This document provides the results of maintenance, inspection, and testing services performed on the electrical power distribution system at a Department of Veterans Affairs medical center. Key details include inspection and testing of medium voltage circuit breakers, station batteries, transformers, and protective relays serving the facility. The services ensured the continued safe and reliable operation of equipment, including circuit breakers, batteries, transformers, and protective relays for the main switchgear and various building feeders. Test results found most equipment suitable for continued use, though some relays required rewiring and one battery replacement should be considered due to age.

View the file

Other files

File Type Posted
Wage Determination 2015-4047 Rev 24 Dated 6.30.2023.pdf PDF
LOS Certification.pdf PDF
Past Performance Worksheet.xlsx XLSX spreadsheet
36C24123Q0921.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MEDIUM VOLTAGE CIRCUIT BREAKER TEST REPORT

Customer: VABHS Jamaica Plain Job#: 19366

Location: NStar Station 304-1 Date: 9/8/2020

Switchgear: Utility 13.8kV Compartment: Main 1 Line 304-1440H

Manufacturer: Cutler-Hammer Volts: Max.15kV

Type: 150VCP-W750 Amps: 1200

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 5051530 Chrge/Clse/Trip: All 120DC Volts

Oper.mech.: ML Air/OilNac.: Vacuum

VISUAL AND MECHANICAL INSPECTION

1.Cubicle OK 9.Arc contacts

2.Shutter mechanism OK 1a.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic. connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 184 / 188

(WL-34854L)

Inspection comments

ELECTRICAL TESTS

pole A pole B poleC

Contact Resist. - micro-ohms (found/left) 43 54 43

Insulation Resistance: Phase to Ground

Megaohms @ 5 kVDC Across Contact

>515000 >515000 >515000

Overpot.test - microAmps@ 37.5 kVDC 7 13 8

Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.3 0.3

Contact gap/wipe - inches (Vac.bottle) OK OK OK lnsul. Resist. Contr.Wiring- MegaOhms@ 250VDC: OK

Comments:

Test results suggest the circuit breaker is suitable for service.

Customer: VABHS Jamaica Plain Job#: 19366

Location: NStar Station 304-1 Date: 9/8/2020

Switchgear: Utility 13.SkV Compartment: Main 2 Line 304-1511

Manufacturer: Cutler-Hammer Volts: Max. 15kV

Type: 150VCP-W750 Amps: 1200

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 5051529 Chrge/Clse/Trip: All 120DC Volts

1.Cubicle

OK 9.Arc contacts

2.Shutter mechanism OK 1a.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic. connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 199 / 203

Contact Resist. - micro-ohms (found/left) 49 50 47

Insulation Resistance: Phase to Ground

Megaohms @ 5 kVDC Across Contact

Overpot.test - microAmps@ 37.5 kVDC 9 10 9

Overpot.test Vac.bottle - microAmps@ 40 kVDC 1.4 1.2 0.1 lnsul. Resist. Contr.Wiring- MegaOhms @250VDC: OK

Customer: Electrical Job#: 19366

Location: VAMC JP - NStar Station 304-1 Date: 3/15/2020

Switchgear: Utility 13.SkV Compartment: 6A- Feeder A

Manufacturer: Cutler-Hammer Volts: Max.15kV

Type: 150VCP-W750 Amps: 1200

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 05051533 Chrge/Clse/Trip: All 120DC Volts

OK 9.Arc contacts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK a.Main contacts Bottles OK 16.Counter found/left 40/ 43

Contact Resist. - micro-ohms (found/left) 41 47 45

Insulation Resistance: Phase to Ground

Megaohms@ 5kVDC Across Contact

2,800,000 3,750,000 3,150,000

>5,000,000 >5,000,000 >5,000,000

Overpot.test - microAmps@ 37.5 kVDC 0.4 0.5 1

Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.5 0.4 2

Location: VAMC JP - NStar Station 304-1 Date: 2/16/2020

Switchgear: Utility 13.SkV Compartment: 68 Feeder C

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 05051515 Chrge/Clse/Trip: All 120DC Volts

OK 9.Arc contacts

2.Shutter mechanism OK 1a.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 26 / 29

Contact Resist. - micro-ohms (found/left) 41 40 43

Insulation Resistance: Phase to Ground

Megaohms@ 5 kVDC Across Contact

Overpot.test - microAmps @ 37.5 kVDC 10 5 3

Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.8 0.3 0.1

Location: VAMC JP - NStar Station 304-1 Date: 3/15/2020

Switchgear: Utility 13.8kV Compartment: 7A - Feeder B

Manufacturer: Cutler-Hammer Volts: Max. 15kV

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 5051539 Chrge/Clse/Trip: All 120DC Volts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK a.Main contacts Bottles OK 16.Counter found/left 84/ 88

Contact Resist. - micro-ohms (found/left) 41 46 49

Insulation Resistance: Phase to Ground

Megaohms@ 5kVDC Across Contact

Overpot.test - microAmps @ 37.5 kVDC 10 6 8

Overpot.test Vac.bottle - microAmps@ 40 kVDC 7 8 11

Location: VAMC JP - NStar Station 304-1 Date: 2/16/2020

Switchgear: Utility 13.SkV Compartment: 8A - Feeder E - Emerg. 1

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 05051537 Chrge/Clse/Trip: All 120DC Volts

OK 9.Arc contacts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 289 / 292

Contact Resist. - micro-ohms (found/left) 45 46 41

Insulation Resistance: Phase to Ground

Megaohms@ 5kVDC Across Contact

Overpot.test - microAmps @ 37.5 kVDC 8 6 11

Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.3 0.1

Location: VAMC JP - NStar Station 304-1 Date: 4/25/2020

Switchgear: Utility 13.8kV Compartment: 88 - Feeder G

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 5051532 Chrge/Clse/Trip: All 120DC Volts

OK 9.Arc contacts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 36 / 40

Contact Resist. - micro-ohms (found/left) 35 34 32

Insulation Resistance: Phase to Ground

Megaohms@ 5 kVDC Across Contact

Overpot.test - microAmps @ 37.5 kVDC 9 2.8 4.5

Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.1 0.1

Location: VAMC JP - NStar Station 304-1 Date: 2/16/.2020

Switchgear: Utility 13.BkV Compartment: 9A - Feeder F - Emerg. 4

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 05051535 Chrge/Clse/Trip: All 120DC Volts

OK 9.Arc contacts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 48 / 52

Contact Resist. - micro-ohms (found/left) 37 41 35

Insulation Resistance: Phase to Ground

Megaohms@ 5 kVDC Across Contact

Overpot.test - microAmps @ 37.5 kVDC 10 5 5

Overpot.test Vac.bottle - microAmps@ 40 kVDC 0.1 0.3 0.1

Location: VAMC JP - NStar Station 304-1 Date: 2/4/2020

Switchgear: Utility 13.SkV Compartment: 98 -Spare

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 05051531 Chrge/Clse/Trip: All 120DC Volts

OK 9.Arc contacts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Mechanic. connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

7.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 37 / 41

Contact Resist. - micro-ohms (found/left) 35 34 34

Insulation Resistance: Phase to Ground

Megaohms@ 5kVDC Across Contact

3,150,000 3,275,000 3,570,000

Overpot.test - microAmps@ 37.5 kVDC 12 9 8

Overpot.test Vac.bottle - microAmps @ 40 kVDC 0.5 0.1 0.1

Switchgear: Utility 13.SkV Compartment: 10A- Spare

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 140802246 Chrge/Clse/Trip: All 120DC Volts

2.Shutter mechanism OK 10.Control wiring OK

3.Racking Device OK 11.Pnl.indic.lights OK

4.Meehanic.connections OK 12.Heaters OK

5.Bushings 13.Ground connect. OK

6.Finger clusters or stabs OK 14.Manual close/trip OK

?.Arc chutes 15.Elect.close/trip OK

8.Main contacts Bottles OK 16.Counter found/left 103/106

{WL-34854L)

Contact Resist. - micro-ohms (found/left) 40 35 36

Insulation Resistance: Phase to Ground

Megaohms@ SkVDC Across Contact

2,750,000 3,550,000 3,950,000

Overpot.test - microAmps@ 37.5 kVDC 7 8 5

Overpot.test Vac.bottle - microAmps@ 40 kVDC 1.1 0.3 0.4

Switchgear: Utility 13.SkV Compartment: 11A - Spare

Wiring Diag.: 691C386H44 Style: 3776A23662

Serial#: 140601475 Chrge/Clseffrip: All 120DC Volts

2.Shutter mechanism

OK

OK

9.Arc contacts

10.Control wiring

OK

3.Racking Device OK 11.Pnl.indic.lights

4.Mechanic.connections OK 12.Heaters

5.Bushings 13.Ground connect.

6.Finger clusters or stabs OK 14.Manual close/trip

7.Arc chutes 15.Elect.close/trip a.Main contacts Bottles OK 16.Counter found/left

75/79

Contact Resist. - micro-ohms (found/left) 37 38 35

Insulation Resistance: Phase to Ground

Megaohms@ 5kVDC Across Contact

3,750,000 2,890,000 2,100,000

Overpot.test - microAmps@ 37.5 kVDC 9 21 25

Overpot.test Vac.bottle - microAmps @ 40 kVDC 0.1 0.5 0.1

ELECTRICAL ENGINEERING & SERVICE CO., INC.

289 Centre St., Holbrook, MA 02343

PROTECTIVE RELAY TEST REPORT Job: 19366

Date: 9/9/2020

Customer:

Location: VA Jamaica Plain

Substation: Main 5kV Switchgear

Circuit ID: Busss Differential Relay

Manuf.& type Basler - BE1-87B

Namepl.Data V Unit: 50-400V, OC Unit: 0.25-2.50A, Alarm: 10-80%

Instruct.book 9282300990 Catalog: BE1-87B-G5BA1YN0N0F

C.T. ratio: ..,..,,..,...,......"""'"= P.T.ratio: N/A Device: 87B

Serial#: H00505459 REV N found/left

VISUAL INSPECTION & MAINTENANCE

--X--

Trip circ. -------

TEST RESULTS

V= Volts

S=Second as found as left (same as found, unless noted)

Phase A Phase B Phase C Phase A Phase B Phase C

Zero Set: N/A N/A N/A

Alarm 26.4V 26.0V 26.3V

Alarm Delay 2.25s 2.32s 2.34s (timed from O to 30V)

Voltage 101V 101V 101V

Time Volt. 6.3ms 6.3ms 6.3ms (timed from O to 120V)

Current P.U. 0.76A 0.76A 0.76A

Time Current 6.7ms 6.7ms 6.7ms (timed from O to 0.80A)

Target OK OK OK

Comments: Test results suggest the relay is suitable for service armco acis1 14n inuse

Overcurrent contacs 19-20 not in use form prot_re_t _

Refer.# Contact numbering left to right bottom and top (Front view)

19366R- 87B Tested By: RP _

SETTINGS Phase

Alarm 50%

Voltage 50V

Current 0.75A

Cover OK Disc gap Glass cln'd. X Taps tight

Spiral spring --- Moisture None Relay cln'd. X Connect.tght

Bearing --- Foreign mat -N-o-ne- Contact cln'd. --- lnsul.resist.

Manuf.& type ABB CR-9

Namepl.Data 4-12amp, 120V Dir.[208v N.]

Instr.book: 41-131 Catalog: 1875592 /1875586

Device: 67 (Found/Left)

Cover ok Disc gap ok Glass cln'd. X Taps tight X Trip circ. n/a

Spiral spring ok Moisture no Relay cln'd. X Connect.tght X

Bearing ok Foreign mat no Contact cln'd. X lnsul.resist. ok

A=Amp, V=Volts as found as left (same as found, unless noted)

S=Second A B C N Test point A Phase Phase B Phase C Neut./Grd.

Pickup 4A 3.99A 3.99A 4.01A 4A

Time@200% 5.59s 5.56s 5.56s 5.68s BA

Time@400% 1.34s 1.38s 1.33s 1.35s 16A

Time@600% 0.79s 0.83s 0.81s 0.83s 24A

Dir. Unit MTA V lag-28.5° V lag-32° V lag-32.5° V Lead 60° @ 120V

!CS Pickup 0.17A 0.18A 0.18A 0.18A 0.2A

58[-122] 55[-120] 146{-30]

Comments: Relay test and inspection results suggest they are suitable for continued service form prot_re/ exc

SETTINGS Relay 1 Relay 2

Tap 4a

Time Dial 4 lnstan.P.U. n/a

ICS tap 0.2

Manuf.& type ABB CP

Namepl.Data 120V reverse phase

Instr.book: 41-222 Catalog: 289B415A09 Device: 27C --------

(Found/Left)

Cover ok Disc gap ok Glass cln'd. X Taps tight X Trip circ. n/a

Spiral spring ok Moisture no Relay cln'd. X Connect.tght X

S=Second 304-1511 304-1440H Test point A Phase Phase B Phase C Neut./Grd.

Pickup 111V 109V

Drop Out 79V 82V

Time 95V to O 1.65s 1.62s

Time 95V to 150 1.14s 1.26s

PH Reversal OK ok

304-1511 _glass case is cracked form prot_rel exc

Volt Range 80-110V

Time Dial n/a

ICS tap n/a

Manuf.& type Basler BE1-25

Namepl.Data Sync-Check

Instr.book: 1702-990

Device: 25

120V

Catalog: M1E-A6P-N5R0F

(Found/Left)

Trip circ. n/a

S=Second 304-1511 304-1440H Test point A Phase Phase B Phase C Neut./Grd.

Angle Difference +/-14 ° +/-15 °

Voltage Diff. +/-20V *+/-20V

Dead Bus 60V 59V

Live Bus 94V 94V

Dead Line 60V 59V

Live Line 95V 94V

Sync Time 8.83s 8.84s

*Delta V light does not work on 304-1440H relay

SETTINGS

Phase Angle

Time Delay

Relay 1

15°

9s

Relay 2

Cover

Spiral spring ok ok

Disc gap

Moisture ok no

Glass cln'd.

Relay cln'd.

X

X

Taps tight

Connect.tght

X

Bearing ok Foreign mat no Contact cln'd X Insul.resist. ok

Manuf.& type ABB CR-9

NamepI.Data 4-12amp, 120V Dir.[208v N.]

Instr.book: 41-131 Catalog: 1875592 /1875586

Device: 67 (Found/Left)

Cover

Spiral spring ok ok

Disc gap

Moisture ok no

Glass cln'd.

Relay cln'd.

X

X

Taps tight

Connect.tght

X

Trip circ. n/a

A=Amp, V=Volts

S=Second as found as left (same as found, unless noted)

A B C N Test point A Phase Phase B Phase C Neut./Grd.

Pickup 3.99A 3.99A 4.0A 3.99A 4A

Time@200% 5.52s 5.52s 5.54s 5.55s BA 6.3s

Time@400% 1.31s 1.31s 1.32s 1.31s 16A

Time@600% 0.79s 0.80s 0.80s 0.72s 24A

Dir. Unit MTA V lag-32.5° V lag-31.5° V lag-32° V lead 58.5° @ 120V

ICS Pickup 0.17A 0.18A 0.18A 0.18A 0.2A

57L-1ZZI 57[-120] 57[-121] 148[-31}

Tap 4a

Time Dial 4

ICS tap 0.2

Substation: Main 5kV Switchgear

Date: 2/16/2019

Circuit ID:

Fe ed er C ------------

Manuf.& type Cutler-Hammer FP5200-00

Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA

Instruct.book IL17569C Style: 66D2041G11

C.T. ratio: 150/5 P.T.ratio: 120/1----=D=-e-v-=-ic_e_: 50/51

Cover OK Disc gap NIA

Spiral spring N/A Moisture NONE

Bearing N/A =oreign mat NONE

VISUAL INSPECTION & MAINTENANCE

Glass cln'd. N/A Taps tight yes

Relay cln'd. yes Connect.tght yes

Contact cln'd. les lnsul.resist. N/A

Trip circ. -----

V = Volts

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 4.00A 4.00A 4.00A 0.75A

LT Delay@2X 17.53s 17.48s 17.57s 0.401s

LT Delay@3X 7.85s 7.79s 7.82s 0.270s

Inst. PU 17.6A 17.7A 17.5A 10.1A form prot rel

Refer.# 19366R- C Tested By: --R-P--

SETTINGS A Phase B Phase C phase Ground

LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A .15xln=0.75A

LT Delay 1 1 1 0.1

LT Curve I2T I2T I2T Mod.Inv.

Inst. PU 3.5xln=17.5A 3.5xln=17.SA 3.5xln=17.5A 2.0xln=10.0A

Substation: Main 5kV Switchgear

PROTECTIVE RELAY TEST REPORT

Job: 19366

Circuit ID: Feeder D

Manuf.& type Cutler-Hammer FP5200-00

Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA

Instruct.book "'IL17569C Style: 66D2041G11

C.T. ratio: 150/5 P.T.ratio: .........120/f]i----D-e-v-ic_e_: 50/51

Cover OK Disc gap N/A

Bearing NIA =oreign mat NONE

VISUAL INSPECTION & MAINTENANCE

Glass cln'd. N/A Taps tight yes

Contact cln'd. yes lnsul.resist. N/A

Trip circ. --O-K--

S = Second

As Found As Left (sames as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 4.00A 4.01A 4.00A 0.76A

LT Delay@2X 17.53s 17.48s 17.57s 0.406s

LT Delay@3X 7.82s 7.80s 7.85s 0.263s

Inst. PU 17.6A 17.6A 17.6A 10.1A

Comments: Test results suggest the relay is suitable for service.

form prot_rel

Refer.# 19366R- D Tested By: --R-P--

SETTINGS A Phase B t-'nase c phase Ground

LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A 0.15xln=0.75A

LT Delay 1 1 1 0.1

Inst. PU 3.5xln=17.5A 3.5xln=17.5A 3.5xln=17.5A 2.0xln=10.0A

Date: 3/15/2020

Customer: .Piquette.&.Howard

Substation: .Main.5kV.switchgear

Circuit ID: .Feeder A.-..Building.1. ..Normal..(2)

Manuf.& type .cutler-Hammer.FP5200-00

Namepl.Data .Power.Supply:.48-1.25VDC,..1.00-120VAC,.20VA

C.T. ratio: ·······3001s······· P.T.ratio: ...."fiolf....A.........Devlce·:.... 50/51

Cover ..........9.. .......... Disc gap ..........ty/........... Glass cln'd............t:'.Y ........... Taps tight .............Y

Trip circ. OK

Spiral spring ..........!' !. ......... Moisture .....9.....ty. ·······

Bearing .......... !..........:oreign mat ....... .9.. . ·······

Relay cln'd............Y.. ........... connect.tght .............Y Contact cln'd. ...........Y.. ........... Insul.resist. .......... }'. !

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 10.0A 10.0A 10.1A 0.50A

LT Delay@ 1.5X 2.44s 2.44s 2.45s 0.682s

LT Delay@2X 1.07s 1.06s 1.07s 0.399s

Inst. PU 52A 52A 53A 10.0A

Comments: Test results sugg_est the relay is not suitable for service output 1 Relay defective.

Relay OUTPUT Rewired by EESCO - now okay

All pick up and test points tested on Alarm output form [)_rot rel

Refer.# 19366R- A Tested By: ..............RP

SETTINGS A Phase B Phase C phase Ground

LT Pick Up 2.0xln=10A 2.0xln=10A 2.0xln=10A 0.1xln=0.50A

LT Delay 0.15 0.15 0.15 0.1

LT Curve V. Inv. V. Inv. V. Inv. Mod.Inv.

Inst. PU 10.4xln=52.0A 10.4xln=52.0A 10.4xln=52.0A 2.0xln=10.0A

Substation: Main 5kV Switchgear

Circuit ID: Feeder B - Building I Normal (3)

Manuf.& type Cutler-Hammer FP5200-00

Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA Instruct.book IL 17569C Style: 66D2041G11

C.T. ratio: ..............'a'o·o1s·............. P.T.ratio: ........'1"2·0Tf" ---=D e-v.,...ic_e_: 50/51

Bearing N/A =oreign mat NONE

VISUAL INSPECTION & MAINTENANCE

Glass cln'd. N/A Taps tight yes

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 4.00A 4.01A 4.00A 0.50A

LT Delay@ 1.5X 2.43s 2.45s 2.44s 0.678s

LT Delay@2X 2.43s 2.45s 2.44s 0.404s

Inst. PU 52A 52A 53A 10.0A

To monitor output apply 24VDC from Omicron and monitor in Binary IN 1 of Omicron, Connect a resistor across binary input of Omicron to drop voltage form prot_rel

Refer.# 19366R- B Tested By: --R-P--

SETTINGS A Phase B Phase C phase Ground

LT Pick Up 2.0xln=10A 2.0xln=10A 2.0xln=10A 0.1xln=0.50A

LT Delay 0.15 0.15 0.15 0.1

LT Curve V. Inv. V. Inv. V. Inv. Mod.Inv.

Inst. PU 10.4xln=52.0A 10.4xln=52.0A 10.4xln=52.0A 2.0xln=10.0A

0evice:

Substation: Main 5kV Switchgear

Circuit ID: Feeder C - ACA Building Left

Manuf.& type Cutler-Hammer FP5200-00

Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA

C.T. ratio: 150/5 P.T.ratio: .........1.20/16 .................... 50/51

Glass cln'd. N/A

Taps tight yes Trip circ. -----

Bearing N/A =oreign mat NONE

Relay cln'd. yes

Contact cln'd. yes

Connect.tght yes lnsul.resist. N/A

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 4.00A 4.00A 4.00A 0.75A

LT Delay@2X 17.53s 17.48s 17.57s 0.401s

LT Delay@3X 7.85s 7.79s 7.82s 0.270s

Inst. PU 17.6A 17.7A 17.5A 10.1A

LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A I0.15xln=0.75A

LT Delay 1 1 1 0.1

Inst. PU 3.5xln=17.5A 3.5xln=17.SA 3.5xln=17.SA 2.0xln=10.0A

Substation: Main 5kV Switchgear

Circuit ID: Feeder D - ACA Building Right

Manuf.& type Cutler-Hammer FP5200-00

Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA

C.T. ratio: 150/5 P.T.ratio: 120/1 21....----=D=-e-v.,...ic-e:- 50/51

Cover OK Disc gap NIA

Bearing N/A =oreign mat NONE

VISUAL INSPECTION & MAINTENANCE

Glass cln'd. N/A Taps tight yes

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 4.00A 4.01A 4.00A 0.76A

LT Delay@2X 17.53s 17.48s 17.57s 0.406s

LT Delay@3X 7.82s 7.80s 7.85s 0.263s

Inst. PU 17.6A 17.6A 17.6A 10.1A

LT Pick Up 0.8xln=4A 0.8xln=4A 0.8xln=4A 0.15xln=0.75A

LT Delay 1 1 1 0.1

Inst. PU 3.Sxln=17.SA 3.Sxln=17.SA 3.Sxln=17 .SA 2.0xln=10.0A

2/16/2019

Customer: ..Piquette.&..Howard

Substation: .Main._5kV_ Switchgear

Circuit ID: .Feeder.E..-.Emergencv.1

Manuf.& type .Cutler-Hammer .FP5200-00

Namepl.Data_Power.Supply:..48-125VOC,..100-1_20VAC,..20VA

C.T. ratio: ........1.50/5....... P.T.ratio: ....f2off·A...........bev1ce:... 50/51

Cover ...........9.!5.......... Disc gap .......... !

Spiral spring .......... / .......... Moisture ....J 9

Bearing ........... !..........:oreign mat .... ) 9

VISUAL INSPECTION & MAINTENANCE

Glass cln'd..........} !. .......... Taps tight ............ ¥ Relay cln'd............¥. ............ Connect.tght ............ ¥

Contact cln'd. ...........¥.. . ........... lnsul.resist. ............. !

Trip circ...................O....K

V=Volts as found as left (same as found, unless noted)

S=Second A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 6.00A 6.00A 6.00A 0.76A

LT Delay@2X 0.652s 0.658s 0.655s 0.399s

LT Delay@3X 0.290s 0.291s 0.287s 0.264s

Inst. PU 35.0A 35.1A 35.1A 7.50A

Comments: Relay output contact 1 did not operate. All timing tests performed on the Alarm contact.

form p_rot rel

Date:

LT Pick Up 1.2xln=6A 1.2xln=6A 1.2xln=6A 0.15xln=O.75A

LT Delay 0.09 0.09 0.09 0.1

LT Curve V. Inverse V. Inverse V. Inverse Mod.Inv.

Inst. PU 7.0xln=35A 7.0xln=35A 7.0xln=35A 1.5xln=7.5A

Date: 4/25/2020

Substation: Main 5kV Switchgear

Circuit ID: Feeder L - Boiler Plant

Manuf.& type Cutler-Hammer FP5200-00

Namepl.Data Power Supply: 48-125VDC, 100-120VAC, 20VA

C.T. ratio: 150/5 P.T.ratio: 120/1 il·---0-e-v-ic_e_: 50/51

Glass cln'd. N/A Taps tight yes

Bearing N/A :oreign mat NONE

Contact cln'd. yes lnsul.resist. NIA

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 5.50A 5.50A 5.50A 0.50A

LT Delay@ 1.SX 1.48s 1.48s 1.49s 0.670s

LT Delay@2X 0.650s 0.655s 0.653s 0.401s

Inst. PU 35A 35A 35A 7.5A

To monitor output apply 24VDC from Omicron and monitor in Binary IN 1 of Omicron, Connect a resistor across binary input of Omicron to drop voltage form e_rot rel

Refer.# 19366R- L Tested By: --R-P--

LT Pick Up 1.1xln=5.5A 1.1xln=S.SA 1.1xln=5.5A 0.1xln=0.50A

LT Delay 0.09 0.09 0.09 0.1

LT Curve Very Inv. Very Inv. Very Inv. Mod.Inv.

Inst. PU 7xln=35A 7xln=35A 7xln=35A 1.5xln=7.SA fs·ois····

Customer: .Piquette.&..Howard

Location: ..V....A.....J...a...m.....a...i..c...a.....P....l..a...i.n Substation: Main 5kV Switchgear

Circuit ID: .Feeder.F.-..Emergency.4

Manuf.& type .cutler-Hammer.FP5200-00

Namepl.Data . Power .Supply:.48-1.25VDC,. 100-1.20VAC,. 20VA

C.T. ratio.:....... P.T.ratio: ....1.2°0/1..'d..........bev'i'ce·:... 50/51

Cover ..........2. .......... Disc gap .......... !

Glass cln'd.......!.................. Taps tight .............¥. ............. Trip circ

Spiral spring .......... !. .......... Moisture ...... 2 Bearing ...... NIA ...... oreign mat NONE

Relay cln'd............¥.. .............connect.tght .............Y

Contact cln'd. ............¥.. . ............ lnsul.resist. ............. !

V= Volts as found as left (same as found, unless noted)

S=Second A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 6.00A 6.01A 6.01A 0.75A

LT Delay@2X 0.652s 0.650s 0.655s 0.408s

LT Delay@ 3X 0.291s 0.290s 0.292s 0.268s

Inst. PU 35.3A 35.1A 35.2A 7.52A

Comments: Relay output contact 1 did not operate. All timing tests performed on the Alarm contact.

form prot rel

Refer.# 19366R- F Tested By: ................R....P

LT Pick Up 1.2xln=6A 1.2xln=6A 1.2xln=6A 0.15xln=0.75A

LT Delay 0.09 0.06 0.09 0.1

LT Curve V. Inverse V. Inverse V. Inverse Mod.Inv.

Inst. PU 7.0xln=35A 7.0xln=35A 7.0xln=35A 1.5xln=7.5A

1.sols·.·.····

Date: 4/25/2020

Customer: .Piquette..&.Howard

Substation: Main 5kV Switchgear

Circuit ID: .Feeder.G.:. Research..Building

Manuf.& type .Cutler-Hammer.FP5200-00

Namepl.Data ..Power..Supply:. 48-125VDC, ..100-120VAC,.20VA

C.T. ratio: ........ P.T.ratio.:....f20T-f"Zr·········oevfce:... 50/51

Glass cln'd......!................. Taps tight .............Y

Trip cir..c...............oK

Spiral spring ··········NiA·········· Moisture ·······N·6r:iif···· Bearing··········NiA········..:oreign mat .......No" .i"if

Relay cln'd............Y.. ............ Connect.tght .............Y Contactcln'd. ...........Y.. . ........... lnsul.resist. ............. /

V =Volts

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 5.00A 5.00A 5.00A 0.60A

LT Delay@ 1.5X 6.79s 6.80s 6.80s 0.665s

LT Delay@2X 2.86s 2.86s 2.86s 0.398s

Inst. PU * * * 10.0A

Comments: Relay is not suitable for service - relay trip output does not operate- Now Okay.

All timing tests performed through the alarm contact.

* Instantaneous pick-up too high for testing (70A) Relay OUTPUT Rewired by EESCO - now okay form E_rot rel

Refer.# 19366R- G Tested By: ................RP

LT Pick Up 1.0xln=5A 1.0xln=5A 1.0xln=5A 0.12xln=0.60A

LT Delay 0.30 0.30 0.30 0.1

LT Curve Ext. Inv. Ext. Inv. Ext. Inv. Mod.Inv.

Inst. PU 14xln=70A 14xln=70A 14xln=70A 2.0xln=10.0A

Style: 66D2041G11

PROTECTIVE RELAY TEST REPORT Job: ..........1...9....3...6...6

Location:

Substation:

Circuit ID:

Manuf.& type Namepl.Data

.Piquette_&_ Howard VA Jamaica Plain

.Main.5kV .switchgear

.spare.98 Cutler-Hammer FP5200-00

. Power.Supply:.48-1.25VDC,..1.00-120VAC,.20VA

Instruct.book

C.T. ratio: ...

I L ...1 s· o u f.

C .... P.T.ratio: ....l:z'oFf'li .. lSevl'ce.·:·..

50/51

Cover ..........9.. .......... Disc gap .......... /

Spiral spring .......... !. ......... Moisture ....... .9 Bearing .........N/A.........=oreign mat NONE

VISUAL INSPECTION & MAINTENANCE

Glass cln'd. N/A Taps tight yes Relay cln'd. ···········yes········.. connect.tght .............yes············

Contactcln'd. . ..........yes........... lnsul.resist. .............NiA

Trip circ..............OK

S=Second as found as left (same as found, unless noted)

A phase B phase C phase Ground A phase B phase C phase Ground

LT Pick Up 2.00A 2.00A 2.00A

LT Delay@ 1.5X

LT Delay@2X

Inst. PU

Comments: Relay output does not operate - Relay OUTPUT 1 needs to be re-wired to ALARM OUTPUT.

To monitor output apply 24VDC from Omicron and monitor in Binary IN 1 of Omicron, Connect a resistor across binary input of Omicron to drop voltage form [!_rot rel

Refer.# 19366R- B Tested By: ..............R....P

SETTINGS A Phase B Phase C phase Ground

LT Pick Up 0.4xln=2.0A 0.4xln=2.0A 0.4xln=2.0A 4xln=20.0A

LT Delay 1.0 1.0 1.0 1.0

LT Curve M. Inv. M. Inv. M. Inv. Ext.Inv.

Inst. PU 1 0xln=50.0A 10xln=50.0A 10xln=50.0A 10.0xln=S0.0A

I.D. #: Station Batteries No. of Cells: 92

Battery Mfg: ALCAD Volts per Cell: 1.36

Battery Type: Nickel Cadmium Model: HC34P Minimum Volts: 1.05

Float Volts: 1.40 Equal.Volts: 1.45 Load Amps:

Ambient Temp: 40° F

Ripple Current: 0.00

Humidity: 73%

Test Current: 11.0

Cell ID

Date and Time

Cell

Impedance

Strap

Cell Volts

DC

Comments

1- 2/4/2016 9:35 0.971 0.061 1.460

2- 2/4/2016 9:35 0.830 0.058 1.364

3- 2/4/2016 9:36 0.918 0.099 1.452

4_ 2/4/2016 9:36 0.980 0.122 1.469

5- 2/4/2016 9:36 0.992 0.066 1.488

6- 2/4/2016 9:37 0.835 0.044 1.432

7- 2/4/2016 9:37 0.992 0.053 1.476

8- 2/4/2016 9:37 0.992 0.211 1.488

9- 2/4/2016 9:37 0.992 0.059 1.476

10- 2/4/2016 9:38 0.992 0.072 1.476

11- 2/4/2016 9:38 0.968 0.141 1.476

12- 2/4/2016 9:39 1.038 0.104 1.471

13- 2/4/2016 9:39 1.025 0.070 1.476

14- 2/4/2016 9:39 0.992 0.081 1.466

15- 2/4/2016 9:39 0.992 0.058 1.474

16- 2/4/2016 9:39 0.880 0.103 1.437

17- 2/4/2016 9:40 1.107 0.119 1.471

18- 2/4/2016 9:40 0.992 0.054 1.461

19- 2/4/2016 9:40 0.931 0.065 1.459

20- 2/4/2016 9:41 1.014 0.096 1.476

21- 2/4/2016 9:41 0.968 0.052 1.493

22- 2/4/2016 9:41 1.003 0.092 1.486

23- 2/4/2016 9:41 0.941 0.483 1.486 Long Strap

24_ 2/4/2016 9:42 1.014 0.064 1.464

Location: VAMC - Jamaica Plain Date: 2/4/2020

I.D. #: Station Batteries No. of Cells: 92

Battery Mfg: ALCAD Volts per Cell: 1.36

Battery Type:

Float Volts:

Nickel Cadmium Model: HC34P

1.40 Equal.Volts: 1.45

Minimum Volts:

Load Amps:

1.05

Ambient Temp: ° F

25- 2/4/2016 9:42 1.014 0.078 1.474

26- 2/4/2016 9:42 0.824 0.106 1.376

27- 2/4/2016 9:43 0.833 0.062 1.381

28- 2/4/2016 9:43 0.992 0.081 1.476

29- 2/4/2016 9:43 0.968 0.077 1.483

30_ 2/4/2016 9:43 0.946 0.057 1.471

31- 2/4/2016 9:44 0.811 0.050 1.376

32- 2/4/2016 9:44 0.863 0.057 1.371

33- 2/4/2016 9:44 1.014 0.063 1.466

34_ 2/4/2016 9:44 0.953 0.199 1.457

35- 2/4/2016 9:45 0.992 0.135 1.361

36_ 2/4/2016 9:45 0.824 0.063 1.393

37- 2/4/2016 9:46 1.035 0.062 1.474

38- 2/4/2016 9:46 1.001 0.072 1.486

39- 2/4/2016 9:46 0.698 0.069 1.369

40_ 2/4/2016 9:47 0.920 0.095 1.369

41- 2/4/2016 9:47 1.059 0.129 1.457

42- 2/4/2016 9:47 1.059 0.161 1.461

43- 2/4/2016 9:47 0.919 0.426 1.178 Slightly abave acceptable

Value

44_ 2/4/2016 9:48 0.932 0.076 1.478

45- 2/4/2016 9:48 1.117 0.200 1.461

46- 2/4/2016 9:48 1.152 1.327 1.478 Very Long Strap

47- 2/4/2016 9:49 0.994 0.042 1.362

48- 2/4/2016 9:49 0.799 0.048 1.371

289 Centre St. Holbrook, MA 02343

STATION BATTERIES IMPEDANCE TEST REPORT

I.D. #: Station Batteries No. of Cells: 92

Battery Mfg: ALCAD Volts per Cell: 1.36

Battery Type: Nickel Cadmium Model: HC34P Minimum Volts: 1.05

Float Volts: 1.40 Equal.Volts: 1.45 Load Amps:

Ambient Temp: 40° F

Humidity:

49- 2/4/2016 9:49 0.944 0.111 1.476 so_ 2/4/2016 9:50 1.012 0.083 1.469

51- 2/4/2016 9:50 0.791 0.080 1.373

52- 2/4/2016 9:50 0.929 0.059 1.483

53- 2/4/2016 9:50 0.951 0.078 1.476

54- 2/4/2016 9:50 0.977 0.060 1.481

55- 2/4/2016 9:51 0.890 0.065 1.432

56- 2/4/2016 9:51 0.920 0.115 1.493

57- 2/4/2016 9:51 0.941 0.077 1.481

58_ 2/4/2016 9:51 0.606 0.065 1.317

59- 2/4/2016 9:52 0.924 0.063 1.373

60_ 2/4/2016 9:52 0.932 0.165 1.471

61- 2/4/2016 9:52 1.012 0.574 1.474

62- 2/4/2016 9:52 1.187 0.059 1.457

63- 2/4/2016 9:52 0.833 0.228 1.351

64- 2/4/2016 9:53 1.024 0.066 1.471

65- 2/4/2016 9:53 1.001 0.127 1.464

66- 2/4/2016 9:53 1.048 0.173 1.447

67- 2/4/2016 9:53 0.932 0.138 1.474

69- 2/4/2016 9:53 1.024 0.580 1.466 Long Strap

70_ 2/4/2016 9:54 0.872 0.043 1.381

71- 2/4/2016 9:54 0.867 0.049 1.381

72- 2/4/2016 9:54 0.952 0.076 1.481

289 Centre St, Holbrook, MA 02343

STATION BATTERIES IMPEDANCE TEST REPORT

Customer: Electrical

Job#: 19366

Location: VAMC - Jamaica Plain Date: 2/4/2020

I.D. #: Station Batteries No. of Cells: 92

Battery Mfg: ALCAD Volts per Cell: 1.36

Battery Type: Nickel Cadmium Model: HC34P Minimum Volts: 1.05

Float Volts: 1.40

Equal.Volts: 1.45 Load Amps:

Ambient Temp: 40° F

Ripple Current:00

73- 2/4/2016 9:54 0.497 0.048 1.305

74_ 2/4/2016 9:55 1.001 0.155 1.478

75- 2/4/2016 9:55 0.977 0.140 1.478

76- 2/4/2016 9:55 0.862 0.043 1.369

77- 2/4/2016 9:55 0.838 0.044 1.442

78- 2/4/2016 9:55 0.895 0.163 1.378

79- 2/4/2016 9:55 0.946 0.050 1.457

80_ 2/4/2016 9:56 0.912 1.012 1.437

81- 2/4/2016 9:56 1.012 0.099 1.471

82- 2/4/2016 9:57 0.924 0.186 1.486

84- 2/4/2016 9:57 0.797 0.060 1.393

85- 2/4/2016 9:57 1.035 0.060 1.457

86- 2/4/2016 9:58 0.943 0.179 1.493

87- 2/4/2016 9:58 1.070 0.143 1.483

88- 2/4/2016 9:58 0.132 0.099 1.461

89- 2/4/2016 9:58 0.946 0.057 1.356

90- 2/4/2016 9:58 0.931 0.749 1.457

91- 2/4/2016 9:59 0.832 1.070 1.466

92- 2/4/2016 9:59 0.060 1.106 1.368

Comments:. Upon completion of inspection, maintenance and testing the battery system is suitable for continued service, but based on the system age replacement should be considered.

formATS_2 Average Cell Imp= 0.951, Average Strap Imp= 0.165, Average Cell Voltage= 1.424

Reference #: 19366 Batt Imp - 1 Tested by: BB,PS

289 Centre Street Holbrook, MA 02343

TRANSFORMER TEST REPORT

Customer: VAMC -Jamaica Plain Job#: 19366

Location: Bldg 1 - Outside Pad - Normal Swbd Date: March 15, 2020

Designation: Bldg 1 - Transformer A - Feeder 1 Temp: 36° F

Manufacturer: Square D Humidity: 41%

Rating (kVA): 3000 / 3360 Prim. Volts/ Connect.: 13.SkV / Delta Date of Mfg.: Aug 1993

Type-class: Pad Mtd / OA # of Prim. Taps/Setting: 5/C Imped.%: 5.98%

Serial#: 930121 -A2 Sec. Volts / Connect.: 480 - 277 / Wye Gals of Oil: 540 Silicone

1. Enclosure OK

2. Radiators OK

3. Bushings OK

4. Coils n/a

5. Insulators n/a

6. Gauges OK

VISUAL AND MECHANICAL INSPECTION

7. Tap Changer OK

8. Arrestors OK

9. Accessories n/a

10. Connections OK

11. Grounding OK

12. Remove Dust OK

Gauge Readings: Fluid Temp = 22°C, Max 56°C (Reset) Pressure = 0.0 PSI, Liquid Level @ 25+0 c

1. Insulation

Resistance

(Mega ohms)

@ 5.0 kVDC: Hi to Grnd.

@ 5.0 kVDC: Hi to Low

@ 1.0 kVDC: Lo to Grnd.

1)

2)

3)

1) Low guarded

2) Grnd guarded

3) High guarded

2. Winding Resistance (ohms):

H1 - H3: X1 - X3: XO - X1:

H2 - H1: X2 - X1: XO - X2:

H3 - H2: X3 - X2: XO - X3:

3. Transformer Turns Ratio:

Comments: Upon completion of lnsp, Maint & Testing the Xfrmr is Suitable for Continued Service.

Lightning Arrestors= Elastimold Type 167 ESA-12, 10.SkV MCOV

Insulation Resistance Test of LA's in Mega-Ohms @ SkVDC:

xfmr.wks H1 = 57,900 H2 = 54,400 H3 = 57,6000

Reference#: 19366 Xfrmr - Bldg 1A Tested By: -B-FB---

123 Felton Street Marlborough, MA 01752 • Imported results - Not acquired by Doble Page 2of4

1 min. 10 min. P.I.

24,906 26,400 1.06

9,977 43,000 4.31

4.695 14,350 3.06

Measured Ratio

Tao No.

Voltaqe

Calculated

Ratio

H1 - Grd

X1 - X2

H1 - Grd

X3 - X2

H1 - Grd

X1 -X3

A 14490 52.310

B 14145 51.065

C 13800 49.819 49.808 49.825 49.825

D 13455 48.574

E 13110 47.329

289 Centre Street Holbrook, MA 02343

Customer: VAMC -Jamaica Plain Job#: 19366

Location: Bldg 1 - Outside Pad - Normal Swbd Date: March 15, 2020

Designation: Bldg 1 - Transformer B - Feeder 2 Temp: 38° F

Manufacturer: General Electric - Prolec Humidity: 43% Rating (kVA): 3000 Prim. Volts/ Connect.: 13.SkV / Delta Date of Mfg.: Nov 2017

Type-class: Pad Mtd / Q A # of Prim. Taps/Setting: 5/C Imped.%: 5.78%

Serial#: M17J24830 Sec. Volts / Connect.: 480 - 277 I Wye Gals of Oil: 502 Nat Ester

1. Enclosure OK

2. Radiators OK

3. Bushings OK

4. Coils n/a

5. Insulators n/a

6. Gauges OK

VISUAL AND MECHANICAL INSPECTION

7. Tap Changer OK

8. Arrestors OK

9. Accessories n/a

10. Connections OK

11. Grounding OK

12. Remove Dust OK

Gauge Readings: Fluid Temp = 24°C, Max 56°C (Reset} Pressure = 0.0 PSI, Liquid Level @ 25°C

ELECTRICAL TESTS

1. Insulation

Resistance

(Mega ohms)

@ 5.0 kVDC: Hi to Grnd.

@ 5.0 kVDC: Hi to Low

@ 1.0 kVDC: Lo to Grnd.

1)

2)

3)

1) Low guarded

2) Grnd guarded

3) High guarded

2. Winding Resistance (ohms):

H1 - H3: X1 - X3: XO - X1:

H2 - H1: X2 - X1: XO - X2:

H3 - H2: X3 - X2: XO - X3:

Comments: Upon completion of lnsp, Maint & Testing the Xfrmr is Suitable for Continued Service.

Lightning Arrestors = Hubble 12.?kV MCOV

Insulation Resistance Test of LA's in Mega-Ohms@ 5kVDC:

xfmr.wks H1 = 737,000 H2 = 856,000 H3 = 921,000

Reference #: 19366 Xfrmr - Bldg 1B Tested By: -B-FB---

1 min. 10 min. P.I.

31,789 39,100 1.23

214,000 647,000 3.02

3.822 8.370 2.19

Tao No.

Voltaae

Calculated

Ratio

H1 - Grd

X1 - X2

H1 - Grd

X3 - X2

H1 - Grd

X1 -X3

A 14490 52.310

B 14145 51.065

C 13800 49.819 49.795 49.800 49.800

D 13455 48.574

E 13110 47.329 seconds seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURVE DATA:

CURVE#:

Temp/Humidity:

In. Cap. (kA)

_85.@508V

INJECTION:

Primary:

Volts/Used: 635/480 Secondary: X

A=Amp

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time @ 300 % 6T 23s 23s 23s

S.D.P.U.

S.D.Time

I@ 150 % 6T OK OK OK

Instantaneous 6T OK OK OK

Gnd.P.U.

Gnd.Time

@ 150 % GFT OK OK OK

Contact Resistance

(micro-ohms) 19 20 22

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Control Wiring

INSULATION RESISTANCE@ 250 VDC (mega-ohms): OK

..Pi_quette & Howard SETTINGS: Found Left

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=4000A

..MainjNormal) LD TIME 24.0s

MalnB Cell 1B SD PICKUP 4.0x=16000A

OS 11840 SD TIME 0.5s 12T Out

Cutler Hammer INST. M1=32000A

ARMS. N/A

HUBS42253 GND. P/U B=1200A

72°F I 30% GND.TIME 0.5s 12T Out

Trip Unit:

Frame Size(A):

.P.!e.!. r.!.P- RMS 510 LSIG Cat No. S56LSIG ( .)

OPERATION: Manual:

Electric:

X X

Sensor/Plug(A): 4000/4000 Cat No. RP6D40A400 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip: 120VAC seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURVE DATA:

CURVE#:

In. Cap. (kA) 200@508V INJECTION: Primary:

Volts/Used: 635/480 Secondary: X

Trip Unit: ..Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X

Frame Size(A): 800 Electric:

Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out

Charge/CIose/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amos as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time I@ 300 %

GT 19s 19s 19s

I@ 150 %

GT OK OK OK

Instantaneous GT OK OK OK

Gnd.P.U. Fuse Cat No. 60SL-B1600

Gnd.Time (@ 150 %

GFT OK OK OK

(micro-ohms) 95 80 88 50 51 52

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

INSULATION RESISTANCE@ 250 voe (mega-ohms): OK

Pi_quette & Howard SETTINGS: Found Left

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=600A

Main {Normal) LD TIME 24.0s

.. eare Cell 1C SD PICKUP 6.0x=3600A

DSL-206 SD TIME 0.2s I2T Out

_s_quare D INST. M1=4800A

ARMS. N/A

CNTJ80785 GND. P/U C=210A

72°F / 30% GND.TIME 0.2s I2T Out seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURVE DATA:

CURVE#:

In. Cap. (kA) ..200@508V INJECTION: Primary:

Volts/Used: 635/480 Secondary: X

Trip Unit: ..Digitrie RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X Frame Size(A): 800 Electric:

Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out

Charge/CIose/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

6T 19s 19s 19s

6T OK OK OK

Gnd.P.U. Fuse Cat No. 6DSL-B1600

Gnd.Time

62 63 57 50 51 51

INSULATION RESISTANCE @1000 VDC - Mega-ohms

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

SETTINGS: Found Left

VAMC Jamaica Plain - Building 1 -Sub Basement LO PICKUP 1.0x=600A

_Main (Normal) LO TIME 24.0s

DDP-H Cell 2B SD PICKUP 6.0x=3600A

DSL-206 SD TIME 0.2s 12T Out

.s,quare D INST. M1=4800A

ARMS. N/A

72°F / 30% GND.TIME 0.2s 12T Out seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

L.D.Time @ 300 %

(ru 150 %

Gnd.Time

59 67 72 52 51 51

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=800A

Main (Normal) LD TIME 24.0s

BDP-H1 Cell 2C SD PICKUP 6.0x=4800A

DSL-206 SD TIME 0.2s I2T Out

.. . uare D INST. M1=6400A

ARMS. NIA

CNTJ80785 GND. P/U C=280A

72°F / 30% GND.TIME 0.2s I2T Out

In. Cap. (kA)

Volts/Used:

Trip Unit:

..200 @_5_0_8V

635/480

,,Oigitrip RMS 500 LSIG Cat No. T56BLSIG

INJECTION: Primary:

Secondary:

OPERATION: Manual:

Frame Size(A): 800 Electric:

Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

I<@ 300 % GT 19s 19s 19s

Gnd.P.U. Fuse Cat No. GDSL-D3000

Gnd.Time @ 150 %

23 25 26 18 16 16

INSULATION RESISTANCE@ 1000 VDC - Mega-ohms

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=B00A

Main (Normal) LD TIME 24.0s

SBDPA Cell 2O SD PICKUP 6.0x=4800A

DSL-416 SD TIME 0.2s I2T Out

..s.guare D INST. M1=6400A

ARMS. N/A

CNTJ80785 GND. P/U C=280A

Temp/Humidity: 72°F / 30% GND.TIME 0.2s I2T Out

In. Cap. (kA) _200 @_5_08_V INJECTION: Primary:

Volts/Used: 635/480 Secondary: X

Trip Unit: ,,Oigitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X

Frame Size(A): 1600 Electric:

Sensor/Plug(A): 1600/800 Cat No. PD6D16A080 Fixed Mount/ Draw-Out: Draw-Out seconds to:

seconds to:

L.D. Time:

S.D. Time:

200@_5_0_8V

Volts/Used:

Trip Unit:

Frame Size(A):

635/480 Secondary: X

..Digitrie RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:

Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

(@ 300 %

Gnd.Time

(@. 150 %

72 60 58 51 53 54

INSULATION RESISTANCE@1000 VDC- Mega-ohms

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=600A

..MainJNormal) LD TIME 24.0s

DP-X Cell 3C SD PICKUP 6.0x=3600A

DSL-206 SD TIME 0.2s I2T Out

..s.guare D INST. M1=4800A

ARMS. N/A

..200 @_5_08_V

635/480

Secondary: X

Trip Unit:

Frame Size(A):

..Di9.itrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X

1600 Electric:

Sensor/Plug(A): 1600/1600 Cat No. PD6D16A160 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

Gnd.P.U. Fuse Cat No. 6DSL-D3000

Gnd.Time

{micro-ohms) 31 32 29 17 16 16

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

CURVE DATA: L.D. Time: seconds to: seconds

CURVE#: S.D. Time: seconds to: seconds

Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds

VISUAL INSPECTION

1. Arc Chutes.

2. Contacts

3. Aux.Devices:

4. Wiring

5. Counter

6. Mechanism:

?.Lube a.Racking

9. Close,Trip OK

10. Electric Operation:

REMARKS: Upon completion of inspection and testing, the circuit breaker is suitable for service.

Connection Diagram 44025-167: 2C

Pi_quette & Howard SETTINGS: Found Left

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=1600A

Main (Normal} LD TIME 24.0s

Building 1A DP1 Cell 3D SD PICKUP 6.0x=9600A

DSL-416 SD TIME 0.2s 12T Out

..s.quare D INST. M1=12800A

ARMS. N/A

CNTJ80785 GND. P/U C=560A

In. Cap. (kA) ..85@ 508V

Trip Unit: ,,Oigitrie RMS 510 LSIG OPERATION: Manual: X Frame Size(A): 4000 Electric: X sensor/Plug(A): _4_0_00_/_40_0_0 C_at_N_o_. Fixed Mount/ Draw-Out:

Charge/Close/Trip:

Draw-Out

120VAC

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

(@. 300 % ST 13s 13s 13s

(Q) 150 %

ST OK OK OK

Instantaneous ST OK OK OK

Gnd.Time

17 13 18

INSULATION RESISTANCE@1000 VDC- Mega-ohms

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds

1.Arc Chutes.

2.Contacts

3.Aux.Devices:

4.Wiring

5.Counter

VISUAL INSPECTION

6.Mechanism:

7. Lube

VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=4000A

Main {Normal) LD TIME 15.0s

Tie Cell 4C SD PICKUP 3.0x=12000A

DS 11840 SD TIME 0.4s 12T Out

Cutler Hammer INST. M1=32000A

ARMS. N/A

HUBS42253 GND. P/U A=600A

72°F / 30% GND.TIME 0.Ss I2T Out

200@_5_0_8V

Trip Unit:

Frame Size(A):

635/480 Secondary: X

Digitrie RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 1600 Electric:

Sensor/Plug(A): 1600/800 Cat No. PD6D16A080 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

l@ 300 % 6T 18s 18s 18s

Gnd.P.U. Fuse Cat No. 6DSL-D3000

Gnd.Time l@ 150 %

24 27 23 19 18 16

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds

VISUAL INSPECTION

1. Arc Chutes.

2. Contacts

3. Aux.Devices:

4. Wiring

5. Counter

6. Mechanism:

Connection Diagram 44025-167: 2C

Pi_quette & Howard SETTINGS: Found Left

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=S00A

Main (Normal} LO TIME 24.0s

ADPH Cell 4D SD PICKUP 6.0x=4800A

DSL-416 SD TIME 0.2s I2T Out

Square D INST. M1=6400A

ARMS. N/A

CNTJ80785 GND. P/U C=280A

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

L.D.Time

6T 20s 20s 20s

@ 150 % 6T OK OK OK

@ 150 % GFT OK OK OK

51 57 56 50 47 50

INSULATION RESISTANCE@1000 VDC - Mega-ohms

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds

VISUAL INSPECTION

1. Arc Chutes.

2. Contacts

3. Aux.Devices:

4. Wiring

5. Counter

6. Mechanism:

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=400A

Main (Normal) LDTIME 24.0s

Transformer T2BL Cell 5A SD PICKUP 6.0x=2400A

DSL-206 SD TIME 0.2s I2T Out

Square D INST. M1=3200A

ARMS. N/A

CNTJ80785 GND. P/U C=140A

Temp/Humidity: 72°F / 30% GND.TIME 0.2s I2T Out

In. Cap. (kA) ..200 @_5_08_V INJECTION: Primary:

Volts/Used: 635/480 Secondary: X

Trip Unit: ..Digitrie RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X

Frame Size(A): 800 Electric:

Sensor/Plug(A): _8_00_/_4_0 0 C_at_N_o_._R_P_6_D_0_8_A_0_4 0 Fixed Mount/ Draw-Out: Draw-Out

In. Cap. (kA) ..200 @_5_08_V INJECTION: Primary:

Trip Unit:

Frame Size(A):

635/480 Secondary: X

..Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X

800 Electric:

Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

.@ 300 %

Gnd.Time

68 62 74 51 52 54

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ 8-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Inst. P.U: amps to: amps Gnd. Time: seconds to: seconds

VISUAL INSPECTION

1. Arc Chutes.

2. Contacts

3. Aux.Devices:

4. Wiring

5. Counter

6. Mechanism:

?.Lube

Pi,quette & Howard SETTINGS: Found Left

Main (Normal) LD TIME 24.0s

MCC-HF Cell 5B SD PICKUP 6.0x=2400A

FH-1 SD TIME 0.2s I2T Out

Square D INST. M1=3200A

ARMS. N/A

CNTJ80785 GND. P/U C=140A

seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURVE DATA:

CURVE#:

In. Cap. (kA) ..200@508V INJECTION: Primary:

Volts/Used: 635/480 Secondary: X Trip Unit: ,,Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X

Frame Size(A): 800 Electric:

Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out

Charge/CIose/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

(Q)_ 150 %

Gnd.Time

61 71 65 50 51 48

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Main (Normal) LD TIME 24.0s

EDP-H Cell 5C SD PICKUP 6.0x=2400A

DSL-206 SD TIME 0.2s I2T Out

_s,guare D INST. M1=3200A

ARMS. N/A

seconds to:

seconds to:

L.D. Time:

S.D. Time:

..200@508V

Trip Unit: ,,DiQitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X Frame Size(A): 800 Electric:

Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out

Charge/CIose/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE 8 PHASE C PHASE A PHASE 8 PHASE C

L.D.P.U.

L.D.Time

6T 18s 18s 18s cm 150 %

Gnd.Time

59 53 58 50 54 50

Phase to Ground: A: 4000+ 8: 4000+ C: 4000+

Phase to Phase: A-8: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ 8: 4000+ C: 4000+

VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=S00A

Main (Normal) LD TIME 24.0s

ATS-EV Cell 6B SD PICKUP 6.0x=4800A

DSL-206 SD TIME 0.2s I2T Out

_s,guare D INST. M1=6400A

ARMS. N/A

seconds to:

seconds to:

L.D. Time:

S.D. Time:

.200 @_5_0_8V

Trip Unit:

Frame Size(A):

..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:

Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out

Control Wmng

VAMC Jamaica Plain - Building 1 - Sub Basement LD PICKUP 1.0x=S00A

Main (Normal) LD TIME 24.0s

CDPH1 Cell 6C SD PICKUP 6.0x=4800A

DSL-206 SD TIME 0.2s I2T Out

..s,9uare D INST. M1=6400A

ARMS. N/A

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

(a) 300 %

(a) 150 %

Gnd.Time @. 150 %

69 59 64 53 53 52

INSULATION RESISTANCE@1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+ seconds to:

seconds to:

L.D. Time:

S.D. Time:

.200 @_5_0_8V

Trip Unit:

Frame Size(A):

635/480 Secondary: X

,,Oigitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:

Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out

Main (Normal) LD TIME 24.0s

DDPH1 Cell 6O SD PICKUP 6.0x=3600A

DSL-206 SD TIME 0.2s I2T Out

..s,quare D INST. M1=4800A

ARMS. N/A

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time t'@ 300 %

!'@ 150 %

I@ 150 % GFT OK OK OK

59 53 58 50 54 50

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+ seconds to:

seconds to:

L.D. Time:

S.D. Time:

.. . ... @_5_08_V

Trip Unit:

Frame Size(A):

..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:

Sensor/Plug(A): 800/800 Cat No. RP6D08A080 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

6T 8s 8s 8s

Gnd.Time

65 71 62 52 51 52

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=800A

Main (Normal) LD TIME 10.0s

Building 1A MCC-4A Cell 7B SD PICKUP 5.0x=4000A

DSL-206 SD TIME 0.2s I2T Out

_quare D INST. 6.0x=4800A

ARMS. N/A

CNTJ80785 GND. P/U A=210A

seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURVE DATA:

In. Cap. (kA) 200@508V

INJECTION: Primary:

Trip Unit: ,_Digitrip RMS 500 LSIG Cat No. T56CLSIG OPERATION: Manual: X

Frame Size(A): 800 Electric:

Sensor/Plug(A): 800/400 Cat No. RP6D08A040 Fixed Mount/ Draw-Out: Draw-Out

Charge/CIose/Trip:

..Pi,quette & Howard SETTINGS: Found Left

Main (Normal) LD TIME 24.0s

Cath Lab Cell 7C SD PICKUP S2=4000A

DSL-206 SD TIME 0.2s I2T Out

S_quare D INST. M1=3200A

ARMS. N/A

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

ca) 150 %

Gnd.Time

(micro-ohms) 73 64 70 51 51 46

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+ seconds to:

seconds to:

L.D. Time:

S.D. Time:

CURVE DATA:

CURVE#:

In. Cap. (kA) ..200 @_5_08_V INJECTION: Primary:

Volts/Used:

Trip Unit:

Frame Size(A):

635/480 Secondary: X

..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X 800 Electric:

Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

IC@. 300 %

GT 19s 19s 19s

(@. 150 %

Gnd.Time

{micro-ohms) 60 64 62 51 51 49

INSULATION RESISTANCE@ 1000 voe - Mega-ohms

Phase to Ground: A: 4000+ B: 4000+ C: 4000+

Phase to Phase: A-8: 4000+ 8-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Main (Normal) LDTIME 24.0s

Building 2 Cell 70 SD PICKUP 6.0x=3600A

DSL-206 SD TIME 0.2s I2T Out

Square D INST. M1=4800A

ARMS. N/A

seconds to:

seconds to:

L.D. Time:

S.D. Time:

S.0.#:

..200 @.'--5_0_8V

Trip Unit:

Frame Size(A):

635/480 Secondary: X

..Digitrip RMS 500 LSIG Cat No. T56BLSIG OPERATION: Manual: X

800 Electric:

Sensor/Plug(A): 800/600 Cat No. RP6D08A060 Fixed Mount/ Draw-Out: Draw-Out

Charge/Close/Trip:

TEST RESULTS

A=Amp

S=Second

CURRENT

Amps as found as left

PHASE A PHASE B PHASE C PHASE A PHASE B PHASE C

L.D.P.U.

LO.Time

Gnd.P.U. Fuse Cat No. 6DSL-B1200

Gnd.Time

77 72 62 58 57 50

Phase to Phase: A-B: 4000+ B-C: 4000+ A-C: 4000+

Across Contact: A: 4000+ B: 4000+ C: 4000+

Pi uette & Howard SETTINGS: Found Left

VAMC Jamaica Plain - Building 1 -Sub Basement LD PICKUP 1.0x=600A

Main (Normal) LD TIME 24.0s

..!Pare Cell 8C SD PICKUP 6.0x=3600A

DSL-206 SD TIME 0.2s I2T Out

Square D INST. M1=4800A

ARMS. N/A

80Y5925 GND. P/U C=210A

seconds to:

seconds to:

L.D. Time:

S.D. Time:

G.0#:

. ............... V

Trip Unit: ..!?..!9..!!. .!.e RMS 510 LSIG Cat No. S56LSIG ( .)...