This is an exhibit document related to an audiovisual and technology services contract for the California Community Colleges system (AVC2026-2027-3 CCD). The document pertains to a project involving the relocation of a 60X40 modular classroom building at Fox Field. The exhibit appears to serve as a supporting document detailing technical specifications, requirements, or cost information associated with the relocation project. The contract involves equipment or systems necessary to support the modular building's functionality at its new location, with the service period spanning the 2026-2027 fiscal years for the community college district.
The document functions as a technical or financial exhibit supporting the competitive bidding process for this relocation work. As an exhibit within a broader solicitation package, it establishes baseline requirements and specifications that bidders must address in their proposals. The specific pricing terms, contract duration, and detailed scope requirements would be established through the primary contract documents and any associated addenda issued by the California Community Colleges system.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DGS DSA 140 (rev 10/02/19) Page 1 of 2 DIVISION OF THE STATE ARCHITECT DEPARTMENT OF GENERAL SERVICES STATE OF CALIFORNIA
APPLICATION FOR SUBMITTAL OF POST-APPROVAL DOCUMENT
This application is for submittal of documents, after the initial approval of the project (post-approval documents), that require Division of the State Architect (DSA) review and approval.This form shall be completed by the Design Professional in General Responsible Charge of the project, in accordance with California Code of Regulations, Title 24, Part 1, Sections 4-317, 4-323 and 4-338 and in compliance with DSA IR A-6: Construction Change Document Submittal and Approval Process.
DSA documents referenced within this form are available on the DSA Forms or DSA Publications webpages.
1. SUBMITTAL TYPE: (Is this a resubmittal? Yes☐ No ☐)
Deferred Submittal ☐ Addendum Number: Revision Number: CCD Number: Category A ☐ or B ☐
2. PROJECT INFORMATION:
School District/Owner: DSA File Number:
Project Name/School: DSA Application Number:
3. APPLICANT INFORMATION:
Date Submitted: Attached Pages? No ☐ Yes ☐ Number of pages?
Firm Name: Contact Name:
Work Email: Work Phone:
Firm Address: City: State: Zip Code:
4. REASON FOR SUBMITTAL: (Check applicable boxes)
☐ For revision or addendum prior to construction. ☐ For a project currently under construction.
☐ For a project that has a form DSA 301-N: Notification of Requirement for Certification, DSA 301-P: Posted Notification of Requirement for Certification or a 90-Day Letter issued.
☐ To obtain DSA approval of an existing uncertified building or buildings.
☐ For Category B CCD this is: ☐ a voluntary submittal, ☐ a DSA required submittal (attach DSA notice requiring submission).
5. DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE:
Name of the Design Professional In General Responsible Charge:
Professional License Number: Discipline:
Design Professional in General Responsible Charge Statement: The attached post-approval documents have been examined by me for design intent and appear to meet the appropriate requirements of Title 24, California Code of Regulations and the project specifications. They are acceptable for incorporation into the construction of the project.
Signature:_______________________________________________________________________________________
DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE
6. CONFIRMATION, DESCRIPTION AND LISTING OF DOCUMENTS:
For addenda, revisions, or CCDs: CHECK THIS BOX ☐ to confirm that all post-approval documents have been stamped and signed by the Responsible Design Professional listed on form DSA 1: Application for Approval of Plans and Specifications for this project. (For Deferred Submittals, refer to IR A-18:
Use of Construction Documents Prepared by Other Professionals, and IR A-19: Design Professional’s Signature and Seal (Stamp) on Construction Documents, when applicable, for signature and seal requirements.)
Provide a brief description of construction scope for this post-approval document (attach additional sheets if needed):
List of DSA-approved drawings affected by this post-approval document:
DSA USE ONLY
SSS Date ☐Approved ☐Disapproved ☐Not Required
Comments:
FLS Date ☐Approved ☐Disapproved ☐Not Required
Comments:
ACS Date ☐Approved ☐Disapproved ☐Not Required
Comments:
Returned DSA STAMP Date:
By:
A0.0N, A1.3N, A4.3N, A8.1, E3.0N, P0.0 & P1.0
DSA Test Mark - EPR Admin Change to "INCORPORATE"
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
04-124946 0
✔ FLS ACS✔ ✔
04/16/2026 https://www.dgs.ca.gov/DSA/Forms https://www.dgs.ca.gov/DSA/Publications
CCD #01 Narrative Letter
January 14, 2026
Division of the State Architect – San Diego
10920 Via Frontera
San Diego, CA 92127
Attention: Plan Checker
Project: Stockpile
DSA A#: 04-124946
DSA File #: Stock-42
Dear Plan Checker, The following changes, omissions, and/or additions to the Approved Plans made to the above-referenced project. Below is a list of items explaining the changes made to the specific sheets.
Sheet A0.0N: Add new sheets. Update total sheet count.
Sheet A1.3N: Update keynotes. Addition of 7’-0” casework including ADA sink & eyewash. Addition of blocking. Addition of 6-gallon water heater.
Sheet A4.3N: Update keynotes. Addition of 7’-0” casework including ADA sink & eyewash. Addition of blocking. Addition of 6-gallon water heater.
Sheet A8.1: Uncrossed details from original approved plans that have become applicable
Sheet E3.0N: Update drawing to reflect architectural floor plan. Add additional dedicated power and j-boxes for low voltage. Update electrical panel.
Sheet P0.0: New sheet added for Plumbing discipline.
Sheet P1.0: New sheet added for Plumbing plans and layout.
End of CCD #01 Narrative
Submitted By
Jeffrey C. Chan-Lugay
Director of Design
Drawing Attachments: A0.0N, A1.3N, A4.3N, A8.1, E3.0, P0.0, & P1.0
DRAWING SYMBOLS & LEGEND SHEET INDEX
ARCHITECTURALSHEET NO. STRUCTURALSHEET NO.
DESIGN PARAMETERS
BUILDING DATA
STRUCTURAL DATA
STRUCTURAL DESIGN: ORDINARY MOMENT FRAME WITH CLEAR SPAN TRUSS
FOUNDATION: (NOT PART OF THIS STOCKPILE)
SEISMIC SEPARATION: 4 1/2" MIN FROM OTHER EXISTING OR FUTURE BUILDINGS
MEASURED FROM ITS FARTHEST PROJECTION
THIS PC (OR BLDG) IS DESIGNED STRUCTURALLY TO SUPPORT THE WEIGHT OF A FIRE
SPRINKLER SYSTEM
RAMP, LANDING AND STAIR (NOT PART OF THIS BUILDING) A0.0N
TITLE SHEET
FLOOR LIVE LOAD: 100 PSF
ROOF LIVE LOAD: 20 PSF
GROUND SNOW LOAD MAXIMUM: 31 PSF FULLY EXPOSED, 28 PARTIALLY EXPOSED, 26 PSF
SHELTERED
ROOF SNOW LOAD: 20 PSF MAX (ASCE 7-16 SEC 7.4)
Ce=0.9 FULLY EXPOSED, 1.0 PARTIALLY EXPOSED, 1.1 SHELTERED I=1.0, Ct=1.0
FOR SNOW DRIFT, THE SITE APPLICATION DSA REVIEWER SHALL VERIFY THAT THE
STRUCTURE IS TO BE LOCATED AT LEAST 20 FT FROM ANY ADJACENT STRUCTURE UNLESS A
DRIFT ANALYS IS PROVIDED (NOT ACCEPTED AT AN OTC REVIEW)
FLOOD HAZARD AREA: NO
WIND DESIGN: (ASCE 7-16)
Kzt=1.0
WIND SPEED=110 MPH, RISK CATEGORY = II, EXPOSURE='C'
INTERNAL PRESSURE COEFFICIENT = ±0.18
COMPONENTS & CLADDING DESIGN BY PC ENGINEER OF RECORD
DESIGN ROOF DEAD LOAD: 15 PSF (BEAMS AND TRUSSES) INCLUDES 3.0 PSF
FOR ROOF MOUNTED SOLAR PANELS
DESIGN FLOOR DEAD LOAD:
PLYWOOD FLOOR - 8 PSF (+15 W/ PARTITIONS),
EARTHQUAKE DESIGN DATA:
1. I=1.0, RISK CATEGORY=II
2. Ss=2.38 (MAX MAPPED VALUE)
SI=1.389 (MAX MAPPED VALUE)
3. SITE CLASS=C AND D-DEFAULT
Fa=1.2 & Fv=1.4
4. SDS=1.6, SDI=1.574
SDS (BUILDING = 0.7 X SDS) = 1.6, SDS (COMPONENTS) = 2.29
5. SEISMIC DESIGN CATEGORY=E
6. LIGHT MODULAR STEEL MOMENT FRAME PER CBC SECTION 2212A
7. DESIGN BASE SHEAR=16113# (FOR 24' X 40' BUILDING), 22415# (FOR 36' X 40' BUILDING), AND 28716# (FOR 48' X 40' BUILDING)
8. CS=0.381
9. R=3.5
10. EQUIVALENT LATERAL FORCE PROCEDURE
11. NO VERTICAL OR HORIZONTAL IRREGULARITIES
12. GROUND MOTION HAZARD ANALYSIS IS NOT REQUIRED PER ASCE 7-16, 11.4.8
EXCEPTION #2. VALUE OF Cs HAS BEEN DETERMINED BY EQN. 12.8-2 FOR A VALUE OF T<1.5 Ts
13. RHO = 1.0
GEOHAZARD REPORTS: THE DESIGN ARCHITECT IN GENERAL RESPONSIBLE CHARGE MUST DETERMINE IF A GEOHAZARD REPORT IS REQUIRED PER DSA IR A-4. IF REQUIRED, THE AOR SHALL VERIFY THAT THE GEOHAZARD REPORT IDENTIFIES NO SITE RELATED GEOLOGIC HAZARDS WHICH WOULD PRECLUDE THE USE OF THE PROPOSED PC DESIGN AT THE SITE, INCLUDING BUT NOT LIMITED TO LIQUEFACTION
POTENTIAL, LANDSLIDE, FLOODING, EARTHQUAKE FAULT, ETC.
TYPE OF CONSTRUCTION: V-B
OCCUPANCY: E NO. OF STORIES: 1
ALLOWABLE AREA: 9,500 SF
MODULES: 12'x40'
2"x4" WOOD STUD
5'-0" CLEAR FLOOR SPACE FOR WHEELCHAIR
ACCESSIBLE MANEUVERING
WITH 12" MIN. ENCROACHMENT
48"x30" CLEAR FLOOR SPACE FOR
WHEELCHAIR ACCESS TO FIXTURE
INDICATES EXTERIOR ELEVATION #
INDICATES SHEET #
INDICATES INTERIOR ELEVATION ORIENTATION
INDICATES SHEET #
INDICATES DETAIL #
INDICATES WINDOW TYPE
INDICATES DOOR TYPE
2"x6" WOOD STUD
2"x8" WOOD STUD
1 HR RATED (DARK LINE THROUGH SYMBOL)
INDICATES DETAIL #
INDICATES SHEET #
* KEY NOTE SYMBOL
GRID LINE NUMBER OR LETTER
INDICATES ROOM NAME
INDICATES ROOM NUMBER
ALLOWABLE SOIL BEARING: WOOD FOUNDATION: SEE SHEET S0.0a CONCRETE FOUNDATION: SEE SHEET S0.0a
60"x60" CLEAR FLOOR SPACE FOR
WHEELCHAIR ENTRY ACCESS.
WHEELCHAIR ACCESSIBLE CLEAR FLOOR SPACE AT
ACCESSIBLE WATER CLOSET
60"x59" AT FLOOR MOUNTED WATER CLOSET 60"x56" AT WALL MOUNTED WATER CLOSET
BUILDING AREAS:
60'x40'=2400 SF
TOTAL SHEET COUNT: 64
STC 40 REQUIRED WHEN USED FOR INTERIOR
WALLS SEPARATING TENANTS OR PUBLIC
SPACES. SEE INTERIOR WALL SCHEDULE ON
SHEET A0.2
INDICATES CUT SECTION DETAIL#
INDICATES SHEET #
NOTES:
1. SITE CLASS A, B, C, AND D TO BE SUBSTANTIATED BY GEOTECHNICAL REPORT, SITE CLASS
D- DEFAULT TO BE USED IN ABSENCE OF GEOTECHNICAL REPORT.
2. UNLESS A SITE SPECIFIC GROUND MOTION HAZARD ANALYSIS IS PERFORMED, THE Sm, VALUE INCREASED BY 50% SHALL BE LESS THAN THE DESIGN CRITERIA STATED HEREIN.
BUILDING CODES AND STANDARDS
A DSA CERTIFIED PROJECT INSPECTOR EMPLOYED BY THE DISTRICT (OWNER), AND APPROVED
BY THE THE DIVISION OF THE STATE ARCHITECT SHALL PROVIDE CONTINUOUS INSPECTION OF THE WORK. THE DUTIES OF THE INSPECTOR ARE DEFINED IN SECTION 4-333 AND 4-342, PART 1, TITLE 24, CCR. CLASS R.B.I.P. FOR IN-PLANT INSPECTIONS.
SITE SPECIFIC:
COMPLY WITH CFC CHAPTERS 5 & 7, CBC CHAPTERS 3, 5, 7,11B & 14
NOTE: "THIS PC IS NOT APPROVED FOR CHAPTER 7A WILDLAND URBAN AREAS". THIS REVIEW IS PART OF THE SITE SPECIFIC PROJECT. THE APPROVAL OF THE PC DOES NOT INCLUDE THE SITE.
NOTES
OPERATIONS & MAINTENANCE
BUILDING MANUFACTURER SHALL LEAVE FOR THE BUILDING OWNER AT OCCUPANCY OPERATING
INFORMATION FOR ALL APPLICABLE MECHANICAL AND ELECTRICAL FEATURES, MATERIALS,
COMPONENTS AND DEVICES INSTALLED IN THE BUILDING RELATED TO EFFICIENT ENERGY USE. IN
ADDITION, THE BUILDING MANUFACTURER SHALL LEAVE MAINTENANCE INFORMATION FOR ALL
FEATURES, MATERIALS, COMPONENTS, AND MANUFACTURED DEVICES THAT REQUIRE ROUTINE
MAINTENANCE FOR EFFICIENT OPERATION OF MECHANICAL EQUIPMENT AND LIGHTING SYSTEM
CAL GREEN NOTES
FIRE LIFE SAFETY
ALLOWABLE USES: THIS PC (OR BLDG) IS NOT APPROVED FOR 'A' OCCUPANCY
AUTOMATIC FIRE SPRINKLER SYSTEM: NOT REQUIRED / REQUIRED
ENERGY MIN SET BACK FROM SLOPE
APPLICABLE STANDARDS
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24, CCR
2022 CALIFORNIA BUILDING CODE (CBC) VOLUMES 1 & 2, PART 2, TITLE 24, CCR
2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24, CCR
2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24, CCR
2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24, CCR)
2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24, CCR
2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24, CCR
2022 CALIFORNIA EXISTING BUILDING STANDARDS CODE (CEBC), PART 10, TITLE 24
2022 CALIFORNIA GREEN BUILDING STANDARD CODE (CALGREEN), PART 11, TITLE 24 CCR
2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24, CCR
TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHALL REGULATIONS
FOR A LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDMENTS TO THE NFPA
STANDARDS, REFER TO 2022 CBC CHAPTER 35 AND CFC CHAPTER 80.
SCOPE OF WORK
1. THE MANUFACTURER (OR PORTABLE/MODULAR PROVIDER) SHALL PROVIDE ALL LABOR AND
MATERIALS PER PLAN UNLESS STATED OTHERWISE IN WRITTEN EXECUTED CONTRACT
BETWEEN THE DISTRICT (OR OWNER). REFER TO THE GENERAL SPECIFICATIONS ON SHEET A0.1
2. CHANGES TO PLAN OR SCOPE OF WORK - NO ADDITIONAL WORK OR RE-WORK SHALL BE
COMMENCED BY THE MANUFACTURER UNLESS STATED OTHERWISE IN WRITTEN EXECUTED
CONTRACT BETWEEN THE DISTRICT (OR OWNER). HERE-SAY, TEXT MESSAGES, EMAILS
AND SOCIAL MEDIA ARE NOT CONSIDERED WORK AUTHORIZATION. REFER TO THE GENERAL
SPECIFICATION SHEET ON SHEET A0.1 FOR ADDITIONAL INFORMATION
3. THE DESIGN AND SCOPE OF WORK OF THE INCOMING SITE INSTRASTRUCTURE TO THE
PORTABLE/MODULAR BUILDING SUCH AS POWER, WASTE, WATER, COMMUNICATION, AND
FIRE ALARM ARE BY DISTRICT (OWNER). REFER TO THE GENERAL SPECIFICATION SHEET ON
SHEET A0.1 FOR ADDITIONAL INFORMATION REGARDING WORK NOT INCLUDED
4. UPGRADED CLASSROOM FINISHES INCLUDING BUT NOT LIMITED TO EXTERIOR PANELS,
INTERIOR TACKBOARD, CARPET, WINDOWS, AND DOOR.
THE CONCRETE BELOW GRADE FOUNDATION (AMM) OPTION IN THIS PC USES A
DSA-APPROVED ALTERNATE MEANS OF COMPLIANCE FOR FOUNDATION DURABILITY
REQUIREMENTS OF CBC SECTIONS 1402.2 AND 1403.2 FOR PROVIDING A
WEATHER-RESISTANT EXTERIOR WALL ENVELOPE AND CONTINUOUS WATER-RESISTANT
BARRIER ON WALLS DOWN TO THE FOUNDATION, AND CBC SECTION 2304.12.1.2 FOR
PROTECTION AGAINST DECAY AND TERMITES.
CONCRETE FOUNDATION
THIS BLDG WILL NOT BE PLACED IN ANY OF THE FOLLOWING LOCATIONS:
1. WITHIN THE 65 CNEL NOISE CONTOUR OF AN AIRPORT
2. WITHIN THE 65 CNEL OR LDN NOISE CONTOUR OF A FREEWAY,
EXPRESSWAY, RAILROAD OR INDUSTRIAL SOURCE GUIDE WAY
3. WHERE EXPOSED TO NOISE LEVEL OF 65 DB LEQ-1-HR DURING
ANY HOUR OF OPERATIONS
STATE AGENCY APPROVAL
REVISIONS
PROFESSIONAL OF RECORD ON PC
PROJECT SPECIFIC PROFESSIONAL OF RECORD
PROJECT NO.:
DRAFTER:
SCALE:
DATE:
SHEET NUMBER
00-0000
AS NOTED
SHEET TITLE:
DISTRICT/CUSTOMER NAME:
NEXTMOD
00-00-00
ALL DESIGNS INDICATED ON THESE PLANS/DRAWINGS ARE PROPERTY OF NEXTMOD,
INC AND ARE FOR THE USE BY NEXTMOD IN THE SPECIFIED JOB ONLY. THEY SHALL
NOT BE USED AND/OR DUPLICATED OR TRANSMITTED IN ANY FORM, FOR ANY
PURPOSE WITHOUT THE PRIOR WRITTEN CONSENT OF NEXTMOD, INC. ANY
UNAUTHORIZED USE OF THESE PLANS SHALL SUBJECT THE OWNER OF SAID
PROPERTY TO LIQUIDATED DAMAGES OF $75,000.00. THESE PLANS ARE PROTECTED
UNDER THE PROVISIONS OF THE 1976 COPYRIGHT ACT
COPYRIGHT NEXTMOD, © ALL RIGHTS RESERVED.
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
SCHOOL/SITE NAME:
STOCKPILE
PRE-CHECK (PC) DOCUMENT
CODE: 2022 CBC
A SEPARATE PROJECT APPLICATION FOR
CONSTRUCTION IS REQUIRED
FIRM:
ADDRESS:
CITY:
PHONE:
FIRM: ORION STRUCTURAL ENGINEERING, INC.
ADDRESS: 11305 RANCHO BERNARDO ROAD, SUITE 121
CITY: SAN DIEGO, CA 92127
PHONE: (858) 679-1974
NEXTMOD
TITLE SHEETA0.0
A1.3
A2.0a
FLOOR PLAN 48'x40'
REFLECTED CEILING DETAILS
WALL FRAMING ELEVATIONS
S3.0 WALL FRAMING DETAILS - WOOD STUD
S3.2
A2.3 REFLECTED CEILING PLAN 48'x40'
ROOF DETAILS-TPO
A4.3 INTERIOR ELEVATIONS 48'x40'
A3.5 A3.6
ELECTRICAL DETAILSE0.0
ELECTRICAL PLAN 48'x40' (WALL MOUNTED HVAC)E3.0
MECHANICAL
MECHANICAL SCHEDULES AND NOTESM0.0
M1.3 MECHANICAL PLAN WALL MOUNT 48'x40'
SPECIFICATIONS AND NOTESA0.1
CONSTRUCTION MATERIALS AND SPECIFICATIONSA0.2
FINISH SCHEDULEA0.3
SIGNAGE SPECIFICATIONS AND DETAILSA0.4
A5.3 EXTERIOR ELEVATIONS 48'x40'-WOOD SIDING
ROOF PLAN MONO & DUAL SLOPE-TPO
FLOOR FRAMING PLAN - PLYWOOD
S2.0 S2.1 S2.2
FLOOR FRAMING DETAILS - PLYWOOD & CONCRETE
A8.0 ARCHITECTURAL DETAILS WOOD STUD OPTION
A8.1
ROOF FRAMING PLAN - PLYWOOD SHEATHING DIAPHRAGM
S1.0 S1.1
ROOF FRAMING DETAILS
ROOF TRUSS AND DETAILS
S0.0a STRUCTURAL NOTES AND SPECIFICATIONS
S0.1 STRUCTURAL BUILDING SECTIONS - PLYWOOD FLOOR
S0.3 TYPICAL STRUCTURAL DETAILS
ALLOWABLE BEAM AND HEADER PENETRATIONS4.0
A8.2 SHEET METAL AND FLASHING DETAILS
ELECTRICAL
M3.0
ARCHITECTURAL DETAILS
S0.0b STRUCTURAL NOTES AND SPECIFICATIONS
SKYLIT & SIDELIT DAYLIT ZONE FLOOR PLANS 60'-120'x40'E4.1DL
M3.1
CAL GREEN REQUIREMENTSA0.6
MECHANICAL DETAILSM0.1
A2.0b REFLECTED CEILING DSA NOTES
CAL GREEN MANDATORY MEASURESA0.9
A13.0 ARCHITECTURAL BUILDING SECTIONS - MONO SLOPE
CONSTRUCTION WASTE MANAGEMENT FORMSA0.10
PC TITLE 24 REPORT WORST CASE SCENARIO (PERFORMANCE RUN)
PC TITLE 24 REPORT WORST CASE SCENARIO (PERFORMANCE RUN)
E7.0
E7.1
PC TITLE 24 REPORT WORST CASE SCENARIO CEC FORMS
PC TITLE 24 REPORT WORST CASE SCENARIO CEC FORMS
A4.3N INTERIOR ELEVATIONS
A5.3N EXTERIOR ELEVATIONS
A1.3N FLOOR PLAN
A2.3N REFLECTED CEILING PLAN
FINISH SCHEDULEA0.3N
TITLE SHEETA0.0N
ELECTRICAL PLANE3.0N
M1.3N MECHANICAL PLAN
M3.0N
M3.1N
TITLE 24 REPORT
TITLE 24 REPORT
NOTE: "N" DESIGNATE PROJECT SPECIFIC SHEET
A8.0N ARCHITECTURAL DETAILS WOOD STUD OPTION
(NOT PART OF THIS STOCKPILE)
FOUNDATION (NOT PART OF THIS STOCKPILE)
RELOCATING THIS STOCKPILE TO A SPECIFIC SITE WILL
REQUIRE FOUNDATION PLANS AND DETAILS TO BE
REVIEWED AND APPROVED UNDER A SEPARATE DSA
APPLICATION. FOUNDATION SHALL BE PER CURRENT
CODE EDITION EITHER PC OR SITE SPECIFIC. PCs
#04-122454 OR #04-122167 MAYBE UTILIZED
2022 CBC
MANUFACTURED RELOCATABLE & MODULAR CLASSROOM BUILDINGS
RISK CATEGORY II
(1) 60'X40' STOCKPILE BUILDING BASED OF PC 04-122454
SERIAL NUMBERS: 25-182-A/B/C/D/E/F
1. THIS BLDG IS APPROVED FOR THE 2022 CALIFORNIA ENERGY CODE IN ALL CALIFORNIA
CLIMATE ZONE #08 USING EXTERIOR WOOD STUD FRAMING FOR WALL MOUNT SINGLE
ZONE PACKAGED UNIT
2. THIS BLDG IS NOT APPROVED FOR THE 2022 CALIFORNIA ENERGY CODE IN CLIMATE
1-16 USING METAL STUD FRAMING
3. ACCEPTANCE TEST SHALL BE COMPLETED ON NEWLY INSTALLED OR REPLACEMENT OF
LIGHTING CONTROLS, MECHANICAL SYSTEMS, FENESTRATION, AND PROCESS
EQUIPMENT BEFORE PROJECT COMPLETION PER THE CALIFORNIA ENERGY CODE
SECTION 10-103. ACCEPTANCE TEST MUST BE PERFORMED BY A CERTIFIED
ACCEPTANCE TEST TECHNICIAN (ATT). THE ACCEPTANCE TESTING PROCEDURES MUST
BE REPEATED, AND DEFICIENCIES CORRECTED UNTIL THE INSTALLATION OF THE
SPECIFIED SYSTEMS CONFORMS AND PASS THE REQUIRED ACCEPTANCE CRITERIA.
COMPLETED NRCA FORMS SHALL BE SUBMITTED TO THE PROJECT INSPECTOR AND
DISTRICT
DESIGN BASED ON SITE CLASS D DEFAULT
NO GEOTECHNICAL INVESTIGATION REQUIRED
Ss = ___________ Fa = 1.2
SE
LE
C T
O N
E
DESIGN BASED ON SITE CLASS DETERMINED PER CHAPTER 20 OF ASCE 7-16
NO GEOTECHNICAL INVESTIGATION REQUIRED
SITE CLASS: C D E
Ss = ___________ Fa = ___________ PER ASCE 7-16 SUPPL 3 TABLE 11.4-1
DESIGN BASED ON SITE CLASS GROUND MOTION HAZARD ANALYSIS PER
CHAPTER 21 OF ASCE 7-16
SHORT-PERIOD DESIGN SPECTRAL RESPONSE PARAMETER, SDS, SHALL BE
AS SPECIFIED IN GEOTECHNICAL INVESTIGATION
CGS APPROVAL REQUIRED
NOT ELIGIBLE FOR OTC REVIEW
SITE CLASS: C D E
Ss = ___________ Fa = ___________
SDS = 2/3 Fa Ss= __________ < 1.904
Cs = 0.381 USED IN DESIGN
SEISMIC DESIGN CATEGORY: D E
ASCE 7-16 12.8.1.3 HAS NOT BEEN USED IN CALCULATION OF Sds
SEISMIC DESIGN FOR SITE SPECIFIC PROJECTS
(NOT PART OF THIS STOCKPILE)
SAMPLE DSA 103 FORM WOOD FOUNDATION OR BUILDING STOCKPILE PROJECTA0.8a
(WHEN APPLICABLE) AUTOMATIC FIRE SPRINKLER SYSTEMS ARE PERMITTED TO BE
HYDRAULICALLY CALCULATED, PER NFPA 13, TO MEET THE WATER SUPPLY AVAILABLE AT
EACH SITE. PLANS FOR SUCH SYSTEMS MAY BE SUBMITTED AS A PLAN REVIEW SUBMITTAL,
AND MAY NOT BE REVIEWED UTILIZING THE "OVER THE COUNTER" PROCESS. A COMPLETE
AUTOMATIC FIRE SPRINKLER SYSTEM SUBMITTAL PACKAGE MUST BE PROVIDED AT THE TIME
OF THE PLAN REVIEW SUBMITTAL.
THE ARCHITECT OF RECORD (DESIGNER) OR THE DIVISION OF THE STATE ARCHITECT WILL
DETERMINE THE USE OF A FIRE SUPPRESSION SYSTEM UNLESS REQUIRED OTHERWISE BY
THE TYPE OF CONSTRUCTION LISTED ON THE BUILDING DATA.
ALL GROUP 'E' OCCUPANCY BUILDING GREATER THAN 12,000 SF SHALL BE FIRE SPRINKLED
PER CBC SECTION 903.2.3(1)
EXTERIOR PROJECTIONS ARE TO BE FIRE PROTECTED UNLESS PROJECTIONS COMPLY WITH
CBC SECTION 705.2
MIN SETBACK FROM ASSUMED LOT LINE = 10'-0". LESS THAN 10'-0" SEE CBC TABLE
705.5
EXTERIOR WALL OPENINGS TO COMPLY WITH CBC TABLE 705.8
IN ROOMS OR AREAS WITH SPECIAL HAZARDS SUCH AS LABORATORIES, VOCATIONAL SHOPS
AND OTHER SUCH AREAS WHERE HAZARDOUS MATERIALS IN EXEMPT AMOUNTS ARE USED
OR STORED SHALL BE FIRE SPRINKLED PER CBC SECTION 903.2.3(4)
PERMANENT PORTABLE BUILDINGS: A PORTABLE BUILDING THAT IS USED TO SERVE OR
HOUSE STUDENTS AND IS CERTIFIED, AS A PERMANENT PORTABLE BUILDING ON A NEW
PUBLIC SCHOOL CAMPUS BY THE PUBLIC SCHOOL ADMINISTRATION SHALL COMPLY WITH
THE REQUIREMENTS OF CBC SECTION 903.2.3
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
NEXTMOD
EXPANDABLE FLOOR PLANS 60'x40'-120'x40'A0.5
A20.0 DETERIORATION PROTECTION FOR BELOW GRADE CONDITION (WOOD SIDING)
CAL GREEN MANDATORY MEASURESA0.9a CAL GREEN MANDATORY MEASURESA0.9b CAL GREEN MANDATORY MEASURESA0.9c
E7.0N
E7.1N
TITLE 24 REPORT CEC FORMS
TITLE 24 REPORT CEC FORMS
SKYLIT & SIDELIT DAYLIT ZONE FLOOR PLANS 60'-120'x40'E4.1DLN
PLUMBING
PLUMBING SCHEDULE AND DETAILSP0.0
PLUMBING PLAN P1.0
CCD-001_01-08-26
04-124946_CCD-001
1/
/2
9:
:0
AM
ORION STRUCTURAL ENGINEERING, INC.
11305 RANCHO BERNARDO ROAD, SUITE 121
SAN DIEGO, CA 92127
(858) 679-1974
EXP 12/31/26
DATE
SIGNED:
03/05/26
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
04-124946 0
✔ FLS ACS✔ ✔
04/16/2026
1. ELECTRICAL PANEL (SEE #10/A8.1 AND ELECTRICAL SHEETS)
2. HEAT PUMP UNIT (SEE MECHANICAL SHEETS)
3. OFOI WALL MOUNTED PROJECTION SCREEN. WEIGHT MAX 30 LBS. SECURE WITH MIN
#8 X 2" WS AT EACH HOLE. SEE DETAIL #5/A4.3N. INSTALLED OVER MARKER BOARDS.
REFER TO A4.3N FOR BLOCKING HEIGHT.
4. FIRE EXTINGUISHER-5 LB DRY CHEMICAL W/ 2-A:10-B:C UL RATING IN SIDE FULLY
RECESSED CABINET, +48" AFF TO TOP OF HANDLE, 4" MAX PROJECTION. MODEL #
526-EL BY ELITE ARCHITECTURAL SERIES. SEE #4A/A4.1 FOR BLOCK-OUT
5. PRIMARY ENTRANCES SHALL REQUIRE A MIN 48" OVERHANG PER CALGREEN
SECTION 5.407.2.2.1
6. CASE WORK (REFER TO INTERIOR ELEVATIONS A4.3N)
7. ACCESSIBLE SINK COUNTER. REFER TO INTERIOR ELEVATIONS A4.3N. (SEE SHEET
A12.0)
8. ACCESSIBLE DROP-IN SINK AND DECK MOUNTED EYEWASH. (REFER TO PLUMBING
SHEETS)
9. OFOI STUDENT DESK. NEXTMOD TO PROVIDE DEDICATED ELECTRICAL OUTLET.
NEXTMOD TO PROVIDE 3/4" SCHEDULE 40 BLACK PIPE STUB OUT WITH SHUT OFF
VALVE AND 1-1/2" MAIN LINE FOR COMPRESSED AIR. (REFER TO ELECTRICAL SHEET
E3.0N AND PLUMBING SHEET P3.0N)
10. OFOI VENDING MACHINE. NEXTMOD TO PROVIDE DEDICATED ELECTRICAL OUTLET
AND DATA. REFER TO ELECTRICAL SHEET E3.0N
11. OFOI TEACHERS DESK. NEXTMOD TO PROVIDE DEDICATED ELECTRICAL OUTLET AND
DATA. NEXTMOD TO PROVIDE 3/4" SCHEDULE 40 BLACK PIPE STUB OUT WITH SHUT
OFF VALVE AND 1-1/2" MAIN LINE FOR COMPRESSED AIR.
12. ECOSMART 6-GALLON ELECTIC MINI- TANK WATER HEATER (REFER TO ELECTRICAL
SHEET E3.0N AND PLUMBING SHEET P1.0)
13. 4'X8' MARKER BOARDS +30" AFF
14. MIN 3'-0" WORK SURFACE. REFER TO INTERIOR ELEVATIONS
KEY NOTES
100 A
A4.3N A
A A5.3N
B A5.3N
D A5.3N
C A5.3N
A
1. SIGNAGE REQUIRED PER APPLICABLE CODES LISTED ON COVER SHEET
PROVIDED AND INSTALLED BY DISTRICT ON SITE, SEE ACCESS SHEET
2. WHEN USING A RAMP OPTION AS SHOWN NEXT TO AN ADJACENT WINDOW, IT MUST
COMPLY WITH THE ILLUSTRATION ON 20/A8.0. THE FOLLOWING TWO OPTIONS CAN BE
CONSIDERED:
OPTION #1: USE A RAMP CONFIGURATION THAT IS AWAY FROM THE
BUILDING
OPTION #2: THE WINDOW SILL HEIGHT NEEDS TO BE ELEVATED OR LOCATED IN A
MANNER TO ACCOMMODATE THE CODE COMPLIANCE ILLUSTRATION
MENTIONED ON 20/A8.0. EXAMPLE USE AN 8X3 WINDOW AND SMALLER IN LIEU OF
8X4 WINDOW OR REMOVE THE WINDOW TRIM/MOULDING
3. WHEN RAMPS AND LANDINGS ARE USED, DOWNSPOUT DRAINAGE MUST DIVERT
AWAY FROM CLEAR LANDING SPACE OR RAMP
4. ASSISTIVE LISTENING SYSTEM REQUIRED. SUPPLIED AND INSTALLED BY DISTRICT.
NOT PART OF THIS PC. A1.3N
FLOOR PLAN
REAR
RIGHT
LEFT
FLOOR PLAN
SCALE: 1/4" = 1'-0"
GENERAL NOTES
A. = ID SIGN - #1G/A0.4
B. = EXIT TACTILE SIGN - #1C/A0.4
C. = ID SIGN WITH ISA IDENTIFICATION - #1H,G/A0.4
D. = EXIT RAMP DOWN SIGN - #1E/A0.4
E. = NOT USED
F. = NOT USED
G. = OCCUPANT LOAD SIGN - #3/A0.4
H. = ASSITIVE LISTENING SYSTEM SIGNAGE - #4/A0.4
SIGNAGE LEGEND
A
WALL NOTE:
SEE SHEET A0.0 FOR WALL LEGEND
BUILDING SQUARE FOOTAGE: 2,400 SQ FT
OCCUPANT NET PER TABLE 1004.1.1: 20
MAXIMUM OCCUPANTS: 120
OCCUPANT LOAD FORMULA
S/N 25-182-A
S/N 25-182-B
B A13.0
A A13.0
STATE AGENCY APPROVAL
REVISIONS
PROFESSIONAL OF RECORD ON PC
PROJECT SPECIFIC PROFESSIONAL OF RECORD
PROJECT NO.:
DRAFTER:
SCALE:
DATE:
SHEET NUMBER
00-0000
AS NOTED
SHEET TITLE:
DISTRICT/CUSTOMER NAME:
NEXTMOD
00-00-00
ALL DESIGNS INDICATED ON THESE PLANS/DRAWINGS ARE PROPERTY OF NEXTMOD,
INC AND ARE FOR THE USE BY NEXTMOD IN THE SPECIFIED JOB ONLY. THEY SHALL
NOT BE USED AND/OR DUPLICATED OR TRANSMITTED IN ANY FORM, FOR ANY
PURPOSE WITHOUT THE PRIOR WRITTEN CONSENT OF NEXTMOD, INC. ANY
UNAUTHORIZED USE OF THESE PLANS SHALL SUBJECT THE OWNER OF SAID
PROPERTY TO LIQUIDATED DAMAGES OF $75,000.00. THESE PLANS ARE PROTECTED
UNDER THE PROVISIONS OF THE 1976 COPYRIGHT ACT
COPYRIGHT NEXTMOD, © ALL RIGHTS RESERVED.
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
SCHOOL/SITE NAME:
STOCKPILE
PRE-CHECK (PC) DOCUMENT
CODE: 2022 CBC
A SEPARATE PROJECT APPLICATION FOR
CONSTRUCTION IS REQUIRED
FIRM:
ADDRESS:
CITY:
PHONE:
FIRM: ORION STRUCTURAL ENGINEERING, INC.
ADDRESS: 11305 RANCHO BERNARDO ROAD, SUITE 121
CITY: SAN DIEGO, CA 92127
PHONE: (858) 679-1974
NEXTMOD
CLASSROOM
1 2 6
B
A C
B
4'-0"
4' -0
H
6'-0"
'-0
12'-0" 12'-0"
60'-0"
6'-0" 2'-10"
3 4 5
6'-0"
12'-0"12'-0" 12'-0"
C
B
4'-0"
4' -0
H
2'-10" 6'-0" 6'-0"
G
VENDING VENDING
1'-0" 10'-0"
2' -0
2'-0" 3'-0" 2'-0"
WH
36" MIN
CLR
1'-0"
S/N 25-182-C
S/N 25-182-D
S/N 25-182-E
A
100A A
FRONT
FLUSH TRANSITION
(TYP)
(TYP OF 2)
(TYP OF 4)
CCD-001_01-08-26
04-124946_CCD-001
7,8,9 A8.1
ORION STRUCTURAL ENGINEERING, INC.
11305 RANCHO BERNARDO ROAD, SUITE 121
SAN DIEGO, CA 92127
(858) 679-1974
EXP 12/31/26
DATE
SIGNED:
03/05/26
MIN 36" WIDE ACCESSIBLE WORK SURFACE. REFER TO INTERIOR ELEVATIONS
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
04-124946 0
1. TYPICAL INTERIOR FINISH
2. FULL SHEET CLOSURE AT MODULAR JOINT STANDARD.
3. TACTILE EXIT SIGNAGE (SEE SIGNAGE SHEET)
4. FIRE ALARM PULL STATION (SEE ELECTRICAL PLAN)
5. OCCUPANCY SENSOR OR LIGHT SWITCH (SEE ELECTRICAL PLAN)
6. TOP SET BASE TYPICAL (SEE FINISH SCHEDULE)
7. RETURN AIR GRILL
8. ELECTRICAL PANEL +48" TO HANDLE
9. SPEAKER/STROBE (SEE ELECTRICAL PLAN)
10. THERMOSTAT (SEE MECHANICAL PLAN)
11. MODULAR JOINT
12. 4'-0" x 8'-0" MARKER BOARD, ERASER RAIL PROJECT 4" MAX
13. FIRE EXTINGUISHER IN FULLY-RECESSED CABINET #4A
14. 12" DIA ELECTRIC CLOCK (SEE ELECTRICAL PLAN)
15. WALL SYSTEM (SEE WALL FRAMING ELEVATION SHEET)
16. INTERIOR FINISH SEAM
17. CO2 DETECTOR
18. STAINLESS STEEL DROP-IN SINK (SEE PLUMBING SHEETS)
19. BASE CABINETS
20. EYEWASH (SEE PLUMBING SHEETS)
21. WATER HEATER IN BASE CABINET (SEE PLUMBING SHEETS) WALL RECEPT PROVIDE IN
CABINET (REFER TO ELECTRICAL PLANS)
22. 3'-0" WORK SURFACE
ELEVATION 1
ELEVATION 2
ELEVATION 3
ELEVATION 4
9 13
A4.3N
INTERIOR ELEVATIONS
KEY NOTES
TYP
TYP
TYP
TYP
TYP
TYP
A
INTERIOR ELEVATIONS
SCALE: 1/4" = 1'-0"
A0.3
STATE AGENCY APPROVAL
REVISIONS
PROFESSIONAL OF RECORD ON PC
PROJECT SPECIFIC PROFESSIONAL OF RECORD
PROJECT NO.:
DRAFTER:
SCALE:
DATE:
SHEET NUMBER
00-0000
AS NOTED
SHEET TITLE:
DISTRICT/CUSTOMER NAME:
NEXTMOD
00-00-00
ALL DESIGNS INDICATED ON THESE PLANS/DRAWINGS ARE PROPERTY OF NEXTMOD,
INC AND ARE FOR THE USE BY NEXTMOD IN THE SPECIFIED JOB ONLY. THEY SHALL
NOT BE USED AND/OR DUPLICATED OR TRANSMITTED IN ANY FORM, FOR ANY
PURPOSE WITHOUT THE PRIOR WRITTEN CONSENT OF NEXTMOD, INC. ANY
UNAUTHORIZED USE OF THESE PLANS SHALL SUBJECT THE OWNER OF SAID
PROPERTY TO LIQUIDATED DAMAGES OF $75,000.00. THESE PLANS ARE PROTECTED
UNDER THE PROVISIONS OF THE 1976 COPYRIGHT ACT
COPYRIGHT NEXTMOD, © ALL RIGHTS RESERVED.
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
SCHOOL/SITE NAME:
STOCKPILE
PRE-CHECK (PC) DOCUMENT
CODE: 2022 CBC
A SEPARATE PROJECT APPLICATION FOR
CONSTRUCTION IS REQUIRED
FIRM:
ADDRESS:
CITY:
PHONE:
FIRM: ORION STRUCTURAL ENGINEERING, INC.
ADDRESS: 11305 RANCHO BERNARDO ROAD, SUITE 121
CITY: SAN DIEGO, CA 92127
PHONE: (858) 679-1974
NEXTMOD
7 8
4'-0"
TYP
4'-0"
TYP
4'-0"
TYP
CENTER
OF WALL
TYP
CENTER
OF WALL
4'-0"
TYP
TYP TYP TYP
TYP TYP
TYP
TYP TYP TYP
TYP
4'-0"
TYP
4'-0"
TYP
CENTER
OF WALL
4'-0"
TYP
4'-0"
TYP
CENTER
OF WALL
7'-0"
2' -9
/4
4"
3'-0"2'-0" 2'-0"
OPEN
7"2' -6
BLOCKING
HEIGHT SEE
DETAIL1,7/A8.1 15
2SINK ACCESSIBILITY DIAGRAM AND CHART
SCALE: N.T.S.
"B"
"C"
(KNEE
CLEARANCE)
9" M
IN
6"
MAX
DIM. "A"
"D"
(TOE CLEARANCE)
"A"
(OBSTRUCTED
HIGH FORWARD
REACH DEPTH)
NOTE:
1. SEE SINK DIAGRAM DIAGRAM AND CHART FOR CLEARANCE DIMENSIONS.
2. THE CLASS ROOM SINK ON DETAIL 15, & 20 SHOW A CENTER REAR DRAIN. DETAIL
MAY CHANGE DEPENDING ON THE SINK, DRAIN LOCATION, AND FAUCET TYPE.
24" 25"
DIM. "B"
15" 16"
DIM. "C"
18" 19"
DIM. "D"
24" 25"
CENTER LINE
OF CONTROLS
15ACCESSIBLE SINK COUNTER AGES 13 & UP
SCALE: 3/4" = 1'-0"
NOTES:
1. MODIFY BASE AS SHOWN FOR WHEELCHAIR ACCESS
2. 30" CLR. NO CABINET DOORS PERMITTED
3. SEE ARCH DETAIL SHEET FOR BLOCKING INFO
4. PIPES UNDER SINK MUST BE INSULATED PER PLUMBING NOTE #2 ON SHEET P0.0
5. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES BELOW COUNTER.
6. THIS SINK DIAGRAM IS FOR A CLASS ROOM SINK WITH CENTER REAR DRAIN.
DETAIL MAY CHANGE DEPENDING ON THE SINK DRAIN LOCATION AND FAUCET.
OPT
GARBAGE
DISPOSAL
" M
AX
AT
S
IN
K R
IM
W
H
ER
E
AP
PL
IE
S
" M
IN
KN
EE
C
LE
AR
AN
C
E "B"
"C"
9" M
IN
19"-24" MAX AT
SINK COUNTER
AREA NOT HATCHED TO
BE ACCESSIBLE AND CLR
BUBBLER
6"
MAX
5"
MAX
" M
AX
℄ OF
CONTROLS
12" APPROX "A"
NOTE:
SEE DETAIL #2 FOR KNEE
AND TOE CLEARANCE
30" MIN CLR
FLOORING
SHALL BE
UNDER SINK
COUNTER
SINK OPENING
(WHERE OCCURS)
WH
3'-0"
OPEN
ATTACHMENT HEIGHT FOR
OFOI PROJECTION SCREEN.
SEE DETAIL14/A8.1
6' -8
BLOCKING AT PRJECTOR
SCALE: 1 1/2" = 1'-0"
WALL FRAMING
PER PLAN
OFOI PROJECTOR. USE MIN
#8 X 2" WS AT EACH HOLE
WALL FINISH
PER SCHEDULE
NOTES:
1. MODIFY BASE AS SHOWN FOR WHEELCHAIR ACCESS
2. 36" CLR. NO CABINET DOORS PERMITTED
3. SEE ARCH DETAIL SHEET FOR BLOCKING INFO
4. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES BELOW COUNTER.
5. THIS DIAGRAM IS FOR A CLASS ROOM WORK SURFACE.
" M
AX
TO
C O
U N
TE
R
" M
IN
KN
EE
C
LE
AR
AN
C
E
19"-24" MAX AT
SINK COUNTER
AREA TO BE
ACCESSIBLE AND CLR
36" MIN CLR
FLOORING
SHALL BE
UNDER SINK
COUNTER
2'-0"
19" MIN
16ACCESSIBLE WORK SURFACE COUNTER AGES 13 & UP
SCALE: 3/4" = 1'-0"
SECTION AT MARKER BOARD
SCALE: 3" = 1'-0" 1
AT WOOD STUD:
#10 MIN FLAT HEAD
WOOD SCREW PER
WALL STUD
SPACING TYP T&B
4" MAX1 1/2" MIN
EMBEDMENT
4AFULLY-RECESSED FIRE EXTINGUISHER CABINET
SCALE: 1-1/2" = 1'-0"
NOTE: EQUIPMENT
CAVITY DETAIL IS
SIM AT INTERIOR
CONDITION
WOOD STUDS
INTERIOR FINISH
PER SCHEDULE
NOTE:
FOR 1 HR RATED
CONDITION SEE 9/A9.0EXTERIOR FINISH
PER SCHEDULE
FULLY-RECESSED
FIRE EXTINGUISHER
CABINET
MIN #10 X 1-1/2"
WS AT EACH HOLE
LOCATION ON MANUF
EQUIPMENT
BLOCKING
WOOD STUDS
FRAMING
4" MAX
TYP
5" R.O.
-1
/4 "H
X
-1 /4
"W R.
O
" M
AX
2' -7
" M
AX
ROUGH OPENING:
ELITE ARCHITECTURAL SERIES #526-EL
8 1/4" (w) x 17 1/4" (h), 49 5/8" TOP OF OPENING
CCD-001_01-08-26
04-124946_CCD-001
ORION STRUCTURAL ENGINEERING, INC.
11305 RANCHO BERNARDO ROAD, SUITE 121
SAN DIEGO, CA 92127
(858) 679-1974
EXP 12/31/26
DATE
SIGNED:
03/05/26
NOTES:
1. MODIFY BASE AS SHOWN FOR WHEELCHAIR ACCESS
2. 30" CLR. NO CABINET DOORS PERMITTED
3. SEE ARCH DETAIL SHEET FOR BLOCKING INFO
4. PIPES UNDER SINK MUST BE INSULATED PER PLUMBING NOTE #2 ON SHEET P0.0
5. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES BELOW COUNTER.
6. THIS SINK DIAGRAM IS FOR A CLASS ROOM SINK WITH CENTER REAR DRAIN.
DETAIL MAY CHANGE DEPENDING ON THE SINK DRAIN LOCATION AND FAUCET.
OPT
GARBAGE
DISPOSAL
M
A X
A T
S
I N
K
R
I M
W H
E R
E
A
P P
L I E
S
M
I N
K N
E
C
L E
A R
A N
C E
"B"
"C"
M I N
19"-24" MAX AT
SINK COUNTER
AREA HATCHED TO BE
ACCESSIBLE AND CLR
BUBBLER
6"
MAX
5"
MAX
M
A X
℄ OF
CONTROLS
12" APPROX
"A"
NOTE:
SEE DETAIL #2 FOR KNEE
AND TOE CLEARANCE
M
N
R
FLOORING
SHALL BE
UNDER SINK
COUNTER
SINK OPENING
(WHERE OCCURS)
"B"
"C"
(KNEE
CLEARANCE)
M I N
6"
MAX
"D"
(TOE CLEARANCE)
"A"
(OBSTRUCTED
HIGH FORWARD
REACH DEPTH)
CENTER LINE
OF CONTROLS
NOTES:
1. MODIFY BASE AS SHOWN FOR WHEELCHAIR ACCESS
2. 36" CLR. NO CABINET DOORS PERMITTED
3. SEE ARCH DETAIL SHEET FOR BLOCKING INFO
4. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES BELOW COUNTER.
5. THIS DIAGRAM IS FOR A CLASS ROOM WORK SURFACE.
M
A X
T O
O U
N T
E R
M
I N
K N
E
A R
A N
C E
19"-24" MAX AT
SINK COUNTER
AREA HATCHED TO BE
ACCESSIBLE AND CLR
N
R
FLOORING
SHALL BE
UNDER SINK
COUNTER
2'-0"
19" MIN
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
04-124946 0
A8.1
ARCHITECTURAL
DETAILS
STL FLANGE FOR TUBING AT
TOP & BTM ARE MOUNTED TO
2x6 BLKG OR STUDS W/ MIN (2)
#10 WS W/ 1 1/2" MIN
EMBEDMENT INTO BLKG OR
STUD TYP FOR EA FLANGE
1 1/2"Ø BENT STL
TUBING GUARDRAIL
BY DISTRICT
4B
BARRIER BLOCKING
CASEWORK AND TV BLOCKING-WOOD
ALTERNATE AT STEEL STUD:
STL FLANGE FOR TUBING AT
TOP & BTM ARE MOUNTED TO 16
GAUGE X 7 1/2" WIDE BLKG OR
STUDS W/ MIN (2) #12 STS TYP
FOR EA FLANGE
STL FLANGE FOR TUBING W/
(2) 1/4"Ø X 2 1/4" HILTI KWIK
BOLT TZ EXPANSION
ANCHORS, 1" MIN EMBED,
PER ICC REPORT # ESR-1917
(BY DISTRICT)
BACK
BOTTOM
BASE
STUD
CASEWORK TO WALL BEHIND TOE KICK
FRONT
BOTTOM
TOE KICK
#10 X 1 1/2" FLAT
HEAD WOOD
SCREW
AT 16" OC MAX
1" MELAMINE
OR PLASTIC
2 X 4 PLATE (TREATED AT
CONCRETE FLOORS)
CASEWORK ATTACHMENT AT TOE KICK
4x OR DOUBLE 2x HF #2 BLKG
SEE DETAIL #1
BACKSPLASH TO BASE COUNTERTOP
WHERE OCCURS W/ #8 FHWS
TYPICAL CASEWORK
1x WOOD CLEAT WOOD SHIM AS REQ W/ 6d FN
WALL COVERING
WALL FRAMING
(BASE CASEWORK SHOWN, WALL AND TALL CASEWORK SIMILAR)
ATTACHMENT: #14 FHWS WITH MIN 2"
PENETRATION INTO WOOD BLKG OR STUD.
AT METAL BLKG OR STUD USE #14x3" SDS
BASE CASEWORK/CABINET:
FHWS SPACING AT MAX 32" OC
WALL CASEWORK/CABINET: FHWS
SPACING AT MAX 16" OC TO TOP
AND BOTTOM
(SIMILAR FOR TALL CABINETS)
CASEWORK TO WALL AT COUNTERTOP
BARRIER FLOOR
ATTACHMENT TO CONCRETE
AT WOOD STUD:
#10 X 3" FLAT HEAD
WOOD SCREW PER
WALL STUD SPACING
AT WOOD FLOOR:
#10 X 3" WOOD
SCREW AT 16" OC
MAX
GUARDRAIL TUBING
(BY DISTRICT)
CONCRETE WALK BY
OTHER'S
BACK
BOTTOM
UPPPER CASEWORK TO WALL
AT WOOD STUD:
#14x3" FLAT HEAD WOOD
SCREW PER WALL STUD
SPACING WITH
2" MIN PENETRATION
4x OR DOUBLE 2x HF
#2 BLKG SEE DETAIL
#1
WALL COVERINGWALL FRAMING
ALTERNATE
ATTACHMENT
TO STEEL STUD,
SEE DETAIL #5
6" M
IN
1/8"
TUBE STEEL ATTACHMENT
1/8"
STEEL TUBE
TYP
3/32 .5" @ 24"
TOP
AND
BTM
26 GA MIN
SHEET METAL
ATTIC DRAFTSTOP DETAIL
NOTES:
1. PROVIDE OPENING FOR
CROSS-OVERS AS REQUIRED
FOR MODULE CONNECTION.
CAULK OPENINGS AND JOINTS
AS REQUIRED
2. DRAFTSTOPS REQUIRED IF
BLDG AREA IS GREATER
THAN 3000 SF.
ML
SEE STRUCTURAL
CEILING FINISH
ML
CEILING FINISH
SEE STRUCTURAL
26 GA MIN SHEET
METAL SECURED WITH
#10 STSMS AT 24" OC
ATTIC DRAFTSTOP DETAIL
BLOCKING:
3-1/2" MIN. DEPTH INTERIOR
WALLS.
5 1/2" MIN DEPTH EXTERIOR
WALLS. SHALL BE 4x OR DOUBLE 2x HF #2 BETWEEN
STUDS WITH 'SIMPSON' A34
ANCHORS TOP & BTM AT
EACH END OF BLOCK TO
STUD ATTACH CABINET W/
#14 SCREWS W/ 2" MIN
PENETRATION INTO STUD OR
BLOCKING @ 16" OC
NOTE:
ALTERNATE ATTACHMENT
SHALL BE DIRECTLY TO
WOOD STUDS PER STUD
SPACING
TV BRACKET
BLOCKING
4x12 MIN
TYPICAL CASEWORK
BLOCKING
*V
ER
IF
Y
*HEIGHTS SHALL MEET ADA
REQUIREMENTS
*V
ER
IF
Y
WOOD STUDS
4x POST EA
SIDE OF
BLOCKING
(HATCHED)
- SIM
E
NOTE: TV
BLOCKING MAX
WT: 100#
PIPE SUPPORT AT TPO ROOF
SCALE: 6" = 1'-0"
NOTES:
1. DO NOT INSTALL WOOD SLEEPER OVER
BATTEN STRIPS, FASTENER HEADS, METAL
PLATES OR FIELD SEAMS
4x MIN PRESSURE
TREATED WOOD SLEEPER
SPACED SO THAT
LOAD DOES NOT EXCEED
16 PSI (SEE NOTES) L-1 1/2" X 1 1/2" X 2" X
18 GA MIN GALV ANGLE
SECURED TO ROOF WITH
MIN #10 X 1-1/2" EXT GRADE
WS (WHERE STEEL MEMBER
OCCURS, USE MIN #10 SDS).
INSTALL TO WOOD SLEEPER
WITH MIN #10 X 1-1/2" EXT
GRADE WS. STAGGERED
OPPOSITE SIDE
TPO ROOF
SYSTEM PER
PLAN
2-HOLE PIPE
STRAP
PIPE (MECH OR ELECT)
CAULK SCREWS
AS NEEDED TYP
" M
IN
48" MAX
30" MIN PASS EDGE OF EQUIPMENT
3"
HSS-2" X 2" X 1/8" SQ TUBE TYP
WIRE MESH
MECHANICAL EQUIPMENT SCREEN
NOTE: REFER TO
CBC SECTION 1015.6
TYP
TYP
SIM TYP
- ALT
SECTION AT TUBE STEEL
SCALE: 3"=1'-0"
ROOF JOIST
BLKG
ROOF JOIST
BLKG
ROOF JOIST
6"X6"X1/4 (MIN THICK)
STEEL PLATE1/
2" 1/
2"
1/2"1/2"
3/8" BOLT TYP
(4) LOCATIONS
1/8" 2"
IN LIEU OF
BOLTING
1/8" 2"
IN LIEU OF
BOLTING
NOTE: CAULK
AROUND BOLT AS
NECCESARY
COMP
PEN
ALT POST TO PLATE
SCALE: 3"=1'-0"
6" M
IN
O
VE
R
LA
P
" M
IN
3"
HSS-2" X 2" X 1/8"
HSS-1-3/4" X 1-3/4" X 11 GA3/8" BOLT
COMP
PEN
1" M
AX
1/8"
TYP AT
EA LEG
CAP AT TUBES WITH 1/8" PLATE AND WELD
ALL AROUND TYP
STEEL
HEADER/
BEAM
EXT WALL INSULATION
PER EXT WALL SCH
ON SHEET A0.2
SAME R-VALUE
INSULATION AS EXT
WALL
ROOF
PURLIN
ROOF INSULATION
PER ROOF FRAMING
SCH ON SHEET A0.2
R-1 DENSDECK (1/4")
PLYWOOD ROOF
R-3 RIGID INSULATION
DURATEMP
SIDING
SINGLE-PLY ROOFING
FINISH WALL OVER
GYPSUM BOARD
22THERMAL ENVELOPE (DURTEMP SIDING)
SCALE: 1-1/2" = 1'-0"
WOOD STUD
INTERIOR FINISH
PER SCHEDULE
NOTE:
FOR 1 HR RATED
CONDITION SEE 9/A9.0
NOTE: EQUIPMENT
CAVITY DETAIL IS
SIM AT INTERIOR
CONDITION
EXTERIOR FINISH
PER SCHEDULE
MIN #10 X 1-1/2"
WS AT EACH HOLE
LOCATION ON MANUF
EQUIPMENT
BLOCKING
WOOD STUDS
FRAMING
SEMI-RECESSED
ELECTRICAL PANEL
ROUGH OPENING:
100 AMP, 12 SPACES SQUARE D - 14" 1/2 (w) x 15 3/16" (h), 52 5/8" TOP OF OPENING
100 AMP, 12 SPACES, EATON - 14" 1/2" (w) x 23 1/4" (h), 58 5/8" TOP OF OPENING
DIFFUSER ATTACHMENT
SCALE: NTS
HANGER WIRE
DIFFUSER
CEILING TILE
MAIN RUNNER OR
CROSS TEE
ANCHOR CLIP. PROVIDED BY
MFG. SEE MFG INSTALLATION
INSTRUCTIONS
(TYP 4 CORNERS)
EYE SCREW. PROVIDED
BY MFG
SEMI-RECESSED ELECT PANEL BLOCK-OUT
SCALE: 1-1/2" = 1'-0"
SEMI-RECESSED FIRE EXTINGUISHER CABINET
SCALE: 1-1/2" = 1'-0"
INSULATION AT FLOOR (PLYWOOD)
SCALE: 1 1/2" = 1'-0"
WOOD STUDS
INTERIOR FINISH
PER SCHEDULE
NOTE:
FOR 1 HR RATED
CONDITION SEE 9/A9.0
NOTE: EQUIPMENT
CAVITY DETAIL IS
SIM AT INTERIOR
CONDITION
EXTERIOR FINISH
PER SCHEDULE
SEMI-RECESSED
FIRE EXTINGUISHER
CABINETMIN #10 X 1-1/2"
WS AT EACH HOLE
LOCATION ON MANUF
EQUIPMENT
BLOCKING
" M
AX
WOOD STUDS
FRAMING
4" MAX
TYP
WOOD STUDS
INTERIOR FINISH
PER SCHEDULE
NOTE:
FOR 1 HR RATED
CONDITION SEE 9/A9.0EXTERIOR FINISH
PER SCHEDULE
FULLY-RECESSED
FIRE EXTINGUISHER
CABINET
MIN #10 X 1-1/2"
WS AT EACH HOLE
LOCATION ON MANUF
EQUIPMENT
BLOCKING
WOOD STUDS
FRAMING
4" MAX
TYP
5" R.O.
-1
/4 "H
X
-1 /4
"W R.
O
" M
AX
2' -7
" M
AX
ROUGH OPENING:
ELITE ARCHITECTURAL SERIES #526-EL
8 1/4" (w) x 17 1/4" (h), 49 5/8" TOP OF OPENING
STATE AGENCY APPROVAL
REVISIONS
PROFESSIONAL OF RECORD ON PC
PROJECT SPECIFIC PROFESSIONAL OF RECORD
PROJECT NO.:
DRAFTER:
SCALE:
DATE:
SHEET NUMBER
00-0000
AS NOTED
SHEET TITLE:
DISTRICT/CUSTOMER NAME:
NEXTMOD
00-00-00
ALL DESIGNS INDICATED ON THESE PLANS/DRAWINGS ARE PROPERTY OF NEXTMOD,
INC AND ARE FOR THE USE BY NEXTMOD IN THE SPECIFIED JOB ONLY. THEY SHALL
NOT BE USED AND/OR DUPLICATED OR TRANSMITTED IN ANY FORM, FOR ANY
PURPOSE WITHOUT THE PRIOR WRITTEN CONSENT OF NEXTMOD, INC. ANY
UNAUTHORIZED USE OF THESE PLANS SHALL SUBJECT THE OWNER OF SAID
PROPERTY TO LIQUIDATED DAMAGES OF $75,000.00. THESE PLANS ARE PROTECTED
UNDER THE PROVISIONS OF THE 1976 COPYRIGHT ACT
COPYRIGHT NEXTMOD, © ALL RIGHTS RESERVED.
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
SCHOOL/SITE NAME:
STOCKPILE
PRE-CHECK (PC) DOCUMENT
CODE: 2022 CBC
A SEPARATE PROJECT APPLICATION FOR
CONSTRUCTION IS REQUIRED
FIRM:
ADDRESS:
CITY:
PHONE:
FIRM: ORION STRUCTURAL ENGINEERING, INC.
ADDRESS: 11305 RANCHO BERNARDO ROAD, SUITE 121
CITY: SAN DIEGO, CA 92127
PHONE: (858) 679-1974
NEXTMOD
26" MIN
THERMAL ENVELOPE (STUCCO SIDING)
SCALE: 1-1/2" = 1'-0"
STEEL
HEADER/
BEAM
EXT WALL INSULATION
PER EXT WALL SCH
ON SHEET A0.2
SAME R-VALUE
INSULATION AS EXT
WALL
ROOF
PURLIN
ROOF INSULATION
PER ROOF FRAMING
SCH ON SHEET A0.2
R-1 DENSDECK (1/4")
PLYWOOD ROOF
R-3 RIGID INSULATION
7/8" STUCCO SIDING
OVER 1/2" PLYWOOD
SINGLE-PLY ROOFING
FINISH WALL OVER
GYPSUM BOARD
FLOORING OVER
PLYWOOD
FIBERGLASS INSULATION
BATT PER SHEET A0.2 UNLESS
OTHERWISE SPECIFIC
PROJECT SPECIFIC
ENERGY REPORT
HEAVY MIL
PLASTIC
HEAVY MIL
PLASTIC
FLOORING OVER 1-1/2"
LIGHTWEIGHT CONC FLOOR FILL
OVER METAL B-DECK
FIBERGLASS INSULATION
BATT PER SHEET A0.2 UNLESS
OTHERWISE SPECIFIC
PROJECT SPECIFIC
ENERGY REPORT
INSULATION AT FLOOR (CONC FLOOR)
SCALE: 1 1/2" = 1'-0"
4AFULLY RECESSED FIRE EXTINGUISHER CABINET
SCALE: 1-1/2" = 1'-0"
CCD-001_01-08-26
04-124946_CCD-001
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
ORION STRUCTURAL ENGINEERING, INC.
11305 RANCHO BERNARDO ROAD, SUITE 121
SAN DIEGO, CA 92127
(858) 679-1974
EXP 12/31/26
BLOCKING AT FIXTURE
SCALE: 1 1/2" = 1'-0"
MIN (2) ROWS
2x6 HF #2 BLKG BETWEEN
STUDS WITH A 'SIMPSON'
A34 ANCHOR AT EACH
END. USE MIN #8 X 1-1/2"
WS AT EACH HOLE
WALL FRAMING
PER PLAN
SEE FIXTURE'S MANUFACTURE
INSTALLATION GUIDE FOR
BLOCKING HEIGHT
WALL FINISH
PER SCHEDULE
VENT PIPE IN
WALL
DATE
SIGNED:
03/05/26
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
04-124946 0
DEVICE SHALL HAVE
SPEAKER OPTION.
TYP
120/240
DESCRIPTION
HEAT PUMP
HEAT PUMP
LOAD
SUB TOTAL
LOAD CENTER SCHEDULE
TOTAL
A
B
MAIN BRKR
VOLTS
PO
LEBA
PO
LE
BR
EA
KE
R
W
IR
E
SI
ZE
C
KT
. N O
C
KT
. N O
BR
EA
KE
R
W
IR
E
SI
ZE
AØ BØ
5 6120
7 8
606 2
3 4
1 2
AMPS
TOTAL LOAD
SUB TOTAL
BØ
42121 20
1 20 12
201 12
201 12
201 12 750
AØ
EXTERIOR LIGHTS
F.A.C.P.
DESCRIPTION
LIGHTS
LIGHTS
MOUNT100 A
WATTS
WIRE
PHASE
1 BUSS FEED
LOCATIONRECESSED
WATTS
100 A
INTERIOR
WALL
PANEL B
- 600
LABEL & LOCK ON DEVICE*
EXT RECEPT 180
6,552
8,235
14,787
AMPS73
MAX DEMAND
W/O FUTURE
LOAD
DEMAND
TOTAL DEMAND =
L.C.L: 880 x 25% =
25% LARGEST MOTOR = 3,120
20% FUTURE LOAD =
TOTAL LOAD DEMAND + FUTURE LOAD =
MAX DEMAND =
14,787 X 20% = 2,958 14,787 + 2,958 = 17,745 17,745 / 240
14,787
-201 12 540
120/240
DESCRIPTION
HEAT PUMP
HEAT PUMP
LOAD
SUB TOTAL
LOAD CENTER SCHEDULE
TOTAL
A
B
PROJECETOR
MAIN BRKR
VOLTS
PO
LEBA
PO
LE
BR
EA
KE
R
W
IR
E
SI
ZE
C
KT
. N O
C
KT
. N O
BR
EA
KE
R
W
IR
E
SI
ZE
AØ
BØ
5 6120
7 8
606 2
3 4
1 2
AMPS
TOTAL LOAD
SUB TOTAL
BØ
42121 20
1 20 12
201 12
AØ
EXTERIOR LIGHTS
F.A.C.P.
RECEPT / DATA
DESCRIPTION
MOUNT120 A
WATTS
WIRE
PHASE
1 BUSS FEED
LOCATIONRECESSED
WATTS
120 A
INTERIOR
WALL
PANEL A
LABEL & LOCK ON DEVICE*
EXT RECEPT 180
6,522
5,280
11,802
AMPS60
MAX DEMAND
W/O FUTURE
LOAD
DEMAND
TOTAL DEMAND =
L.C.L: 880 x 25% =
25% LARGEST MOTOR = 3,120
20% FUTURE LOAD =
TOTAL LOAD DEMAND + FUTURE LOAD =
MAX DEMAND =
11,802 X 20% = 2,361 11,802 + 2,361 = 14,163 14,163 / 240
11,802
-201 12 RECEPT / DATA / CLOCK540
DED GFI VENDING MACHINE1800 - 1800 -
AIR PURIFIER 12 120180- AIR PURIFIER 12 120180- RECEPT / DATA
RECEPT / DATA / CLOCK
5220 7020
5580 3780
LIGHTING LEGEND & SYMBOLS
DESCRIPTIONSYMBOL
'SUNCO' MODEL #JNL-F2-60W-3065, 2'x4' LED GRID FRAME LIGHT, WEIGHT 3 LBS, 40 WATT MAX TUNABLE, 4000K COLOR TEMP TUNABLE, 0-10V DIMMING, SUITABLE
AT DAMP LOCATIONS
DED FLOOR RECEPT FLOOR RECEPTS
DED GFI VENDING MACHINE
201 12
12 12012 120
12 120 180201 12 -
DED FLOOR RECEPT
DED FLOOR RECEPT
DED FLOOR RECEPT
- 600
-201 12 180
180201 12 -
-201 12 180
2019- - - -- -
INSTA-HOT 12 20 1- 1440
17- - - -- -
19- - - -- -
- - - - - -18
ROCKER SWITCH (20 AMPS, 125 VOLTS). INSTALL PER MOUNTING HEIGHT
DETAIL U.N.O.
S
'NSL' MODEL #JNL-BLD-HM15D-YYY, 15W 90 MIN EMERGENCY BATTERY BACK-UP,
INSTALLED WITH 'SUNCO' MODEL #JNL-F2-60W-3065, 2'x4' LED GRID FRAME LIGHT
WEIGHT 3 LBS, 40 WATT MAX TUNABLE, 4000K COLOR TEMP TUNABLE, 0-10V
DIMMING, SUITABLE AT DAMP LOCATIONS
STATE AGENCY APPROVAL
REVISIONS
PROFESSIONAL OF RECORD ON PC
PROJECT SPECIFIC PROFESSIONAL OF RECORD
PROJECT NO.:
DRAFTER:
SCALE:
DATE:
SHEET NUMBER
00-0000
AS NOTED
SHEET TITLE:
DISTRICT/CUSTOMER NAME:
NEXTMOD
00-00-00
ALL DESIGNS INDICATED ON THESE PLANS/DRAWINGS ARE PROPERTY OF NEXTMOD,
INC AND ARE FOR THE USE BY NEXTMOD IN THE SPECIFIED JOB ONLY. THEY SHALL
NOT BE USED AND/OR DUPLICATED OR TRANSMITTED IN ANY FORM, FOR ANY
PURPOSE WITHOUT THE PRIOR WRITTEN CONSENT OF NEXTMOD, INC. ANY
UNAUTHORIZED USE OF THESE PLANS SHALL SUBJECT THE OWNER OF SAID
PROPERTY TO LIQUIDATED DAMAGES OF $75,000.00. THESE PLANS ARE PROTECTED
UNDER THE PROVISIONS OF THE 1976 COPYRIGHT ACT
COPYRIGHT NEXTMOD, © ALL RIGHTS RESERVED.
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
SCHOOL/SITE NAME:
STOCKPILE
PRE-CHECK (PC) DOCUMENT
CODE: 2022 CBC
A SEPARATE PROJECT APPLICATION FOR
CONSTRUCTION IS REQUIRED
FIRM:
ADDRESS:
CITY:
PHONE:
FIRM: ORION STRUCTURAL ENGINEERING, INC.
ADDRESS: 11305 RANCHO BERNARDO ROAD, SUITE 121
CITY: SAN DIEGO, CA 92127
PHONE: (858) 679-1974
NEXTMOD
ELECTRICAL PLAN
GENERAL NOTES
1. SEE SHEET E0.0 FOR ELECTRICAL, FIRE ALARM AND SIGNAL PLAN DESIGN NOTES
2. PROVIDE EMERGENCY LIGHTING AT ALL EXTERIOR DOORS PER SECTION
1008.2.3. LOCATION OF EMERGENCY LIGHTING TO BE DETERMINED BY
SITE ARCHITECT BASED ON PROJECT SPECIFIC DESIGN
3. CBC SECTION 907.5.2.2, EMERGENCY POWER FOR EMERGENCY VOICE
COMMUNICATION.
4. SEE DAYLIT FLOOR PLANS FOR DAYLIT LOCATIONS
5. WHEN ELECTRICAL PANEL WEIGHT EXCEEDS >20 LBS, SEE DETAILS
FOR ATTACHMENT.
A8.1
ELECTRICAL PLAN
SCALE: 1/4" = 1'-0"
E3.0N
CCD-001_01-08-26
04-124946_CCD-001
2/ 9/
:4
3:
P M
1 2 6
B
A
3 4 5
A8
A8
B8
A10
A6
B8
PANEL 'A'
WATERPROOF J-BOX
@ +18" AFF WITH 3/4"
CONDUIT STUBBED
TO ATTIC FOR FIRE
ALARM
A5
A10
DEVICE SHALL
HAVE SPEAKER
OPTION. TYP
B10
HH
J
WP
J
WP
WP
GFI
M
HH
M
HH
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
S
J
AIR
PURIFIERJ
AIR
PURIFIER
E E
S
S
S
S
WP
GFI
EXIT EXIT
J
OFOI
PROJ.
DED
4'-1"
'-5
/2
" T
YP
'-1
/2
" T
YP
4'-0 1/2"
'-9
/4
J
OFOI
WIFI
ROUTER
'-9
'-7
/2
'-7
/2
'-1
1/
2"
2'-1 1/2"
3'-9 1/2"
4'-1 1/2"
3'-11 1/2"
+24
AFF
DED
+24
AFF
DED
+24
AFF
DED
+24
AFF
DED
+24
AFF
DED
+24
AFF
VENDING VENDING
3 3 3 3
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
B2
B4
'-9
5'-10" 5'-11 1/2"
5'-10" 5'-11 1/2"
1' -2
2'-2 1/2"2'-2 1/2"
8' -0
" T
YP
8' -0
" T
YP
WH
DED GFI DED GFIGFI
J
A6
B5A1,3 B1,3
A9 B10
A8 B10
PANEL 'B'
A11 B7
A8
A6 A6
A12
A16 A18
A14
B9
B12
A7
DED J-BOX FOR
INSTA-HOT
B11
AIR PURIFIER SWITCH
IN 3 GANG BOX
(TYP OF 2)
DATE
SIGNED:
03/05/26
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
04-124946 0
P0.0
PLUMBING SCHEDULE
AND DETAILS
PLUMBING NOTES
GENERAL PLUMBING SPECIFICATIONS
4 1
OPTIONAL CONDENSATE LINE
FROM ROOF MOUNT HVAC
OPTIONAL TANKLESS
INSTA HOT WATER
HEATER
VENT UP
THRU
ROOF
WASTE DOWN
WALL THRU
FLOOR
TYPICAL LAVATORY PIPING
SEE PLUMBING
NOTES #2 (TYP)
A8.1
9" M
IN
EQ
EQ
" M
AX
AT
/8
" R O
D (6
0" M
AX
S
PA
C
IN
G
ROOF/FLOOR JOIST/BLKG
SIDE BEAM ATTACHMENT
#14 X 1"
HEX HEAD SDS
ADJ SWIVEL LOOP
HANGER
3" MAX PIPE
A307 3/8"
ALL THREAD
NUT (TYP)
FELT
" M
AX
P
ER
A.
1.
(2
" M
AX
AT
/8
" R O
D
ADJ SWIVEL LOOP
HANGER
3" MAX PIPE
A307 3/8"
ALL THREAD
NUT (TYP)
FELT
ROOF/FLOOR JOIST/BLKG
SIDE BEAM ATTACHMENT
EQ
EQ
#14 X 1"
HEX HEAD SDS
" M
AX
P
ER
A.
1.
(2
NOTES
3" MAX PIPE HANGER SUPPORT
SCALE: 3" = 1'-0"
3" MAX PIPE HANGER SUPPORT
SCALE: 3" = 1'-0"
MECHANICAL PIPING (MP), MECHANICAL DUCTS (MD), PLUMBING PIPING (PP), ELECTRICAL
DISTRIBUTION SYSTEMS (E):
MP MD PP E - OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH
PROJECT SPECIFIC NOTES AND DETAILS
MP MD PP E - OPTION 2: SHALL COMPLY WITH THE APPLICABLE OSHPD
PRE-APPROVAL (OPM #) #_________________
MEP COMPONENT ANCHORAGE NOTE
PIPING, DUCTWORK AND ELECTRRICAL DISTRIBUTION
SYSTEM BRACING NOTE
NOTE:
THE OPTIONAL INSTA-HOT SHALL NOT ENCROACH INTO THE KNEE
AND TOE CLEARANCES. NO SHARP OR ABRASIVE SURFACES ARE
ALLOWED IN PROMIXTY TO THE KNEE AND TOE CLEARANCES.
SEE DETAILS #15 OR 5/A10.1 FOR REFERENCE
STATE AGENCY APPROVAL
REVISIONS
PROFESSIONAL OF RECORD ON PC
PROJECT SPECIFIC PROFESSIONAL OF RECORD
PROJECT NO.:
DRAFTER:
SCALE:
DATE:
SHEET NUMBER
00-0000
AS NOTED
SHEET TITLE:
DISTRICT/CUSTOMER NAME:
NEXTMOD
00-00-00
ALL DESIGNS INDICATED ON THESE PLANS/DRAWINGS ARE PROPERTY OF NEXTMOD,
INC AND ARE FOR THE USE BY NEXTMOD IN THE SPECIFIED JOB ONLY. THEY SHALL
NOT BE USED AND/OR DUPLICATED OR TRANSMITTED IN ANY FORM, FOR ANY
PURPOSE WITHOUT THE PRIOR WRITTEN CONSENT OF NEXTMOD, INC. ANY
UNAUTHORIZED USE OF THESE PLANS SHALL SUBJECT THE OWNER OF SAID
PROPERTY TO LIQUIDATED DAMAGES OF $75,000.00. THESE PLANS ARE PROTECTED
UNDER THE PROVISIONS OF THE 1976 COPYRIGHT ACT
COPYRIGHT NEXTMOD, © ALL RIGHTS RESERVED.
6361 BOX SPRINGS ROAD, RIVERSIDE, CA 92570
OFFICE: (909) 740-3120, FAX: (909) 726-9470
WEBSITE: WWW.NEXTMODINC.COM
SCHOOL/SITE NAME:
STOCKPILE
PRE-CHECK (PC) DOCUMENT
CODE: 2022 CBC
A SEPARATE PROJECT APPLICATION FOR
CONSTRUCTION IS REQUIRED
FIRM:
ADDRESS:
CITY:
PHONE:
FIRM: ORION STRUCTURAL ENGINEERING, INC.
ADDRESS: 11305 RANCHO BERNARDO ROAD, SUITE 121
CITY: SAN DIEGO, CA 92127
PHONE: (858) 679-1974
NEXTMOD
SYMBOL
PLUMBING FIXTURE SCHEDULE (SINKS)
DESCRIPTION CWWASTE VENT HW
ACCESSIBLE
FOR
SINK: 'JUST MANUFACTURING' - MODEL# SLADA2231A65-J, 3- HOLE, 31" X 22" X 6-1/2",18 GA TOP MOUNT, EQUAL SINGLE BOWL DROP-IN ADA SINK WITH REAR CENTER DRAIN
FAUCET: 'CHICAGO FAUCET' - MODEL #50-317XKABCP, DECK MOUNTED, SINGLE HOLE, MANUAL LEVER, HOT AND COLD GOOSNECK FAUCET, 1.5 GPM. WHEN HOT WATER IS PROVIDED, IT SHALL NOT EXCEED
110° F. A TEMPERING VALVE SHALL BE PROVIDED (CPC 407.3)
SINK PIPE COVER: 'IPS' - MODEL #82522 SOFT GUARD PLUS TRAP COVER (FLAME SPREAD: 25; SMOKE RATING: 450)
1. FAUCET CONTROLS & OPERATING MECHANISMS: SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO MORE THAN 5 LBS LEVER OPERATED, PUSH TYPE & ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE SELF CLOSING
VALVES ARE ALLOWED IF THE FAUCET REMAINS OPEN FOR AT LEAST 10 SECONDS.
2. ALL WATER & DRAIN PIPES ACCESSIBLE UNDER LAVATORIES AND SINKS: SHALL BE INSULATED (CLASS I FLAME SPREAD INDEX 0-25, SMOKE DEVELOP 450) OR OTHERWISE COVERED.
THERE SHALL BE NO SHARP OR ABRASIVE OBJECTS OR SURFACES UNDER LAVATORIES.
3. ALL VENTS TO ROOF AND VENT RISER CONNECTIONS TO BE OFFSET ABOVE CEILING FROM WALLS IN ORDER TO PREVENT PENETRATION THROUGH TOP PLATES.
4. ALL WASTE DROPS IN WALLS TO BE OFFSET PRIOR TO WALL BOTTOM PLATES.
5. FOR ALLOWABLE CUTTING/NOTCHING/BORED HOLES IN 2X WALL STUDS AND JOISTS, SEE TYPICAL DETAILS ON STRUCTURAL SHEETS
6. TOILET CURB ON FLOORS: FOR TOILET ROOMS WITH MORE THAN TWO (2) FIXTURES IN RELOCATABLE BUILDINGS, PROVIDE A CONTINUOUS VINYL FLOORING WITH FULLY SEALED JOINTS.
VINYL FLOORING TO EXTEND A MIN OF SIX (6) INCHES UP THE STUD WALL FROM THE FINISH FLOOR LEVEL.
7. ALL INTERIOR COLD AND HOT WATER IS OVERHEAD PIPING EXCEPT AT INSIDE WALLS UNLESS OTHERWISE NOTED.
8. ALL DRAIN AND SEWER FITTINGS BELOW FLOOR LINE SITE INSTALLED
9. SEWER/WATER STUB OUTS: SHALL BE LOCATED WITHIN THE ALLOWABLE AREA AS SHOWN ON PLANS AND CONNECTIONS SHOULD BE EASILY ACCESSIBLE FOR FUTURE RELOCATION STUB OUT HEIGHT SHOULD BE COORDINATED WITH BUILDING MFR AND SITE CONTRACTOR/OWNER.
10. ALL DIMENSIONS ON THIS SHEET ARE TO FACE OF FINISH
11. FOR ALL WALL HUNG WATER CLOSETS, USE 'JOSAM COMPANY' (OR EQUAL) CLOSET CARRIERS, MODEL #12674 (LEFT HAND) OR #12694 (BACK TO BACK) OR #12704 (VERTICAL W/ LEFT
HAND VENT) OR #12724 (VERTICAL BACK TO BACK)
A. PLUMBING EQUIPMENT, FIXTURE AND ACCESSORIES: FURNISH AND INSTALL ALL PIPING, VALVES, VENTS, STOPS AND TRAPS REQUIRED TO CONNECT ALL FIXTURES AND EQUIPMENT
PROVIDE ALL ELECTRICAL CONNECTIONS AS REQUIRED
B. MATERIALS AND WORKMANSHIP: ALL WORKMEN SHALL BE SKILLED AND QUALIFIED FOR THE WORK WHICH THEY PERFORM ALL MATERIALS USED, UNLESS OTHERWISE SPECIFIED, SHALL BE NEW AND OF THE TYPES AND GRADE SPECIFIED WORKMANSHIP SHALL BE EQUAL OF BETTER IN QUALITY TO THAT REQUIRED BY THE CONSTRUCTION TRADES FOR A FINISHED PRODUCT
C. THE DETAILS ON THIS SHEET ONLY ILLUSTRATE THE SPECIFIC REQUIREMENTS FOR INSTALLING THE FIXTURES AND THE ACCESSORIES SHOWN INSTALL FIXTURES PER MFR'S INSTRUCTIONS SEE PROJECT SPECIFICATIONS FOR THE ACCESSORIES AND FIXTURES THAT APPLY TO THIS PROJECT.
D. THE USE OF PEX TUBING, AND ITS FITTINGS AND INSTALLATION, SHALL COMPLY WITH…