE CONTRACTOR SHALL TAKE INTO ACCOUNT THE ITEMS LISTED IN UFC 3-260-01, B14-6.3, "SAFETY CONSIDERATIONS," AND B14-6.4, "EXAMPLES OF HAZARDOUS AND

MARGINAL CONDITIONS," WHILE PLANNING AND EXECUTING WORK ON THE AIRFIELD.

6. VEHICLE TRAFFIC ON THE AIRFIELD SHOULD BE KEPT TO A MINIMUM. AIRCRAFT ON THE AIRFIELD ALWAYS HAS THE RIGHT OF WAY. VEHICLES OPERATING ON THE AIRFIELD SHALL BE MARKED

AND/OR FLAGGED FOR DAYTIME VISIBILITY, AND SHALL BE LIGHTED FOR NIGHTTIME OPERATIONS. VEHICLE OPERATORS SHALL COORDINATE WITH AIR TRAFFIC CONTROL VIA TWO-WAY RADIO

DURING NORMAL OPERATING HOURS OF THE AIRFIELD. THE CONTRACTOR SHALL CONFORM TO THE AIRFIELD MANAGEMENT CONSTRUCTION VEHICLE TRAFFIC PLAN. THE PLAN SHALL BE SIGNED

BY ALL PARTICIPANTS AND SHALL BECOME A PART OF THE CONTRACT. CONTRACTOR PERSONNEL WHO DO NOT HAVE AN AIRFIELD DRIVERS LICENSE WILL BE REQUIRED TO ATTEND THE DRIVERS

COURSE. THE CONTRACTOR SHALL GIVE THE AIRFIELD MANAGER A LIST OF PERSONNEL WHO WILL ATTEND THE COURSE TWO WEEKS PRIOR TO BEGINNING CONSTRUCTION.

7. CONSTRUCTION EQUIPMENT SHOULD NOT PENETRATE THE 50:1 APPROACH-DEPARTURE CLEARANCE SURFACE. CONSTRUCTION ACTIVITIES SHOULD GENERALLY NOT BE PERMITTED WITHIN 100

FEET OF THE RUNWAY EDGE. HOWEVER, THE INSTALLATION COMMANDER MAY ISSUE A TEMPORARY WAIVER WHICH ALLOWS WORK TO BE PERFORMED CLOSER TO THE RUNWAY EDGE. WINGTIP

CLEARANCES PLUS ONE-HALF THE WINGSPAN OF THE LARGEST AIRCRAFT WILL BE MAINTAINED ALONG TAXIWAYS.

8. EXCAVATIONS AND OPEN TRENCHES MY BE PERMITTED ALONG RUNWAYS UP TO 100 FEET FROM THE EDGE OF AN ACTIVE RUNWAY PROVIDED THEY ARE ADEQUATELY SIGNED, LIGHTED AND

MARKED. HOWEVER, THE INSTALLATION COMMANDER MAY ISSUE A TEMPORARY WAIVER WHICH ALLOWS OPEN TRENCHES CLOSER TO THE RUNWAY EDGE. ALONG TAXIWAYS, OPEN TRENCHES MAY

BE PERMITTED UP TO THE EDGE OF THE STRUCTURAL TAXIWAY AND APRON PAVEMENT, PROVIDED THE DROP-OFF IS ADEQUATELY SIGNED, LIGHTED AND MARKED.OPEN TRENCHES, EXCAVATIONS

AND STOCKPILED MATERIAL AT THE CONSTRUCTION SITE SHOULD BE PROMINENTLY MARKED WITH ORANGE FLAGS, AND LIGHTED WITH FLASHING RED OR YELLOW LIGHT UNITS DURING HOURS OF

RESTRICTED VISIBILITY AND/OR DARKNESS. THE USE OF FLARE POTS WILL NOT BE PERMITTED NEAR AIRCRAFT OPERATING AREAS.

9. EXTENSIVE STOCKPILED MATERIALS WILL NOT BE PERMITTED WITHIN THE CONSTRUCTION ACTIVITY AREAS.

10. OPEN FLAME WELDING OR TORCH CUTTING OPERATIONS WILL NOT BE PERMITTED UNLESS ADEQUATE FIRE AND SAFETY PRECAUTIONS ARE PROVIDED AND HAVE BEEN APPROVED BY THE FIRE

CHIEF.

11. TO ENSURE ADEQUATE MARKING AND LIGHTING IS PROVIDED FOR THE DURATION OF THE PROJECT, THE CONTRACTOR SHALL HAVE A PERSON ON-CALL 24 HOURS A DAY FOR EMERGENCY

MAINTENANCE OF AIRPORT HAZARD LIGHTING AND BARRICADES.

12. IT IS ANTICIPATED THAT THE EXISTING APPROACH LIGHTING SYSTEM WILL REMAIN IN OPERATION DURING THE CONSTRUCTION OF THE NEW APPROACH LIGHTING SYSTEM. THE NEW APPROACH

LIGHTING AND SEQUENCED FLASHING LIGHTS SHALL BE OPERATIONAL PRIOR TO DEMOLITION OF THE EXISTING APPROACH LIGHTING SYSTEM AND STRUCTURES.

13. CONTRACTOR SHALL INSTALL BIRD NESTING MITIGATION ON TOPS OF LIGHTING STRUCTURE CROSSARMS. BIRD SPIKES SHALL BE NIXALITE PREMIUM BIRD BARRIER, MODEL S, OR APPROVED EQUAL.

BIRD SPIKES SHALL BE ALL STAINLESS STEEL WIRE AND STRIP BARRIERS WITH THE FOLLOWING CHARACTERISTICS:

A. WIRES SHALL BE HIGH GRADE STAINLESS STEEL, 0.041" DIAMETER, FULL-HARD SPRING TEMPER, 4" HIGH X 2" WIDE, WITH NO LESS THAN 60 WIRE POINTS PER FOOT. SPIKES SHALL PROVIDE

90 DEGREE MINIMUM WIRE COVERAGE FOR SURFACES LESS THAN 2" IN DEPTH.

B. BASE STRIP SHALL BE HIGH GRADE STAINLESS STEEL, 0.25" WIDE X 0.02" THICK, FULL ANNEAL FOR FLEXIBILITY, EASY STRIP CUTTING AND SURFACE SHAPE MEMORY.

C. MOUNTING HARDWARE SHALL BE STAINLESS STEEL OR NON-CORROSIVE MATERIAL, AND SHALL ALLOW FOR STRIP REMOVAL AND REINSTALLATION WITHOUT CAUSING DAMAGE TO THE

INSTALLATION SURFACE, BIRD NESTING MITGATION SYSTEM OR MOUNTING SYSTEM. THE MOUNTING HARDWARE SHALL BE WIRE TIES W/ WIRE TYING TOOL AND ADHESIVE FOR

INSTALLATION ON MAST CROSSARM.

BASE BID AND BID OPTION NOTE:

ALL WORK SHOWN, UNLESS NOTED OTHERWISE, WILL BE ACCOMPLISHED UNDER BASE

BID. WORK REQUIRED UNDER BID OPTION # 1 IS SHOWN ON SHEETS E-12 AND E-13.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

PETERSON ENGINEERING INC.

SCALE: 1" = 30'-0"

ELECTRICAL SITE PLAN - APPROACH AREA 1 - DEMOLITION

M A

T C

H

L

I N

E

E

E

1 REMOVE EXISTING PRE-THRESHOLD LIGHT BAR IN ITS ENTIRETY, INCLUDING LIGHTS, BASE CANS, CONDUITS, WIRING, HANDHOLE &

CONCRETE FOUNDATION. PATCH EXISTING ASPHALT OVERRUN WHERE BAR IS REMOVED. SEE "DETAIL 'A'," SHEET C501.

WORK NOTES: (THIS SHEET ONLY)

4 REMOVE EXISTING SERIES LIGHTING CIRCUIT CABLES. ABANDON EXISTING CONDUITS WHERE CONCEALED BELOW ASPHALT OR GRADE.

5 EXISTING MANHOLE TO REMAIN.

6 REMOVE EXISTING SERIES LIGHTING CIRCUIT CABLES SERVING THE EXISTING APPROACH LIGHTING SYSTEM. REMOVE EXISTING

SEQUENCED FLASHER CONTROL CABLE. REMOVE EXISTING 5 KV PRIMARY CABLE & NEUTRAL CABLE. EXISTING SERIES LIGHTING

CIRCUITS SERVING EXISTING RUNWAY EDGE LIGHTS AND OTHER VISUAL NAVIGATION AIDS SHALL REMAIN.

REMOVE EXISTING TERMINATING LIGHT BAR IN ITS ENTIRETY, INCLUDING LIGHTS, BASE CANS, CONDUITS, WIRING & CONCRETE

FOUNDATION. PATCH EXISTING ASPHALT OVERRUN WHERE BAR IS REMOVED. SEE "DETAIL 'A'," SHEET C501.

REMOVE EXISTING APPROACH LIGHT CENTERLINE BARRETTE IN ITS ENTIRETY, INCLUDING LIGHTS, BASE CANS, CONDUITS, WIRING &

CONCRETE FOUNDATION. PATCH EXISTING ASPHALT OVERRUN WHERE BAR IS REMOVED. SEE "DETAIL 'A'," SHEET C501.

7 EXISTING THRESHOLD LIGHT BAR TO REMAIN.

5 6

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

REMOVE EXISTING 5 KV PRIMARY CABLE & NEUTRAL CABLE. ABANDON EXISTING CONDUIT WHERE CONCEALED BELOW GRADE.8

6 8

6 8

ELECTRICAL LEGEND - DEMOLITION:

EXISTING UNDERGROUND DUCTBANK - TO REMAIN.

EXISTING MANHOLE - TO REMAIN.

EXISTING APPROACH CENTERLINE BARRETTE & HANDHOLE - REMOVE.

EXISTING APPROACH ELEVATED STRUCTURE & HANDHOLE - REMOVE.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

GRAVEL R

OAD

A S

P H

A L T

R

O A

D

T

SCALE: 1" = 30'-0"

ELECTRICAL SITE PLAN - APPROACH AREA 2 - DEMOLITION

M A

T C

H

L

I N

E

E

E

M A

T C

H

L

I N

E

E

E

WORK NOTES: (THIS SHEET ONLY)

REMOVE EXISTING SERIES LIGHTING CIRCUIT CABLES. ABANDON EXISTING CONDUITS WHERE CONCEALED BELOW GRADE.5

REMOVE EXISTING SERIES LIGHTING CIRCUIT CABLES, FLASHER CONTROL CABLES & FLASHER POWER CABLES. ABANDON EXISTING

CONDUITS WHERE CONCEALED BELOW GRADE.

REMOVE EXISTING APPROACH LIGHT CENTERLINE BARRETTE IN ITS ENTIRETY, INCLUDING LIGHTS, BASE CANS, CONDUITS, WIRING, HANDHOLE & CONCRETE FOUNDATION.

REMOVE EXISTING ELEVATED APPROACH LIGHT STRUCTURE IN ITS ENTIRETY, INCLUDING LIGHTS, CONDUITS, WIRING, HANDHOLE &

WOODEN STRUCTURE. SEE DEMOLITION ELEVATIONS, SHEET E-5.

REMOVE EXISTING ELEVATED APPROACH LIGHT 1000 FOOT CROSSBAR IN ITS ENTIRETY, INCLUDING APPROACH LIGHTS, SEQUENCED

FLASHER LIGHTS, FLASHER CONTROL CABINETS, CONDUITS, WIRING, HANDHOLE & WOODEN STRUCTURE. SEE DEMOLITION

ELEVATIONS, SHEET E-5.

REMOVE EXISTING ELEVATED APPROACH LIGHT STRUCTURE IN ITS ENTIRETY, INCLUDING APPROACH LIGHTS, SEQUENCED FLASHER

LIGHTS, FLASHER CONTROL CABINETS, CONDUITS, WIRING, HANDHOLE & WOODEN STRUCTURE. SEE DEMOLITION ELEVATIONS, SHEET E-5.

EXISTING STRUCTURE

IS APPROXIMATELY

6'-6" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

10'-5" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

10'-0" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

19'-8" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

24'-5" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

27'-2" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

27'-0" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

22'-3" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

11'-10" ABOVE GRADE.

REMOVE EXISTING PAD MOUNTED TRANSCLOSURE &

TRANSFORMER SERVING EXISTING SEQUENCED

FLASHING LIGHT SYSTEM. REMOVE EXISTING

CONCRETE PAD. REMOVE EXISTING WIRING &

ABANDON CONDUITS BELOW GRADE.

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

REMOVE EXISTING 5 KV PRIMARY CABLE & NEUTRAL CABLE. ABANDON EXISTING CONDUIT WHERE CONCEALED BELOW GRADE.7

7 7

7 7

ELECTRICAL LEGEND - DEMOLITION:

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

B

E

A

V

P

N

D

SCALE: 1" = 30'-0"

ELECTRICAL SITE PLAN - APPROACH AREA 3 - DEMOLITION

M A

T C

H

L

I N

E

E

E

WORK NOTES: (THIS SHEET ONLY)

REMOVE EXISTING ELEVATED APPROACH LIGHT STRUCTURE IN ITS ENTIRETY, INCLUDING APPROACH LIGHTS, SEQUENCED FLASHER

LIGHTS, FLASHER CONTROL CABINETS, CONDUITS, WIRING, HANDHOLE & WOODEN STRUCTURE. SEE DEMOLITION ELEVATIONS, SHEET E-5.

REMOVE EXISTING SERIES LIGHTING CIRCUIT CABLES, FLASHER CONTROL CABLES & FLASHER POWER CABLES. ABANDON EXISTING

CONDUITS WHERE CONCEALED BELOW GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

11'-3" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

8'-6" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

9'-2" ABOVE GRADE.

EXISTING STRUCTURE

IS APPROXIMATELY

9'-2" ABOVE GRADE.

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

EXISTING CHAIN LINK FENCE TO REMAIN.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

NOTE:

N.T.S.

REMOVE EXISTING GUTTER & WIRING. REMOVE

EXISTING ISOLATION TRANSFORMERS IN GUTTER.

TURN TRANSFORMERS OVER TO GOVERNMENT.

REMOVE EXISTING APPROACH LIGHTS &

TURN OVER TO GOVERNMENT.

REMOVE EXISTING WOOD CROSSARMS

REMOVE EXISTING WOOD PLATFORM,

HANDRAIL & WOOD SUPPORTS.

PLATFORM HANDRAIL OMITTED FOR CLARITY

REMOVE EXISTING WOOD POLES

& SUPPORT BRACES, ETC., IN

THEIR ENTIRETY.

REMOVE EXISTING 2" RIGID GALV.

STEEL CONDUIT & WIRING

REMOVE EXISTING HANDHOLE.

DEMOLITION ELEVATION - EXISTING

APPROACH STRUCTURE W/O SFL

REMOVE FLEXIBLE CORD CONNECTIONS.

NOTE:

N.T.S.

REMOVE EXISTING GUTTER & WIRING. REMOVE

EXISTING ISOLATION TRANSFORMERS IN GUTTER.

TURN TRANSFORMERS OVER TO GOVERNMENT.

REMOVE EXISTING APPROACH LIGHTS &

TURN OVER TO GOVERNMENT.

REMOVE EXISTING WOOD CROSSARMS

REMOVE EXISTING WOOD PLATFORM,

HANDRAIL & WOOD SUPPORTS.

PLATFORM HANDRAIL OMITTED FOR CLARITY

REMOVE EXISTING WOOD POLES

& CROSS BRACES, ETC., IN THEIR

ENTIRETY.

REMOVE EXISTING 2" RIGID GALV.

STEEL CONDUIT & WIRING

REMOVE EXISTING HANDHOLE.

DEMOLITION ELEVATION - EXISTING

APPROACH STRUCTURE W/ SFL

REMOVE FLEXIBLE CORD CONNECTIONS.

REMOVE EXISTING SEQUENCED FLASHER

LIGHT & TURN OVER TO GOVERNMENT.

NOTE:

EXISTING STRUCTURES VARY IN HEIGHT,

CROSS BRACING CONFIGURATIONS, ETC.

THE CONTRACTOR SHALL REMOVE ALL

EXISTING STRUCTURES ENTIRELY. POLES

SHALL BE REMOVED TO A POINT AT LEAST

1'-0" BELOW GRADE.

NOTE:

EXISTING STRUCTURES VARY IN HEIGHT,

CROSS BRACING CONFIGURATIONS, ETC.

THE CONTRACTOR SHALL REMOVE ALL

EXISTING STRUCTURES ENTIRELY. POLES

SHALL BE REMOVED TO A POINT AT LEAST

1'-0" BELOW GRADE.

REMOVE EXISTING APPROACH LIGHT JUNCTION

BOX & TURN OVER TO GOVERNMENT.

REMOVE EXISTING SEQUENCED FLASHER LIGHT

CONTROLLER & TURN OVER TO GOVERNMENT.

1000 FOOT CROSSBAR NOTE:

THE 1000 FOOT CROSSBAR IS CONSTRUCTED SIMILARLY TO THE ABOVE DETAIL,

EXCEPT IT CONSISTS OF EIGHT (8) WOOD POLES, THREE (3) WIRING GUTTERS AND

TWENTY-FIVE (25) APPROACH LIGHTS.

REMOVE EXISTING 2" PVC, SCH. 40

CONDUIT & WIRING

REMOVE EXISTING 2" PVC, SCH. 40

CONDUIT & WIRING

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

0+001+002+003+004+005+006+007+00

0+001+002+003+004+005+006+007+00

END OF OVERRUN

THRESHOLD

EDGE OF LIGHT PLANE

SCALE: 1" = 30'-0"

SITE PLAN - APPROACH AREA 1

SCALE: 1" = 30'-0"

PROFILE - APPROACH AREA 1

EDGE OF LIGHT PLANE

M A

T C

H

L

I N

E

E

E

PROPOSED LIGHT

PLANE # 2 (-0.83° ANGLE

FROM 1+00 TO 5+00)

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

PROPOSED LIGHT PLANE

# 3 (+0.09° ANGLE FROM

0+00 TO 1+00)

PROPOSED LIGHT

PLANE # 1 (-0.56° ANGLE

FROM 5+00 TO 24+00)

200'-0"

200'-0"

PROPOSED LIGHT PLANE (1.0% SLOPE)

IDEAL LIGHT PLANE (HORIZONTAL)

PROFILE LEGEND:

EXISTING LIGHT PLANE

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

GRAVEL R

OAD

A S

P H

A

A

D

7+008+009+0010+0011+0012+0013+0014+0015+0016+00

12+00 7+008+009+0010+0011+0013+0014+0015+0016+00

ROAD

EDGE OF LIGHT PLANE

T

A

SECTION - STATION 10+00

-50 -40 -30 -20 -10 0 10 20 30 40 50

A

SCALE: 1" = 30'-0"

SCALE: 1" = 30'-0"

SITE PLAN - APPROACH AREA 2

SCALE: 1" = 30'-0"

PROFILE - APPROACH AREA 2

EDGE OF LIGHT PLANE

M A

T C

H

L

I N

E

E

E

M A

T C

H

L

I N

E

E

E

E7 E7

E7 E7

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

PROPOSED LIGHT

PLANE # 1 (-0.56° ANGLE

FROM 5+00 TO 24+00)

200'-0"

200'-0"

STATION 10+00, STRUCTURE 5

STATION 10+00, STRUCTURE 4

STATION 10+00, STRUCTURE 3

STATION 10+00, STRUCTURE 2

STATION 10+00, STRUCTURE 1

STRUCTURE 5

STRUCTURE 4

STRUCTURE 3

STRUCTURE 2

STRUCTURE 1

PROPOSED LIGHT PLANE (1.0% SLOPE)

IDEAL LIGHT PLANE (HORIZONTAL)

PROFILE LEGEND:

EXISTING LIGHT PLANE

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

A

V

N

D

16+0017+0018+0019+0020+0021+0022+0023+0024+00

16+0017+0018+0019+0020+0021+0022+0023+0024+00

EDGE OF LIGHT PLANE

PROPOSED LIGHT PLANE

SLOPE (1.0%) -

(2400' @ 1.0% = 24'-0")

SCALE: 1" = 30'-0"

SITE PLAN - APPROACH AREA 3

SCALE: 1" = 30'-0"

PROFILE - APPROACH AREA 3

EDGE OF LIGHT PLANE

EDGE OF LIGHT PLANE

M A

T C

H

L

I N

E

E

E

IDEAL LIGHT PLANE

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

PROPOSED LIGHT

PLANE # 1 (-0.56° ANGLE

FROM 5+00 TO 24+00)

200'-0"

200'-0"

200'-0"

PROPOSED LIGHT PLANE (1.0% SLOPE)

IDEAL LIGHT PLANE (HORIZONTAL)

PROFILE LEGEND:

EXISTING LIGHT PLANE

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

0+001+002+003+004+005+006+00

SCALE: 1" = 30'-0"

ELECTRICAL SITE PLAN - APPROACH AREA 1

M A

T C

H

L

I N

E

E

E

1 EXISTING THRESHOLD LIGHT BAR.

WORK NOTES: (THIS SHEET ONLY)

2 NEW CENTERLINE BARRETTE - (5) FAA-E-982 ELEVATED APPROACH LIGHTS ON CONCRETE FOUNDATION.

3 3 3 3 3

3 NEW CENTERLINE BARRETTE - (5) L-850E SEMI-FLUSH APPROACH LIGHTS IN CONCRETE FOUNDATION.

4 NEW TERMINATING BAR - (3) L-850E SEMI-FLUSH TERMINATING BAR LIGHTS W/ RED LENSES IN CONCRETE FOUNDATION.

5 NEW PRE-THRESHOLD BAR - (5) L-850E SEMI-FLUSH PRE-THRESHOLD BAR LIGHTS W/ RED LENSES IN CONCRETE FOUNDATION.

6 CUT & PATCH EXISTING ASPHALT OVERRUN. SEE "DETAIL 'A'," SHEET C501 FOR CUTTING AND PATCHING REQUIREMENTS.

ELECTRICAL LEGEND - NEW WORK:

EXISTING UNDERGROUND DUCTBANK - TO REMAIN.

NEW SERIES LIGHTING CIRCUITS & CONDUITS - 2 # 6 (L-824) CABLES & 1 # 6 (THW) GROUND IN 2" PVC, SCH. 40 CONDUIT, UNLESS NOTED OTHERWISE IN WORK NOTES - BURY CONDUITS 24" BELOW

FINISHED GRADE. PROVIDE A NEW # 4 BARE COPPER COUNTERPOISE CONDUCTOR 6" ABOVE ALL NEW

CONDUITS.

EXISTING MANHOLE - TO REMAIN - CORE DRILL MANHOLE WALL FOR NEW DUCT ENTRANCES.

NEW APPROACH CENTERLINE BARRETTE OR PRE-THRESHOLD BAR W/ SEMI-FLUSH LIGHTS.

NEW TERMINATING BAR W/ SEMI-FLUSH LIGHTS.

NEW APPROACH CENTERLINE BARRETTE W/ ELEVATED LIGHTS.

NEW APPROACH CENTERLINE MG-20 LOW IMPACT RESISTANT STRUCTURE.

NEW APPROACH CENTERLINE MG-30 OR MG-40 LOW IMPACT RESISTANT STRUCTURE.

NEW 3'-0" X 3'-0" PRECAST CONCRETE HANDHOLE W/ LIFT ASSIST LID.

(APPLIES TO SHEETS E-6 THRU E-13.)

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

EXISTING APPROACH CENTERLINE BARRETTE - TO BE REMOVED - SHOWN ON NEW WORK PLANS FOR REFERENCE ONLY.

EXISTING APPROACH ELEVATED STRUCTURE - TO BE REMOVED - SHOWN ON NEW WORK PLANS FOR REFERENCE ONLY.

LIR LOW IMPACT RESISTANT

SFL SEQUENCED FLASHING LIGHT

NEW 6'-0" X 6'-0" PRECAST CONCRETE MANHOLE W/ LIFT ASSIST LID.

SEE "ELECTRICAL SITE PLAN - EXISTING AIRFIELD

AREA 1," SHEET E-12, FOR CONTINUATION.

7 NEW 6 WAY 4" DUCTBANK - INSTALL BY DIRECTIONAL BORE METHOD - 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 4"

DUCT, AND 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT, AND 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT, W/ (3) SPARE 4" DUCTS.

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN 2" PVC, SCH. 40 CONDUIT.

NEW 6 WAY 2" CONCRETE ENCASED DUCTBANK - 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 2" DUCT, AND 1 - 6/C # 10

AWG, L-824, TYPE C CABLE IN (1) 2" DUCT, AND 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (3) SPARE 2" DUCTS.

10 REPAINT EXISTING OVERRUN MARKINGS AFTER ASPHALT CUTTING AND PATCHING HAS BEEN COMPLETED. PAINT SHALL BE

YELLOW, IN ACCORDANCE WITH FEDERAL STANDARD 595, YELLOW - 33538. RETRO-REFLECTIVE GLASS BEADS ARE NOT

REQUIRED ON OVERRUN CHEVRONS.

10 10 10101010

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

A S

P H

A

A

D

7+008+009+0010+0011+0012+0013+0014+0015+0016+00

SCALE: 1" = 30'-0"

ELECTRICAL SITE PLAN - APPROACH AREA 2

M A

T C

H

L

I N

E

E

E

M A

T C

H

L

I N

E

E

E

1 NEW CENTERLINE STRUCTURE - (5) FAA-E-982 ELEVATED APPROACH LIGHTS ON LIR STRUCTURE.

WORK NOTES: (THIS SHEET ONLY)

2 NEW CENTERLINE STRUCTURE - (5) FAA-E-982 ELEVATED APPROACH LIGHTS & (1) SEQUENCED FLASHING LIGHT ON LIR STRUCTURE.

3 NEW 1000 FOOT STRUCTURE - (4) FAA-E-982 ELEVATED APPROACH LIGHTS ON LIR STRUCTURE.

11222222

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

4 NEW CENTERLINE BARRETTE - (5) FAA-E-982 ELEVATED APPROACH LIGHTS ON CONCRETE FOUNDATION.

275'-0" MIN. FROM

RUNWAY CENTERLINE

5 NEW PAD MOUNTED TRANSFORMER FOR SEQUENCED FLASHING LIGHT SYSTEM.

6 NEW SEQUENCED FLASHING LIGHT MASTER CONTROL PANEL.

5 6

N.T.S.

ENLARGED PLAN - PAD MOUNTED TRANSFORMER

TRANSFORMER PRIMARY CABLE &

CONDUIT - 1 # 6 (5KV) L-824 & 1 # 6 (600 V.) N.

IN 2" PVC, SCH. 40 CONDUIT. SEE "SINGLE

LINE DIAGRAM - SFL SYSTEM," SHEET E-25.

(1) 6/C # 10 AWG CONTROL CABLE - 2" PVC, SCH. 40. SEE "WIRING

DIAGRAM - SEQUENCED FLASHING LIGHTS," SHEET E-25.

(3) 7/C # 12 AWG CABLE , (1) 4/C # 12 AWG CABLE AND 3 # 10 & 1 #

10 GND. IN 2" PVC, SCH. 40. SEE "WIRING DIAGRAM - SEQUENCED

FLASHING LIGHTS," SHEET E-25.

SEQUENCED FLASHING LIGHT MASTER

CONTROL CABINET - SEE "WIRING DIAGRAM -

SEQUENCED FLASHING LIGHTS," SHEET E-25.

SEE "ENLARGED PLAN - PAD MOUNTED

TRANSFORMER," THIS SHEET.

EXTEND CONDUIT & WIRING TO NEW HANDHOLE

LOCATED AT 1000 FOOT CROSSBAR. SEE "ELECTRICAL

SITE PLAN - APPROACH AREA 2," THIS SHEET, FOR

WIRING & CONDUIT DESCRIPTIONS.

STATION 10+00, STRUCTURE 5

STATION 10+00, STRUCTURE 4

STATION 10+00, STRUCTURE 3

STATION 10+00, STRUCTURE 2

STATION 10+00, STRUCTURE 1

7 DIRECTIONAL BORE BELOW EXISTING ASPHALT ROAD AND DRAINAGE SWALE.

8 SEE "LARGE SCALE PLAN - APPROACH STRUCTURE MG-30 & MG-40 W/ SFL," SHEET E-11.

9 SEE "LARGE SCALE PLAN - APPROACH STRUCTURE MG-20 W/ SFL," SHEET E-11.

128 8 8

9 9 9

10 SEE "LARGE SCALE PLAN - APPROACH STRUCTURE MG-30 & MG-40 W/O SFL," THIS SHEET.

11 SEE "LARGE SCALE PLAN - OUTER BAR," THIS SHEET.

LARGE SCALE PLAN - APPROACH

STRUCTURE MG-30 & MG-40 W/O SFL

SCALE: 1/4" = 1'-0"

12 SEE "LARGE SCALE PLAN - APPROACH STRUCTURE MG-20 W/O SFL," THIS SHEET.

LARGE SCALE PLAN - OUTER BAR

SCALE: 1/4" = 1'-0"

LARGE SCALE PLAN - APPROACH

STRUCTURE MG-20 W/O SFL

SCALE: 1/4" = 1'-0"

50 A., 2 P., NEMA 3R ENCLOSED

CIRCUIT BREAKER

5 - L-823 APPROACH LIGHT SECONDARY CABLES & 1 # 6 GND. IN 2" PVC, SCH. 40 CONDUIT

LIGHT BASE

LIGHT BASE

LIGHT BASE

LIR STRUCTURE MAST

LIR CONCRETE FOUNDATION

LIR STRUCTURE MAST

LIR CONCRETE FOUNDATION

LIR STRUCTURE MAST

LIR CONCRETE FOUNDATION

NEW UNDERGROUND SECONDARY - SEE "SINGLE

LINE DIAGRAM - SFL SYSTEM," SHEET E-25.

PAD MOUNTED TRANSFORMER -

10 KVA, 1Ø, 4.16/2.4 KV PRIMARY

TO 240/120 V. SECONDARY -

SEE "SINGLE LINE DIAGRAM -

SFL SYSTEM," SHEET E-25.

HANDHOLE - SEE "DETAIL -

3' X 3' PRECAST HANDHOLE,"

SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE," SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE," SHEET E-27.

CONDUIT & WIRING TO NEXT HANDHOLE - WIRING

BETWEEN HANDHOLES VARIES. SEE ELECTRICAL

SITE PLANS FOR EXACT WIRING DESCRIPTIONS.

CONDUIT & WIRING TO NEXT HANDHOLE -

WIRING BETWEEN HANDHOLES VARIES.

SEE ELECTRICAL SITE PLANS FOR EXACT

WIRING DESCRIPTIONS.

CONDUIT & WIRING TO NEXT HANDHOLE - WIRING

BETWEEN HANDHOLES VARIES. SEE ELECTRICAL

SITE PLANS FOR EXACT WIRING DESCRIPTIONS.

CONDUIT & WIRING TO NEXT HANDHOLE - WIRING

BETWEEN HANDHOLES VARIES. SEE ELECTRICAL

SITE PLANS FOR EXACT WIRING DESCRIPTIONS.

CONDUIT & WIRING TO NEXT HANDHOLE - WIRING

BETWEEN HANDHOLES VARIES. SEE ELECTRICAL

SITE PLANS FOR EXACT WIRING DESCRIPTIONS.

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN 2" PVC, SCH. 40 CONDUIT.

NEW 6 WAY 2" CONCRETE ENCASED DUCTBANK - 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 2" DUCT, AND 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 2" DUCT, AND 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2"

DUCT, W/ (3) SPARE 2" DUCTS.

NEW 6 WAY 2" CONCRETE ENCASED DUCTBANK - 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 2" DUCT, AND 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 2" DUCT, AND (3) 7/C # 12 & (1) 4/C # 12, AND 3 # 10 & 1 # 10 GND. IN

(1) 2" DUCT, W/ (3) SPARE 2" DUCTS.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE," SHEET E-27.

FLEXIBLE CONDUIT & WIRING CONNECTION - SEE

"SINGLE LINE DIAGRAM - SFL SYSTEM," SHEET E-25.

NEW 6 WAY 2" CONCRETE ENCASED DUCTBANK - 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 2" DUCT, AND 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 2" DUCT, AND (3) 7/C # 12 & (1) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1)

2" DUCT, AND 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

18 NEW 2 WAY 2" CONCRETE ENCASED DUCTBANK - 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (1)

SPARE 2" DUCTS.

19 NEW 4 WAY 2" CONCRETE ENCASED DUCTBANK - (4) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

1919191920

20 NEW 4 WAY 2" CONCRETE ENCASED DUCTBANK - (2) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

21 NEW 4 WAY 2" DUCTBANK (DIRECTIONAL BORE) - (3) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

22 NEW 4 WAY 2" CONCRETE ENCASED DUCTBANK - (3) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

17+0018+0019+0020+0021+0022+0023+0024+00

M A

T C

H

L

I N

E

E

E

SCALE: 1" = 30'-0"

ELECTRICAL SITE PLAN - APPROACH AREA 3

WORK NOTES: (THIS SHEET ONLY)

NEW CENTERLINE STRUCTURE - (5) FAA-E-982 ELEVATED APPROACH LIGHTS & (1) SEQUENCED FLASHING LIGHT

ON LOW IMPACT RESISTANT STRUCTURE.

11111111

GRAPHIC SCALE

30'30' 0 90'60'

1" = 30'-0"

ENLARGED PLAN - PAD MOUNTED TRANSFORMER

TRANSFORMER PRIMARY CABLE &

CONDUIT - 1 # 6 (5KV) L-824 & 1 # 6 (600 V.) N.

IN 2" PVC, SCH. 40 CONDUIT. SEE "SINGLE

LINE DIAGRAM - SFL SYSTEM," SHEET E-25.

LARGE SCALE PLAN - APPROACH

STRUCTURE MG-30 & MG-40 W/ SFL

SCALE: 1/4" = 1'-0"

LARGE SCALE PLAN - APPROACH

STRUCTURE MG-20 W/ SFL

SCALE: 1/4" = 1'-0"

2 SEE "LARGE SCALE PLAN - APPROACH STRUCTURE MG-30 & MG-40 W/ SFL," THIS SHEET.

3 SEE "LARGE SCALE PLAN - APPROACH STRUCTURE MG-20 W/ SFL," THIS SHEET.

2 2 2 3 3 3 3 3

6 # 4, (2) 7/C # 12 & (2) 4/C # 12 CABLES IN 2" PVC, SCH. 40 CONDUIT4

5 - L-823 APPROACH LIGHT SECONDARY CABLES & 1 # 6 GND. IN 2" PVC, SCH. 40 CONDUIT5

SFL JUNCTION BOX

SFL INDIVIDUAL CONTROL CABINET

LIGHT BASE

SFL JUNCTION BOX

SFL INDIVIDUAL CONTROL CABINET

LIGHT BASE

LIR STRUCTURE MAST

LIR CONCRETE FOUNDATION

LIR STRUCTURE MAST

LIR CONCRETE FOUNDATION

EDGE OF WETLANDS JURISDICTION

EDGE OF WETLANDS BUFFER

B

E

A

V

N

D

PAD MOUNTED TRANSFORMER -

10 KVA, 1Ø, 4.16/2.4 KV PRIMARY

TO 240/120 V. SECONDARY -

SEE "SINGLE LINE DIAGRAM -

SFL SYSTEM," SHEET E-25.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE," SHEET E-27.

CONDUIT & WIRING TO NEXT HANDHOLE -

WIRING BETWEEN HANDHOLES VARIES.

SEE ELECTRICAL SITE PLANS FOR EXACT

WIRING DESCRIPTIONS.

CONDUIT & WIRING TO NEXT HANDHOLE - WIRING

BETWEEN HANDHOLES VARIES. SEE ELECTRICAL

SITE PLANS FOR EXACT WIRING DESCRIPTIONS.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE," SHEET E-27.

6 NEW 4 WAY 2" CONCRETE ENCASED DUCTBANK - (3) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

7 NEW 4 WAY 2" CONCRETE ENCASED DUCTBANK - (1) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

NEW 4 WAY 2" CONCRETE ENCASED DUCTBANK - (2) 7/C # 12 & (2) 4/C # 12 & 3 # 10 & 1 # 10 GND. IN (1) 2" DUCT, AND

2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 2" DUCT, W/ (2) SPARE 2" DUCTS.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

X I W

Y

TAXIWAY A

KEY PLAN

N.T.S.

AREA 1 AREA 2

SCALE: 1" = 100'-0"

ELECTRICAL SITE PLAN - EXISTING AIRFIELD AREA 1

GENERAL NOTES:

1. NEW AIRFIELD LIGHTING CABLES SHALL BE HIPOT TESTED IN ACCORDANCE WITH SPECIFICATION

SECTION 26 56 20.00 10, PARAGRAPH 3.16.5.2. EXISTING AIRFIELD LIGHTING CABLES SHALL BE TESTED

FOR CONTINUITY IN ACCORDANCE WITH SPECIFICATION SECTION 26 56 20.00 10, PARAGRAPH 3.16.5.1.

2. IN ALL LOCATIONS WHERE THE NEW COUNTERPOISE CONDUCTOR CROSSES AN EXISTING

COUNTERPOISE CONDUCTOR, THE CONTRACTOR SHALL BOND THE COUNTERPOISE CONDUCTORS

TOGETHER BY EXOTHERMIC WELD. THIS WILL OCCUR WHEREVER A NEW DUCTBANK CROSSES AN

EXISTING DUCTBANK AND AT EVERY EXISTING MANHOLE OR HANDHOLE. FOR BID PURPOSES, THE

CONTRACTOR SHALL INCLUDE 50 EXOTHERMIC WELDS TO ALLOW FOR UNFORESEEN CIRCUMSTANCES

IN THE FIELD.

100' 100'0 200' 300'

GRAPHIC SCALE

1" = 100'-0"

SEE GENERAL NOTE 2, THIS SHEET.

M A

T C

H

L

I N

E

E

E

WORK NOTES: (THIS SHEET ONLY)

PULL EXISTING APPROACH LIGHT SERIES LIGHTING CIRCUIT OUT OF EXISTING DUCTBANK. PULL EXISTING

SEQUENCED FLASHER LIGHT CONTROL CABLE OUT OF EXISTING DUCTBANK. PULL EXISTING 5 KV PRIMARY CABLE &

600 V. NEUTRAL CONDUCTOR OUT OF EXISTING DUCTBANK.

2 INSTALL NEW 6'-0" X 6'-0" PRECAST CONCRETE MANHOLE. SEE DETAILS, SHEET E-27.

3 INSTALL 4 WAY 4" DUCTBANK BY DIRECTIONAL BORE METHOD. INSTALL COUNTERPOISE CONDUCTOR IN 2" HDPE

CONDUIT ABOVE 4" DUCTS.

4 INSTALL 4 WAY 4" CONCRETE ENCASED DUCTBANK BY TRENCH & BACKFILL METHOD.

5 CORE DRILL EXISTING MANHOLE WALL FOR NEW CONDUIT ENTRANCES. INSTALL NON-SHRINK GROUT AROUND

CONDUIT PENETRATIONS.

SEE "ELECTRICAL SITE PLAN - APPROACH

AREA 1," SHEET E-9, FOR CONTINUATION.

6 INSTALL NEW 3'-0" X 3'-0" PRECAST CONCRETE HANDHOLE. SEE DETAILS, SHEET E-27.

7 CUT & PATCH EXISTING ASPHALT DRIVE. SEE "DETAIL 'A'," SHEET C-501 FOR CUTTING & PATCHING REQUIREMENTS.

8 UNDER BASE BID, PULL NEW WIRING IN EXISTING DUCTBANKS: 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1)

4" DUCT FOR SFL PAD MOUNTED TRANSFORMER, 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT FOR SFL

CONTROLS, 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING.

9 9 9

SEE GENERAL NOTE 2, THIS SHEET.

1 BB

BO1

BB

BB

BO1

BO1

BO1 BO1 BO1

BO1

BO1

BB

9 UNDER BID OPTION # 1, PULL NEW WIRING IN NEW DUCTBANKS: 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN

(1) 4" DUCT FOR SFL PAD MOUNTED TRANSFORMER, 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT FOR SFL

CONTROLS, 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING, (1) SPARE 4" DUCT.

BO1

BO1

BO1

BO1

BO1

5 BO1

BO1

5 BO1

BO1

BO1

BO1

BO1

BO1

BB

BB

BB8

BB8

BB8

BB8

BB8

BB8

1 BB8

BB

BO1

INDICATES WORK TO BE ACCOMPLISHED UNDER BASE BID.

INDICATES WORK TO BE ACCOMPLISHED UNDER BID OPTION # 1.

RUNWAY

5 BO1

BO1

BB

BB

1 BB

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

CONTROL

TOWER

VAULT 3056

T A

X I W

C

100' 100'0 200' 300'

GRAPHIC SCALE

1" = 100'-0"

SCALE: 1" = 100'-0"

ELECTRICAL SITE PLAN - EXISTING AIRFIELD AREA 2

KEY PLAN

N.T.S.

AREA 1 AREA 2

SEE "ELECTRICAL PLAN - VAULT 3056,"

SHEET E-14, FOR WORK IN THIS AREA.

2 2

M A

T C

H

L

I N

E

E

E

WORK NOTES: (THIS SHEET ONLY)

PULL EXISTING APPROACH LIGHT SERIES LIGHTING CIRCUIT OUT OF EXISTING DUCTBANK. PULL EXISTING

SEQUENCED FLASHER LIGHT CONTROL CABLE OUT OF EXISTING DUCTBANK. PULL EXISTING 5 KV PRIMARY CABLE &

600 V. NEUTRAL CONDUCTOR OUT OF EXISTING DUCTBANK.

2 INSTALL NEW 6'-0" X 6'-0" PRECAST CONCRETE MANHOLE. SEE DETAILS, SHEET E-27.

3 INSTALL 4 WAY 4" DUCTBANK BY DIRECTIONAL BORE METHOD. INSTALL COUNTERPOISE CONDUCTOR IN 2" HDPE

CONDUIT ABOVE 4" DUCTS.

4 INSTALL 4 WAY 4" CONCRETE ENCASED DUCTBANK BY TRENCH & BACKFILL METHOD.

5 INSTALL 12 WAY 4" DUCTBANK BY DIRECTIONAL BORE METHOD. INSTALL COUNTERPOISE CONDUCTOR IN 2" HDPE

CONDUIT ABOVE 4" DUCTS.

6 CORE DRILL EXISTING MANHOLE WALL FOR NEW CONDUIT ENTRANCES. INSTALL NON-SHRINK GROUT AROUND

CONDUIT PENETRATIONS.

7 UNDER BASE BID, PULL NEW WIRING IN NEW DUCTBANKS: 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 4"

DUCT FOR SFL PAD MOUNTED TRANSFORMER, 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT FOR SFL

CONTROLS, 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING, (9) SPARE 4" DUCTS.

SEE GENERAL NOTE 2, THIS SHEET.

SEE GENERAL NOTE 2, THIS SHEET.

GENERAL NOTES:

1. NEW AIRFIELD LIGHTING CABLES SHALL BE HIPOT TESTED IN ACCORDANCE WITH SPECIFICATION

SECTION 26 56 20.00 10, PARAGRAPH 3.16.5.2. EXISTING AIRFIELD LIGHTING CABLES SHALL BE TESTED

FOR CONTINUITY IN ACCORDANCE WITH SPECIFICATION SECTION 26 56 20.00 10, PARAGRAPH 3.16.5.1.

2. IN ALL LOCATIONS WHERE THE NEW COUNTERPOISE CONDUCTOR CROSSES AN EXISTING

COUNTERPOISE CONDUCTOR, THE CONTRACTOR SHALL BOND THE COUNTERPOISE CONDUCTORS

TOGETHER BY EXOTHERMIC WELD. THIS WILL OCCUR WHEREVER A NEW DUCTBANK CROSSES AN

EXISTING DUCTBANK AND AT EVERY EXISTING MANHOLE OR HANDHOLE. FOR BID PURPOSES, THE

CONTRACTOR SHALL INCLUDE 50 EXOTHERMIC WELDS TO ALLOW FOR UNFORESEEN CIRCUMSTANCES

IN THE FIELD.

BO1 BO1 BO1

BO1

BO1

BO1

BO1

BO1 BO1

BB8

BB8

BB8

1 BB

BB

BB

BB

BB

BB

BB

BB

BB

BB

BB

BB

BB

BB

BB

UNDER BASE BID, PULL NEW WIRING IN EXISTING DUCTBANKS: 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1)

4" DUCT FOR SFL PAD MOUNTED TRANSFORMER, 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT FOR SFL

CONTROLS, 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING.

9 UNDER BID OPTION # 1, PULL NEW WIRING IN NEW DUCTBANKS: 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN

(1) 4" DUCT FOR SFL PAD MOUNTED TRANSFORMER, 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT FOR SFL

CONTROLS, 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING, (1) SPARE 4" DUCT.

10 UNDER BASE BID, PULL NEW WIRING IN NEW DUCTBANKS: 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 # 6 (600V.) N. IN (1) 4"

DUCT FOR SFL PAD MOUNTED TRANSFORMER, 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 4" DUCT FOR SFL

CONTROLS, 2 # 6 L-824, TYPE C & 1 # 6 (600 V.) GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING, (1) SPARE 4" DUCT.

BO1

BO1

BB

BO1

INDICATES WORK TO BE ACCOMPLISHED UNDER BASE BID.

INDICATES WORK TO BE ACCOMPLISHED UNDER BID OPTION # 1.

AIRCRAFT PARKING APRON

TAXIWAY A

RUNWAY

BO1

BO1

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

ELECTRICAL PLAN - VAULT 3056

SCALE: 1/4" = 1'-0"

VAULT

GENERATOR ROOM

REGULATOR ROOM

T

EXISTING MANHOLE

N

EXISTING APPROACH REGULATOR

T T

EXISTING MANHOLE

EXISTING PIT

EXISTING 6 WAY 2" CONCRETE

ENCASED DUCTBANK

4' 4'0 8' 12'

GRAPHIC SCALE

1/4" = 1'-0"

EXISTING 6 WAY 4" CONCRETE

ENCASED DUCTBANK.

EXISTING 4 WAY 3" CONCRETE ENCASED

DUCTBANK.

EXTEND NEW SERIES LIGHTING CIRCUIT FROM

REGULATOR TO SERIES CUTOUTS. EXTEND NEW CIRCUITS

FROM SERIES CUTOUTS THROUGH WALL MOUNTED

GUTTER SYSTEM TO EXISTING MANHOLE OUTSIDE OF

VAULT. SERIES LIGHTING CIRCUIT SHALL BE 2 # 6, L-824

TYPE C, 5 KV CABLES & 1 # 6, 600 V. GROUND CONDUCTOR.

EXISTING WALL MOUNTED GUTTER SYSTEM

EXISTING SERIES CUTOUT FOR FEEDER TO SFL PAD MOUNTED

TRANSFORMER. EXTEND 1 # 6 (5 KV) L-824 CABLE FROM SERIES

CUTOUT THROUGH WALL MOUNTED GUTTER SYSTEM TO

EXISTING MANHOLE OUTSIDE OF VAULT. EXTEND 1 # 6 (600 V.)

NEUTRAL CONDUCTOR FROM EXISTING GROUND CONNECTION IN

GUTTER SYSTEM THRU GUTTER TO MANHOLE OUTSIDE OF VAULT.

NEW 12 WAY 4" DUCTBANK. SEE

"ELECTRICAL SITE PLAN - EXISTING

AIRFIELD AREA 2," SHEET E-13, FOR

CONTINUATION.

EXISTING 6 WAY 2" DUCTBANK W/ FOUR (4) SPARE 2" DUCTS. PULL NEW 1 # 6 (5 KV) L-824, TYPE C CABLE & 1 #

6 (600V.) N. IN (1) 2" DUCT FOR SFL PAD MOUNTED TRANSFORMER THRU EXISTING WALL MOUNTED GUTTER

TO SERIES CUTOUT, PULL NEW 1 - 6/C # 10 AWG, L-824, TYPE C CABLE IN (1) 2" DUCT FOR SFL CONTROLS

THRU WALL MOUNTED GUTTER TO EXISTING RELAY PANEL, PULL NEW 2 # 6 L-824, TYPE C & 1 # 6 (600 V.)

GROUND IN (1) 4" DUCT FOR APPROACH LIGHTING THRU WALL MOUNTED GUTTER TO EXISTING SERIES

CUTOUTS AT APPROACH REGULATOR.

EXISTING SEQUENCED FLASHING LIGHT RELAY PANEL.

EXTEND 1 - 6/C # 10 AWG, L-824, TYPE C CABLE THRU

WALL MOUNTED GUTTER SYSTEM TO EXISTING MANHOLE

OUTSIDE OF VAULT.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

BRICK

HIGH INTENSITY SEMI-FLUSH L-850E UNI-DIRECTIONAL

W/ (2) 105 W., 6.6 A. LAMPS WITH SEALED OPTICAL

ASSEMBLY & TWO RED LENSES.

# 6 (GREEN) COPPER GROUND CONDUCTOR

L-830 20/6.6 A. 200 W. TRANSFORMER

PLAN VIEW

2 # 6 L-824, TYPE C & 1 # 6

THW GROUND - 2" PVC,

SCH. 40 CONDUIT

3500 PSI CONCRETE

DETAIL - PRE-THRESHOLD & TERMINATING BAR LIGHT -

L-850E (MILITARY)

N.T.S.

BRICK

HIGH INTENSITY SEMI-FLUSH L-850E UNI-DIRECTIONAL

W/ (2) 105 W., 6.6 A. LAMPS WITH SEALED OPTICAL

ASSEMBLY & TWO CLEAR LENSES.

# 6 (GREEN) COPPER GROUND CONDUCTOR

5KV L-824 TYPE C CABLE -

LEAVE MINIMUM 2'-0" SLACK

L-823 CONNECTOR W/

HEAT SHRINK KIT (TYP.)

L-830 20/6.6 A. 200 W. TRANSFORMER

PLAN VIEW

3500 PSI CONCRETE

L-867 LIGHT BASE

GROUND LUG

DETAIL - CENTERLINE BARRETTE LIGHT - L-850E (MILITARY)

BOND TO GROUND ROD W/ EXOTHERMIC WELD (TYP.)

3/4" X 10'-0" COPPERCLAD GROUND ROD -

LOCATED EVERY 1000'-0"

# 4 SDBC COUNTERPOISE - ROUTE AROUND LIGHT BASE

AS REQUIRED TO MAINTAIN A 12" MINIMUM SEPARATION

FROM LIGHT BASE & LIGHT BASE GROUND ROD.

4"

BOND TO GROUND ROD W/ EXOTHERMIC WELD (TYP.)

4"

5KV L-824 TYPE C CABLE -

LEAVE MINIMUM 2'-0" SLACK

L-823 CONNECTOR W/

HEAT SHRINK KIT (TYP.)

L-867 LIGHT BASE

GROUND LUG

3/4" X 10'-0" COPPERCLAD GROUND ROD -

LOCATED EVERY 1000'-0"

# 4 SDBC COUNTERPOISE - ROUTE AROUND LIGHT BASE AS

REQUIRED TO MAINTAIN A 12" MINIMUM SEPARATION FROM

LIGHT BASE & LIGHT BASE GROUND ROD.

1/4" MIN. TO 1/2" MAX.

1/4" MIN. TO 1/2" MAX.

DETAIL - CENTERLINE BARRETTE LIGHT - FAA-E-982

N.T.S.

BASE PLATE WITH GASKET AND BOLTS

FRANGIBLE COUPLING

1/4" MIN. TO 1/2" MAX.

BRICK

BOND TO GROUND ROD W/ EXOTHERMIC WELD (TYP.)

L-867 LIGHT BASE

5KV L-824 TYPE C CABLE -

LEAVE MINIMUM 2'-0" SLACK

L-823 CONNECTOR W/

HEAT SHRINK KIT (TYP.)

L-830 20/20 A. 300 W. TRANSFORMER

3500 PSI CONCRETE

4"

HIGH INTENSITY ELEVATED FAA-E-982 UNI-DIRECTIONAL

W/ (1) 300 W., 20 A., PAR-56 LAMP (NO FILTER.)

3/4" X 10'-0" COPPERCLAD GROUND ROD -

LOCATED EVERY 1000'-0"

# 4 SDBC COUNTERPOISE - ROUTE AROUND LIGHT BASE AS

REQUIRED TO MAINTAIN A 12" MINIMUM SEPARATION FROM

LIGHT BASE & LIGHT BASE GROUND ROD.

2" EMT CONDUIT

# 6 (GREEN) COPPER GROUND CONDUCTOR

2 # 6 L-824, TYPE C & 1 # 6 THW

GROUND - 2" PVC, SCH. 40 CONDUIT

2 # 6 L-824, TYPE C & 1 # 6 THW

GROUND - 2" PVC, SCH. 40 CONDUIT

2 # 6 L-824, TYPE C & 1 # 6 THW

GROUND - 2" PVC, SCH. 40 CONDUIT

2 # 6 L-824, TYPE C & 1 # 6

THW GROUND - 2" PVC,

SCH. 40 CONDUIT

2 # 6 L-824, TYPE C & 1 # 6

THW GROUND - 2" PVC,

SCH. 40 CONDUIT

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

APPROACH STRUCTURE PLAN - MG-20 W/ SEQUENCED FLASHING LIGHTS

SECTION

MOUNTING STAND

ASSEMBLY

MAST

STAND PLATE

N.T.S.

NOTES:

A

A

N.T.S.

TILT DEVICE

APPROACH LIGHT

40 1/2"40 1/2" 40 1/2"40 1/2"

MOUNTING FRAME

GRADE

1" MAX.

NOTE: THIS DETAIL IS TYPICAL FOR STRUCTURES FROM 6'-1" TO 21'-1" HIGH.

SEQUENCED FLASHING LIGHT (FLASHERS

ARE LOCATED ON STRUCTURES FROM

STATION 10+00 TO STATION 24+00 ONLY)

DETAIL "A"

N.T.S.

L-823 SECONDARY CABLES - EXTEND FROM

TRANSFORMERS IN HANDHOLE TO

APPROACH LIGHTS ON LIR STRUCTURE.

LEAVE 2'-0" SLACK IN LIGHT BASE.

12" DIA X 24" DEEP L-867 BASE

# 6 (GREEN) COPPER

GROUND CONDUCTOR

GROUND LUG

1. ANCHOR BOLTS SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.

2. SECONDARY ELECTRICAL CONNECTIONS SHALL ENTER AT THE BASE OF THE

TOWER AND BE BROUGHT UP INSIDE THE TOWER MAST. ALL FITTINGS AND

CONDUITS SHALL BE WATERTIGHT. WIRING TO INDIVIDUAL FIXTURES (APPROACH

& STROBE) SHALL BE RUN INTERNALLY THRU SLIPFITTERS AND ADAPTERS

WITHOUT ANY EXPOSED CORDS.

3. TOWERS FROM 6'-1" TO 21'-1" SHALL UTILIZE FOUNDATION AS SHOWN ON DETAILS,

THIS SHEET.

4. TOWERS SHALL BE FRANGIBLE, LOW-IMPACT RESISTANT TYPE, CONSTRUCTED OF

FIBERGLASS CONFORMING TO FAA-E-2702 AND FAA DRAWING SERIES D-6155.

5. CONTRACTOR SHALL FURNISH TWO TILT DEVICES UNDER THIS CONTRACT.

WATERTIGHT FLASHER INDIVIDUAL CONTROL CABINET MOUNTED ON FRANGIBLE

COUPLINGS - LOCATED AT STATION 10+00 THROUGH STATION 24+00 ONLY.

WATERTIGHT FLASHER JUNCTION BOX MOUNTED ON FRANGIBLE

COUPLINGS - LOCATED AT STATION 10+00 THROUGH STATION 24+00 ONLY.

HIGH INTENSITY ELEVATED FAA-E-982 UNI-DIRECTIONAL

W/ (1) 300 W., 20 A., PAR-56 LAMP (NO FILTER.)

APPROACH LIGHT MOUNTING TENON

N.T.S.

DETAIL - APPROACH LIGHT - MOUNTED

ON LIR STRUCTURE - FAA-E-982

LIR STRUCTURE CROSSARM

B

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

WORK NOTES:

(THIS SHEET ONLY)

6 # 4, (2) 7/C # 12 & (2) 4/C # 12 CABLES IN 2" PVC, SCH. 40 CONDUIT

2 3 # 10 & 1 # 10 GND. AND 5 # 12 IN 2" RIGID GALV. STEEL CONDUIT

3 5 # 12 SEQUENCED FLASHING LIGHT CABLES IN 1" LIQUIDTIGHT FLEXIBLE METAL CONDUIT

4 5 # 10 L-824 APPROACH LIGHT SECONDARY CABLES & 1 # 6 GND. IN 2" PVC, SCH. 40 CONDUIT

5 5 # 10 L-824 APPROACH LIGHT SECONDARY CABLES IN 1" LIQUIDTIGHT FLEXIBLE METAL CONDUIT

SECTION C

N.T.S.

LOCATE CONDUITS CLOSE TO

CORNERS OF HANDHOLE (TYP.)

ISOLATION TRANSFORMER MOUNTED IN HANDHOLE (TYP. FOR 5) -

EXTEND SECONDARY WIRING TO APPROACH HEAD ON LIR

STRUCTURE, AS SHOWN. MOUNT ISOLATION TRANSFORMERS ON

A BRICK.

UNI-DIRECTIONAL SEQUENCED FLASHING

LIGHT W/ PAR-56 XENON FLASHTUBE

FLASHER MOUNTING TENON

N.T.S.

DETAIL - SEQUENCED FLASHING LIGHT -

MOUNTED ON LIR STRUCTURE

FLASHER MOUNTING BRACKET

LIR STRUCTURE MAST

TRUNION CLAMPS

INSTALL BELL ENDS ON ALL

CONDUITS ENTERING HANDHOLES

1'-0"

1 2

LIGHT BASE

3'-0" DIAMETER X 4'-0" DEEP

CONCRETE FOUNDATION - SEE

STRUCTURAL DETAILS, SHEET S-1.

SEE "DETAIL - SEQUENCED FLASHING LIGHT INDIVIDUAL CONTROL CABINET

AND JUNCTION BOX," SHEET E-21.

CONCRETE FOUNDATION - SEE

STRUCTURAL DRAWINGS.

SEE "DETAIL A," THIS SHEET.

ISOLATION TRANSFORMER MOUNTED IN

HANDHOLE (TYP. FOR 5) - EXTEND

SECONDARY WIRING TO APPROACH HEAD

ON LIR STRUCTURE, AS SHOWN. MOUNT

ISOLATION TRANSFORMERS ON A BRICK.

WEATHERPROOF

"LB" CONDULET

SECTION B

N.T.S.

TILT DEVICE - SEE DETAIL,

THIS SHEET.

DETAIL - TILT DEVICE

N.T.S.

C

6"

8"

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

8+00

18+00

21+00

22+00

20+00

19+00

16+00

17+00

14+00

15+00

10+00 - STRUCTURE 4

11+00

12+00

13+00

10+00 - STRUCTURE 5

10+00 - STRUCTURE 2

10+00 - STRUCTURE 3

9+00

10+00 - STRUCTURE 1

6+00

7+00

CONDUIT SUPPORTS

APPROACH STRUCTURE SCHEDULE

LIR STRUCTURE

23+00

24+00

STRUCTURE STATION SUPPORT TYPE LIR STRUCTURE TYPE

MG-20 W/O FLASHER

MG-30 W/O FLASHER

MG-30 W/ FLASHER

1'-2"

4'-3"

15'-6"

CONDUIT SUPPORTS

24'-7"

24'-9"

27'-0"

29'-6"

31'-8"

33'-6"

28'-10"

25'-10"

19'-4"

12'-8"

12'-5"

8'-5"

11'-9"

11'-6"

10'-10"

13'-6"

18'-7"

24'-7"

30'-1"

34'-11"

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

LIR STRUCTURE

MG-30 W/ FLASHER

MG-30 W/O FLASHER

MG-30 W/O FLASHER

MG-40 W/O FLASHER

MG-40 W/O FLASHER

MG-20 W/ FLASHER

MG-30 W/ FLASHER

MG-30 W/ FLASHER

MG-20 W/ FLASHER

MG-20 W/ FLASHER

MG-20 W/ FLASHER

MG-20 W/ FLASHER

MG-20 W/ FLASHER

MG-20 W/ FLASHER

MG-20 W/ FLASHER

MG-30 W/ FLASHER

MG-40 W/ FLASHER

MG-40 W/ FLASHER

DISTANCE FROM TOP

OF FOUNDATION TO

CENTER OF

APPROACH LIGHT

CENTERLINE BARRETTE

CENTERLINE BARRETTE

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

CONCRETE FOUNDATION -

SEE STRUCTURAL DETAILS,

SHEET S-1.

SHEET #

E-6 & E-9

E-7 & E-10

E-8 & E-11

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-7 & E-10

E-8 & E-11

E-8 & E-11

E-8 & E-11

E-8 & E-11

E-8 & E-11

E-8 & E-11

E-8 & E-11

24"

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

APPROACH STRUCTURE PLAN - MG-30 & MG-40 W/ SEQUENCED FLASHING LIGHTS

MAST

STAND

N.T.S.

NOTES:

N.T.S.

APPROACH LIGHT

40 1/2"40 1/2" 40 1/2"40 1/2"

NOTE: THIS DETAIL IS TYPICAL FOR STRUCTURES FROM 21'-2" TO 40'-0" HIGH.

TILT DEVICE

GRADE

1" MAX.

PLATE

JOINT

15'-1 9/16"

STABILIZER ROD

TURNBUCKLE

HORIZONTAL STABILIZER

GUY ANCHOR SUPPORT

CROSSBAR

MOUNTING STAND

ASSEMBLY

CONCRETE FOUNDATIONS - SIZES VARY -

SEE STRUCTURAL DETAILS, SHEET S-2.

GRADE

SEQUENCED FLASHING LIGHT (FLASHERS

ARE LOCATED ON STRUCTURES FROM

STATION 10+00 TO STATION 24+00 ONLY)

1. ANCHOR BOLTS SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.

2. SECONDARY ELECTRICAL CONNECTIONS SHALL ENTER AT THE BASE OF THE

TOWER AND BE BROUGHT UP INSIDE THE TOWER MAST. ALL FITTINGS AND

CONDUITS SHALL BE WATERTIGHT. WIRING TO INDIVIDUAL FIXTURES (APPROACH

& STROBE) SHALL BE RUN INTERNALLY THRU SLIPFITTERS AND ADAPTERS

WITHOUT ANY EXPOSED CORDS.

3. TOWERS FROM 21'-2" TO 40'-0" SHALL UTILIZE FOUNDATIONS AS SHOWN ON

DETAILS, THIS SHEET.

4. TOWERS SHALL BE FRANGIBLE, LOW-IMPACT RESISTANT TYPE, CONSTRUCTED OF

FIBERGLASS CONFORMING TO FAA-E-2702 AND FAA DRAWING SERIES D-6155.

5. TOWERS FROM 21'-2" TO 30'-0" SHALL BE TYPE MG-30. TOWERS FROM 30'-1" TO

40'-0" SHALL BE TYPE MG-40.

6. CONTRACTOR SHALL FURNISH TWO TILT DEVICES UNDER THIS CONTRACT.

HIGH INTENSITY ELEVATED FAA-E-982 UNI-DIRECTIONAL

W/ (1) 300 W., 20 A., PAR-56 LAMP (NO FILTER.)

APPROACH LIGHT MOUNTING TENON

N.T.S.

DETAIL - APPROACH LIGHT - MOUNTED

ON LIR STRUCTURE - FAA-E-982

LIR STRUCTURE CROSSARM

FLASHER MOUNTING TENON

N.T.S.

DETAIL - SEQUENCED FLASHING LIGHT -

MOUNTED ON LIR STRUCTURE

FLASHER MOUNTING BRACKET

LIR STRUCTURE MAST

TRUNION CLAMPS

A

A

WORK NOTES:

(THIS SHEET ONLY)

6 # 4, (2) 7/C # 12 & (2) 4/C # 12 CABLES IN 2" PVC, SCH. 40 CONDUIT

2 3 # 10 & 1 # 10 GND. AND 5 # 12 IN 2" RIGID GALV. STEEL CONDUIT

3 5 # 12 SEQUENCED FLASHING LIGHT CABLES IN 1" LIQUIDTIGHT FLEXIBLE METAL CONDUIT

DETAIL "A"

N.T.S.

L-823 SECONDARY CABLES - EXTEND FROM

TRANSFORMERS IN HANDHOLE TO

APPROACH LIGHTS ON LIR STRUCTURE.

LEAVE 2'-0" SLACK IN LIGHT BASE.

12" DIA X 24" DEEP L-867 BASE

# 6 (GREEN) COPPER

GROUND CONDUCTOR

GROUND LUG

WATERTIGHT FLASHER INDIVIDUAL CONTROL CABINET MOUNTED ON FRANGIBLE

COUPLINGS - LOCATED AT STATION 10+00 THROUGH STATION 24+00 ONLY.

WATERTIGHT FLASHER JUNCTION BOX MOUNTED ON FRANGIBLE

COUPLINGS - LOCATED AT STATION 10+00 THROUGH STATION 24+00 ONLY.

5 3

UNI-DIRECTIONAL SEQUENCED FLASHING

LIGHT W/ PAR-56 XENON FLASHTUBE

CONCRETE FOUNDATION - SEE

STRUCTURAL DRAWINGS.

CONCRETE FOUNDATION - SEE

STRUCTURAL DRAWINGS.

CONCRETE FOUNDATION - SEE

STRUCTURAL DRAWINGS.

1'-0"

6"

1'-0"

DETAIL - TILT DEVICE

N.T.S.

LOCATE CONDUITS CLOSE TO

CORNERS OF HANDHOLE (TYP.)

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

LOCATE CONDUITS CLOSE TO

CORNERS OF HANDHOLE (TYP.)

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

TILT DEVICE - SEE DETAIL,

THIS SHEET.

B

C

SECTION C

N.T.S.

ISOLATION TRANSFORMER MOUNTED IN HANDHOLE (TYP. FOR 5) -

EXTEND SECONDARY WIRING TO APPROACH HEAD ON LIR

STRUCTURE, AS SHOWN. MOUNT ISOLATION TRANSFORMERS ON

A BRICK.

INSTALL BELL ENDS ON ALL

CONDUITS ENTERING HANDHOLES

SEE "DETAIL A," THIS SHEET.

ISOLATION TRANSFORMER MOUNTED IN

HANDHOLE (TYP. FOR 5) - EXTEND

SECONDARY WIRING TO APPROACH HEAD

ON LIR STRUCTURE, AS SHOWN. MOUNT

ISOLATION TRANSFORMERS ON A BRICK.

WEATHERPROOF

"LB" CONDULET

SECTION B

N.T.S.

8"

5 # 10 L-824 APPROACH LIGHT SECONDARY CABLES & 1 # 6 GND. IN 2" PVC, SCH. 40 CONDUIT

5 # 10 L-824 APPROACH LIGHT SECONDARY CABLES IN 1" LIQUIDTIGHT FLEXIBLE METAL CONDUIT

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE," SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

CONCRETE FOUNDATION -

SEE STRUCTURAL DETAILS,

SHEET S-2.

24"

3"

21"±

3"

11"±

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

MOUNTING STAND

ASSEMBLY

MAST

STAND PLATE

N.T.S.

NOTES:

N.T.S.

6"

6"

APPROACH LIGHT

40 1/2"40 1/2" 40 1/2"40 1/2"

NOTE: THIS DETAIL IS TYPICAL FOR STRUCTURES FROM 6'-1" TO 21'-1" HIGH AND OCCURS AT STATION 8+00 ONLY.

1. ANCHOR BOLTS SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.

2. SECONDARY ELECTRICAL CONNECTIONS SHALL ENTER AT THE BASE OF THE

TOWER AND BE BROUGHT UP INSIDE THE TOWER MAST. ALL FITTINGS AND

CONDUITS SHALL BE WATERTIGHT. WIRING TO INDIVIDUAL FIXTURES (APPROACH

& STROBE) SHALL BE RUN INTERNALLY THRU SLIPFITTERS AND ADAPTERS

WITHOUT ANY EXPOSED CORDS.

3. TOWERS FROM 6'-1" TO 21'-1" SHALL UTILIZE FOUNDATION AS SHOWN ON DETAILS,

THIS SHEET.

4. TOWERS SHALL BE FRANGIBLE, LOW-IMPACT RESISTANT TYPE, CONSTRUCTED OF

FIBERGLASS CONFORMING TO FAA-E-2702 AND FAA DRAWING SERIES D-6155.

5. CONTRACTOR SHALL FURNISH TWO TILT DEVICES UNDER THIS CONTRACT.

HIGH INTENSITY ELEVATED FAA-E-982 UNI-DIRECTIONAL

W/ (1) 300 W., 20 A., PAR-56 LAMP (NO FILTER.)

APPROACH LIGHT MOUNTING TENON

N.T.S.

DETAIL - APPROACH LIGHT - MOUNTED

ON LIR STRUCTURE - FAA-E-982

LIR STRUCTURE CROSSARM

CROSSBAR

APPROACH STRUCTURE PLAN - MG-20 W/O SEQUENCED FLASHING LIGHTS

SEE "DETAIL A," THIS SHEET.

ISOLATION TRANSFORMER MOUNTED IN

HANDHOLE (TYP. FOR 5) - EXTEND

SECONDARY WIRING TO APPROACH HEAD

ON LIR STRUCTURE, AS SHOWN. MOUNT

ISOLATION TRANSFORMERS ON A BRICK.

WEATHERPROOF

"LB" CONDULET

A

B

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

LOCATE CONDUITS CLOSE TO

CORNERS OF HANDHOLE (TYP.)

A

WORK NOTES:

(THIS SHEET ONLY)

DETAIL "A"

L-823 SECONDARY CABLES - EXTEND FROM

TRANSFORMERS IN HANDHOLE TO

APPROACH LIGHTS ON LIR STRUCTURE.

LEAVE 2'-0" SLACK IN LIGHT BASE.

12" DIA X 24" DEEP L-867 BASE

# 6 (GREEN) COPPER

GROUND CONDUCTOR

GROUND LUG

SECTION B

N.T.S.

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

EXTEND CONDUITS TO NEXT

HANDHOLE AT ADJACENT

STRUCTURE. SEE ELECTRICAL SITE

PLANS ON SHEETS E-9 THRU E-11

FOR CONDUIT & WIRING DATA.

ISOLATION TRANSFORMER MOUNTED IN HANDHOLE (TYP. FOR

5) - EXTEND SECONDARY WIRING TO APPROACH HEAD ON LIR

STRUCTURE, AS SHOWN. MOUNT ISOLATION TRANSFORMERS

ON A BRICK.

INSTALL BELL ENDS ON ALL

CONDUITS ENTERING HANDHOLES

TILT DEVICE

MOUNTING FRAME

GRADE

1" MAX.

DETAIL - TILT DEVICE

N.T.S.

6"

CONCRETE FOUNDATION - SEE

STRUCTURAL DRAWINGS.

TILT DEVICE - SEE DETAIL,

THIS SHEET.

5 # 10 L-824 APPROACH LIGHT SECONDARY CABLES & 1 # 6 GND. IN 2" PVC, SCH. 40 CONDUIT

5 # 10 L-824 APPROACH LIGHT SECONDARY CABLES IN 1" LIQUIDTIGHT FLEXIBLE METAL CONDUIT

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

HANDHOLE - SEE "DETAIL - 3' X 3'

PRECAST HANDHOLE, SHEET E-27.

3'-0" DIAMETER X 4'-0" DEEP

CONCRETE FOUNDATION - SEE

STRUCTURAL DETAILS, SHEET S-1.

CONCRETE FOUNDATION -

SEE STRUCTURAL DETAILS,

SHEET S-1.

12"±

24"

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

APPROACH STRUCTURE PLAN - MG-30 & MG-40 W/O SEQUENCED FLASHING LIGHT

MAST

STAND

N.T.S.

NOTES:

N.T.S.

6"

APPROACH LIGHT

40-1/2"40-1/2" 40-1/2"40-1/2"

NOTE: THIS DETAIL IS TYPICAL FOR STRUCTURES FROM 21'-2" TO 40'-0" HIGH.

PLATE

JOINT

15'-1 9/16"

STABILIZER ROD

TURNBUCKLE

HORIZONTAL STABILIZER

GUY ANCHOR SUPPORT

CROSSBAR

ANCHOR BOLTS - PER

MANUFACTURER'S

RECOMMENDATIONS

GRADE

1. ANCHOR BOLTS SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.

2. SECONDARY ELECTRICAL CONNECTIONS SHALL ENTER AT THE BASE OF THE

TOWER AND BE BROUGHT UP INSIDE THE TOWER MAST. ALL FITTINGS AND

CONDUITS SHALL BE WATERTIGHT. WIRING TO INDIVIDUAL FIXTURES (APPROACH

& STROBE) SHALL BE RUN INTERNALLY THRU SLIPFITTERS AND ADAPTERS

WITHOUT ANY EXPOSED CORDS.

3. TOWERS FROM 21'-2" TO 40'-0" SHALL UTILIZE FOUNDATIONS AS SHOWN ON

DETAILS,…