This document provides the results of maintenance, inspection, and testing services performed on the electrical power distribution system at a Department of Veterans Affairs medical center. Key details include inspection and testing of medium voltage circuit breakers, station batteries, transformers, and protective relays serving the facility. The services ensured the continued safe and reliable operation of equipment, including circuit breakers, batteries, transformers, and protective relays for the main switchgear and various building feeders. Test results found most equipment suitable for continued use, though some relays required rewiring and one battery replacement should be considered due to age.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Wage Determination 2015-4047 Rev 24 Dated 6.30.2023.pdf | ||
| LOS Certification.pdf | ||
| Past Performance Worksheet.xlsx | XLSX spreadsheet | |
| 36C24123Q0921.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEDIUM VOLTAGE CIRCUIT BREAKER TEST REPORT
Customer: VABHS Jamaica Plain Job#: 19366
Location: NStar Station 304-1 Date: 9/8/2020
Switchgear: Utility 13.8kV Compartment: Main 1 Line 304-1440H
Manufacturer: Cutler-Hammer Volts: Max.15kV
Type: 150VCP-W750 Amps: 1200
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 5051530 Chrge/Clse/Trip: All 120DC Volts
Oper.mech.: ML Air/OilNac.: Vacuum
VISUAL AND MECHANICAL INSPECTION
1.Cubicle OK 9.Arc contacts
2.Shutter mechanism OK 1a.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic. connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 184 / 188
(WL-34854L)
Inspection comments
ELECTRICAL TESTS
pole A pole B poleC
Contact Resist. - micro-ohms (found/left) 43 54 43
Insulation Resistance: Phase to Ground
Megaohms @ 5 kVDC Across Contact
>515000 >515000 >515000
Overpot.test - microAmps@ 37.5 kVDC 7 13 8
Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.3 0.3
Contact gap/wipe - inches (Vac.bottle) OK OK OK lnsul. Resist. Contr.Wiring- MegaOhms@ 250VDC: OK
Comments:
Test results suggest the circuit breaker is suitable for service.
Customer: VABHS Jamaica Plain Job#: 19366
Location: NStar Station 304-1 Date: 9/8/2020
Switchgear: Utility 13.SkV Compartment: Main 2 Line 304-1511
Manufacturer: Cutler-Hammer Volts: Max. 15kV
Type: 150VCP-W750 Amps: 1200
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 5051529 Chrge/Clse/Trip: All 120DC Volts
1.Cubicle
OK 9.Arc contacts
2.Shutter mechanism OK 1a.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic. connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 199 / 203
Contact Resist. - micro-ohms (found/left) 49 50 47
Insulation Resistance: Phase to Ground
Megaohms @ 5 kVDC Across Contact
Overpot.test - microAmps@ 37.5 kVDC 9 10 9
Overpot.test Vac.bottle - microAmps@ 40 kVDC 1.4 1.2 0.1 lnsul. Resist. Contr.Wiring- MegaOhms @250VDC: OK
Customer: Electrical Job#: 19366
Location: VAMC JP - NStar Station 304-1 Date: 3/15/2020
Switchgear: Utility 13.SkV Compartment: 6A- Feeder A
Manufacturer: Cutler-Hammer Volts: Max.15kV
Type: 150VCP-W750 Amps: 1200
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 05051533 Chrge/Clse/Trip: All 120DC Volts
OK 9.Arc contacts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK a.Main contacts Bottles OK 16.Counter found/left 40/ 43
Contact Resist. - micro-ohms (found/left) 41 47 45
Insulation Resistance: Phase to Ground
Megaohms@ 5kVDC Across Contact
2,800,000 3,750,000 3,150,000
>5,000,000 >5,000,000 >5,000,000
Overpot.test - microAmps@ 37.5 kVDC 0.4 0.5 1
Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.5 0.4 2
Location: VAMC JP - NStar Station 304-1 Date: 2/16/2020
Switchgear: Utility 13.SkV Compartment: 68 Feeder C
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 05051515 Chrge/Clse/Trip: All 120DC Volts
OK 9.Arc contacts
2.Shutter mechanism OK 1a.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 26 / 29
Contact Resist. - micro-ohms (found/left) 41 40 43
Insulation Resistance: Phase to Ground
Megaohms@ 5 kVDC Across Contact
Overpot.test - microAmps @ 37.5 kVDC 10 5 3
Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.8 0.3 0.1
Location: VAMC JP - NStar Station 304-1 Date: 3/15/2020
Switchgear: Utility 13.8kV Compartment: 7A - Feeder B
Manufacturer: Cutler-Hammer Volts: Max. 15kV
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 5051539 Chrge/Clse/Trip: All 120DC Volts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK a.Main contacts Bottles OK 16.Counter found/left 84/ 88
Contact Resist. - micro-ohms (found/left) 41 46 49
Insulation Resistance: Phase to Ground
Megaohms@ 5kVDC Across Contact
Overpot.test - microAmps @ 37.5 kVDC 10 6 8
Overpot.test Vac.bottle - microAmps@ 40 kVDC 7 8 11
Location: VAMC JP - NStar Station 304-1 Date: 2/16/2020
Switchgear: Utility 13.SkV Compartment: 8A - Feeder E - Emerg. 1
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 05051537 Chrge/Clse/Trip: All 120DC Volts
OK 9.Arc contacts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 289 / 292
Contact Resist. - micro-ohms (found/left) 45 46 41
Insulation Resistance: Phase to Ground
Megaohms@ 5kVDC Across Contact
Overpot.test - microAmps @ 37.5 kVDC 8 6 11
Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.3 0.1
Location: VAMC JP - NStar Station 304-1 Date: 4/25/2020
Switchgear: Utility 13.8kV Compartment: 88 - Feeder G
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 5051532 Chrge/Clse/Trip: All 120DC Volts
OK 9.Arc contacts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 36 / 40
Contact Resist. - micro-ohms (found/left) 35 34 32
Insulation Resistance: Phase to Ground
Megaohms@ 5 kVDC Across Contact
Overpot.test - microAmps @ 37.5 kVDC 9 2.8 4.5
Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.1 0.1
Location: VAMC JP - NStar Station 304-1 Date: 2/16/.2020
Switchgear: Utility 13.BkV Compartment: 9A - Feeder F - Emerg. 4
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 05051535 Chrge/Clse/Trip: All 120DC Volts
OK 9.Arc contacts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 48 / 52
Contact Resist. - micro-ohms (found/left) 37 41 35
Insulation Resistance: Phase to Ground
Megaohms@ 5 kVDC Across Contact
Overpot.test - microAmps @ 37.5 kVDC 10 5 5
Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.3 0.1
Location: VAMC JP - NStar Station 304-1 Date: 2/4/2020
Switchgear: Utility 13.SkV Compartment: 98 -Spare
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 05051531 Chrge/Clse/Trip: All 120DC Volts
OK 9.Arc contacts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Mechanic. connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
7.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 37 / 41
Contact Resist. - micro-ohms (found/left) 35 34 34
Insulation Resistance: Phase to Ground
Megaohms@ 5kVDC Across Contact
3,150,000 3,275,000 3,570,000
Overpot.test - microAmps@ 37.5 kVDC 12 9 8
Overpot.test Vac.bottle - microAmps @ 40 kVDC 0.5 0.1 0.1
Switchgear: Utility 13.SkV Compartment: 10A- Spare
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 140802246 Chrge/Clse/Trip: All 120DC Volts
2.Shutter mechanism OK 10.Control wiring OK
3.Racking Device OK 11.Pnl.indic.lights OK
4.Meehanic.connections OK 12.Heaters OK
5.Bushings 13.Ground connect. OK
6.Finger clusters or stabs OK 14.Manual close/trip OK
?.Arc chutes 15.Elect.close/trip OK
8.Main contacts Bottles OK 16.Counter found/left 103/106
{WL-34854L)
Contact Resist. - micro-ohms (found/left) 40 35 36
Insulation Resistance: Phase to Ground
Megaohms@ SkVDC Across Contact
2,750,000 3,550,000 3,950,000
Overpot.test - microAmps@ 37.5 kVDC 7 8 5
Overpot.test Vac.bottle - microAmps@ 40 kVDC 1.1 0.3 0.4
Switchgear: Utility 13.SkV Compartment: 11A - Spare
Wiring Diag.: 691C386H44 Style: 3776A23662
Serial#: 140601475 Chrge/Clseffrip: All 120DC Volts
2.Shutter mechanism
OK
OK
9.Arc contacts
10.Control wiring
OK
3.Racking Device OK 11.Pnl.indic.lights
4.Mechanic.connections OK 12.Heaters
5.Bushings 13.Ground connect.
6.Finger clusters or stabs OK 14.Manual close/trip
7.Arc chutes 15.Elect.close/trip a.Main contacts Bottles OK 16.Counter found/left
75/79
Contact Resist. - micro-ohms (found/left) 37 38 35
Insulation Resistance: Phase to Ground
Megaohms@ 5kVDC Across Contact
3,750,000 2,890,000 2,100,000
Overpot.test - microAmps@ 37.5 kVDC 9 21 25
Overpot.test Vac.bottle - microAmps @ 40 kVDC 0.1 0.5 0.1
ELECTRICAL ENGINEERING & SERVICE CO., INC.
289 Centre St., Holbrook, MA 02343
PROTECTIVE RELAY TEST REPORT Job: 19366
Date: 9/9/2020
Customer:
Location: VA Jamaica Plain
Substation: Main 5kV Switchgear
Circuit ID: Busss Differential Relay
Manuf.& type Basler - BE1-87B
Namepl.Data V Unit: 50-400V, OC Unit: 0.25-2.50A, Alarm: 10-80%
Instruct.book 9282300990 Catalog: BE1-87B-G5BA1YN0N0F
C.T. ratio: ..,..,,..,...,......"""'"= P.T.ratio: N/A Device: 87B
Serial#: H00505459 REV N found/left
VISUAL INSPECTION & MAINTENANCE
--X--
Trip circ. -------
TEST RESULTS
V= Volts
S=Second as found as left (same as found, unless noted)
Phase A Phase B Phase C Phase A Phase B Phase C
Zero Set: N/A N/A N/A
Alarm 26.4V 26.0V 26.3V
Alarm Delay 2.25s 2.32s 2.34s (timed from O to 30V)
Voltage 101V 101V 101V
Time Volt. 6.3ms 6.3ms 6.3ms (timed from O to 120V)
Current P.U. 0.76A 0.76A 0.76A
Time Current 6.7ms 6.7ms 6.7ms (timed from O to 0.80A)
Target OK OK OK
Comments: Test results suggest the relay is suitable for service armco acis1 14n inuse
Overcurrent contacs 19-20 not in use form prot_re_t _
Refer.# Contact numbering left to right bottom and top (Front view)
19366R- 87B Tested By: RP _
SETTINGS Phase
Alarm 50%
Voltage 50V
Current 0.75A
Cover OK Disc gap Glass cln'd. X Taps tight
Spiral spring --- Moisture None Relay cln'd. X Connect.tght
Bearing --- Foreign mat -N-o-ne- Contact cln'd. --- lnsul.resist.
Manuf.& type ABB CR-9
Namepl.Data 4-12amp, 120V Dir.[208v N.]
Instr.book: 41-131 Catalog: 1875592 /1875586
Device: 67 (Found/Left)
Cover ok Disc gap ok Glass cln'd. X Taps tight X Trip circ. n/a
Spiral spring ok Moisture no Relay cln'd. X Connect.tght X
Bearing ok Foreign mat no Contact cln'd. X lnsul.resist. ok
A=Amp, V=Volts as found as left (same as found, unless noted)
S=Second A B C N Test point A Phase Phase B Phase C Neut./Grd.
Pickup 4A 3.99A 3.99A 4.01A 4A
Time@200% 5.59s 5.56s 5.56s 5.68s BA
Time@400% 1.34s 1.38s 1.33s 1.35s 16A
Time@600% 0.79s 0.83s 0.81s 0.83s 24A
Dir. Unit MTA V lag-28.5° V lag-32° V lag-32.5° V Lead 60° @ 120V
!CS Pickup 0.17A 0.18A 0.18A 0.18A 0.2A
58[-122] 55[-120] 146{-30]
Comments: Relay test and inspection results suggest they are suitable for continued service form prot_re/ exc
SETTINGS Relay 1 Relay 2
Tap 4a
Time Dial 4 lnstan.P.U. n/a
ICS tap 0.2
Manuf.& type ABB CP
Namepl.Data 120V reverse phase
Instr.book: 41-222 Catalog: 289B415A09 Device: 27C --------
(Found/Left)
Cover ok Disc gap ok Glass cln'd. X Taps tight X Trip circ. n/a
Spiral spring ok Moisture no Relay cln'd. X Connect.tght X
S=Second 304-1511 304-1440H Test point A Phase Phase B Phase C Neut./Grd.
Pickup 111V 109V
Drop Out 79V 82V
Time 95V to O 1.65s 1.62s
Time 95V to 150 1.14s 1.26s
PH Reversal OK ok
304-1511 _glass case is cracked form prot_rel exc
Volt Range 80-110V
Time Dial n/a
ICS tap n/a
Manuf.& type Basler BE1-25
Namepl.Data Sync-Check
Instr.book: 1702-990
Device: 25
120V
Catalog: M1E-A6P-N5R0F
(Found/Left)
Trip circ. n/a
S=Second 304-1511 304-1440H Test point A Phase Phase B Phase C Neut./Grd.
Angle Difference +/-14 ° +/-15 °
Voltage Diff. +/-20V *+/-20V
Dead Bus 60V 59V
Live Bus 94V 94V
Dead Line 60V 59V
Live Line 95V 94V
Sync Time 8.83s 8.84s
*Delta V light does not work on 304-1440H relay
SETTINGS
Phase Angle
Time Delay
Relay 1
15°
9s
Relay 2
Cover
Spiral spring ok ok
Disc gap
Moisture ok no
Glass cln'd.
Relay cln'd.
X
X
Taps tight
Connect.tght
X
Bearing ok Foreign mat no Contact cln'd X Insul.resist. ok
Manuf.& type ABB CR-9
NamepI.Data 4-12amp, 120V Dir.[208v N.]
Instr.book: 41-131 Catalog: 1875592 /1875586
Device: 67 (Found/Left)
Cover
Spiral spring ok ok
Disc gap
Moisture ok no
Glass cln'd.
Relay cln'd.
X
X
Taps tight
Connect.tght
X
Trip circ. n/a
A=Amp, V=Volts
S=Second as found as left (same as found, unless noted)
A B C N Test point A Phase Phase B Phase C Neut./Grd.
Pickup 3.99A 3.99A 4.0A 3.99A 4A
Time@200% 5.52s 5.52s 5.54s 5.55s BA 6.3s
Time@400% 1.31s 1.31s 1.32s 1.31s 16A
Time@600% 0.79s 0.80s 0.80s 0.72s 24A
Dir. Unit MTA V lag-32.5° V lag-31.5° V lag-32° V lead 58.5° @ 120V
ICS Pickup 0.17A 0.18A 0.18A 0.18A 0.2A
57L-1ZZI 57[-120] 57[-121] 148[-31}
Tap 4a
Time Dial 4
ICS tap 0.2
Substation: Main 5kV Switchgear
Date: 2/16/2019
Circuit ID:
Fe ed er C ------------
Manuf.& type Cutler-Hammer FP5200-00
Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA
Instruct.book IL17569C Style: 66D2041G11
C.T. ratio: 150/5 P.T.ratio: 120/1----=D=-e-v-=-ic_e_: 50/51
Cover OK Disc gap NIA
Spiral spring N/A Moisture NONE
Bearing N/A =oreign mat NONE
VISUAL INSPECTION & MAINTENANCE
Glass cln'd. N/A Taps tight yes
Relay cln'd. yes Connect.tght yes
Contact cln'd. les lnsul.resist. N/A
Trip circ. -----
V = Volts
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 4.00A 4.00A 4.00A 0.75A
LT Delay@2X 17.53s 17.48s 17.57s 0.401s
LT Delay@3X 7.85s 7.79s 7.82s 0.270s
Inst. PU 17.6A 17.7A 17.5A 10.1A form prot rel
Refer.# 19366R- C Tested By: --R-P--
SETTINGS A Phase B Phase C phase Ground
LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A .15xln=0.75A
LT Delay 1 1 1 0.1
LT Curve I2T I2T I2T Mod.Inv.
Inst. PU 3.5xln=17.5A 3.5xln=17.SA 3.5xln=17.5A 2.0xln=10.0A
Substation: Main 5kV Switchgear
PROTECTIVE RELAY TEST REPORT
Job: 19366
Circuit ID: Feeder D
Manuf.& type Cutler-Hammer FP5200-00
Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA
Instruct.book "'IL17569C Style: 66D2041G11
C.T. ratio: 150/5 P.T.ratio: .........120/f]i----D-e-v-ic_e_: 50/51
Cover OK Disc gap N/A
Bearing NIA =oreign mat NONE
VISUAL INSPECTION & MAINTENANCE
Glass cln'd. N/A Taps tight yes
Contact cln'd. yes lnsul.resist. N/A
Trip circ. --O-K--
S = Second
As Found As Left (sames as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 4.00A 4.01A 4.00A 0.76A
LT Delay@2X 17.53s 17.48s 17.57s 0.406s
LT Delay@3X 7.82s 7.80s 7.85s 0.263s
Inst. PU 17.6A 17.6A 17.6A 10.1A
Comments: Test results suggest the relay is suitable for service.
form prot_rel
Refer.# 19366R- D Tested By: --R-P--
SETTINGS A Phase B t-'nase c phase Ground
LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A 0.15xln=0.75A
LT Delay 1 1 1 0.1
Inst. PU 3.5xln=17.5A 3.5xln=17.5A 3.5xln=17.5A 2.0xln=10.0A
Date: 3/15/2020
Customer: .Piquette.&.Howard
Substation: .Main.5kV.switchgear
Circuit ID: .Feeder A.-..Building.1. ..Normal..(2)
Manuf.& type .cutler-Hammer.FP5200-00
Namepl.Data .Power.Supply:.48-1.25VDC,..1.00-120VAC,.20VA
C.T. ratio: ·······3001s······· P.T.ratio: ...."fiolf....A.........Devlce·:.... 50/51
Cover ..........9.. .......... Disc gap ..........ty/........... Glass cln'd............t:'.Y ........... Taps tight .............Y
Trip circ. OK
Spiral spring ..........!' !. ......... Moisture .....9.....ty. ·······
Bearing .......... !..........:oreign mat ....... .9.. . ·······
Relay cln'd............Y.. ........... connect.tght .............Y Contact cln'd. ...........Y.. ........... Insul.resist. .......... }'. !
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 10.0A 10.0A 10.1A 0.50A
LT Delay@ 1.5X 2.44s 2.44s 2.45s 0.682s
LT Delay@2X 1.07s 1.06s 1.07s 0.399s
Inst. PU 52A 52A 53A 10.0A
Comments: Test results sugg_est the relay is not suitable for service output 1 Relay defective.
Relay OUTPUT Rewired by EESCO - now okay
All pick up and test points tested on Alarm output form [)_rot rel
Refer.# 19366R- A Tested By: ..............RP
SETTINGS A Phase B Phase C phase Ground
LT Pick Up 2.0xln=10A 2.0xln=10A 2.0xln=10A 0.1xln=0.50A
LT Delay 0.15 0.15 0.15 0.1
LT Curve V. Inv. V. Inv. V. Inv. Mod.Inv.
Inst. PU 10.4xln=52.0A 10.4xln=52.0A 10.4xln=52.0A 2.0xln=10.0A
Substation: Main 5kV Switchgear
Circuit ID: Feeder B - Building I Normal (3)
Manuf.& type Cutler-Hammer FP5200-00
Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA Instruct.book IL 17569C Style: 66D2041G11
C.T. ratio: ..............'a'o·o1s·............. P.T.ratio: ........'1"2·0Tf" ---=D e-v.,...ic_e_: 50/51
Bearing N/A =oreign mat NONE
VISUAL INSPECTION & MAINTENANCE
Glass cln'd. N/A Taps tight yes
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 4.00A 4.01A 4.00A 0.50A
LT Delay@ 1.5X 2.43s 2.45s 2.44s 0.678s
LT Delay@2X 2.43s 2.45s 2.44s 0.404s
Inst. PU 52A 52A 53A 10.0A
To monitor output apply 24VDC from Omicron and monitor in Binary IN 1 of Omicron, Connect a resistor across binary input of Omicron to drop voltage form prot_rel
Refer.# 19366R- B Tested By: --R-P--
SETTINGS A Phase B Phase C phase Ground
LT Pick Up 2.0xln=10A 2.0xln=10A 2.0xln=10A 0.1xln=0.50A
LT Delay 0.15 0.15 0.15 0.1
LT Curve V. Inv. V. Inv. V. Inv. Mod.Inv.
Inst. PU 10.4xln=52.0A 10.4xln=52.0A 10.4xln=52.0A 2.0xln=10.0A
0evice:
Substation: Main 5kV Switchgear
Circuit ID: Feeder C - ACA Building Left
Manuf.& type Cutler-Hammer FP5200-00
Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA
C.T. ratio: 150/5 P.T.ratio: .........1.20/16 .................... 50/51
Glass cln'd. N/A
Taps tight yes Trip circ. -----
Bearing N/A =oreign mat NONE
Relay cln'd. yes
Contact cln'd. yes
Connect.tght yes lnsul.resist. N/A
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 4.00A 4.00A 4.00A 0.75A
LT Delay@2X 17.53s 17.48s 17.57s 0.401s
LT Delay@3X 7.85s 7.79s 7.82s 0.270s
Inst. PU 17.6A 17.7A 17.5A 10.1A
LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A I0.15xln=0.75A
LT Delay 1 1 1 0.1
Inst. PU 3.5xln=17.5A 3.5xln=17.SA 3.5xln=17.SA 2.0xln=10.0A
Substation: Main 5kV Switchgear
Circuit ID: Feeder D - ACA Building Right
Manuf.& type Cutler-Hammer FP5200-00
Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA
C.T. ratio: 150/5 P.T.ratio: 120/1 21....----=D=-e-v.,...ic-e:- 50/51
Cover OK Disc gap NIA
Bearing N/A =oreign mat NONE
VISUAL INSPECTION & MAINTENANCE
Glass cln'd. N/A Taps tight yes
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 4.00A 4.01A 4.00A 0.76A
LT Delay@2X 17.53s 17.48s 17.57s 0.406s
LT Delay@3X 7.82s 7.80s 7.85s 0.263s
Inst. PU 17.6A 17.6A 17.6A 10.1A
LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A 0.15xln=0.75A
LT Delay 1 1 1 0.1
Inst. PU 3.Sxln=17.SA 3.Sxln=17.SA 3.Sxln=17 .SA 2.0xln=10.0A
2/16/2019
Customer: ..Piquette.&..Howard
Substation: .Main._5kV_ Switchgear
Circuit ID: .Feeder.E..-.Emergencv.1
Manuf.& type .Cutler-Hammer .FP5200-00
Namepl.Data_Power.Supply:..48-125VOC,..100-1_20VAC,..20VA
C.T. ratio: ........1.50/5....... P.T.ratio: ....f2off·A...........bev1ce:... 50/51
Cover ...........9.!5.......... Disc gap .......... !
Spiral spring .......... / .......... Moisture ....J 9
Bearing ........... !..........:oreign mat .... ) 9
VISUAL INSPECTION & MAINTENANCE
Glass cln'd..........} !. .......... Taps tight ............ ¥ Relay cln'd............¥. ............ Connect.tght ............ ¥
Contact cln'd. ...........¥.. . ........... lnsul.resist. ............. !
Trip circ...................O....K
V=Volts as found as left (same as found, unless noted)
S=Second A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 6.00A 6.00A 6.00A 0.76A
LT Delay@2X 0.652s 0.658s 0.655s 0.399s
LT Delay@3X 0.290s 0.291s 0.287s 0.264s
Inst. PU 35.0A 35.1A 35.1A 7.50A
Comments: Relay output contact 1 did not operate. All timing tests performed on the Alarm contact.
form p_rot rel
Date:
LT Pick Up 1.2xln=6A 1.2xln=6A 1.2xln=6A 0.15xln=O.75A
LT Delay 0.09 0.09 0.09 0.1
LT Curve V. Inverse V. Inverse V. Inverse Mod.Inv.
Inst. PU 7.0xln=35A 7.0xln=35A 7.0xln=35A 1.5xln=7.5A
Date: 4/25/2020
Substation: Main 5kV Switchgear
Circuit ID: Feeder L - Boiler Plant
Manuf.& type Cutler-Hammer FP5200-00
Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA
C.T. ratio: 150/5 P.T.ratio: 120/1 il·---0-e-v-ic_e_: 50/51
Glass cln'd. N/A Taps tight yes
Bearing N/A :oreign mat NONE
Contact cln'd. yes lnsul.resist. NIA
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 5.50A 5.50A 5.50A 0.50A
LT Delay@ 1.SX 1.48s 1.48s 1.49s 0.670s
LT Delay@2X 0.650s 0.655s 0.653s 0.401s
Inst. PU 35A 35A 35A 7.5A
To monitor output apply 24VDC from Omicron and monitor in Binary IN 1 of Omicron, Connect a resistor across binary input of Omicron to drop voltage form e_rot rel
Refer.# 19366R- L Tested By: --R-P--
LT Pick Up 1.1xln=5.5A 1.1xln=S.SA 1.1xln=5.5A 0.1xln=0.50A
LT Delay 0.09 0.09 0.09 0.1
LT Curve Very Inv. Very Inv. Very Inv. Mod.Inv.
Inst. PU 7xln=35A 7xln=35A 7xln=35A 1.5xln=7.SA fs·ois····
Customer: .Piquette.&..Howard
Location: ..V....A.....J...a...m.....a...i..c...a.....P....l..a...i.n Substation: Main 5kV Switchgear
Circuit ID: .Feeder.F.-..Emergency.4
Manuf.& type .cutler-Hammer.FP5200-00
Namepl.Data . Power .Supply:.48-1.25VDC,. 100-1.20VAC,. 20VA
C.T. ratio.:....... P.T.ratio: ....1.2°0/1..'d..........bev'i'ce·:... 50/51
Cover ..........2. .......... Disc gap .......... !
Glass cln'd.......!.................. Taps tight .............¥. ............. Trip circ
Spiral spring .......... !. .......... Moisture ...... 2 Bearing ...... NIA ...... oreign mat NONE
Relay cln'd............¥.. .............connect.tght .............Y
Contact cln'd. ............¥.. . ............ lnsul.resist. ............. !
V= Volts as found as left (same as found, unless noted)
S=Second A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 6.00A 6.01A 6.01A 0.75A
LT Delay@2X 0.652s 0.650s 0.655s 0.408s
LT Delay@ 3X 0.291s 0.290s 0.292s 0.268s
Inst. PU 35.3A 35.1A 35.2A 7.52A
Comments: Relay output contact 1 did not operate. All timing tests performed on the Alarm contact.
form prot rel
Refer.# 19366R- F Tested By: ................R....P
LT Pick Up 1.2xln=6A 1.2xln=6A 1.2xln=6A 0.15xln=0.75A
LT Delay 0.09 0.06 0.09 0.1
LT Curve V. Inverse V. Inverse V. Inverse Mod.Inv.
Inst. PU 7.0xln=35A 7.0xln=35A 7.0xln=35A 1.5xln=7.5A
1.sols·.·.····
Date: 4/25/2020
Customer: .Piquette..&.Howard
Substation: Main 5kV Switchgear
Circuit ID: .Feeder.G.:. Research..Building
Manuf.& type .Cutler-Hammer.FP5200-00
Namepl.Data ..Power..Supply:. 48-125VDC, ..100-120VAC,.20VA
C.T. ratio: ........ P.T.ratio.:....f20T-f"Zr·········oevfce:... 50/51
Glass cln'd......!................. Taps tight .............Y
Trip cir..c...............oK
Spiral spring ··········NiA·········· Moisture ·······N·6r:iif···· Bearing··········NiA········..:oreign mat .......No" .i"if
Relay cln'd............Y.. ............ Connect.tght .............Y Contactcln'd. ...........Y.. . ........... lnsul.resist. ............. /
V =Volts
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 5.00A 5.00A 5.00A 0.60A
LT Delay@ 1.5X 6.79s 6.80s 6.80s 0.665s
LT Delay@2X 2.86s 2.86s 2.86s 0.398s
Inst. PU * * * 10.0A
Comments: Relay is not suitable for service - relay trip output does not operate- Now Okay.
All timing tests performed through the alarm contact.
* Instantaneous pick-up too high for testing (70A) Relay OUTPUT Rewired by EESCO - now okay form E_rot rel
Refer.# 19366R- G Tested By: ................RP
LT Pick Up 1.0xln=5A 1.0xln=5A 1.0xln=5A 0.12xln=0.60A
LT Delay 0.30 0.30 0.30 0.1
LT Curve Ext. Inv. Ext. Inv. Ext. Inv. Mod.Inv.
Inst. PU 14xln=70A 14xln=70A 14xln=70A 2.0xln=10.0A
Style: 66D2041G11
PROTECTIVE RELAY TEST REPORT Job: ..........1...9....3...6...6
Location:
Substation:
Circuit ID:
Manuf.& type Namepl.Data
.Piquette_&_ Howard VA Jamaica Plain
.Main.5kV .switchgear
.spare.98 Cutler-Hammer FP5200-00
. Power.Supply:.48-1.25VDC,..1.00-120VAC,.20VA
Instruct.book
C.T. ratio: ...
I L ...1 s· o u f.
C .... P.T.ratio: ....l:z'oFf'li .. lSevl'ce.·:·..
50/51
Cover ..........9.. .......... Disc gap .......... /
Spiral spring .......... !. ......... Moisture ....... .9 Bearing .........N/A.........=oreign mat NONE
VISUAL INSPECTION & MAINTENANCE
Glass cln'd. N/A Taps tight yes Relay cln'd. ···········yes········.. connect.tght .............yes············
Contactcln'd. . ..........yes........... lnsul.resist. .............NiA
Trip circ..............OK
S=Second as found as left (same as found, unless noted)
A phase B phase C phase Ground A phase B phase C phase Ground
LT Pick Up 2.00A 2.00A 2.00A
LT Delay@ 1.5X
LT Delay@2X
Inst. PU
Comments: Relay output does not operate - Relay OUTPUT 1 needs to be re-wired to ALARM OUTPUT.
To monitor output apply 24VDC from Omicron and monitor in Binary IN 1 of Omicron, Connect a resistor across binary input of Omicron to drop voltage form [!_rot rel
Refer.# 19366R- B Tested By: ..............R....P
SETTINGS A Phase B Phase C phase Ground
LT Pick Up 0.4xln=2.0A 0.4xln=2.0A 0.4xln=2.0A 4xln=20.0A
LT Delay 1.0 1.0 1.0 1.0
LT Curve M. Inv. M. Inv. M. Inv. Ext.Inv.
Inst. PU 1 0xln=50.0A 10xln=50.0A 10xln=50.0A 10.0xln=S0.0A
I.D. #: Station Batteries No. of Cells: 92
Battery Mfg: ALCAD Volts per Cell: 1.36
Battery Type: Nickel Cadmium Model: HC34P Minimum Volts: 1.05
Float Volts: 1.40 Equal.Volts: 1.45 Load Amps:
Ambient Temp: 40° F
Ripple Current: 0.00
Humidity: 73%
Test Current: 11.0
Cell ID
Date and Time
Cell
Impedance
Strap
Cell Volts
DC
Comments
1- 2/4/2016 9:35 0.971 0.061 1.460
2- 2/4/2016 9:35 0.830 0.058 1.364
3- 2/4/2016 9:36 0.918 0.099 1.452
4_ 2/4/2016 9:36 0.980 0.122 1.469
5- 2/4/2016 9:36 0.992 0.066 1.488
6- 2/4/2016 9:37 0.835 0.044 1.432
7- 2/4/2016 9:37 0.992 0.053 1.476
8- 2/4/2016 9:37 0.992 0.211 1.488
9- 2/4/2016 9:37 0.992 0.059 1.476
10- 2/4/2016 9:38 0.992 0.072 1.476
11- 2/4/2016 9:38 0.968 0.141 1.476
12- 2/4/2016 9:39 1.038 0.104 1.471
13- 2/4/2016 9:39 1.025 0.070 1.476
14- 2/4/2016 9:39 0.992 0.081 1.466
15- 2/4/2016 9:39 0.992 0.058 1.474
16- 2/4/2016 9:39 0.880 0.103 1.437
17- 2/4/2016 9:40 1.107 0.119 1.471
18- 2/4/2016 9:40 0.992 0.054 1.461
19- 2/4/2016 9:40 0.931 0.065 1.459
20- 2/4/2016 9:41 1.014 0.096 1.476
21- 2/4/2016 9:41 0.968 0.052 1.493
22- 2/4/2016 9:41 1.003 0.092 1.486
23- 2/4/2016 9:41 0.941 0.483 1.486 Long Strap
24_ 2/4/2016 9:42 1.014 0.064 1.464
Location: VAMC - Jamaica Plain Date: 2/4/2020
I.D. #: Station Batteries No. of Cells: 92
Battery Mfg: ALCAD Volts per Cell: 1.36
Battery Type:
Float Volts:
Nickel Cadmium Model: HC34P
1.40 Equal.Volts: 1.45
Minimum Volts:
Load Amps:
1.05
Ambient Temp: ° F
25- 2/4/2016 9:42 1.014 0.078 1.474
26- 2/4/2016 9:42 0.824 0.106 1.376
27- 2/4/2016 9:43 0.833 0.062 1.381
28- 2/4/2016 9:43 0.992 0.081 1.476
29- 2/4/2016 9:43 0.968 0.077 1.483
30_ 2/4/2016 9:43 0.946 0.057 1.471
31- 2/4/2016 9:44 0.811 0.050 1.376
32- 2/4/2016 9:44 0.863 0.057 1.371
33- 2/4/2016 9:44 1.014 0.063 1.466
34_ 2/4/2016 9:44 0.953 0.199 1.457
35- 2/4/2016 9:45 0.992 0.135 1.361
36_ 2/4/2016 9:45 0.824 0.063 1.393
37- 2/4/2016 9:46 1.035 0.062 1.474
38- 2/4/2016 9:46 1.001 0.072 1.486
39- 2/4/2016 9:46 0.698 0.069 1.369
40_ 2/4/2016 9:47 0.920 0.095 1.369
41- 2/4/2016 9:47 1.059 0.129 1.457
42- 2/4/2016 9:47 1.059 0.161 1.461
43- 2/4/2016 9:47 0.919 0.426 1.178 Slightly abave acceptable
Value
44_ 2/4/2016 9:48 0.932 0.076 1.478
45- 2/4/2016 9:48 1.117 0.200 1.461
46- 2/4/2016 9:48 1.152 1.327 1.478 Very Long Strap
47- 2/4/2016 9:49 0.994 0.042 1.362
48- 2/4/2016 9:49 0.799 0.048 1.371
289 Centre St. Holbrook, MA 02343
STATION BATTERIES IMPEDANCE TEST REPORT
I.D. #: Station Batteries No. of Cells: 92
Battery Mfg: ALCAD Volts per Cell: 1.36
Battery Type: Nickel Cadmium Model: HC34P Minimum Volts: 1.05
Float Volts: 1.40 Equal.Volts: 1.45 Load Amps:
Ambient Temp: 40° F
Humidity:
49- 2/4/2016 9:49 0.944 0.111 1.476 so_ 2/4/2016 9:50 1.012 0.083 1.469
51- 2/4/2016 9:50 0.791 0.080 1.373
52- 2/4/2016 9:50 0.929 0.059 1.483
53- 2/4/2016 9:50 0.951 0.078 1.476
54- 2/4/2016 9:50 0.977 0.060 1.481
55- 2/4/2016 9:51 0.890 0.065 1.432
56- 2/4/2016 9:51 0.920 0.115 1.493
57- 2/4/2016 9:51 0.941 0.077 1.481
58_ 2/4/2016 9:51 0.606 0.065 1.317
59- 2/4/2016 9:52 0.924 0.063 1.373
60_ 2/4/2016 9:52 0.932 0.165 1.471
61- 2/4/2016 9:52 1.012 0.574 1.474
62- 2/4/2016 9:52 1.187 0.059 1.457
63- 2/4/2016 9:52 0.833 0.228 1.351
64- 2/4/2016 9:53 1.024 0.066 1.471
65- 2/4/2016 9:53 1.001 0.127 1.464
66- 2/4/2016 9:53 1.048 0.173 1.447
67- 2/4/2016 9:53 0.932 0.138 1.474
69- 2/4/2016 9:53 1.024 0.580 1.466 Long Strap
70_ 2/4/2016 9:54 0.872 0.043 1.381
71- 2/4/2016 9:54 0.867 0.049 1.381
72- 2/4/2016 9:54 0.952 0.076 1.481
289 Centre St, Holbrook, MA 02343
STATION BATTERIES IMPEDANCE TEST REPORT
Customer: Electrical
Job#: 19366
Location: VAMC - Jamaica Plain Date: 2/4/2020
I.D. #: Station Batteries No. of Cells: 92
Battery Mfg: ALCAD Volts per Cell: 1.36
Battery Type: Nickel Cadmium Model: HC34P Minimum Volts: 1.05
Float Volts: 1.40
Equal.Volts: 1.45 Load Amps:
Ambient Temp: 40° F
Ripple Current:00
73- 2/4/2016 9:54 0.497 0.048 1.305
74_ 2/4/2016 9:55 1.001 0.155 1.478
75- 2/4/2016 9:55 0.977 0.140 1.478
76- 2/4/2016 9:55 0.862 0.043 1.369
77- 2/4/2016 9:55 0.838 0.044 1.442
78- 2/4/2016 9:55 0.895 0.163 1.378
79- 2/4/2016 9:55 0.946 0.050 1.457
80_ 2/4/2016 9:56 0.912 1.012 1.437
81- 2/4/2016 9:56 1.012 0.099 1.471
82- 2/4/2016 9:57 0.924 0.186 1.486
84- 2/4/2016 9:57 0.797 0.060 1.393
85- 2/4/2016 9:57 1.035 0.060 1.457
86- 2/4/2016 9:58 0.943 0.179 1.493
87- 2/4/2016 9:58 1.070 0.143 1.483
88- 2/4/2016 9:58 0.132 0.099 1.461
89- 2/4/2016 9:58 0.946 0.057 1.356
90- 2/4/2016 9:58 0.931 0.749 1.457
91- 2/4/2016 9:59 0.832 1.070 1.466
92- 2/4/2016 9:59 0.060 1.106 1.368
Comments:. Upon completion of inspection, maintenance and testing the battery system is suitable for continued service, but based on the system age replacement should be considered.
formATS_2 Average Cell Imp= 0.951, Average Strap Imp= 0.165, Average Cell Voltage= 1.424
Reference #: 19366 Batt Imp - 1 Tested by: BB,PS
289 Centre Street Holbrook, MA 02343
TRANSFORMER TEST REPORT
Customer: VAMC -Jamaica Plain Job#: 19366
Location: Bldg 1 - Outside Pad - Normal Swbd Date: March 15, 2020
Designation: Bldg 1 - Transformer A - Feeder 1 Temp: 36° F
Manufacturer: Square D Humidity: 41%
Rating (kVA): 3000 / 3360 Prim. Volts/ Connect.: 13.SkV / Delta Date of Mfg.: Aug 1993
Type-class: Pad Mtd / OA # of Prim. Taps/Setting: 5/C Imped.%: 5.98%
Serial#: 930121 -A2 Sec. Volts / Connect.: 480 - 277 / Wye Gals of Oil: 540 Silicone
1. Enclosure OK
2. Radiators OK
3. Bushings OK
4. Coils n/a
5. Insulators n/a
6. Gauges OK
VISUAL AND MECHANICAL INSPECTION
7. Tap Changer OK
8. Arrestors OK
9. Accessories n/a
10. Connections OK
11. Grounding OK
12. Remove Dust OK
Gauge Readings: Fluid Temp = 22°C, Max 56°C (Reset) Pressure = 0.0 PSI, Liquid Level @ 25+0 c
1. Insulation
Resistance
(Mega ohms)
@ 5.0 kVDC: Hi to Grnd.
@ 5.0 kVDC: Hi to Low
@ 1.0 kVDC: Lo to Grnd.
1)
2)
3)
1) Low guarded
2) Grnd guarded
3) High guarded
2. Winding Resistance (ohms):
H1 - H3: X1 - X3: XO - X1:
H2 - H1: X2 - X1: XO - X2:
H3 - H2: X3 - X2: XO - X3:
3. Transformer Turns Ratio:
Comments: Upon completion of lnsp, Maint & Testing the Xfrmr is Suitable for Continued Service.
Lightning Arrestors= Elastimold Type 167 ESA-12, 10.SkV MCOV
Insulation Resistance Test of LA's in Mega-Ohms @ SkVDC:
xfmr.wks H1 = 57,900 H2 = 54,400 H3 = 57,6000
Reference#: 19366 Xfrmr - Bldg 1A Tested By: -B-FB---
123 Felton Street Marlborough, MA 01752 • Imported results - Not acquired by Doble Page 2of4
1 min. 10 min. P.I.
24,906 26,400 1.06
9,977 43,000 4.31
4.695 14,350 3.06
Measured Ratio
Tao No.
Voltaqe
Calculated
Ratio
H1 - Grd
X1 - X2
H1 - Grd
X3 - X2
H1 - Grd
X1 -X3
A 14490 52.310
B 14145 51.065
C 13800 49.819 49.808 49.825 49.825
D 13455 48.574
E 13110 47.329
289 Centre Street Holbrook, MA 02343
Customer: VAMC -Jamaica Plain Job#: 19366
Location: Bldg 1 - Outside Pad - Normal Swbd Date: March 15, 2020
Designation: Bldg 1 - Transformer B - Feeder 2 Temp: 38° F
Manufacturer: General Electric - Prolec Humidity: 43% Rating (kVA): 3000 Prim. Volts/ Connect.: 13.SkV / Delta Date of Mfg.: Nov 2017
Type-class: Pad Mtd / Q A # of Prim. Taps/Setting: 5/C Imped.%: 5.78%
Serial#: M17J24830 Sec. Volts / Connect.: 480 - 277 I Wye Gals of Oil: 502 Nat Ester
1. Enclosure OK
2. Radiators OK
3. Bushings OK
4. Coils n/a
5. Insulators n/a
6. Gauges OK
VISUAL AND MECHANICAL INSPECTION
7. Tap Changer OK
8. Arrestors OK
9. Accessories n/a
10. Connections OK
11. Grounding OK
12. Remove Dust OK
Gauge Readings: Fluid Temp = 24°C, Max 56°C (Reset} Pressure = 0.0 PSI, Liquid Level @ 25°C
ELECTRICAL TESTS
1. Insulation
Resistance
(Mega ohms)
@ 5.0 kVDC: Hi to Grnd.
@ 5.0 kVDC: Hi to Low
@ 1.0 kVDC: Lo to Grnd.
1)
2)
3)
1) Low guarded
2) Grnd guarded
3) High guarded
2. Winding Resistance (ohms):
H1 - H3: X1 - X3: XO - X1:
H2 - H1: X2 - X1: XO - X2:
H3 - H2: X3 - X2: XO - X3:
Comments: Upon completion of lnsp, Maint & Testing the Xfrmr is Suitable for Continued Service.
Lightning Arrestors = Hubble 12.?kV MCOV
Insulation Resistance Test of LA's in Mega-Ohms@ 5kVDC:
xfmr.wks H1 = 737,000 H2 = 856,000 H3 = 921,000
Reference #: 19366 Xfrmr - Bldg 1B Tested By: -B-FB---
1 min. 10 min. P.I.
31,789 39,100 1.23
214,000 647,000 3.02
3.822 8.370 2.19
Tao No.
Voltaae
Calculated
Ratio
H1 - Grd
X1 - X2
H1 - Grd
X3 - X2
H1 - Grd
X1 -X3
A 14490 52.310
B 14145 51.065
C 13800 49.819 49.795 49.800 49.800
D 13455 48.574
E 13110 47.329 seconds seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURVE DATA:
CURVE#:
Temp/Humidity:
In. Cap. (kA)
_85.@508V
INJECTION:
Primary:
Volts/Used: 635/480 Secondary: X
A=Amp
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time @ 300 % 6T 23s 23s 23s
S.D.P.U.
S.D.Time
I@ 150 % 6T OK OK OK
Instantaneous 6T OK OK OK
Gnd.P.U.
Gnd.Time
@ 150 % GFT OK OK OK
Contact Resistance
(micro-ohms) 19 20 22
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Control Wiring
INSULATION RESISTANCE@ 250 VDC (mega-ohms): OK
..Pi_quette & Howard SETTINGS: Found Left
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=4000A
..MainjNormal) LD TIME 24.0s
MalnB Cell 1B SD PICKUP 4.0x=16000A
OS 11840 SD TIME 0.5s 12T Out
Cutler Hammer INST. M1=32000A
ARMS. N/A
HUBS42253 GND. P/U B=1200A
72°F I 30% GND.TIME 0.5s 12T Out
Trip Unit:
Frame Size(A):
.P.!e.!. r.!.P- RMS 510 LSIG Cat No. S56LSIG ( .)
OPERATION: Manual:
Electric:
X X
Sensor/Plug(A): 4000/4000 Cat No. RP6D40A400 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip: 120VAC seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURVE DATA:
CURVE#:
In. Cap. (kA) 200@508V INJECTION: Primary:
Volts/Used: 635/480 Secondary: X
Trip Unit: ..Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X
Frame Size(A): 800 Electric:
Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out
Charge/CIose/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amos as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time I@ 300 %
GT 19s 19s 19s
I@ 150 %
GT OK OK OK
Instantaneous GT OK OK OK
Gnd.P.U. Fuse Cat No. 60SL-B1600
Gnd.Time (@ 150 %
GFT OK OK OK
(micro-ohms) 95 80 88 50 51 52
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
INSULATION RESISTANCE@ 250 voe (mega-ohms): OK
Pi_quette & Howard SETTINGS: Found Left
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=600A
Main {Normal) LD TIME 24.0s
.. eare Cell 1C SD PICKUP 6.0x=3600A
DSL-206 SD TIME 0.2s I2T Out
_s_quare D INST. M1=4800A
ARMS. N/A
CNTJ80785 GND. P/U C=210A
72°F / 30% GND.TIME 0.2s I2T Out seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURVE DATA:
CURVE#:
In. Cap. (kA) ..200@508V INJECTION: Primary:
Volts/Used: 635/480 Secondary: X
Trip Unit: ..Digitrie RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X Frame Size(A): 800 Electric:
Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out
Charge/CIose/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
6T 19s 19s 19s
6T OK OK OK
Gnd.P.U. Fuse Cat No. 6DSL-B1600
Gnd.Time
62 63 57 50 51 51
INSULATION RESISTANCE @1000 VDC - Mega-ohms
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
SETTINGS: Found Left
VAMC Jamaica Plain - Building 1 -Sub Basement LO PICKUP 1.0x=600A
_Main (Normal) LO TIME 24.0s
DDP-H Cell 2B SD PICKUP 6.0x=3600A
DSL-206 SD TIME 0.2s 12T Out
.s,quare D INST. M1=4800A
ARMS. N/A
72°F / 30% GND.TIME 0.2s 12T Out seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
L.D.Time @ 300 %
(ru 150 %
Gnd.Time
59 67 72 52 51 51
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=800A
Main (Normal) LD TIME 24.0s
BDP-H1 Cell 2C SD PICKUP 6.0x=4800A
DSL-206 SD TIME 0.2s I2T Out
.. . uare D INST. M1=6400A
ARMS. NIA
CNTJ80785 GND. P/U C=280A
72°F / 30% GND.TIME 0.2s I2T Out
In. Cap. (kA)
Volts/Used:
Trip Unit:
..200 @_5_0_8V
635/480
,,Oigitrip RMS 500 LSIG Cat No. T56BLSIG
INJECTION: Primary:
Secondary:
OPERATION: Manual:
Frame Size(A): 800 Electric:
Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
I<@ 300 % GT 19s 19s 19s
Gnd.P.U. Fuse Cat No. GDSL-D3000
Gnd.Time @ 150 %
23 25 26 18 16 16
INSULATION RESISTANCE@ 1000 VDC - Mega-ohms
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=B00A
Main (Normal) LD TIME 24.0s
SBDPA Cell 2O SD PICKUP 6.0x=4800A
DSL-416 SD TIME 0.2s I2T Out
..s.guare D INST. M1=6400A
ARMS. N/A
CNTJ80785 GND. P/U C=280A
Temp/Humidity: 72°F / 30% GND.TIME 0.2s I2T Out
In. Cap. (kA) _200 @_5_08_V INJECTION: Primary:
Volts/Used: 635/480 Secondary: X
Trip Unit: ,,Oigitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X
Frame Size(A): 1600 Electric:
Sensor/Plug(A): 1600/800 Cat No. PD6D16A080 Fixed Mount/ Draw-Out: Draw-Out seconds to:
seconds to:
L.D. Time:
S.D. Time:
200@_5_0_8V
Volts/Used:
Trip Unit:
Frame Size(A):
635/480 Secondary: X
..Digitrie RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:
Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
(@ 300 %
Gnd.Time
(@. 150 %
72 60 58 51 53 54
INSULATION RESISTANCE@1000 VDC- Mega-ohms
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=600A
..MainJNormal) LD TIME 24.0s
DP-X Cell 3C SD PICKUP 6.0x=3600A
DSL-206 SD TIME 0.2s I2T Out
..s.guare D INST. M1=4800A
ARMS. N/A
..200 @_5_08_V
635/480
Secondary: X
Trip Unit:
Frame Size(A):
..Di9.itrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X
1600 Electric:
Sensor/Plug(A): 1600/1600 Cat No. PD6D16A160 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
Gnd.P.U. Fuse Cat No. 6DSL-D3000
Gnd.Time
{micro-ohms) 31 32 29 17 16 16
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
CURVE DATA: L.D. Time: seconds to: seconds
CURVE#: S.D. Time: seconds to: seconds
Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds
VISUAL INSPECTION
1. Arc Chutes.
2. Contacts
3. Aux.Devices:
4. Wiring
5. Counter
6. Mechanism:
?.Lube a.Racking
9. Close,Trip OK
10. Electric Operation:
REMARKS: Upon completion of inspection and testing, the circuit breaker is suitable for service.
Connection Diagram 44025-167: 2C
Pi_quette & Howard SETTINGS: Found Left
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=1600A
Main (Normal} LD TIME 24.0s
Building 1A DP1 Cell 3D SD PICKUP 6.0x=9600A
DSL-416 SD TIME 0.2s 12T Out
..s.quare D INST. M1=12800A
ARMS. N/A
CNTJ80785 GND. P/U C=560A
In. Cap. (kA) ..85@ 508V
Trip Unit: ,,Oigitrie RMS 510 LSIG OPERATION: Manual: X Frame Size(A): 4000 Electric: X sensor/Plug(A): _4_0_00_/_40_0_0 C_at_N_o_. Fixed Mount/ Draw-Out:
Charge/Close/Trip:
Draw-Out
120VAC
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
(@. 300 % ST 13s 13s 13s
(Q) 150 %
ST OK OK OK
Instantaneous ST OK OK OK
Gnd.Time
17 13 18
INSULATION RESISTANCE@1000 VDC- Mega-ohms
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds
1.Arc Chutes.
2.Contacts
3.Aux.Devices:
4.Wiring
5.Counter
VISUAL INSPECTION
6.Mechanism:
7. Lube
VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=4000A
Main {Normal) LD TIME 15.0s
Tie Cell 4C SD PICKUP 3.0x=12000A
DS 11840 SD TIME 0.4s 12T Out
Cutler Hammer INST. M1=32000A
ARMS. N/A
HUBS42253 GND. P/U A=600A
72°F / 30% GND.TIME 0.Ss I2T Out
200@_5_0_8V
Trip Unit:
Frame Size(A):
635/480 Secondary: X
Digitrie RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 1600 Electric:
Sensor/Plug(A): 1600/800 Cat No. PD6D16A080 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
l@ 300 % 6T 18s 18s 18s
Gnd.P.U. Fuse Cat No. 6DSL-D3000
Gnd.Time l@ 150 %
24 27 23 19 18 16
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds
VISUAL INSPECTION
1. Arc Chutes.
2. Contacts
3. Aux.Devices:
4. Wiring
5. Counter
6. Mechanism:
Connection Diagram 44025-167: 2C
Pi_quette & Howard SETTINGS: Found Left
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=S00A
Main (Normal} LO TIME 24.0s
ADPH Cell 4D SD PICKUP 6.0x=4800A
DSL-416 SD TIME 0.2s I2T Out
Square D INST. M1=6400A
ARMS. N/A
CNTJ80785 GND. P/U C=280A
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
L.D.Time
6T 20s 20s 20s
@ 150 % 6T OK OK OK
@ 150 % GFT OK OK OK
51 57 56 50 47 50
INSULATION RESISTANCE@1000 VDC - Mega-ohms
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds
VISUAL INSPECTION
1. Arc Chutes.
2. Contacts
3. Aux.Devices:
4. Wiring
5. Counter
6. Mechanism:
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=400A
Main (Normal) LDTIME 24.0s
Transformer T2BL Cell 5A SD PICKUP 6.0x=2400A
DSL-206 SD TIME 0.2s I2T Out
Square D INST. M1=3200A
ARMS. N/A
CNTJ80785 GND. P/U C=140A
Temp/Humidity: 72°F / 30% GND.TIME 0.2s I2T Out
In. Cap. (kA) ..200 @_5_08_V INJECTION: Primary:
Volts/Used: 635/480 Secondary: X
Trip Unit: ..Digitrie RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X
Frame Size(A): 800 Electric:
Sensor/Plug(A): _8_00_/_4_0 0 C_at_N_o_._R_P_6_D_0_8_A_0_4 0 Fixed Mount/ Draw-Out: Draw-Out
In. Cap. (kA) ..200 @_5_08_V INJECTION: Primary:
Trip Unit:
Frame Size(A):
635/480 Secondary: X
..Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X
800 Electric:
Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
.@ 300 %
Gnd.Time
68 62 74 51 52 54
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ 8-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds
VISUAL INSPECTION
1. Arc Chutes.
2. Contacts
3. Aux.Devices:
4. Wiring
5. Counter
6. Mechanism:
?.Lube
Pi,quette & Howard SETTINGS: Found Left
Main (Normal) LD TIME 24.0s
MCC-HF Cell 5B SD PICKUP 6.0x=2400A
FH-1 SD TIME 0.2s I2T Out
Square D INST. M1=3200A
ARMS. N/A
CNTJ80785 GND. P/U C=140A
seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURVE DATA:
CURVE#:
In. Cap. (kA) ..200@508V INJECTION: Primary:
Volts/Used: 635/480 Secondary: X Trip Unit: ,,Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X
Frame Size(A): 800 Electric:
Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out
Charge/CIose/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
(Q)_ 150 %
Gnd.Time
61 71 65 50 51 48
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Main (Normal) LD TIME 24.0s
EDP-H Cell 5C SD PICKUP 6.0x=2400A
DSL-206 SD TIME 0.2s I2T Out
_s,guare D INST. M1=3200A
ARMS. N/A
seconds to:
seconds to:
L.D. Time:
S.D. Time:
..200@508V
Trip Unit: ,,DiQitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X Frame Size(A): 800 Electric:
Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out
Charge/CIose/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE 8 PHASE C PHASE A PHASE 8 PHASE C
L.D.P.U.
L.D.Time
6T 18s 18s 18s cm 150 %
Gnd.Time
59 53 58 50 54 50
Phase to Ground: A: 4000+ 8: 4000+ C: 4000+
Phase to Phase: A-8: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ 8: 4000+ C: 4000+
VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=S00A
Main (Normal) LD TIME 24.0s
ATS-EV Cell 6B SD PICKUP 6.0x=4800A
DSL-206 SD TIME 0.2s I2T Out
_s,guare D INST. M1=6400A
ARMS. N/A
seconds to:
seconds to:
L.D. Time:
S.D. Time:
.200 @_5_0_8V
Trip Unit:
Frame Size(A):
..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:
Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out
Control Wmng
VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=S00A
Main (Normal) LD TIME 24.0s
CDPH1 Cell 6C SD PICKUP 6.0x=4800A
DSL-206 SD TIME 0.2s I2T Out
..s,9uare D INST. M1=6400A
ARMS. N/A
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
(a) 300 %
(a) 150 %
Gnd.Time @. 150 %
69 59 64 53 53 52
INSULATION RESISTANCE@1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+ seconds to:
seconds to:
L.D. Time:
S.D. Time:
.200 @_5_0_8V
Trip Unit:
Frame Size(A):
635/480 Secondary: X
,,Oigitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:
Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out
Main (Normal) LD TIME 24.0s
DDPH1 Cell 6O SD PICKUP 6.0x=3600A
DSL-206 SD TIME 0.2s I2T Out
..s,quare D INST. M1=4800A
ARMS. N/A
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time t'@ 300 %
!'@ 150 %
I@ 150 % GFT OK OK OK
59 53 58 50 54 50
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+ seconds to:
seconds to:
L.D. Time:
S.D. Time:
.. . ... @_5_08_V
Trip Unit:
Frame Size(A):
..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:
Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
6T 8s 8s 8s
Gnd.Time
65 71 62 52 51 52
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=800A
Main (Normal) LD TIME 10.0s
Building 1A MCC-4A Cell 7B SD PICKUP 5.0x=4000A
DSL-206 SD TIME 0.2s I2T Out
_quare D INST. 6.0x=4800A
ARMS. N/A
CNTJ80785 GND. P/U A=210A
seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURVE DATA:
In. Cap. (kA) 200@508V
INJECTION: Primary:
Trip Unit: ,_Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X
Frame Size(A): 800 Electric:
Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out
Charge/CIose/Trip:
..Pi,quette & Howard SETTINGS: Found Left
Main (Normal) LD TIME 24.0s
Cath Lab Cell 7C SD PICKUP S2=4000A
DSL-206 SD TIME 0.2s I2T Out
S_quare D INST. M1=3200A
ARMS. N/A
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
ca) 150 %
Gnd.Time
(micro-ohms) 73 64 70 51 51 46
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+ seconds to:
seconds to:
L.D. Time:
S.D. Time:
CURVE DATA:
CURVE#:
In. Cap. (kA) ..200 @_5_08_V INJECTION: Primary:
Volts/Used:
Trip Unit:
Frame Size(A):
635/480 Secondary: X
..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:
Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
IC@. 300 %
GT 19s 19s 19s
(@. 150 %
Gnd.Time
{micro-ohms) 60 64 62 51 51 49
INSULATION RESISTANCE@ 1000 voe - Mega-ohms
Phase to Ground: A: 4000+ B: 4000+ C: 4000+
Phase to Phase: A-8: 4000+ 8-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Main (Normal) LDTIME 24.0s
Building 2 Cell 70 SD PICKUP 6.0x=3600A
DSL-206 SD TIME 0.2s I2T Out
Square D INST. M1=4800A
ARMS. N/A
seconds to:
seconds to:
L.D. Time:
S.D. Time:
S.0.#:
..200 @.'--5_0_8V
Trip Unit:
Frame Size(A):
635/480 Secondary: X
..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X
800 Electric:
Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out
Charge/Close/Trip:
TEST RESULTS
A=Amp
S=Second
CURRENT
Amps as found as left
PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C
L.D.P.U.
LO.Time
Gnd.P.U. Fuse Cat No. 6DSL-B1200
Gnd.Time
77 72 62 58 57 50
Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+
Across Contact: A: 4000+ B: 4000+ C: 4000+
Pi uette & Howard SETTINGS: Found Left
VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=600A
Main (Normal) LD TIME 24.0s
..!Pare Cell 8C SD PICKUP 6.0x=3600A
DSL-206 SD TIME 0.2s I2T Out
Square D INST. M1=4800A
ARMS. N/A
80Y5925 GND. P/U C=210A
seconds to:
seconds to:
L.D. Time:
S.D. Time:
G.0#:
. ............... V
Trip Unit: ..!?..!9..!!. .!.e RMS 510 LSIG Cat No. S56LSIG ( .)...