Amendment_2_-_Answers_to_Questions_&_Other_Changes.pdf

PDF 124 KB Posted

Attached to
Elevator Repair, Bldg. 1470 Federal contract opportunity
Solicitation number
FA2517-18-Q-5050
Issued by
Department of the Air Force Space Command

About this file

Amendment 2 to the Combo FA2517-18-Q-5050.

View the file

Other files for this federal contract opportunity

Other files attached to Elevator Repair, Bldg. 1470, newest first.
File Type Posted
Amendment_1_-_Revised_Site_Visit_Pre-Registration_Date.pdf PDF
Attachment_1,_PWS_dated_10_July_2018.pdf PDF
Combo;_Elevator_Repair_Bldg_1470.pdf PDF
Attachment_3;_Contractor_Submittal_Form.docx DOCX document
Attachment_2;_WD_1986-0346_Rev_No_51;_20180309.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

21ST SPACE WING

17 August 2018

MEMORANDUM FOR POTENIAL CONTRACTORS

FROM: 21 CONS/PKAB

SUBJECT: Amendment 2, FA2517-18-Q-5050, Elevator Repair Bldg. 1470

1. This is Amendment 2 to the subject line project in order to: change the proposal due date from 20 August 2018 at 9:00 A.M. Mountain Time to 21 August 2018 at 10:00 A.M. Mountain Time; to include in the requirement for the contractor to provide schematics and wiring diagrams for any changes made under this contract; and to provide answers to the following industry questions:

a. Question 1: Is the new elevator contractor to provide new fixtures and wiring?

Answer: No, except for those required for the repair work as set out in the Statement of Work.

b. Question 2: What code year does the elevator need to be modernized to?

Answer: This should be a repair, not a modernization. The elevators need to comply with American Society of Mechanical Engineers (ASME) A17.1-2013.

c. Question 3: Is the elevator contractor to complete any building related work to bring the elevator up to code?

Answer: No.

d. Question 4: Are we to do any work to the door operator, clutch, door tracks or rollers?

e. Question 5: Are there any cab upgrades that are to be done?

f. Question 6: Are you required to comply with the conveyance regulations enforced by the Colorado Division of Oil and Public safety?

Answer: All work as part of this repair is required to comply with specific requirements of the current ASME A17.1 Code edition. See ASME A17.1 for requirements.

g. Question 7: What agency regularly inspects your elevators?

Answer: None, the elevator is not required to be inspected by an agency.

2. If you have any questions, please email the undersigned at dylan.huntley@us.af.mil.