David.Sanford Callout Add 5/8" fire rated plywood surfacing over previously specified drywall on all interior wall surfaces in the electrical room portion of the building, in accordance with the Special Note on this sheet.

David.Sanford Line

David.Sanford Line

David.Sanford Polygonal Line

David.Sanford Line

David.Sanford Text Box SPECIAL NOTE- Electrical Room Wall Surfacing.

As shown on the plan on this sheet, provide 5/8" fire rated plywood over the drywall surfacing on all interior walls of the electrical room in accordance with the following:

1. Overlay plywood over the drywall and fasten to studding system using proper code-compliant fasteners at minimum spacings.

2. Plywood shall extend up 8 feet from the floor level, i.e. cover the lower 8 feet of the wall with the plywood.

3. Finish all edges and perimeters of plywood with FRP J-bead

4. Prime and paint plywood to match interior color and finish as specified.

5. Other aspects of the interior wall construction do not change from the project specifications

David.Sanford Text Box

David.Sanford Text Box 8/10/17

David.Sanford Text Box Add plywood surfacing to the lower 8' of electrical room interior walls