Exhibit 6 - Drawings.pdf
PDF 7 MB Posted
- Attached to
- ODOT North Plains Scale House Replacement
- Solicitation number
- S-73000-00017816
- Issued by
- Oregon
About this file
This is a comprehensive drawing and design document for the Oregon Department of Transportation (ODOT) North Plains Scale House Replacement project located at US Highway 26, Mile Post 54.10, in Cornelius, Oregon. The project involves the demolition of an existing scale house and construction of a new replacement facility, including site work, utilities coordination, electrical infrastructure, concrete paving, building construction with full mechanical and interior systems, and reconnection of existing equipment. The new scale house will be constructed to Building Code Type V-B with an office occupancy classification, featuring 349 square feet of usable area, accommodating an occupant load of 2 persons. The building design incorporates significant structural and environmental specifications including R-60 closed cell foam roof insulation, R-35 closed cell foam wall insulation, R-20 rigid foam foundation insulation, a 51 PSF ultimate ground snow load design, 96 MPH wind speed rating, and seismic design category D. The project encompasses extensive coordination with underground utilities, including mandatory notification to the Oregon Utility Notification Center at least 48 business-day hours before excavation or boring activities, and requires contractor responsibility for locating, protecting, and reconnecting all existing utilities including electrical, telecommunications, drainage systems, and specialized site equipment such as the truck scale, variable message signs, and traffic control systems.
The construction scope includes detailed specifications for site demolition, utility coordination, a new concrete sidewalk and paving system around the building, interior finishes including customer service areas with specialized counters and windows, a server room, restroom facilities with electric incinerating toilet systems, and office space. The project requires coordination with Portland General Electric (PGE) for electrical service connection to a building-mounted 200-amp meter base, installation of new underground conduit systems for power and communications throughout the site, and reconnection of existing site lighting, scale pit connections, and signage controls. All electrical work must be performed by licensed electricians, with specifications requiring equipment installations to comply with manufacturer instructions, and all work to conform to applicable Oregon codes and laws. The contractor is responsible for providing as-built drawings upon project completion, managing erosion control during construction, and maintaining positive site drainage away from the building with finish floor elevation set 1.5 inches above the existing truck scale. Hard soil or rock is anticipated below grade with no additional compensation provided for subsurface conditions encountered during excavation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment B - Sample Contract~14.docx | DOCX document | |
| 00017816_Addendum Two.docx | DOCX document | |
| Attachment C - Reference Document.pdf | ||
| Exhibit 5 - Specifications~26.pdf | ||
| Revised Exhibit 6 - Drawings.pdf | ||
| Exhibit 7 - Project Overview.doc | DOC document | |
| 00017816_Addendum One.docx | DOCX document | |
| 17816_Sign In Sheet.pdf | ||
| Exhibit 6.1 - BlueSheets-Qualification.pdf | ||
| 00017816_Invitation to Bid.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CODE INFORMATION
OCCUPANCY
OFFICE B
CONSTRUCTION
TYPE V-B
AREA
OFFICE
ALLOWABLE AREA
B OCCUPANCY
OCCUPANT LOAD
OFFICE 2 AT 1:150
9,000 SQ. FT.
349 SQ. FT.
DOOR AREA = 60 SQ. FT.
4% FLOOR AREA = 14 SQ. FT.
OUTSIDE VENTILATION PROVIDED BY NATURAL
VENTILATION FROM EXTERIOR DOORS.
VENTILATION
WALLS
ROOF R-60 CLOSED CELL FOAM
R-35 CLOSED CELL FOAM
ENERGY CONSERVATION
FOUNDATION R-20 RIGID FOAM
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
VMS SIGN
NEW SCALE
HOUSE
EXISTING SCALE
HOUSE TO BE
REMOVED
BYPASS LANETRUCK SCALE LANE
U.S HWY 26 (NW SUNSET HWY) EASTBOUND
U.S HWY 26 (NW SUNSET HWY) WESTBOUND
1/2 MILE TO JCT.
WITH OR HWY 6
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
SITE PLAN~
BUILDING DESIGN CRITERIA
GROUND SNOW LOAD: 51 PSF (ULTIMATE)
SNOW EXPOSURE FACTOR, Ce: 1.0 SNOW IMPORTANCE FACTOR, Is: 1.0 THERMAL FACTOR, Ct: 1.2
WIND SPEED: 96 MPH (ULTIMATE)
WIND EXPOSURE: C
ENCLOSED
WIND IMPORTANCE FACTOR: 1.0
SEISMIC IMPORTANCE FACTOR, Is: 1.0
RISK CATEGORY: II
MAPPED SPEC. RESPONSE ACCEL. Ss AND S1: 1.02 AND 0.42
SITE CLASS: D
SEISMIC DESIGN CATEGORY: D
BASE SHEAR: 1,902 LB (STRENGTH LEVEL)
2025 OREGON STRUCTURAL SPECIALITY CODE
PROJECT WILL CONSTRUCT A NEW SCALE HOUSE TO
REPLACE AN EXISTING SCALE HOUSE. PROJECT WILL
INCLUDE RECONNECTION OF EXISTING UTILITIES AND
EQUIPMENT AND NEW CONCRETE PAVING AROUND SCALE
HOUSE.
DESCRIPTION OF WORK
1. THE LOCATION AND DESCRIPTION OF EXISTING UTILITIES SHOWN ARE FROM AVAILABLE
RECORDS AND/OR FIELD SURVEYS. UTILITIES THAT ARE NOT SHOWN ARE KNOWN TO EXIST ON
THE SITE. ONLY KNOWN LOCATIONS ARE SHOWN. NO GUARANTEE OF THE ACCURACY NOR
COMPLETENESS OF SUCH INFORMATION IS IMPLIED.
2. OREGON LAW REQUIRES THE CONTRACTOR TO FOLLOW RULES ADOPTED BY THE OREGON
UTILITY NOTIFICATION CENTER. THOSE RULES ARE SET FORTH IN OAR 952-001-0010 THROUGH OAR 952-001-0090. COPIES OF THE RULES ARE AVAILABLE BY CALLING THE OREGON UTILITY
NOTIFICATION CENTER AT (800) 332-2344.
3. THE CONTRACTOR SHALL NOTIFY EACH UNDERGROUND UTILITY AT LEAST 48 BUSINESS-DAY
HOURS PRIOR TO EXCAVATING, BORING, OR POTHOLING. ALL UTILITY CROSSINGS SHALL BE
POTHOLED AS NECESSARY PRIOR TO EXCAVATING OR BORING TO ALLOW THE CONTRACTOR TO
PREVENT GRADE OR ALIGNMENT CONFLICTS.
4. PROVISIONS SHALL BE MADE BY THE CONTRACTOR TO KEEP ALL EXISTING UTILITIES IN SERVICE
AND PROTECT THEM DURING CONSTRUCTION.
5. UTILITIES, OR INTERFERING PORTIONS OF UTILITIES, THAT ARE ABANDONED IN PLACE SHALL BE
REMOVED BY THE CONTRACTOR TO THE EXTENT NECESSARY TO ACCOMPLISH THE WORK.
WHERE PRACTICABLE, THE CONTRACTOR SHALL CAP OR PLUG WITH CONCRETE BOTH ENDS OF
ABANDONED UTILITIES.
COORDINATION WITH UTILITIES
1. CONTRACTOR SHALL PERFORM ALL NEW WORK INDICATED ON DRAWINGS UNLESS SPECIFICALLY
NOTED AS EXISTING OR AS BEING BY ODOT OR BY OTHERS.
2. ALL WORK SHALL CONFORM TO APPLICABLE CODES, LAWS AND ORDINANCES OF THE AUTHORITY
HAVING JURISDICTION.
3. DO NOT SCALE THE DRAWINGS.
4. CLARIFICATIONS SHALL BE REQUESTED IN WRITING PRIOR TO ANY INSTALLATION. INCORRECT
INSTALLATIONS SHALL BE CORRECTED AT NO ADDITIONAL COST TO ODOT.
5. DRAWINGS ARE SCHEMATIC IN NATURE. MAJOR COMPONENTS AND EQUIPMENT ARE SHOWN ON THE DRAWINGS. SUPPLY AND INSTALL ALL MINOR COMPONENTS AND MATERIALS NECESSARY TO PROVIDE A COMPLETE AND FUNCTIONAL PROJECT WHETHER OR NOT ALL SUCH COMPONENTS ARE NOTED IN THE
DRAWINGS.
6. PLANS CALL OUT SPECIFIC MAKES AND MODELS OF EQUIPMENT IN SOME LOCATIONS. SUBSTITUTION REQUESTS SHALL BE MADE AT LEAST 14 CALENDAR DAYS IN ADVANCE OF SCHEDULED INSTALLATIONS.
ODOT SHALL AT ITS SOLE DISCRETION DETERMINE THE ACCEPTABILITY OF SUBSTITUTIONS. NO
SUBSTITUTIONS SHALL BE INSTALLED WITHOUT PRIOR WRITTEN APPROVAL FROM THE ODOT
CONSTRUCTION PROJECT MANAGER.
7. ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
PUBLISHED INSTALLATION INSTRUCTIONS AND RECOMMENDATIONS.
8. SPECIFIC LOCATION OF NEW SCALE HOUSE SHALL BE COORDINATED WITH ODOT CONSTRUCTION PROJECT MANAGER TO MATCH EXISTING SITE CONDITIONS. MAKE ADJUSTMENTS IN THE FIELD AS
REQUIRED, MAINTAIN ALL REQUIRED CLEARANCES.
9. HARD SOIL OR ROCK IS ANTICIPATED TO BE ENCOUNTERED BELOW GRADE. CONTRACTOR SHALL MAKE THEIR OWN DETERMINATION OF EXCAVATION EFFORT REQUIRED PRIOR TO PROVIDING A BID. NO EXTRA
PAYMENT WILL BE MADE FOR SUBSURFACE CONDITIONS UNCOVERED DURING EXCAVATION.
10. ALL NEW UNDERGROUND UTILITIES SHALL BE A MINIMUM OF 24" BELOW FINISH GRADE UNLESS NOTED OTHERWISE. MINIMUM TRENCH WIDTH SHALL BE TOTAL OF UTILITY SIZES PLUS 12". PROVIDE 1/4" MINUS OR SAND BEDDING AND 3/4" MINUS CRUSHED AGGREGATE BACKFILL. AREAS OUTSIDE OF VEHICLE WAYS AND MORE THAN 5' FROM BUILDING MAY BE BACKFILLED WITH NATIVE SOIL PROVIDED THERE ARE NO
ROCKS LARGER THAN 3/4" IN BACKFILL.
11. ALL ELECTRICAL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICIAN.
12. GRADE ALL DISTURBED AREAS IN CONSTRUCTION AREA SMOOTH AND UNIFORM. NO ABRUPT GRADE
CHANGES OR BREAKS WILL BE ACCEPTED. PLANTING AND LANDSCAPING IS NOT IN CONTRACT.
13. ALL DISTURBED SURFACES WITHOUT PAVING SHALL HAVE 8" MINIMUM THICKNESS COMPACTED
CRUSHED AGGREGATE SURFACING.
14. STOP WORK IMMEDIATELY IN THE CASE THAT ANY ARCHEOLOGICAL ARTIFACTS ARE ENCOUNTERED IN
PROJECT RELATED EXCAVATIONS. NOTIFY ODOT CONSTRUCTION PROJECT MANAGER AT ONCE.
CONTRACTOR DELAYS DUE TO THE DISCOVERY OF ARCHEOLOGICAL ARTIFACTS ARE CONSIDERED TO
BE OUTSIDE OF THE CONTRACT SCOPE.
15. CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS AT THE END OF THE PROJECT.
16. ODOT WILL PROVIDE TRAFFIC CONTROL TO CLOSE SCALE SITE ACCESS FROM HIGHWAY.
GENERAL NOTES
SHEET INDEX
C1 SITE PLAN
C2 DETAIL SITE DEMOLITION PLAN
C3 DETAIL SITE PLAN
A1 FLOOR PLAN
A2 ELEVATIONS
A3 DETAILS
S1 DETAILS
S2 SECTIONS
E1 ELECTRICAL PLAN
0 20'
SITE PLAN
SCALE: 1" = 20'
SEE DETAIL SITE PLAN
DRAWINGS C2 AND C3
C1
21 MILES TO
PORTLAND
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
E
BYPASS LANETRUCK SCALE LANE
15'-0"
9'-0"
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
0 10'
DETAIL SITE DEMOLITION PLAN
SCALE: 1" = 10'
SITE DEMOLITION PLAN NOTES
1. PRESERVE AND PROTECT ALL EXISTING FEATURES NOT TO BE REMOVED.
2. PULL BACK ALL CABLES AND WIRES TO NEAREST ADJACENT JUNCTION BOX TO REMAIN.
ALL CABLES AND WIRES ARE TO BE NEATLY LABELED AND COILED FOR RECONNECTION.
3. INSTALL EROSION CONTROL FEATURES AS REQUIRED TO PREVENT EROSION AND
SEDIMENT MIGRATION DURING CONSTRUCTION. MAINTAIN UNTIL PROJECT COMPLETION
AND SURFACE RESTORATION.
DETAIL SITE DEMOLITION PLAN KEYED NOTES
1. REMOVE AND SALVAGE EXISTING CONCRETE BARRIER FOR RE-INSTALLATION.
2. SAW CUT AND REMOVE EXISTING PAVEMENT TO EXTENTS SHOWN. NOTE THAT A SECOND SAWCUT IS REQUIRED PRIOR TO
CONSTRUCTING NEW WALKS.
3. SAW CUT EXISTING CONCRETE VAULT AT LOCATION SHOWN AND REMOVE LID AND WALLS AS REQUIRED TO INSTALL NEW CONSTRUCTION. REMOVE WALLS TO 6” MINIMUM BELOW THE LEVEL OF THE BOTTOM OF NEW FOUNDATION.
4. REMOVE EXISTING SCALE HOUSE AND FOUNDATIONS.
5. REMOVE EXISTING CONCRETE LANDING AND HANDRAIL.
6. VERIFY WHICH EXISTING ANTENNAS AND OTHER EQUIPMENT ON SCALE HOUSE ARE TO BE SALVAGED WITH CONSTRUCTION
PROJECT MANAGER. RETURN SALVAGE MATERIAL TO ODOT.
7. REMOVE EXISTING ASPHALT PAVING, TYPICAL.
8. DISCONNECT ALL EXISTING UNDERGROUND CONNECTIONS FROM SCALE HOUSE. PULL BACK, COIL AND LABEL ALL CABLES AT NEAREST JUNCTION BOX TO REMAIN. AT DIRECT BURIAL CABLES, CAREFULLY UNCOVER TO PULL BACK.
9. REMOVE EXISTING JUNCTION BOX.
10. REMOVE INTERFERING UNDERGROUND UTILITIES AFTER PULLING BACK ALL CABLING, TYPICAL.
11. ABANDON EXISTING DRAIN PIPE AND REMOVE WHERE PIPE INTERFERES WITH NEW CONSTRUCTION.
12. PRESERVE AND PROTECT EXISTING UTILITY POLE.
13. REMOVE EXISTING TREE. CUT STUMP FLUSH WITH THE EXISTING GROUND SURFACE AND LEAVE IN-PLACE.
DETAIL SITE DEMOLITION PLAN
LEGEND:
EXISTING LIGHT POLE
EXISTING UTILITY POLE
EXISTING OVERHEAD POWER LINEOHP
EXISTING UNDERGROUND POWER LINEE
EXISTING TELEPHONE LINECOM
EXISTING JUNCTION BOX
EXISTING SCALE ACCESS HOLE
NEW UNDERGROUND UTILITY
NEW JUNCTION BOX OR HANDHOLE
C2
EXITING UTILITY POLE GUY
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
E
E
E
E E
BYPASS LANETRUCK SCALE LANE
42 41
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
DETAIL SITE PLAN GENERAL NOTES
1. ALIGN WEST EDGE OF NEW BUILDING WITH WEST EDGE OF EXISTING TRUCK SCALE.
COORDINATE EXACT BUILDING LOCATION IN THE FIELD WITH THE ODOT CONSTRUCTION
PROJECT MANAGER.
2. SET BUILDING FINISH FLOOR TO PROVIDE POSITIVE DRAINAGE AWAY FROM BUILDING IN ALL
DIRECTIONS. FINISH FLOOR SHALL BE 1-1/2" ABOVE TRUCK SCALE.
3. FINISH GRADES SHALL SLOPE AWAY FROM DOORS BETWEEN 1% AND 2% SLOPE.
4. USE SCHEDULE 40 PVC SWEEP ELBOWS FOR CONDUITS AT ALL LOCATIONS.
5. EXISTING UNDERGROUND UTILITY LOCATIONS ARE UNKNOWN. MULTIPLE UN-LOCATED
UTILITIES EXIST WITHIN THE PROJECT AREA. CONTRACTOR SHALL LOCATE ALL UTILITIES.
6. ELECTRIC UTILITY IS PORTLAND GENERAL ELECTRIC (PGE).
7. LOCATIONS SHOWN FOR UTILITIES AND CONNECTIONS ARE SCHEMATIC AND MUST BE
VERIFIED IN THE FIELD AFTER LOCATES ARE COMPLETED.
8. RECONNECT ALL EXISTING SITE CONNECTIONS TO NEW BUILDING INCLUDING OPEN/CLOSED
SIGN, VARIABLE MESSAGE SIGN (VMS), SITE LIGHTING, SCALE PIT, AND POWER SERVICE.
CONNECTIONS INCLUDE POWER AND COMMUNICATIONS TO MATCH EXISTING.
9. EXISTING CONDUCTORS AND CABLES MAY BE REUSED IF LONG ENOUGH TO REACH NEW
BUILDING. WHERE EXISTING WIRES AND CABLES ARE NOT LONG ENOUGH, REPLACE WITH
NEW FULL LENGTH MATERIALS MATCHING EXISTING. SPLICING IS NOT ALLOWED.
10. JUNCTION BOXES AND HANDHOLES ARE PER ODOT STANDARD DRAWING TM702. DO NOT
PROVIDE 12" WIDE PCC APRON AROUND BOXES AS SHOWN IN DETAIL FOR UNSURFACED
AREAS.
11. SEE ODOT STANDARD DRAWING TM701 FOR REQUIREMENTS AT JUNCTION BOXES AND
HANDHOLES. DO NOT USE FIBERGLASS CONDUIT ELBOWS AS SHOWN ON STANDARD
DRAWING.
12. BASIS OF DESIGN JUNCTION BOX JB2 IS JH AMERICAN ENCLOSURES PART NO. APC 1324.
OTHER MAKES AND MODELS COMPLYING WITH STANDARD DRAWINGS AND BLUESHEETS
STANDARDS MAY BE USED.
13. SEE ODOT STANDARD DRAWING TM700 FOR CONDUIT TRENCHING REQUIREMENTS.
14. PARTICIPATE IN UNDERGROUND CONDUIT PRE-INSTALLATION COORDINATION MEETING
PRIOR TO INSTALLING UNDERGROUND CONDUITS. PROVIDE 48 HOURS MINIMUM NOTICE TO
CPM OF MEETING TIME.
15. PARTICIPATE IN A CONDUIT POST-INSTALLATION MEETING PRIOR TO COVERING
UNDERGROUND CONDUITS. PROVIDE 48 HOURS MINIMUM NOTICE TO CPM OF MEETING TIME.
16. ADDITIONAL SPECIFICATION INFORMATION RELATED TO STANDARD DRAWING TM702 CAN BE
FOUND AT THE FOLLOWING WEB ADDRESSES. IT MAY BE NECESSARY TO TYPE "OREGON DOT
BLUE SHEETS" INTO WEB SEARCH ENGINE TO FIND THE LINKS.
https://www.oregon.gov/odot/Engineering/Documents_TrafficStandards/BlueSheets.pdf https://www.oregon.gov/odot/Engineering/Documents_TrafficStandards/BlueSheets-Qualification.pdf
17. BED NEW UTILITIES IN SAND, CRUSHED AGGREGATE, OR CONTROLLED LOW STRENGTH
MATERIAL (CLSM) FROM 2" MINIMUM BELOW TO 2" MINIMUM ABOVE UTILITY. TRENCH WIDTH
SHALL BE MINIMUM PRACTICAL FOR INSTALLATION AND COMPACTION.
18. BACKFILL UNDER STRUCTURES AND PAVEMENTS WITH COMPACTED CRUSHED AGGREGATE
OR CLSM. UNSURFACED AREAS MAY BE BACKFILLED WITH CLEAN NATIVE SOILS.
19. CLEAN EXCAVATION SPOILS FREE OR DEBRIS, ROOTS, AND ROCK LARGER THAN 1" MAY BE
PLACED ON THE SLOPE TO THE SOUTHWEST OF THE NEW BUILDING AT THE CONTRACTOR'S
OPTION. SITE PLACED SPOILS MUST BE PLACED AND COMPACTED TO FORM A SMOOTH
UNIFORM SURFACE SLOPING FROM THE EDGE OF NEW EMBANKMENT TO MATCH INTO
EXISTING GRADES AT THE SOUTHWEST. MAXIMUM SLOPE IS 1 UNIT VERTICAL TO 4 UNITS
HORIZONTAL. ALL TRANSITIONS MUST BE SMOOTH AND UNIFORM WITHOUT DETECTABLE
GRADE BREAKS. ALL DISTURBED AREAS MUST BE HYDROSEEDED AND HYDROMULTCHED
USING A NATIVE SEED MIX SUITABLE FOR RE-ESTABLISHING VEGETATION.
DETAIL SITE PLAN KEYED NOTES
1. COORDINATE AND PAY FOR ELECTRICAL UTILITY POWER SERVICE CONNECTION TO NEW BUILDING MOUNTED METER BASE.
2. CONSTRUCT POLE MOUNTED AND UNDERGROUND CONDUIT TO ELECTRICAL UTILITY SERVICE REQUIREMENTS FROM EXISTING UTILITY POLE TO INTERIOR OF BUILDING AND TO BUILDING MOUNTED METER BASE. CONDUIT SHALL BE SIZED PER UTILITY REQUIREMENTS, BUT NOT LESS THAN 2-1/2” DIAMETER.
3. INSTALL NEW POWER METER BASE ON SIDE OF NEW BUILDING TO ELECTRICAL UTILITY REQUIREMENTS. SURFACE MOUNT BASE ON FLAT TRIM BOARDS ENTIRELY COVERED WITH
PRE-FINISHED SHEET METAL. FLASH AND SEAL INSTALLATION WEATHER TIGHT.
4. CONSTRUCT APPROXIMATELY 60 LINEAL FEET OF 4” DIAMETER SCHEUDLE 40 PVC DRAINPIPE SYSTEM FOR ROOF DRAINS. SLOPE PIPES AT 2% MINIMUM. PROVIDE 18” MINIMUM COVER.
INSTALL 12 GAUGE SOLID COPPER TRACER WIRE, EXTEND END 12” ABOVE FINISH GRADE.
5. CONNECT DOWNSPOUT TO DRAINPIPE, SEE DETAIL
6. CONSTRUCT APPROXIMATELY 60 LINEAL FEET OF 4” DIAMETER SCHEUDLE 40 PVC DRAINPIPE FOR SCALE PIT. SLOPE PIPE AT 1% MINIMUM. INSTALL 12 GAUGE SOLID COPPER TRACER
WIRE, EXTEND END 12” ABOVE FINISH GRADE.
7. EXTEND NEW 4” DIAMETER PVC DRAINPIPE THROUGH NEW HEADER WALL INTO SCALE PIT. PLACE DRAINPIPE AT THE BOTTOM OF WALL.
8. USE 4" DIA. PERFORATED PIPE THROUGH EXISTING VAULT TO BE FILLED.
9. CORE HOLE THROUGH EXISTING CONCRETE VAULT WALL FOR NEW 4” DIAMETER PERFORATED PVC DRAINPIPE. BACKFILL THE BOTTOM 12” OF VAULT WITH PEA GRAVEL OR OTHER
APPROVED DRAIN ROCK.
10. VERIFY PIPE GRADES BEFORE INSTALLATION. DAYLIGHT SCALE PIT DRAIN AND ROOF DRAINPIPES NEXT TO EACH OTHER AT TOE OF EXISTING SLOPE. PROVIDE CONCRETE OUTFALL
PROTECTION, SEE DETAIL
11. CONSTRUCT (5) 1-1/4” DIAMETER SCHEDULE 40 PVC CONDUITS FROM BUILDING TO EXISTING SCALE PIT. COORDINATE CONNECTION POINT AT EXISTING SCALE PIT WITH ODOT STAFF.
CORE HOLES IN EXISTING CONCRETE PIT FOR NEW CONDUITS. GROUT CONDUITS INTO PIT WALL. PROVIDE 18” MINIMUM COVER. PROVIDE PULL STRINGS IN ALL NEW CONDUITS (4 CONDUITS ARE FOR LOAD CELL CONNECTIONS BY OTHERS, 1 CONDUIT IS FOR SUMP PUMP POWER AND PIT LIGHTS).
12. LOCATE EXISTING UNDERGROUND POWER TO EXISTING SITE LIGHTING.
13. CONSTRUCT (2) 2” DIAMETER SCHEDULE 40 CONDUITS FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUITS PROVIDE CONNECTION TO WEST SITE LIGHTING
AND SPARE CAPACITY.
14. CONSTRUCT JUNCTION BOX JB2 ON EXISTING LINE FOR SITE LIGHTING CONNECTION. FEED EXISTING WEST SITE LIGHTING. POUR CONCRETE APRON AROUND BOX.
15. CONNECT TO EXISTING SITE LIGHTING. EXTEND 2” SCHEDULE 40 PVC CONDUIT FROM BOX TO 2' MINIMUM BEYOND EDGE OF BOX.
16. INSTALL SPARE 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BOX TO 2' MINIMUM BEYOND EDGE OF BOX. CAP FOR FUTURE CONNECTION.
17. CONSTRUCT (2) 2” DIAMETER SCHEDULE 40 CONDUITS FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUITS PROVIDE CONNECTION TO EAST SITE LIGHTING
AND SPARE CAPACITY.
18. CONSTRUCT JUNCTION BOX JB2 ON EXISTING LINE FOR SITE LIGHTING CONNECTION. FEED EXISTING EAST SITE LIGHTING. SET TOP OF BOX FLUSH WITH FINISH GRADE.
19. CONNECT TO EXISTING SITE LIGHTING. EXTEND 2” SCHEDULE 40 PVC CONDUIT FROM BOX TO 2' MINIMUM BEYOND EDGE OF BOX.
20. INSTALL SPARE 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BOX TO 2' MINIMUM BEYOND EDGE OF BOX. CAP FOR FUTURE CONNECTION.
21. LOCATE EXISTING UNDERGROUND HIGH AND LOW VOLTAGE LINES TO VARIABLE MESSAGE SIGN (VMS), SCALE WEIGHT DISPLAY, AND RED LIGHT/ GREEN LIGHT.
22. CONSTRUCT 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUIT PROVIDES POWER TO VMS SIGN POLE CIRCUITS.
23. CONSTRUCT JUNCTION BOX JB2 ON EXISTING ALIGNMENT OF VMS HIGH VOLTAGE LINES. PULL BACK EXISTING LINES AND INSTALL NEW SWEEPS INTO JUNCTION BOX. RECONNECT
EXISTING LINES TO BUILDING. SET TOP OF BOX FLUSH WITH FINISH GRADE.
24. CONSTRUCT 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUIT PROVIDES PATHWAY FOR RED / GREEN BEACON
SWITCH.
25. CONSTRUCT JUNCTION BOX JB2 ON EXISTING ALIGNMENT OF VMS LOW VOLTAGE LINES. PULL BACK EXISTING LINES AND INSTALL NEW SWEEPS INTO JUNCTION BOX. RECONNECT
EXISTING LINES TO BUILDING. SET TOP OF BOX FLUSH WITH FINISH GRADE.
26. CONSTRUCT 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUIT PROVIDES PATHWAY FOR LOW VOLTAGE
CONNECTIONS TO VMS.
27. CONSTRUCT 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUIT PROVIDES PATHWAY FOR OPEN / CLOSED SIGN
CONTROLS.
28. CONSTRUCT 2” DIAMETER SCHEDULE 40 PVC CONDUIT FROM BUILDING TO NEW JUNCTION BOX. PROVIDE 30” MINIMUM COVER. CONDUIT PROVIDES POWER FOR OPEN / CLOSED SIGN.
29. CONSTRUCT JUNCTION BOX JB2 ON EXISTING ALIGNMENT OF POWER SUPPLY TO OPEN / CLOSED SIGN. PULL BACK EXISTING LINES AND INSTALL NEW SWEEPS INTO JUNCTION BOX.
RECONNECT EXISTING LINES TO BUILDING. SET TOP OF BOX FLUSH WITH FINISH GRADE.
30. CONSTRUCT JUNCTION BOX JB2 ADJACENT TO BUILDING IN CONCRETE WALK FOR CONNECTION TO SERVER ROOM CONDUITS. SET TOP OF BOX FLUSH WITH FINISH GRADE.
31. CONSTRUCT (4) 2” DIAMETER SCHEDULE 40 CONDUITS FROM ACCESS WALL INTO JUNCTION BOX.
32. CONSTRUCT (2) SPARE 2” DIAMETER SCHEDULE 40 PVC CONDUITS FROM JUNCTION BOX TO 6'-0” BEYOND THE EDGE OF CONCRETE WALK. PROVIDE 30” MINIMUM COVER. CAP FOR
FUTURE CONNECTION.
33. CONSTRUCT COMPACTED CRUSHED AGGREGATE EMBANKMENT AROUND BACK OF BUILDING TO SUPPORT CONCRETE WALK AND JUNCTION BOXES. MATCH FINISH GRADES AT NEW AND EXISTING PAVED SURFACES. SLOPE FINISHED AGGREGATE SURFACE SLIGHTLY TO THE SOUTHWEST.
34. SLOPE AGGREGATE EMBANKMENT AT 1 VERTICAL TO 2 HORIZONTAL (MINIMUM) FROM NEW FINISH GRADE TO MATCH INTO EXISTING SLOPE GRADE.
35. CONSTRUCT CONCRETE WALK AROUND BUILDING, SEE DRAWING A1.
36. MATCH EDGE OF NEW CONCRETE WALK TO EXISTING CONCRETE EDGE ALONG TRUCK LANE.
37. MATCH EDGE OF NEW CONCRETE WALK TO SAW CUT EDGE OF EXISTING ASPHALT PAVEMENT. SAW CUT EDGE MUST BE STRAIGHT, VERTICAL, AND FREE OF DAMAGE. RE-SAW CUT EDGE
PRIOR TO POUR.
38. RESTORE FINISHED SURFACE ABOVE DRAINPIPES TO MATCH INTO SURROUNDING GRADES. SLIGHTLY MOUND SURFACE ABOVE UTILITY TRENCH. HYDROSEED AND HYDROMULCH
DISTURBED AND EXPOSED SOIL PRIOR TO SUBSTANTIAL COMPLETION.
39. REINSTALL SALVAGED CONCRETE BARRIER AT LOCATION SHOWN.
40. REINSTALL SALVAGED CONCRETE BARRIER AT LOCATION SHOWN AFTER NEW CONCRETE WALK HAS CURRED FOR A MINIMUM OF FOURTEEN DAYS.
41. CONSTRUCT 1" DIA. SCHEDULE 40 CONDUIT FROM BUILDING TO JUNCTION BOX.
42. CONSTRUCT JUNCTION BOX JB2 AT EDGE OF CONCRETE WALK FOR FUTURE BARRIER MOUNTED LIGHTING CONNECTION. SET TOP OF BOX FLUSH WITH FINISH GRADE.
43. INSTALL SPARE 1" DIA. SCHEDULE 40 CONDUIT FROM BOX TO SAWCUT LINE. CAP FOR FUTURE USE.
44. CONSTRUCT 2" DIA. SCHEDULE 40 CONDUIT FROM BUILDING TO NEW ELECTRIC VEHICLE CHARGER FOUNDATION. STUB CONDUIT UP 6" ABOVE FINISHED SURFACE OF FOUNDATION AND
CAP FOR FUTURE USE.
45. CONSTRUCT CONCRETE FOUNDATION FOR FUTURE ELECTRIC VEHICLE CHARGER. FOUNDATION IS 2'-0"x2'-0" BY 1'-3" THICK. TOP OF FOUNDATION IS TO BE 3" ABOVE ADJACENT FINISHED
GRADE. INSTALL (3) #4 REBARS EACH WAY 3" CLEAR OF BOTTOM OF FOOTING.
DETAIL SITE PLAN
LEGEND:
EXISTING LIGHT POLE
EXISTING UTILITY POLE
EXISTING OVERHEAD POWER LINEOHP
EXISTING UNDERGROUND ELECTRICALE
EXISTING TELEPHONE LINECOM
EXISTING JUNCTION BOX
EXISTING SCALE ACCESS HOLE
NEW UNDERGROUND UTILITY
NEW JUNCTION BOX OR HANDHOLE
0 10'
DETAIL SITE PLAN
SCALE: 1" = 10'
PROJECT BENCH MARK (PBM)
PROJECT BENCH MARK IS THE STEEL ANGLE
CORNER SOUTHEAST OF THE TRUCK SCALE
ASSUMED ELEVATION = 100'-0"
C3
A3
C4
EXISTING SCALEEXISTING VAULT
FINISH FLOOR
EXISTING SCALE PIT
EXISTING
CONCRETE
FLOOR
NEW CONCRETE
HEADER WALL,
SEE DETAIL
SAWCUT AND REMOVE INTERFERING
SECTION OF EXISTING CONCRETE VAULT
TO 6" BELOW FOOTING LEVEL
NEW SCALE HOUSE
CORE HOLE IN VAULT
WALL FOR 4" DIAMETER
VAULT DRAIN, SEE SITE
PLAN
COMPACTED CRUSHED
AGGREGATE FILL,
COMPACT TO 95% PER
ASTM D698, TYP.
OPTIONAL FILL SLOPE FOR
CLEAN EXCAVATION SPOILS,
SEE DRAWING C3
APPROXIMATE
EXISTING GRADE
CONCRETE WALK
APPROXIMATE
EXISTING GRADE
UNDISTURBED
EXISTING SOIL
DRAIN ROCK BACKFILL,
SEE DRAWING C3
SAW CUT
VAULT
6"
FIELD VERIFY
1'-0" MIN.
6"
6"
CUT PIPE TO MATCH EXISTING
GROUND SLOPE, TYPICAL
HINGED STAINLESS
STEEL RODENT GUARD
EXISTING GROUND
FROM SCALE PIT AND
DOWNSPOUTS (SEPARATE PIPES)
NEW CONCRETE OUTFALL
PROTECTION 6" MINIMUM ALL
AROUND AND BETWEEN PIPES
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
SITE SECTION
C4
SITE SECTION
SCALE: 1/2" = 1'-0"
C4
A3
OUTFALL PROTECTION
SCALE: 1-1/2" = 1'-0"
C4
ROOM FINISH SCHEDULE
WINDOW SHUTTERS (ALL WINDOWS) : MOTORIZED ROLL DOWN METAL SHUTTERS. PROVIDE BACKUP MANUAL OPERATORS.
COORDINATE INSTALLATIONS OF INTERIOR OPERATOR CONTROLS FOR ALL SHUTTERS.
• SEE DOOR AND WINDOW MANUFACTURER SPECIFICATIONS FOR ROUGH FRAMING DIMENSIONS.
• ALL DOORS TO BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY.
• ALL HARDWARE ON DOORS, CABINETS, PLUMBING FIXTURES AND STORAGE FACILITIES SHALL BE LEVER OR OTHER SHAPE TO ALLOW OPERATION
WITHOUT TIGHT GRASPING, PINCHING OR TWISTING TO OPERATE. OPERATION FORCE MAY NOT EXCEED 5 POUNDS, EXCEPT EXTERIOR DOORS, WHICH
MAY BE 8-1/2 POUNDS.
• DOOR THRESHOLDS TO BE A MAXIMUM 1/2" HEIGHT WITH BEVELED SLOPE NOT EXCEEDING 1:2. THRESHOLDS MUST COMPLY WITH ADA.
• ALL DOOR AND WINDOW OPENINGS TO BE FLASHED AND SEALED IN ACCORDANCE WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS. OTHER
OPENINGS TO BE FLASHED IN A MANNER TO MAKE THEM WEATHERPROOF.
• ALL EXTERIOR WINDOW HEAD TRIM MEMBERS ARE TO BE 5/4 BY 10" CEDAR. ALL OTHER DOOR AND WINDOW TRIM MEMBERS ARE TO BE 5/4 BY 4" CEDAR.
• INTERIOR CUSTOMER WINDOW IS 3/8" THICK POLYCARBONATE.
NOTES AND COMMENTS:
• ALL GYPSUM BOARD IS TO BE MOLD AND MOISTURE RESISTANT. PROVIDE LIGHT "ORANGE PEEL" TEXTURE.
• INTERIOR WINDOW TRIM IS TO BE PAINTED 1X3 MDF.
• COUNTER SURFACES ARE TWO LAYERS OF 3/4" THICK PARTICLE BOARD FINISHED WITH PLASTIC LAMINATE.
• FIXED - TEMPERED WITH SEALED INSULATING GLASS WITH THERMAL BREAK SEPARATING THE INSIDE
FROM THE OUTSIDE GLASS.
• LOW-E U-FACTOR OF 0.27
• ALMOND COLORED FRAME
• FIXED - TEMPERED WITH SEALED INSULATING GLASS WITH THERMAL BREAK SEPARATING THE INSIDE
FROM THE OUTSIDE GLASS.
• LOW-E U-FACTOR OF 0.27
• ALMOND COLORED FRAME
WINDOW SCHEDULE
NO. SIZE MATERIAL REMARKS
1 7'-0"x4'-0" DOUBLE PANE
VINYL
4'-0"x4'-0" DOUBLE PANE
VINYL
DOOR SCHEDULE
NO. SIZE FRAME DOOR REQUIREMENTS
1 3'-0"x6'-8" DOOR AND FRAME
D2
HOLLOW METAL
F1
INSULATED
HOLLOW
METAL
4 3'-0"x6'-8" DOOR AND FRAME
D1
3'-0"x6'-8" DOOR AND FRAME
D3
3'-0"x6'-8" DOOR AND FRAME
D1
HOLLOW METAL
HOLLOW METAL
INSULATED
HOLLOW
METAL
FLOOR BASE WALLS CLG. COUNTER PAINT
W
AT
ER
P
R O
O F
VI
N
YL
P
LA
N
K
4" V
IN
YL
B
AS
E- C
O
VE
D
5/ 8"
G
YP
. B O
AR
D
5/ 8"
G
YP
. B O
AR
D
LA
M
IN
AT
ED
P
LA
ST
IC
C
EI
LI
N
G
W
AL
L
H O
LL
O
W M
ET
AL
D O
O R
S
SERVER ROOM
CUSTOMER AREA
WORK AREA
REST ROOM
CUSTOMER COUNTER
3 FIXED - SITE BUILT. SEE DETAILFIELD VERIFY POLYCARBONATE 3
S2
HOLLOW METAL
F1
HOLLOW METAL
F1
HOLLOW METAL
F1
SEE DRAWING A3 FOR DOOR TYPES
• INTERIOR PANIC HARDWARE, EXTERIOR PULL -
PROVIDED BY ODOT, INSTALLED BY
CONTRACTOR
• LOCKSET “L1” - SEE SPECIFICATIONS
• ELECTRIC STRIKE CONTROLLED BY “BUZZ-IN”
UNLOCK BUTTON MOUNTED UNDER OPERATOR
COUNTER - ELECTRIC STRIKE IS PROVIDED BY
ODOT, INSTALLED BY CONTRACTOR
• DEADBOLT - PROVIDED AND INSTALLED BY
ODOT
• 6”x30” TWO-WAY WINDOW, SAFETY GLASS
• MECHANICAL CLOSER
• WEATHERSTRIPPING ALL AROUND DOOR
• 36”x12” STAINLESS STEEL KICK-PLATE AT
INTERIOR
• MORTISE PRIVACY LOCK WITH
INTERCONNECTED OCCUPIED INDICATOR
- PROVIDED BY ODOT, INSTALLED BY
CONTRACTOR
• LOCKSET “L2” - SEE SPECIFICATIONS
• MECHANICAL CLOSER
• INTERIOR PANIC HARDWARE, EXTERIOR PULL -
PROVIDED BY ODOT, INSTALLED BY
CONTRACTOR
• LOCKSET “L1” - SEE SPECIFICATIONS
• ELECTRIC STRIKE CONTROLLED BY “BUZZ-IN”
UNLOCK BUTTON MOUNTED UNDER OPERATOR
COUNTER - ELECTRIC STRIKE IS PROVIDED BY
ODOT, INSTALLED BY CONTRACTOR
• DEADBOLT - PROVIDED AND INSTALLED
BY ODOT
• 24”x30” TWO-WAY WINDOW, SAFETY
GLASS
• MECHANICAL CLOSER
• WEATHERSTRIPPING ALL AROUND DOOR
• 36”x12” STAINLESS STEEL KICK-PLATE AT
INTERIOR
• LOCKSET - PROVIDED AND INSTALLED
BY ODOT
• LOCKSET “L3” - SEE SPECIFICATIONS
• MECHANICAL CLOSER
• MINIMUM 12”x12” LOUVERED VENT KIT
INSTALLED IN DOOR
5 3'-0"x6'-8" DOOR AND FRAME
D2
HOLLOW METAL
F1
INSULATED
HOLLOW
METAL
• INTERIOR PANIC HARDWARE, EXTERIOR PULL -
PROVIDED BY ODOT, INSTALLED BY
CONTRACTOR
• LOCKSET “L1” - SEE SPECIFICATIONS
• ELECTRIC STRIKE WIRED TO ATTIC AND
LABELED FOR FUTURE USE - ELECTRIC STRIKE
IS PROVIDED BY ODOT, INSTALLED BY
CONTRACTOR
• DEADBOLT - PROVIDED AND INSTALLED BY
ODOT
• 6”x30” TWO-WAY WINDOW, SAFETY GLASS
• MECHANICAL CLOSER
• WEATHERSTRIPPING ALL AROUND DOOR
• 36”x12” STAINLESS STEEL KICK-PLATE AT
INTERIOR
NOTE: DEADBOLTS, LOCK SETS, AND ELECTRIC STRIKES ARE FURNISHED BY ODOT. CONTRACTOR SHALL PROVIDE CONSTRUCTION CORES FOR USE DURING CONSTRUCTION. ODOT WILL INSTALL PERMANENT CORES AFTER FINAL COMPLETION, SEE SPECIFICATIONS.
7'-7" 7'-10" 5'-4"5'-3"
2X6 EXTERIOR WALL (TYP.)
2X4 INTERIOR WALL (TYP.)
S2
S2
S2
CUSTOMER
WINDOW
24"X38"HIGH
LAM. COUNTER
W/ 24"X36" HINGED TOP. PROVIDE
POSITIVE LOCKING LATCH
ELECTRIC STRIKE UNLOCK
BUTTON UNDER COUNTER,
ONE FOR EACH DOOR
CENTRALLY LOCATED
CEILING MOUNTED
HEAT PUMP
2" RADIUS,
TYP.
2" GROMMET THROUGH
COUNTER IN POSITIONS
SHOWN, TYP., UNLESS
NOTED OTHERWISE
ELECTRIC STRIKE
AT FRONT DOOR
18"x57"x43.25"HIGH
LAM. COUNTER
HINGE
3/4" THICK FIRE
RATED PLYWOOD
FASTENED TO WALL
ELECTRIC STRIKE
AT BACK DOOR
VENT FOR AIR
FLOW BETWEEN
AREAS
EXTERIOR WALL
MOUNTED
HEAT PUMP
FUTURE
DATA RACK
WORK AREA
5'-7" Ø CLEAR
" D
EE
P x 3 0"
H
IG
H
LA
M. C
OUN
TE
R
ADA CUSTOMER AREA
5'-7 Ø CLEAR
REST ROOM
42" MIN.
CLEARANCE
5'-2"6'-0"±6'-5"±3'-11"
21'-6"4'-6"
3'-6"
3'-6"
7'-0"
3'-6"
7'-6"
6'-6"
SERVER ROOM
RECESSED
ELECTRICAL PANEL
INCINOLET
ELECTRIC
TOILET
INCINOLET VENT PIPE IN
CHASE, SEE NOTES
MATCH GRADE WITH
NEW WALK
MATCH GRADE
WITH NEW WALK
5'-7"
2'-0"
CUSTOMER COUNTER
POSITION WINDOWS AS CLOSE
TO CORNER AS POSSIBLE
CABINET BELOW
COUNTER
GROMMET THROUGH
COUNTER TOP
ELECTRIC
STRIKE
MATCH GRADE
WITH NEW WALK
ACCESS WALL BELOW
COUNTER, SEE DETAIL A3
ACCESS WALL,
SEE DETAIL A2
5'-0" 26'-0" 6'-0"
5'-0"
14'-0"
8'-0"
EXISTING
POWER POLE
MATCH
6" THICK CONCRETE WALK IN FRONT
OF BUILDING WITH #4 REINFORCING
AT 16" ON CENTER EACH WAY 2"
CLEAR FROM SURFACE, PROVIDE
LIGHT BROOM FINISH
MATCH
EXISTING EDGE OF
CONCRETE / STRIPE LINE
100'-0 1/2"
100'-0 1/2"
10"
1'-6"
FINISH FLOOR
= 100'-1 1/2"
100'-0 1/2"
INCINOLET, VENT AND CHASE NOTES
1. SEE INCINOLET MANUFACTURER'S CURRENT INSTALLATION INSTRUCTIONS FOR VENT LOCATION.
2. VENT SHALL BE 4" DIAMETER SCHEDULE 40 PVC PIPE. GLUE JOINTS.
3. EXTEND VENT THROUGH WALL AND UP INTO CHASE WITH A LONG SWEEP ELBOW.
4. CENTER VENT IN CHASE. PROVIDE 2" MINIMUM CLEARANCE BETWEEN VENT AND CHASE WALLS.
5. INSTALL 5/8" GYPSUM BOARD AT INTERIOR CHASE WALLS. NO FINISH IS REQUIRED.
6. EXTEND VENT PIPE INTO RESTROOM AND CONNECT TO INCINOLET TOILET.
7. PROVIDE ESCUTCHEON FINISH PLATE AROUND VENT AT WALL PENETRATION.
8. PROVIDE 2x12 SOLID BLOCKING BETWEEN STUDS ON BOTH WALLS ADJACENT TO INCINOLET TOILET.
BEHIND ALL GRAB BARS ATTACH POINTS.
9. EXTEND VENT THROUGH ROOF WITH UV RESISTANT WEATHER SEALED ROOF BOOT.
10. PROVIDE WEATHER TIGHT VENT CAP WITH 1/4" STEEL MESH BUG SCREEN.
100'-0 1/2"
DOWNSPOUT
CONNECTION,
SEE DETAIL
A3
DOWNSPOUT
CONNECTION,
SEE DETAIL A3
TOOLED JOINT,
TYPICAL
S2
S2
4" THICK CONCRETE
WALK AROUND BUILDING
WITH #4 REINFORCING
AT 16" ON CENTER EACH
WAY, 1-1/2" CLEAR FROM
SURFACE, PROVIDE
LIGHT BROOM FINISH
6" THICK
4" THICK
6" THICK
4" THICK
18"
100'-0 1/2" 100'-0 1/2"
STEEL ANGLE CORNER
SOUTHEAST OF SCALE SURFACE
(ASSUMED ELEVATION = 100'-0")
3" GROMMET THROUGH
COUNTER AT THIS LOCATION
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
FLOOR PLAN A1
FLOOR PLAN
SCALE: 1/2" = 1'-0"
5S T R U C T U R A L
J A
N U A R Y 1 3 , 2
0 0
SHUTTER
ROLL-DOWN
(TYPICAL)
FLOOD LIGHTS,
SEE DRAWING E1
INSTALL 18" DIA. CONVEX
ACRYLIC SAFETY MIRROR
MOUNTED ON ROOF BEAM
TO PROVIDE VIEW OF DOOR
WALL MOUNT OUTDOOR HEAT
PUMP UNIT, INSTALL ±7'-0"
ABOVE FINISHED GRADE
1X8 FIBER CEMENT TRIM BAND
WITH "Z" FLASHING, TYPICAL AT EACH END
TYPICAL FIBER CEMENT SIDING
WITH 7" EXPOSURE
HEAT PUMP
ROLL-DOWN
SHUTTER
ROLL-DOWN
SHUTTER
ROLL-DOWN
SHUTTER
METAL ROOFING
FLOOD LIGHTS,
SEE DRAWING E1
MANUAL WINDOW SHUTTERS
ARE TO BE INSTALLED ON
CONTRACTOR CONSTRUCTED
WINDOW TRIM
TRIM COVERING
ROOF BEAM
WALL MOUNTED
HEAT PUMP
INCINOLET EXHAUST
PIPE WITH WEATHER
RESISTANT CAP
SERVER ROOM
EXHAUST VENT
REST ROOM
EXHAUST VENT
SEE NOTE
REFERENCE ON
DRAWING E1, TYP.
ROLL-DOWN
SHUTTER
SAFETY MIRROR
TYPICAL DIMENSION,
VERIFY WITH CPM
S1
S1
WALL MOUNTED
SPEAKER
RECEPTACLE WITH WEATHER
CAP MOUNTED ON GABLE
SEE DRAWING
E1, TYP.
WEATHER PROTECTED WALL PENETRATION
FOR RADIO ANTENNA CONNECTION
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
ELEVATIONS A2
REAR ELEVATION
SCALE: 1/2" = 1'-0"
FRONT ELEVATION
SCALE: 1/2" = 1'-0"
LEFT ELEVATION
SCALE: 1/2" = 1'-0"
RIGHT ELEVATION
SCALE: 1/2" = 1'-0"
6S T R U C T U R A L
J A
N U A R Y 1 3 , 2
0 0
6" CONC. SLAB
15 MIL VAPOR BARRIER
OVER COMPACTED
CRUSHED AGGREGATE
INCINOLET
ELECTRIC TOILET
(WHERE SHOWN)
2x4 STUDS 16" O.C.
SOUND INSULATION
5/8" GYP. BD. EA. SIDE
1/2" DIA. BY 6" ANCHOR BOLT
AT 6'-0" ON CENTER MAXIMUM
FLOOR FINISH
THREADED
CLEANOUT CAP
BUILDING LINE
FINISH GRADE
PER PLAN
RECTANGULAR TO
PIPE ADAPTER
PREFINISHED RECTANGULAR
METAL DOWNSPOUT LEADER
SCH. 40 ABS CLOSE TEE AND
FITTINGS, PAINT TO MATCH
DOWNSPOUT LEADER COLOR
18" MIN.
NOTE: TURN CLEANOUT TEE FITTING
PARALLEL TO BUILDING WALL TO
MINIMIZE PROJECTION INTO SIDEWALK.
CONCRETE
SIDEWALK
JUNCTION BOX,
SIZE AS REQUIRED
EXTEND CONDUIT INTO
JUNCTION BOX, PROVIDE
BUSHINGS AT ALL CONDUITS
NOTE: JUNCTION BOXES SHALL NOT HAVE
ANY WIRES OR CONNECTIONS PASSING
THROUGH REMOVABLE COVERS. WALL
PENETRATIONS MAY PASS THROUGH
SUITABLE WALL PLATES DESIGNED FOR
SUCH USE. CONFIGURE WALL
PENETRATIONS SO THAT REMOVABLE MDO
WALL COVERING IS NOT OBSTRUCTED BY
WALL PENETRATIONS.
CONDUIT
PER PLAN
FOR ADDITIONAL
NOTES, SEE DETAIL
A3
FACE OF JUNCTION BOX SHALL COVER
REMOVABLE MDO PLYWOOD WALL
COVERING AT EDGES, AND SHALL BE
REMOVABLE WITH SCREWS
1/2" THICK REMOVABLE MDO
PLYWOOD WALL COVERING
1/2" THICK BY 6" TALL MDO PLYWOOD
PERMANENT BASE BOARD WITH
RUBBER BASE ATTACHEDCONCRETE
SIDEWALK
DOUBLE FRAMED WALL,
INTERIOR WALL IS UN-INSULATED
FOR UTILITY ACCESS
1/2" THICK REMOVABLE MDO
PLYWOOD WALL COVERING
1/2" THICK BY 6" TALL MDO PLYWOOD
PERMANENT BASE BOARD WITH
RUBBER BASE ATTACHED
6"-8"
FRAMING SIZE
PER PLAN
TYPICAL EXTERIOR
WALL PER PLAN
CONDUIT
PER PLAN
NOTE: REMOVABLE MDO PLYWOOD WALL COVERING SHALL BE
PRECISELY FIT AT ALL EDGES WITH STRAIGHT LEVEL AND PLUMB
SEAMS NO WIDER THAN 1/16". CONFIGURE SO THAT PANEL CAN BE
REMOVED WITHOUT OBSTRUCTION FROM PERMANENT CONSTRUCTION.
PANEL SHALL EXTEND FROM PERMANENT WALL BASE TO CEILING OR
UNDERSIDE OF COUNTER, AS APPLICABLE. SIZE PANEL TO FIT AROUND
COUNTER SUPPORTS WHERE REQUIRED. FASTEN PANEL TO WALL WITH
#9 BY 1 1/2" STAINLESS STEEL PHILIP HEAD SCREWS AT 16" ON CENTER
AT SUPPORTING FRAMING. ARRANGE SCREW PATTERN IN UNIFORM
HORIZONTAL AND VERTICAL ROWS. USE COUNTERSUNK SCREW HEADS
SET FLUSH WITH PANEL SURFACE. FINISH PAINT REMOVABLE PANEL,
INCLUDING EDGES, PRIOR TO SECURING WITH SCREWS. SCREW HEADS
ARE TO REMAIN UNPAINTED.
NOTE: USE 3/4" FIRE RATED PLYWOOD
INSTEAD OF MDO AT WALL WITH FUTURE
DATA RACK. LOWER 18" OF PLYWOOD
SHALL BE SEPARATE AND REMOVABLE.
CONCRETE
SIDEWALK
FOR ADDITIONAL
NOTES, SEE DETAIL
A3
CONDUIT
PER PLAN
1/2" THICK BY 6" TALL MDO PLYWOOD
PERMANENT BASE BOARD WITH
RUBBER BASE ATTACHED
1/2" THICK REMOVABLE MDO
PLYWOOD WALL COVERING
PROVIDE 2" GAP FOR CONDUITS AND
CABLES AT TOP OF REMOVABLE COVER
WORK COUNTER
GROMMET THROUGH COUNTER
WHERE SHOWN ON PLAN
CONDUITS FROM JUNCTION
BOXES, AS REQUIRED
2x4 ACCESS WALL TO
BOTTOM OF COUNTER
JUNCTION BOX,
AS REQUIRED
NOTE: SIZE REMOVABLE
WALL COVERING UNDER
COUNTER SO THAT
SUPPORT BRACKETS DO
NOT PREVENT REMOVAL.
3'-0"
6'-8"
D1F1
3'-0"
6'-8"
FRAME TYPES
3'-0"
D2
DOOR TYPES
3'-0"
D3
6'-8"
EXISTING EDGE OF
CONCRETE SCALE
10"
#4 REBAR AT 12" ON
CENTER EACH WAY
2'-0" LONG #4 REBAR DOWEL BARS
AT 12" ON CENTER AT TOP, BOTTOM
AND SIDE WALLS, EMBED 6" IN
EPOXY
EXISTING VAULT
CONCRETE FLOOR
STRUCTURAL FILL
NEW CONCRETE
WALK
6"
4" MIN.
SA
W
C U
T
LI
N E
1'-0"
3"
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
DETAILS A3
7S T R U C T U R A L
J A
N U A R Y 1 3 , 2
0 0
INTERIOR PARTITION WALL
SCALE: 3/4" = 1'-0"
A3
DOWNSPOUT DETAIL
SCALE: 1" = 1'-0"
A3
DOUBLE FRAMED ACCESS WALL
SCALE: 3/4" = 1'-0"
A3
JUNCTION BOX AT ACCESS WALL
SCALE: 3/4" = 1'-0"
A3
JUNCTION BOX AT COUNTER ACCESS WALL
SCALE: 3/4" = 1'-0"
A3
NOTE: SEE DRAWING A1 FOR DOOR CALLOUT.
VAULT HEADER WALL
SCALE: 1-1/2" = 1'-0"
A3
NOTE: JUNCTION BOX FACE PLATES SHALL
COVER GAP BETWEEN BOX AND MDO.
REMOVABLE MDO MUST ALSO BE ABLE TO BE
REMOVED AFTER JUNCTION BOX FACE PLATE
IS REMOVED.
3" CLR.
2'-0"
12"
TYPICAL ANCHOR BOLTS, TITEN
GALVANIZED 1/2" x 6" BOLTS 4'-0" O.C.
AND 12" MAXIMUM FROM END OF PLATE,
PROVIDE 5"x5" BY 1/4" THICK GALV.
PLATE WASHERS
6" CONC. SLAB
15 MIL VAPOR BARRIER
OVER COMP. CRUSHED AGG.
P.T. SILL PLATE OVER
FOAM GASKET
FIBER CEMENT LAP SIDING
WEATHER BARRIER
15/32" PLYWOOD
2x6 STUDS AT 16" O.C.
5" CLOSED CELL SPRAY FOAM INSULATION
5/8" GYP BOARD
PROVIDE 24 GAUGE BY 8"
WIDE STAINLESS STEEL "Z"
FLASHING ACROSS SILL
JOINT WITH CONCRETE
(2) #4 REBAR
CONTINUOUS
CONCRETE
SIDEWALK
NOTE: USE 24" x 24" "L" BARS
AT FOOTINGS AT CORNERS.
MATCH ANGLE OF CORNER.
4" XPS RIGID INSULATION FULL
DEPTH OF THICKENED
FOUNDATION EDGE
#4 EDGE BARS AT 2'-0"
ON CENTER
24"
18"
8"
6'-6" 7'-6" 1'-0"1'-0"
ENGINEERED
TRUSS
VARIES BY MFGR.
1'-0"1'-0"
14'-0"
1'-0"1'-0" 14'-0"
ENGINEERED
TRUSS
ENGINEERED
TRUSS
TR
U
SS
C
" O
.C
1'-0"
TR
U
SS
B
1'-0"
HD
HD
DOWNSPOUT
4X6 HEADER, TYP.
GABLE TRUSS A WITH
VERTICALS AT 16" ON
CENTER
22" X 34" ATTIC
ACCESSES
CONTINUOUS 5 12" X 6"
24F-V8 GLULAM BEAM.
NO CAMBER
1'-0"
1'-0"
DOWNSPOUT
HD
HD
GABLE TRUSS C WITH
VERTICALS AT 16" ON
CENTER
HD
HD2
HD2
STEEL COLUMN IN
CORNER, SEE DETAIL 3
S1
USE 4" ON CENTER
EDGE NAILING AT
THIS WALL
FASTEN ANGLED GLULAM TO
CONTINUOUS GLULAM, USE (4)
SDWH271000G SCREWS 1
S1
S1
6" WALL
S1
VERIFY SIZE AND LOCATION OF
ALL UNDER GROUND UTILITY
CONNECTIONS WITH MOTOR
CARRIER AND ODOT CPM.
6" CONC. SLAB W/ #4
BARS 16" O.C. EA. WAY
A3
S1
COORDINATE CONDUIT
INSTALLATIONS, SEE
DRAWINGS C3 AND E1
TO VMSTO PIT
21'-41 2"4'-51
2"
6'-51 4"
7'-43 4"
25'-10"
6'-11"
6'-11"
13'-10"
PROVIDE #4 REBAR DOWEL PROJECTING
12" ABOVE TOP OF SLAB IN ACCESS WALL
FOR ELECTRICAL GROUND, BAR IS TO BE A
MINIMUM OF 20'-0" LONG AND LAPPED WITH
FOUNDATION REINFORCING. GROUND
SHALL COMPLY WITH ALL ELECTRICAL
CODE REQUIREMENTS
TO OPEN AND
CLOSED SIGN
STEEL COLUMN, SEE DETAIL
TYPICAL WALL FRAMING
TYPICAL WALL SHEATHING
TYPICAL GYPSUM
WALL BOARD
S1
TYPICAL WINDOW
SHUTTER TRACK
TYPICAL WALL SHEATHING
CONTINUOUS WOOD WEDGE FOR
ATTACHMENT, FASTEN SECURELY
TO STEEL COLUMN, TYPICAL
TYPICAL INTERIOR TRIM
STEEL COLUMN,
SEE DETAIL
S1
VERIFY
BOTTOM OF GLULAM BEAM
1/2" DIA. THROUGH BOLT WITH 3"x3" BY
1/4" THICK PLATE WASHER ON TOP
TYP.
1" 4"x2" BY 3/8" THICK PLATE WELDED TO
COLUMN, TYPICAL AT TOP AND BOTTOM
CONCRETE SLAB
SIMPSON 1/2" DIA. BY 8"
LONG GALV. TITEN HD BOLT
TYPICAL
WINDOW
TRIM
TYPICAL VINYL
WINDOW FLAME
HSS 2x2x1
4 STEEL TUBE
TYPICAL FURRED
WALL FRAMING
2" 1"
WEATHER
BARRIER
FLASHING
PER NOTE
STARTER STRIP
1/2" MINIMUM GAP
UNDER SIDING
2"
2"
2"
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
DETAILS S1
8S T R U C T U R A L
J A
N U A R Y 1 3 , 2
0 0
TRUSS A
SCALE: 1/4" = 1'-0"
TYPICAL WALL SHEATHING
USE 15/32" PLYWOOD WITH 8d
NAILS AT 6" O.C. (EXCEPT WHERE
NOTED OTHERWISE) AT EDGES AND
12" O.C. IN THE FIELD
BLOCK ALL EDGES.
ROOF FRAMING PLAN
SCALE: 1/4" = 1'-0"
HD
SYMBOL INDICATES HOLDOWN LOCATION.
PROVIDE MINIMUM DOUBLE STUDS AT HOLDOWN.
INSTALL SIMPSON DTT2Z ANCHOR WITH (8) SDS 1/4 x 2 12
SCREWS. USE SIMPSON GALV. 1/2" DIA.
TITEN BY 8" LONG BOLT INTO CONCRETE.
ATTACH HOLDOWN TO DOUBLE 2x6 STUD LAMINATED WITH 10d NAILS AT 6" ON CENTER
AT HD2 SYMBOL. USE SIMPSON DTT2Z HOLDOWN WITH
(8) SDS1/4x2.5" SCREWS.
DESIGN ENGINEERED TRUSSES
FOR 45 PSF SNOW LOAD, AND 96
MPH EXPOSURE C WIND LOAD.
TRUSSES SHALL BE DESIGNED
FOR A COLLATERAL DEAD LOAD
OF 5 PSF IN ADDITION TO OTHER
LOADS TO ACCOMMODATE
FUTURE SOLAR LOADS.
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
FOUNDATION PLAN
SCALE: 1/4" = 1'-0"
TRUSS B
SCALE: 1/4" = 1'-0"
TRUSS C
SCALE: 1/4" = 1'-0"
COLUMN AT FRAMED WALL
SCALE: 3" = 1'-0"
COLUMN AT WINDOWS
SCALE: 3" = 1'-0"
STEEL COLUMN
SCALE: 3" = 1'-0"
THICKENED SLAB FOUNDATION
SCALE: 3/4" = 1'-0"
S1
S1
S1
S1
S1
NOTE: ALL TRUSSES ARE AT 24" ON CENTER
NOTE: SPRAY FOAM INSULATION IS NOT
SHOWN ON DRAWING S1 FOR CLARITY.
18"
MIN.
COUNTER
CABINET
STANDING SEAM METAL
ROOFING, TYPICAL
2x8 FASCIA, TYP.
CONTINUOUS
PREFINISHED
GUTTER,
TYPICAL
CUSTOMER
WINDOW
ROLL-DOWN
METAL SHUTTER,
TYPICAL
6"
SIMPSON H2.5 CLIP
EA. TRUSS EA.
END, TYPICAL
24" DEEP x 30" HIGH
COUNTER, TYPICAL
4" SPLASH, TYP.
PREFINISHED
DOWNSPOUT,
TYPICAL
38" MAX.
TEXTURE-FACED
VENTED SOFFIT
SHEATHING, TYPICAL 3/4" THICK MDO
PLYWOOD LAMINATE
ENCASED SWINGING
COUNTER
CONTINUOUS
STAINLESS
STEEL PIANO
HINGE
3/4" THICK BY 3" LAMINATE
COVERED COUNTER SUPPORT
1" x 3/4" NOTCH TO SUPPORT
SWINGING COUNTER
R-60 CLOSED CELL FOAM
INSULATION, TYPICAL
ENGINEERED
TRUSS, TYPICAL
FUTURE
TOILET
2x4 STUDS 16" O.C.
SOUND INSULATION
5/8" GYP. BD. EA. SIDE
CONTINUOUS RIDGE
CAP, TYPICAL
TYPICAL FULL DEPTH
BLOCKING BETWEEN
TRUSSES
36"
6"
33" - 36"
FUTURE GRAB BAR
AND FIXTURES,
NOT IN CONTRACT.
4" VINYL COVE BASE, TYPICAL
2'-6"
FRAMED WALL 18" DEEP x 43.25" HIGH
COUNTER ON TOP OF BUILT-IN
CABINET, SEE DETAIL
WINDOW TRIM
15 MIL. VAPOR
BARRIER
2x4 STUDS 16" O.C.
SOUND INSULATION
5/8" GYP. BD. EA. SIDE
TYPICAL EXTERIOR WALL
• FIBER CEMENT LAP SIDING WITH
7" EXPOSURE
• WEATHER BARRIER
• 15/32" PLYWOOD
• 2x6 16" O.C.
• R-35 CLOSED CELL FOAM
• 5/8"GYP BOARDWALL MOUNT
HEATER
VENT THROUGH
WALL
VENT
THROUGH
WALL
WINDOW
BEHIND WALL
DOOR REFERENCE, SEE
DRAWING A1
4" TOE KICK WITH RUBBER
BASE, TYPICAL
WALL MOUNT
HEATER ACCESS WALL,
SEE DETAIL A3
S2
8'-0"
3'-71 4"
GYPSUM BOARD, TYPICAL
RECESSED
ELECTRICAL
PANEL
CUSTOMER WINDOW,
SEE DETAIL
6"
S2
TYPICAL
ENGINEERED
TRUSSES
2x4 STUDS 16" O.C.
SOUND INSULATION
5/8" GYP. BD. EA. SIDE
4'-0"
DATA
RACK
INCINOLET
TOILET
40" 36" 26"
36"
42"12"
40"
18"
TOP OF BAR
GRAB BAR
GRAB BAR
TOILET PAPER
DISPENSER
VENT PIPE
CHASE
THRESHOLD
EXTENDS OVER
FOAM ONTO
CONCRETE
WALK, SEAL ALL
EXPOSED
EDGES, TYPICAL
PANIC
HARDWARE
1'-6"
REMOVABLE
ACCESS
6"
1" 2"
TWO ADJUSTABLE
SHELVES - PLASTIC LAM.
OVER 3/4" PLYWOOD
COUNTER OF (2)
LAYERS OF 3/4" THICK
PARTICLE BOARD
CENTER WINDOW
OVER COUNTER
SANDED AND PAINTED OAK
TRIM ALL AROUND WINDOW
3/8" THICK POLYCARBONATE
WINDOW IN 3/8" BY 1/2"
GROOVE ALL AROUND
PLASTIC LAMINATE SURFACING
AT ALL FACES, TYPICAL
1'-6"
PLASTIC LAM. SWINGING DOORS
WITH CONCEALED HINGES
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
SECTIONS S2
9S T R U C T U R A L
J A
N U A R Y 1 3 , 2
0 0
SECTION 6
SCALE: 1/2" = 1'-0"
S2
SECTION 5
SCALE: 1/2" = 1'-0"
S2
SECTION 4
SCALE: 1/2" = 1'-0"
S2
SECTION 1
SCALE: 1/2" = 1'-0"
S2
SECTION 2
SCALE: 1/2" = 1'-0"
S2
CUSTOMER COUNTER
SCALE: 1" = 1'-0"
S2
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
S
S
S
S
S
A
J
DUPLEX CONVENIENCE OUTLET SPECIFICATION
GRADE GROUNDED TYPE RATED AT 20 AMP, 125
VOLT. COLOR SHALL BE WHITE. PROVIDE WHITE
COLOR PLASTIC COVER.
QUADRAPLEX RECEPTACLE OUTLET
(DOUBLE DUPLEX)
WEATHERPROOF OUTLET RATED AT 20 AMPS,
125 VOLTS. PROVIDE FLUSH DEVICE COVER.
COVER SHALL BE METAL AND SELF-CLOSING
INSTALL AS SHOWN.
SINGLE-POLE SWITCH
SWITCH - DIMMER ON/OFF WITH FULL RANGE
FROM 0% TO 100%. SWITCH SHALL BE RATED
AT 600 WATT, 120 VOLT. PROVIDE WHITE
COLORED PLASTIC COVER PLATE.
SWITCH - OPEN / CLOSED SIGN
TRAFFIC SIGNAL (RED LIGHT / GREEN LIGHT)
CONTROL STATION, INSTALL IN COUNTER TOP.
INSTALL FOOT SWITCH BELOW COUNTER.
THREE-WAY SWITCH
TELEPHONE DATA JACK
CEILING MOUNT CAN LIGHT FIXTURE. SEE
TWIST TIMER SWITCH
CEILING MOUNT LED LIGHT. SEE 15
12EXTERIOR LIGHT. SEE
FUTURE ALARM ABOVE CEILING
(NOT IN CONTRACT)
JUNCTION BOX ABOVE CEILING. INSTALL
REQ'D. WIRING FOR FUTURE ALARM.
LEGEND
240 VOLT INCINOLET MODEL WB 15. TERMINATE POWER AT WALL JUNCTION
BOX FOR FUTURE CONNECTION. PROVIDE COVER PLATE.
WALL MOUNTED, 1000 WATT, 240 VOLT, CADET
MODEL CSC102W.
RECESSED & ADJUSTABLE TYPE WITH WHITE EXTERIOR FINISH. LITHONIA
LIGHTING J6RL D8 09LM 35K 90CRI 120 FRPC WWH IN HOUSING.
WALL MOUNTED, 1000 WATT, 240 VOLT, CADET MODEL CSC102W. MOUNT AS CLOSE
TO FLOOR AS POSSIBLE. COORDINATE LOCATION WITH OTHER UNDER COUNTER
COMPONENTS TO MAINTAIN ALL REQUIRED CLEARANCES.
PIT LIGHTS (VERIFY IF REQUIRED).
TRAFFIC SIGNAL CONTROL (VERIFY IF REQUIRED).
SURFACE MOUNT EXTERIOR DISCONNECT FOR HEAT PUMP.
2" PVC CONDUIT
SWITCH
SWITCH
LIGHTING CONTACTOR
FORCED FAN HEATER
RECESSED CAN LIGHTS
FORCED FAN HEATER
200 AMP ELECTRICAL
SERVICE PANEL
SHUTTER POWER SUPPLY
SURFACE MOUNT LIGHT FIXTURE
SWITCH
2" PVC CONDUIT
EXTERIOR LIGHT
MINI SPLIT DUCTLESS
HEAT PUMP UNIT
THERMOSTAT
SERVER ROOM VENT FAN
OUTLET
EXHAUST FAN
ELECTRICAL NOTES
PANASONIC MODEL FV-0511VK2 WITH MODEL FV-MSVK1
MOTION SENSOR. SET FAN TO 80 CFM. VENT TO EXTERIOR.
DUPLEX CONVENIENCE OUTLET FOR WEIGHT INDICATOR.
0 TO 60 MINUTE TWIST TIMER CONTROL FOR HEATER,
INTERMATIC MODEL FF460M.
LITHONIA LIGHTING TFX1 LED 50K MVOLT YK DDBXD OUTDOOR FLOODLIGHT WITH
YOKE MOUNT. VERIFY POSITION WITH AGENCY PRIOR TO INSTALLATION.
TO VMS LOW VOLTAGE. TERMINATE IN WALL AT 16"x16"x4" METAL JUNCTION BOX ABOVE
FLOOR WITH REMOVABLE METAL COVER PLATE, SEE DRAWING C3.
CONNECT ELECTRIC SERVICE, SEE DRAWING C3. VERIFY CONDUIT SIZE
WITH ELECTRIC UTILITY.
DATA JACK (NUMBER EQUALS
REQUIRED CONNECTIONS)
NO. COMMENTS
TO SCALE PIT, SEE DRAWING C3. TERMINATE IN WALL AT 16"x16"x4" METAL
JUNCTION BOX ABOVE FLOOR WITH REMOVABLE METAL COVER PLATE.
6 FLOODLIGHT - WALL MOUNTED
(4) 2" PVC CONDUITS
(2) PUSH BUTTONS
2" PVC CONDUIT
2 1/2" PVC CONDUIT (MIN.)
(5) 1 1/4" PVC CONDUIT
ITEM
MITSUBISHI INDOOR UNIT SLZ-AF12NL, OUTDOOR UNIT
SUZ-AA12NL 20.3 MINIMUM SEER2, 9.70 HSPF2.
LITHONIA LIGHTING TWX1 LED ALO 40K MVOLT DDBTXD ON PHOTOCELL CONTROL.
TO FUTURE ELECTRIC VEHICLE CHARGE FOUNDATION.
DIMMER.
LITHONIA LIGHTING LBL4 LP840 (CI-254RKH).
PROVIDE POWER SUPPLY JUNCTION BOX FOR EACH WINDOW SHUTTER WITH
CONDUIT RUN BACK TO PANEL, COORDINATE LOCATION.
FLUSH MOUNTED WITH DOOR, 200 AMP MAIN BREAKER WITH SPACE FOR 40 (MIN.)
SINGLE POLE PLUG-IN CIRCUIT BREAKERS.
CIRCUIT BREAKERS SHALL BE DOUBLE POLE OR SINGLE POLE, 10,000 A/C PLUG-IN.
CIRCUIT BREAKERS FOR OUTDOOR OUTLETS SHALL BE GFCI.
ELECTRIC INCINERATING
TOILET SYSTEM
28 DISCONNECT
PROVIDE TWO PUSH BUTTONS. ONE TO CONTROL EACH DOOR ELECTRIC STRIKE. ALL WIRING
SHALL BE CONCEAL IN JUNCTION BOXES AND CONDUIT UNDER COUNTER. BUTTONS SHALL
BE COMMERCIAL GRADE.
PANASONIC MODEL FV-0511VK2, SET FAN TO 80 CFM. VENT TO EXTERIOR.
ACTIVATED BY THERMOSTAT WHEN TEMPERATURE EXCEEDS 75° F.
PROVIDE LIGHTING CONTACTOR FOR EXTERIOR LIGHTING IN SUITABLE ELECTRICAL BOX
RECESSED IN ACCESS WALL. PROVIDE SWINGING ACCESS DOOR.
MOUNT ODOT SUPPLIED SPEAKER ON EXTERIOR WALL, CONNECT TO
RADIO BASE STATION.
29 WALL MOUNT PA SPEAKER
S SWITCH - FLOODLIGHT SINGLE POLE, SPEC.
GRADE, RATED AT 15 AMP, 227 VOLT. COLOR
SHALL BE WHITE INCLUDING COVER PLATE.
MOUNT ON WALL ABOVE COUNTER.
COORDINATE ATTIC ACCESS LOCATION TO AVOID CONFLICT WITH
TRUSSES AND LIGHTS, SEE DRAWING S1.
30 WIRING ACCESS
POWER FOR EAST EXTERIOR LIGHTING AND SPARE. TERMINATE IN WALL AT COMMON
16"x16"x4" METAL JUNCTION BOX 24" ABOVE FLOOR WITH REMOVABLE METAL COVER PLATE.
31 (2) 2" PVC CONDUIT
POWER FOR WEST EXTERIOR LIGHTING AND SPARE. TERMINATE IN WALL AT COMMON
16"x16"x4" METAL JUNCTION BOX 24" ABOVE FLOOR WITH REMOVABLE METAL COVER PLATE.
32 (2) 2" PVC CONDUIT
FOR FUTURE USE. TERMINATE IN WALL AT 10"x10"x4" METAL JUNCTION BOX ABOVE FLOOR
WITH REMOVABLE METAL COVER PLATE AT EACH END.
33 2" PVC CONDUIT
COORDINATE INSTALLATION.34 SCALE CONTROL BOX
PROVIDE DEDICATED CIRCUIT. LOCATE SWITCH ON WALL.35 OPEN/CLOSED CONTROL SWITCH
S OCCUPANCY SENSOR SWITCH - SET TO
REMAIN ON FOR 20 MINUTES AFTER
LAST DETECTED MOVEMENT.
TT
L5-20 TWIST LOCK RECEPTACLE
EXTERIOR SITE LIGHTS.36 SWITCH
TERMINATE ONE END UNDER COUNTER IN 10"x10"x4" METAL JUNCTION BOX ABOVE FLOOR
WITH REMOVABLE METAL COVER PLATE. STUB OPPOSITE END UP IN ACCESS WALL UNDER
DATA RACK.
38 2" PVC CONDUIT
PROVIDE CONDUITS TO EXTERIOR AT WEST WALL GABLE FOR RADIO ANTENNAS LOCATED AT
ROOF. RUN EMT CONDUIT DOWN THROUGH WALL TO BELOW COUNTER ACCESS WALL.
PROVIDE WEATHER TIGHT RUBBER BOOTS AT CONDUIT TERMINATIONS TO SEAL ENDS
AROUND CABLES.
39 2" CONDUIT
TO JUNCTION BOX FOR FUTURE CONCRETE BARRIER MOUNTED LIGHTING.40 1" CONDUIT
NOT USED
TO OPEN AND CLOSED SIGN CONTROLS.
26 2" PVC CONDUIT TO POWER FOR OPEN AND CLOSED SIGN.
EXTERIOR BUILDING LIGHTS.
TO POWER CIRCUITS AT VMS SIGN.
2" PVC CONDUIT42
PROVIDE JUNCTION BOX ON GABLE WALL WITH WEATHER TIGHT FACE PLATE AND
CABLE BOOT / GROMMET FOR CAMERA INSTALLATIONS. PROVIDE 1" EMT CONDUIT IN
ATTIC FROM BOX TO DATA ROOM ACCESS WALL.
GABLE CAMERA ACCESS
43 CEILING MOUNT DATA PORT
CEILING MOUNT DATA PORT PROVIDES CONNECTION FOR WIRELESS ACCESS POINT.
SWITCH
44 TO RED / GREEN BEACON AT VMS SIGN. TERMINATE IN WALL AT 16"x16"x4" METAL
JUNCTION BOX ABOVE FLOOR WITH REMOVABLE METAL COVER PLATE.
2" PVC CONDUIT
SPARES TO EXTERIOR JUNCTION BOX FOR FUTURE USE.
S SWITCH - SUMP PUMP
SCALE WEIGHT INDICATOR (VERIFY)
SURGE SUPPRESSION KIT (VERIFY)
INTERIOR OUTLETS
INTERIOR OUTLETS
INTERIOR OUTLETS
20 AMP
20 AMP
SPARE
GROUND
PER NEC
S/NPANEL WIRING DIAGRAM
20 AMP
15 AMP
15 AMP
15 AMP
20 AMP
20 AMP
20 AMP
20 AMP INTERIOR OUTLETS
120/240 VOLT 1 PHASE
200 AMP SERVICE
200 AMP MAIN BREAKER
(VERIFY) PIT LIGHTS
(VERIFY) TRAFFIC SIGNAL
(RED LIGHT / GREEN LIGHT)
INCINERATING TOILET SYSTEM
EXTERIOR FLOOD LIGHTS
WEATHERPROOF OUTLETS
INTERIOR LIGHTS
EXH. FAN
EXH. FAN
WIRELESS ACCESS POINT
WALL MOUNT HEATER
HEAT PUMP (VERIFY)
OPEN/CLOSED SIGNS
15 AMP
15 AMP
20 AMP
20 AMP
20 AMP
15 AMP
15 AMP
15 AMP
15 AMP
GFCI
20 AMP
15 AMP
20 AMP
20 AMP
15 AMP
15 AMP
WALL MOUNT HEATER
20 AMP
15 AMP
EXTERIOR LIGHTS
OUTLET FOR SCALE CONTROL
EXTERIOR SITE LIGHTING (VERIFY)
L5-20 RECEPTACLE
SPARE
SPARE
SPARE
39SPARE
SPARE
FUTURE ALARM
VMS SIGN OUTLET
VMS SIGN
34 SPARE33SPARE
36 SPARE35SPARE
SPARE
SPARE
FUTURE EV CHARGER {
A
J
2,4
5,7
CENTRALLY LOCATED
CEILING CASSETTE
HEAT PUMP
EXTERIOR WALL
MOUNTED
HEAT PUMP
6,8
ELECTRIC
STRIKE
FUTURE DATA
RACK
ELECTRIC STRIKE
UNLOCK BUTTONS
ELECTRIC
STRIKE
70"
70"
JUNCTION BOX
FOR FUTURE
LENEL
JUNCTION BOX
FOR FUTURE
LENEL
21 21,23
TT
TT
L5
CONDUITS STUB UP THROUGH
SLAB IN ACCESS WALL, TYPICAL
16 16 16
ELECTRIC STRIKE
WP1 11
JUNCTION BOX FOR
FUTURE LENEL
4 4
NOTE: CONDUIT POSITIONS ARE
SCHEMATIC AND MAY BE ADJUSTED IN
THE FIELD TO FIT. COORDINATE WITH
CONSTRUCTION PROJECT MANAGER.
26 2
STUB UP
CONDUIT
IN WALL
STUB UP IN
FRONT OF WALL
15 15
S
20 20 20
S T
S
S
VENT
THROUGH
END WALL
FUTURE DATA
RACK
S
S 13 9
FD
S S 1
S
O S
MANUAL FAN ON /
OFF SWITCH
S 28
S 22
S S
FAN WITH
THERMOSTAT
VENT
THROUGH
END WALL
OCS 35
TYPICAL
ELECTRICAL
NOTE NUMBER
TYPICAL PANEL
CIRCUIT NUMBER
TH
IS
D R
AW
IN
G
IS
R
ED
U C
ED
IF
B O
R D
ER
IS
N O
T
/2
" x
2"
F5340202
ODOT NORTH PLAINS SCALE HOUSE
REPLACEMENT
US HIGHWAY 26, MILE POST 54.10, CORNELIUS, OR 97113 10
08/18/26
FRANCO
JON DOUGHTON
ELECTRICAL PLAN E1
REDUCED 50%
WHEN PRINTED
AT 11" x 17"
ELECTRICAL PLAN
SCALE: 1/2" = 1'-0"
LIGHTING & SWITCHES
SCALE: 1/2" = 1'-0"
1. COORDINATE ALL ELECTRICAL AND RELATED WORK REQUIREMENTS WITH
ODOT CONSTRUCTION PROJECT MANAGER, ODOT MOTOR CARRIER STAFF
AND ODOT ELECTRICIANS PRIOR TO PERFORMING ANY WORK. FIELD
VERIFICATION AND ADJUSTMENT WILL BE REQUIRED.
2. POWER SERVICE TO BUILDING IS TO BE PROVIDED IN ACCESS WALL.
CONNECT TO EXTERIOR MOUNTED METER BASE AND TO INTERIOR
ELECTRIC PANEL. ALSO SEE DRAWING C3.
3. PLANS SHOW APPROXIMATE LOCATIONS OF IN GROUND COMPONENTS AND
JUNCTIONS BOXES. ACTUAL LOCATIONS SHALL BE VERIFIED AND
APPROVED BY CPM PRIOR TO CONSTRUCTION.
4. PLAN SHOWS ITEMS TO BE INCLUDED IN THE WORK. LOCATIONS OF
SWITCHES AND COMPONENTS MAY NEED TO BE ADJUSTED. VERIFY PRIOR
TO PERFORMING WORK.
5. WALL SWITCHES LOCATED ABOVE OPERATOR'S COUNTER WILL BE LOCATED
IN THE FIELD, VERIFY PRIOR TO INSTALLING.
6. COORDINATE CONNECTIONS TO NEW AND EXISTING SITE UTILITIES. SEE
DRAWING C2 AND C3 FOR ADDITIONAL SITE INFORMATION.
7. CONVENIENCE OUTLETS ARE TO BE LOCATED AT 12” ABOVE FINISH FLOOR
UNLESS OTHERWISE NOTED.
8. COORDINATE INCINOLET ELECTRIC TOILET ELECTRICAL POWER SUPPLY
AND INSTALLATION.
9. STUB CONDUIT UP IN ACCESS WALLS. CONNECT TO JUNCTION BOXES OR
PANELS AS REQUIRED.
10. PROVIDE A 4"x4"x4" WALL BOX WITH MUD RING FOR DATA JACKS AT 18"
ABOVE FINISH FLOOR UNLESS NOTED OTHERWISE. CONFIRM LOCATION
WITH CPM. PROVIDE 1" CONDUIT FROM WALL BOX TO ATTIC. USE FLEX DUCT
IN ATTIC TO DATA RACK LOCATION IN CORNER OF BUILDING. DATA CABLING
AND FACE PLATES ARE BY OTHERS.
11. PROVIDE POWER FOR WIRELESS ACCESS POINT BY OTHERS. VERIFY
POSITION IN THE FIELD.
12. ALL ELECTRICAL CONDUCTORS ARE TO BE COPPER. ALUMINUM IS NOT
ALLOWED.
13. ELECTRICAL SERVICE SHALL BE 200 AMP.
14. VERIFY LOCATION OF ALL UNDERGROUND CONDUIT. SEE DRAWINGS C2 AND
C3.
15. VERIFY EXISTING EXTERIOR SITE LIGHTING VOLTAGE AND LOAD
REQUIREMENTS.
16. TIE EXTERIOR SITE LIGHTING AND EXTERIOR BUILDING LIGHTS TO
PHOTOCELL CONTROLS. PROVIDE MANUAL OVERRIDE SWITCH INSIDE
BUILDING.
17. PROVIDE (2) CONDUITS AT EACH EXTERIOR DOOR, ONE FROM ELECTRIC
STRIKE AND ONE FROM WALL JUNCTION BOX FOR EXTERIOR CARDS
READER. RUN CONDUITS TO WALL WHERE DATA RACK IS LOCATED FOR
FUTURE LENEL CONNECTION. COORDINATE SPECIFIC LOCATION WITH CPM.
18. VERIFY FINAL POSITION OF ALL SWITCHES WITH CPM.
19. PROVIDE FINISH PLATES AND COVERS FOR ALL WALL PENETRATIONS.
20. THE ENTIRE WALL BEHIND DATA RACK SHALL BE COVERED WITH 3/4" THICK
FIRE RATED PLYWOOD.
21. CONNECT ALL EXISTING SITE UTILITIES TO NEW BUILDING.
22. PROVIDE PRINTED LABELS ON ALL SWITCH AND RECEPTACLE COVER
PLATES SHOWING PANEL CIRCUIT NUMBER. LABEL PANEL TO MATCH.
23. PROVIDE PRINTED LABELS ON ALL SWITCH COVER PLATES SHOWING
CONNECTED LOAD.
24. PROVIDE SEPARATE CONDUITS AND JUNCTION BOXES FOR LOW AND HIGH
VOLTAGE.
25. PROVIDE BUSHINGS AT ALL CONDUIT TERMINATIONS.
26. FASTEN CONTROL BOXES TO COUNTER AS DIRECTED.
27. COORDINATE RADIO ANTENNA MOUNTING STYLES AND LOCATIONS WITH
CPM. PROVIDE WEATHER TIGHT BOOTS WHERE PENETRATIONS ARE USED.
GENERAL ELECTRICAL NOTES
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN 08.18.26.pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN C1 (1).pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN C2 (1).pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN C3 (1).pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN C4 (1).pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN A1 (1).pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN A2 (1).pdf |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN 08.18.26 |
| F5340202 - 02_NORTH PLAINS NEW SCALE HOUSE_PLAN A3 (1).pdf |