ELECTRICAL FLOOR PLANS - AREA B.pdf
PDF 342 KB Posted
- Attached to
- Metal Fabrication Equipment
- Solicitation number
- 6100049057
- Issued by
- Clearfield County, Manns Choice Borough, Pennsylvania
About this file
This document appears to be an electrical floor plan for Area B of the Construction of Building 6 project for the Pennsylvania Department of General Services. The plan details the electrical layout, including the location of various electrical equipment and fixtures such as panels, receptacles, lighting, and mechanical equipment connections. Key details include the conduit routing, circuit designations, and equipment specifications. The document also includes general notes regarding the installation, coordination, and requirements for the electrical work. No additional information about the contract opportunity or procurement process is provided in the document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BOP-1304 Request to Advertise 9-27-19.pdf | ||
| SCI Forest - Preliminary Load Calculation.pdf | ||
| Terms & Conditions.pdf | ||
| Specifications 9.25.19.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F F F
F
F
F
J
F
F
F
F
J
F
F M
F
FFF
F
F
F
F
F
F
F
F
F
F P
F P
F
F F
J
J
F
J
F
F
J
GFI GFI GFI GFI GFI
J
J
J
J
J
J
J G
FIG
FI
G
FI
GFI
G
FI
GFI
G
FI
G
FI
G
FI G
FI
B
32 32.1 33 34
A
C
D
E
F
G
G.5
35 36 37 38 39 40 41 42 43
HP6-37,39,41
EWH 6-1
RP6C-20
RP6C-20
RP6C-20
RP6C-19
RP6C-19
RP6C-19
RP6C-19
RP6C-18
RP6C-18
RP6C-18 RP6C-18RP6C-17
RP6C-17
RP6C-17
RP6C-16
RP6C-16
RP6C-16
RP6C-16
HP6-38,40,42
EWH 6-2
RP6C-21
RP6C-21 RP6C-21
RP6C-22 RP6C-22 RP6C-22 RP6C-22RP6C-19
WG WG
WG
WG
RP6C-23
RP6C-23
RP6C-23
RP6C-23
WG
WG WG
WG
WG
WG
RRP6A-35
AD 6-1
WG
WG
WGWGWG
WG
WG
WG
WG
WG
WG
PP6W RP6C
TS
T
T
PLOW STAGING BAY
TEAR DOWN BAY
PAINT BOOTH DRYING BOOTH
SAND BLASTING BOOTH
PALLET STORAGE
FORKLIFT STORAGE
PALLET STORAGE
PALLET STORAGE
WELDING STATIONS
1 2 3 4
PLASMA CUTTER GAS WELDERS
PALLET STORAGE
IRON WORKER
BRAKE PRESS
HEAVY DUTY LIFT SYSTEM
BAND SAW
SHEAR
DRILL PRESS?
MILL
BENDER
EX
EX
EXEX
EX
EX
RP6A-6
RP6A-6
RP6A-6
RP6A-6
RP6A-31
RP6A-33
RP6A-16
RP6A-16
RP6A-9
WR1
WG
WG
RP6C-1,3
EXISTING OVERHEAD
DOOR AND CONTROLS
EXISTING OVERHEAD
DOOR, AIR CURTAIN
AND CONTROLS
MDS6-3
A
A
R
E
HP6 - 61,63,65
WHEEL REFINISHING UNIT
(EXISTING TO REMAIN)
EX
B
MDS6-6
RP6A-19 2
2 2
C
RP6C
6 6
HP62
EXISTING EXIT
SIGN (TYP.)
EXISTING LIGHT
FIXTURE (TYP.)
EXISTING SMOKE
DETECTOR (TYP.)
EXISTING
RECEPTACLE (TYP.)
EXISTING FIRE ALARM
DEVICE (TYP.)
T
EXISTING OVERHEAD
DOOR, AIR CURTAIN
AND CONTROLS
A
B C
MDS6-7
HP6-44,46,48
HP6-50,52,54
HP6-43,47,49
AD 6-1
CORD REEL (TYP.) CORD REEL (TYP.)
G
Q P
NEW 480V/3PH 225A
MCB PANEL
EQUIPMENT MOUNTED
JUNCTION BOX (TYP.)
E
E
E
F F P
JACK STANDS?F
L
L
R
O
O
K
K
M
M
J
J
N
N
PP UUUPU
Q
AIR CURTAIN
HP6-8,10,12
DRAWN BY: DATE:
CHECKED BY: SCALE:
DRAWING NO.
COMMONWEALTH OF PENNSYLVANIA
DEPARTMENT OF GENERAL SERVICES
HARRISBURG, PENNSYLVANIA
209 SANDUSKY STREET
PITTSBURGH, PA 15212
PH: 412-287-7333
Professional's Signature Date Professional's Signature Date
KEY PLAN
AE WORKS
1/8" = 1'-0"
AEW 04/19/2019
AEW
E-1.2
ELECTRICAL FLOOR PLANS - AREA B
SCI FOREST - COMPLETE CONSTRUCTION
OF BUILDING 6
286 Woodland Drive Marienville, PA 16239
PROJECT NO. DGS A-0377-001 PHASE 2
FOR CONSTRUCTION
1/8" = 1'-0"E-1.2
1 ELECTRICAL NEW WORK PLAN - AREA B
ELECTRICAL SHEET GENERAL NOTES
1 FINAL LOCATION OF ALL EQUIPMENT SHALL BE DETERMINED IN THE FIELD AND SHALL
BE INSTALLED AS DIRECTED BY THE ARCHITECT OR CLIENT'S AGENCY. WHERE
STRUCTURAL OPENINGS ARE NOT AVAILABLE, THE CONTRACTOR SHALL CORE DRILL
WALLS AND FLOORS AS REQUIRED TO PERMIT PASSAGE OF CONDUITS. THE
ELECTRICAL CONTRACTOR SHALL PROVIDE A MARKED-UP PLAN WITH LOCATION
PENETRATIONS FOR REVIEW AND APPROVAL OF THE STRUCTURAL ENGINEER
BEFORE ROUGH-IN BEGINS.
2 RECEPTACLES FOR ALL EQUIPMENT SHALL BE COMPLETE WITH PLUGS FOR THIS
EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL VERIFY NEMA CONFIGURATIONS
OF PLUGS AND RECEPTACLES FOR EQUIPMENT IN THE SPACE.
3 THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAKE ALL FEEDER RUNS
CONTINUOUS (NO CABLE BREAKS). IF SPLICING CABLES IN BOXES BECOMES
NECESSARY, USE O.Z.G. TYPE "XW" CABLE TAPS, OR APPROVED EQUAL, AND TAPE
EACH TAP IN APPROVED MANNER.
4 THE MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES, VFD'S. OR
COMBINATION STARTERS FOR ALL OF THEIR UNITS. THE ELECTRICAL CONTRACTOR
SHALL RECEIVE THESE ITEMS FROM THE MECHANICAL CONTRACTOR FOR
INSTALLATION BY THE ELECTRICAL CONTRACTOR.
5 THE ELECTRICAL CONTRACTOR SHALL COORDINATE CONDUIT PENETRATIONS FOR
ROOFTOP EQUIPMENT WITH MECHANICAL AND ROOFING CONTRACTORS. IF
PROVISIONS ARE NOT IN PLACE FOR THESE PENETRATIONS THE ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING OWN PENETRATIONS AND
CONTRACTING THE ROOF CONTRACTOR FOR SEALING THE ROOF PENETRATIONS.
6 REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT.
7 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO
CONFORM TO NEC REQUIREMENTS.
8 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO
PANELBOARD SCHEDULES.
9 REFER TO EQUIPMENT CONNECTION SCHEDULE FOR ELECTRICAL REQUIREMENTS
AND CIRCUIT DESIGNATIONS.
10 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS
WHERE NECESSARY TO AVOID DUCT WORK AND HVAC SYSTEM.
11 VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT
WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO INSTALLATION OF
EQUIPMENT.
12 EXISTING ELECTRICAL DEVICES, INCLUDING BUT NOT LIMITED TO, OUTLETS, FIRE
ALARM DEVICES, LIGHT FIXTURES AND DISCONNECT SWITCHES SHALL REMAIN IN
PLACE UNLESS NOTED OTHERWISE. PROVIDE PROTECTIVE COVERS ON SMOKE
DETECTORS DURING CONSTRUCTION.
13 FINAL LOCATIONS OF ELECTRICAL CONNECTIONS SHALL BE COORDINATED WITH
EQUIPMENT MANUFACTURER, DOC AND FINAL EQUIPMENT LAYOUT.
ELECTRICAL KEYNOTES
1 EXISTING JUNCTION BOX AND CIRCUIT FOR CONNECTION TO SECURITY SYSTEM.
2 RELOCATE EXISTING DEVICES AND EXTEND WIRING TO NEW LOCATIONS.
COORDINATE WITH FINAL LOCATIONS OF NEW EQUIPMENT.
3 PROVIDE A JUNCTION BOX, CONDUIT AND CIRCUIT FOR SECURITY CAMERA
CONNECTION SIMILAR TO EXISTING.
4 CEILING MOUNTED CORD REEL AND OUTLETS. REFER TO EQUIPMENT CONNECTION
SCHEDULE AND PROVIDE CEILING MOUNTED LOCKABLE SINGLE RECEPTACLE AT
EACH LOCATION FOR POWER CONNECTION TO CORD REELS.
5 EQUIPMENT MOUNTED JUNCTION BOX WITH DIRECT CONNECTION TO EQUIPMENT
WITH LFMC. HOMERUN CIRCUIT SHALL BE RUN UNDERGROUND. COORDINATE
CONDUIT STUB UP LOCATIONS IN FIELD WITH EQUIPMENT LAYOUT AND
CONNECTION POINT.
6 WATER HEATER (GAS) RECEPTACLES IN WEATHER PROOF IN-USE TYPE METALLIC
ENCLOSURES.
DESCRIPTION DESCRIPTION
| Sheets |
| E-1.2 - ELECTRICAL FLOOR PLANS - AREA B |
File details come from the government source that posted it. Updated .