Drawings.pdf

PDF 6 MB Posted

Attached to
Fire and Intrusion Alarms Replacement Federal contract opportunity
Solicitation number
140P6425B0009
Issued by
Department of the Interior National Park Service Midwest Region

About this file

These are detailed architectural and electrical drawings for the Park-Wide Replacement of Fire & Intrusion Alarms at the Dayton Aviation Heritage National Historical Park in Dayton, Ohio. The comprehensive set of 37 drawings covers five buildings (16 S. Williams, 22 S. Williams, 26 S. Williams, 30 S. Williams, and 277 S. Williams) and includes electrical demolition plans, camera installation details, site plans, electrical symbols, and specific floor plans for basement, first, second, and third levels.

The drawings outline a complete system replacement involving removal of existing fire alarm, intrusion alarm, and security camera systems, and installation of new wireless systems. Key specifications include using specific camera models like Axis M3216-LVE and P3737-PLE, running plenum-rated Category 6A cabling through existing conduits, integrating with existing communications racks, and ensuring compatibility with the National Park Service's Milestone VMS server. The project involves precise camera positioning, routing of new cabling, and coordination with the Contracting Officer Representative for exact mounting locations and heights.

View the file

Other files for this federal contract opportunity

Other files attached to Fire and Intrusion Alarms Replacement, newest first.
File Type Posted
Questions_and_Answers_0001.pdf PDF
Sol_140P6425B0009_Amd_0001.pdf PDF
Sol_140P6425B0009.pdf PDF
Specifications.pdf PDF
Limitations_on_Subcontracting_Report.xlsx XLSX spreadsheet
Bid_Schedule.xlsx XLSX spreadsheet
Bid_Schedule.pdf PDF
Alarms_Product_File.pdf PDF
DOL_Wage_Determination.pdf PDF
Submittal_List.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

277 S. WILLIAMS

22 S. WILLIAMS -WRIGHT BICYCLE SHOP

16 S. WILLIAMS

26 (LEFT) & 30 S. WILLIAMS

PHOTO SHEET

A1

Ja n

, 2

- 2 :2

9p m

C :\1

To dd

\1 A-

KH

A wo rk

\1

-0 p ar ks

A lar m s a nd F ire P ro te cti on

\D

AA

V\

DR

AW

IN

GS

\ 0

0_

DA

AV

A

Ph ot o

Sh ee t 2

4.

dw g

- U

SE

R to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

LOCATE FIRE ALARM NOTIFICATION

DEVICE UNDER EAVE WITH CLEAR

LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE ELECTRICAL.

KEYED NOTES

LOCATE FIRE ALARM NOTIFICATION

DEVICE WITH A CLEAR LINE OF

SIGHT. COORDINATE LOCATION

WITH CO/COR. INSTALL

WEATHERTIGHT. SEE ELECTRICAL.

INSTALL CAMERAS PER E1C.

COORDINATE LOCATION AND

ELEVATION WITH CO/COR. LOCATE

CAMERAS WITH CLEAR LINE OF

SIGHT. INSTALL WEATHERTIGHT.

SEE CAMERA SHEETS.

INSTALL CAMERAS PER E2C.

LOCATE CAMERAS WITH CLEAR LINE

OF SIGHT. INSTALL WEATHERTIGHT.

SEE CAMERA SHEETS.

INSTALL CAMERA PER E3C/E5C.

COORDINATE LOCATION AND

ELEVATION WITH CO/COR. LOCATE

CAMERAS WITH CLEAR LINE OF

SIGHT. INSTALL WEATHERTIGHT.

SEE CAMERA SHEETS.

INSTALL CAMERA AT EACH BUILDING

CORNER (TYP) PER E6C.

COORDINATE ELEVATION WITH

CO/COR. VERIFY CAMERAS HAVE

CLEAR LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE CAMERA

SHEETS.

UP

DN

STORAGE

STORAGE

STORAGE

STAIR

S5

EXHIBITS

EXHIBITS

EXHIBITS

EXHIBITS

EXHIBITS

FOYER

EXHIBITS

PRINTSHOP

SUITE

PRINTSHOP

SUITE

PRINTSHOP

SUITE

CORRIDOR

EXHIBITS

EXHIBITS

EXHIBITS

EXHIBITS

STAIR

HALL

STAIR

S4

CORRIDOR

OFFICE

LIBRARY

WORKROOM

STAIR

HALL

STAIR

S4

16 S. WILLIAMS PLANS-W

FIRE ALARM/INTRUSION ALARM

A2

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

FIRST FLOOR PLAN

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

BASEMENT PLAN

N

GENERAL NOTES

G1. PATCH/REPAIR/PAINT CEILING/WALL

FINISHES AS REQUIRED TO MATCH

ADJACENT AREA WHERE NEW

DEVICES DON'T COMPLETELY

COVER OLD DEVICE LOCATIONS.

G2. PATCH CEILING/WALL WHERE A

DEVICE/CONDUIT WAS REMOVED

AND NOT REPLACED AT THE SAME

LOCATION.

G3. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ DEMOLITION/

PATCHING; PAINT ENTIRE CEILING/

WALL PLANE CORNER TO CORNER,

EDGE TO EDGE. PAINT COLOR AND

FINISH TO MATCH ADJACENT

CEILING/ WALL.

G4. BUILDING HAS WALL/ CEILING

COVERINGS (W/CC) IN SOME

ROOMS. CONTRACTOR IS TO

PROTECT W/CC AND MAKE EFFORT

TO NOT HAVE TO PATCH OR REPAIR

W/CC. CONTRACTOR IS

RESPONSIBLE TO PATCH /REPAIR

W/CC IF NEEDED BY REMOVAL/

DEMOLITION SCOPE OR IF DAMAGE

IS INCURRED BY THE GC.

LOCATE FIRE ALARM NOTIFICATION

DEVICE WITH A CLEAR LINE OF

SIGHT. COORDINATE LOCATION

WITH CO/COR. INSTALL

WEATHERTIGHT. SEE AX AND

ELECTRICAL.

KEYED NOTES

Ja n

, 2

- 2 :3

0p m

C :\1

To dd

\1 A-

KH

A wo rk

\1

-0 p ar ks

A lar m s a nd F ire P ro te cti on

\D

AA

V\

DR

AW

IN

GS

\ 1

6_

DA

AV

_A

FL

R

PL

N

.d wg

US

ER

to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

THIRD FLOOR PLAN

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

SECOND FLOOR PLAN

N

REPAIR DOOR FRAME WHERE

CONTACT WAS REMOVED, IF

NEEDED, PRIOR TO INSTALLING

NEW DEVICE. FINISH TO MATCH

FRAME. (TYP.)

INSTALL CAMERAS PER E1C.

COORDINATE LOCATION AND

ELEVATION WITH CO/COR. LOCATE

CAMERAS WITH CLEAR LINE OF

SIGHT. INSTALL WEATHERTIGHT.

SEE CAMERA SHEETS.

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

CRAWL

SPACE

STORAGE

ELEV.

EQ.

PASSAGE

WAY

STAIR

S1

STAIR

S2

EXHIBIT

THEATER

111EQUIP.

RM

KITCHNT.

MEN

WOMEN

J.C.

COM.

CLOSET

ATRIUM

STAIR

S3

STAIR

S1

BOOKSTORE

GIFTSHOP

STAIR

S2

VESTIBULE

EXHIBIT

KITCHNT.

CONF.

RM.

COAT

RM.

CONF.

RM.

OFFICE

201A

MEN

WOMEN

STAIR

S1

J.C.

CORRIDOR

ATRIUM

STAIR

S3

ROOF

R1

BREAK

RM.

BOILER

RM.

CORRIDOR

MEN

J.C.

WOMEN

STAIR

S1

GENERAL NOTES

G1. PATCH/REPAIR/PAINT CEILING/WALL

FINISHES AS REQUIRED TO MATCH

ADJACENT AREA WHERE NEW

DEVICES DON'T COMPLETELY

COVER OLD DEVICE LOCATIONS.

G2. PATCH CEILING/WALL WHERE A

DEVICE/CONDUIT WAS REMOVED

AND NOT REPLACED AT THE SAME

LOCATION.

G3. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ DEMOLITION/

PATCHING; PAINT ENTIRE CEILING/

WALL PLANE CORNER TO CORNER,

EDGE TO EDGE. PAINT COLOR AND

EDGE TO EDGE. PAINT COLOR AND

FINISH TO MATCH ADJACENT

CEILING/ WALL.

G4. PAINT NEW CEILING MOUNTED

CONDUITS TO MATCH EXISTING

CEILING.

16 S. WILLIAMS PLANS-E

FIRE ALARM/INTRUSION ALARM

A3

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

BASEMENT PLAN -SETZER BLDG.

N

KEYED NOTES

Ja n

, 2

- 2 :3

0p m

C :\1

To dd

\1 A-

KH

A wo rk

\1

-0 p ar ks

A lar m s a nd F ire P ro te cti on

\D

AA

V\

DR

AW

IN

GS

\ 1

6_

DA

AV

_A

FL

R

PL

N

.d wg

US

ER

to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

FIRST FLOOR PLAN -SETZER BLDG.

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

SECOND FLOOR PLAN -SETZER BLDG.

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

THIRD FLOOR PLAN -SETZER BLDG.

N

REPAIR DOOR FRAME WHERE

CONTACT WAS REMOVED, IF

NEEDED, PRIOR TO INSTALLING

NEW DEVICE. FINISH TO MATCH

FRAME. (TYP.)

G3 CONT.

INSTALL CAMERAS PER E2C.

COORDINATE LOCATION AND

ELEVATION WITH CO/COR. LOCATE

CAMERAS WITH CLEAR LINE OF

SIGHT. INSTALL WEATHERTIGHT.

SEE CAMERA SHEETS.

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

BASEMENT

CRAWL

SPACE

002STAIR

S0

SHOP

RR

STAIR

S1

OFFICE

HALLWAY

STAIR

S0

STAIR

S2

OPEN

OFFICE

COPY

OFFICE

OFFICE

OFFICE

RR

22 S. WILLIAMS PLANS

FIRE ALARM/INTRUSION ALARM

A4

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

FIRST FLOOR PLAN

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

BASEMENT PLAN

N

GENERAL NOTES

G1. PATCH/REPAIR/PAINT CEILING/WALL

FINISHES AS REQUIRED TO MATCH

ADJACENT AREA WHERE NEW

DEVICES DON'T COMPLETELY

COVER OLD DEVICE LOCATIONS.

G2. PATCH CEILING/WALL WHERE A

DEVICE/CONDUIT WAS REMOVED

AND NOT REPLACED AT THE SAME

LOCATION.

G3. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ DEMOLITION/

PATCHING; PAINT ENTIRE CEILING/

WALL PLANE CORNER TO CORNER,

EDGE TO EDGE. PAINT COLOR AND

FINISH TO MATCH ADJACENT

CEILING/ WALL.

LOCATE FIRE ALARM NOTIFICATION

DEVICE UNDER EAVE WITH CLEAR

LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE AX AND

ELECTRICAL.

KEYED NOTES

Ja n

, 2

- 2 :3

0p m

C :\1

To dd

\1 A-

KH

A wo rk

\1

-0 p ar ks

A lar m s a nd F ire P ro te cti on

\D

AA

V\

DR

AW

IN

GS

\ 2

2_

DA

AV

_A

FL

R

PL

N

.d wg

US

ER

to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

SECOND FLOOR PLAN

N

REPAIR DOOR FRAME WHERE

CONTACT WAS REMOVED, IF

NEEDED, PRIOR TO INSTALLING

NEW DEVICE. FINISH TO MATCH

FRAME. (TYP.)

INSTALL CAMERA PER E3C.

COORDINATE LOCATION AND

ELEVATION WITH CO/COR. LOCATE

CAMERA WITH CLEAR LINE OF

SIGHT. INSTALL WEATHERTIGHT.

SEE CAMERA SHEETS.

PARLOR

101 DINING

RM

HALLWAY

KITCHEN

RR

CONFERENCE

OFFICE

OFFICE

RR

CLOSET

HALL

OFFICE

CLOSET

CLOSET

26 S. WILLIAMS PLANS

FIRE ALARM/INTRUSION ALARM

A5

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

FIRST FLOOR PLAN

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

BASEMENT PLAN

N

GENERAL NOTES

G1. PATCH/REPAIR/PAINT CEILING/WALL

FINISHES AS REQUIRED TO MATCH

ADJACENT AREA WHERE NEW

DEVICES DON'T COMPLETELY

COVER OLD DEVICE LOCATIONS.

G2. PATCH CEILING/WALL WHERE A

DEVICE/CONDUIT WAS REMOVED

AND NOT REPLACED AT THE SAME

LOCATION.

G3. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ DEMOLITION/

PATCHING; PAINT ENTIRE CEILING/

WALL PLANE CORNER TO CORNER,

EDGE TO EDGE. PAINT COLOR AND

FINISH TO MATCH ADJACENT

CEILING/ WALL.

LOCATE FIRE ALARM NOTIFICATION

DEVICE UNDER EAVE WITH CLEAR

LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE AX AND

ELECTRICAL.

KEYED NOTES

Ja n

, 2

- 2 :3

0p m

C :\1

To dd

\1 A-

KH

A wo rk

\1

-0 p ar ks

A lar m s a nd F ire P ro te cti on

\D

AA

V\

DR

AW

IN

GS

\ 2

6_

DA

AV

_A

FL

R

PL

N

.d wg

US

ER

to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

SECOND FLOOR PLAN

N

REPAIR DOOR FRAME WHERE

CONTACT WAS REMOVED, IF

NEEDED, PRIOR TO INSTALLING

NEW DEVICE. FINISH TO MATCH

FRAME. (TYP.)

STAIR

S0

UP

CRAWL

SPACE

CRAWL

SPACE

CONFERENCE

RR

FRONT

ENTRY/WAITING

OFFICE

CORRIDOR

REAR

ENTRY

STAIR

S1

RECEPT.

STAIR

S2

UP DN

OPEN

OFFICE

RR

OFFICE

OFFICE

CORRIDOR

WORK

ROOM

STAIR

S1

DN

30 S. WILLIAMS PLANS

FIRE ALARM/INTRUSION ALARM

A6

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

FIRST FLOOR PLAN

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

BASEMENT PLAN

N

GENERAL NOTES

G1. PATCH/REPAIR/PAINT CEILING/WALL

FINISHES AS REQUIRED TO MATCH

ADJACENT AREA WHERE NEW

DEVICES DON'T COMPLETELY

COVER OLD DEVICE LOCATIONS.

G2. PATCH CEILING/WALL WHERE A

DEVICE/CONDUIT WAS REMOVED

AND NOT REPLACED AT THE SAME

LOCATION.

G3. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ DEMOLITION/

PATCHING; PAINT ENTIRE CEILING/

WALL PLANE CORNER TO CORNER,

EDGE TO EDGE. PAINT COLOR AND

FINISH TO MATCH ADJACENT

CEILING/ WALL.

LOCATE FIRE ALARM NOTIFICATION

DEVICE UNDER EAVE WITH CLEAR

LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE AX AND

ELECTRICAL.

KEYED NOTES

M ay

7,

- 8

:4 7a m C

:\1 To dd \1

A-

KH

A wo rk \1

-0 p ar ks A lar m s a nd

F ire

P ro te cti on \D

AA

V\

DR

AW

IN

GS

\ 3 0_

DA

AV

_A

FL

R

PL

N fin al.

dw g

- U

SE

R to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

SECOND FLOOR PLAN

N

2 REPAIR DOOR FRAME WHERE

CONTACT WAS REMOVED, IF

NEEDED, PRIOR TO INSTALLING

NEW DEVICE. FINISH TO MATCH

FRAME. (TYP.)

3 INSTALL CAMERA PER E5C.

COORDINATE LOCATION WITH

CO/COR. LOCATE CAMERA WITH

CLEAR LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE CAMERA

SHEETS.

STORAGE

OFFICE

WORK

RM.

STORAGE

STORAGE

MEZZANINE

(ABOVE)

277 S. WILLIAMS PLAN

FIRE ALARM/INTRUSION ALARM

A7

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

FIRST FLOOR PLAN

N

GENERAL NOTES

G1. PAINT ALL NEW CEILING/WALL

MOUNTED CONDUIT TO MATCH

ADJACENT SURFACE IF THE

MOUNTING SURFACE IS ALREADY

PAINTED.

G2. INSTALL SURFACE MOUNTED

CONDUIT IN A NEAT AND ORDERLY

MANNER. DO NOT RUN CONDUIT

DIAGONALLY. SEE ELECTRICAL

DRAWINGS AND SPECIFICATIONS.

G3. PATCH CEILING/WALL WHERE A

DEVICE/CONDUIT WAS REMOVED

AND NOT REPLACED AT THE SAME

LOCATION.

G4. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ DEMOLITION/

PATCHING; PAINT ENTIRE CEILING/

WALL PLANE CORNER TO CORNER,

EDGE TO EDGE. PAINT COLOR AND

FINISH TO MATCH ADJACENT

CEILING/ WALL.

LOCATE FIRE ALARM NOTIFICATION

DEVICE UNDER EAVE WITH CLEAR

LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE AX AND

ELECTRICAL.

KEYED NOTES

Ja n

, 2

- 2 :3

0p m

C :\1

To dd

\1 A-

KH

A wo rk

\1

-0 p ar ks

A lar m s a nd F ire P ro te cti on

\D

AA

V\

DR

AW

IN

GS

\ 2

_D

AA

V_

A7 F

LR

P

LN

4.

dw g

- U

SE

R to dd

SUB SHEET NO.

OF

DESIGNED:

KJH

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

1/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CZ

FINAL CONSTRUCTION DOCUMENTS

REPAIR DOOR FRAME WHERE

CONTACT WAS REMOVED, IF

NEEDED, PRIOR TO INSTALLING

NEW DEVICE. FINISH TO MATCH

FRAME. (TYP.)

2 1

INSTALL CAMERA AT EACH BUILDING

CORNER (TYP) PER E6C.

COORDINATE ELEVATION WITH

CO/COR. VERIFY CAMERAS HAVE

CLEAR LINE OF SIGHT. INSTALL

WEATHERTIGHT. SEE CAMERA

SHEETS.

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ma y 0

6, :34 am

E 0.d wg lq uic k

E0

ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND NOTES

CARBON MONOXIDE DETECTOR

ELECTRICAL SYMBOLS

FIBER OPTIC CABLE

("#" INDICATES NUMBER OF STRANDS

"T" INDICATES TYPE AND

"X" INDICATES CABLE NAME)

COMBINATION DATA/AV FLOOR OUTLET

("#" INDICATES DEVICE TYPE IN SCHEDULE)

CABLE SLACK

("X" INDICATES SLACK LENGTH)

CABLE PROTECTOR

("XXX" INDICATES NUMBER OF PROTECTORS)

WIRELESS RECEIVER

WIRELESS REPEATER

UNSHIELDED TWISTED PAIR COPPER CABLE -

"C" INDICATES CATEGORY NUMBER

"#" INDICATES NUMBER OF PAIRS

"G" INDICATES AWG, "X" INDICATES CABLE NAME

CROSS-CONNECT FIELD

SPLICE

MECHANICAL TERMINATION OF CABLE

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

TELECOMMUNICATIONS

#-T X

XXX

X C-#-G X

COMMUNICATIONS OUTLET CEILING COMMUNICATIONS OUTLET FLOOR COMMUNICATIONS OUTLET

MUTOA - MULTI-USER TELECOMMUNICATIONS

OUTLET ASSEMBLYSPECIAL SERVICES COMMUNICATIONS OUTLET

WIRELESS ACCESS POINT

("#" INDICATES QUANTITY OF ANTENNAS)

AV

AV GEAR BOX, REFER TO

SCHEMATICS AND SPECS

GROUND BAR

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

PATHWAYS

CONDUIT SLEEVE WITH BUSHINGS DISTRIBUTION RINGS

WALL MOUNT TELECOMMUNICATIONS EQUIPMENT J-HOOK STYLE CABLE HANGERS CABLE TRAY DROP OUT

CABLE TRAY

("#" INDICATES TRAY DIMENSIONS)

CABLE RUNWAY

("#" INDICATES TRAY DIMENSIONS)

CABLE TRAY - SOLID BOTTOM

("#" INDICATES TRAY DIMENSIONS)

CABLE TRAY - WALL MOUNTED

("#" INDICATES TRAY DIMENSIONS)

EQUIPMENT RACK

("#" INDICATES RACK NO. AND FRONT OF RACK)#

FIRE ALARM AUTOMATIC SMOKE DETECTOR FIRE SPRINKLER VALVE TAMPER SWITCH

WIRELESS FIRE ALARM SMOKE DETECTOR FIRE SPRINKLER FLOW SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM AUTOMATIC WALL SMOKE DETECTOR CEILING FIRE ALARM HORN AND LIGHT COMBINATION

(# INDICATES CANDELA RATING)

FIRE ALARM CONTROL PANEL

FIRE ALARM AUTOMATIC CEILING HEAT DETECTOR

FIRE ALARM AUTOMATIC WALL HEAT DETECTOR

FIRE ALARM MANUAL STATION

FIRE ALARM CONTROL MODULE

CEILING FIRE ALARM LIGHT

(# INDICATES CANDELA RATING)

WALL FIRE ALARM LIGHT

(# INDICATES CANDELA RATING)

SAMPLING TUBE TYPE SMOKE DETECTOR

FIRE ALARM MAGNETIC DOOR HOLDER

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

FIRE DETECTION AND ALARM

F

F CM

F MM

F

F #

F

F #

F

F FAA

FACP

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

SUBSCRIPTS

SUBSCRIPT "E" ADDED TO ANY SYMBOL

INDICATES EXISTING

SUBSCRIPT "PD" ADDED TO ANY FLOOR OUTLET

INDICATES PEDESTAL MOUNTED

SUBSCRIPT "K" ADDED TO ANY SYMBOL

INDICATES KEY OPERATED

SUBSCRIPT "WG" ADDED TO ANY SYMBOL

INDICATES WIRE GUARD

SUBSCRIPT "P" ADDED TO ANY SYMBOL

INDICATES PILOT LIGHT

SUBSCRIPT "AC" ADDED TO ANY SYMBOL INDICATES ABOVE COUNTER. LOCATE CENTER OF DEVICE 4" ABOVE COUNTER SURFACE OR WHERE PRESENT, 4" ABOVE BACKSPLASH.

WHERE INDICATED ADJACENT TO LAVATORY WITHOUT COUNTER, LOCATE CENTER OF DEVICE 8" ABOVE RIM OF LAVATORY.

EP

E

PD

AC

K

WG

P

RT WP

SUBSCRIPT "RT" APPLIED TO ANY SYMBOL

INDICATES RAIN TIGHT NEMA 3R

OR EQUIVALENT

SUBSCRIPT "WP" APPLIED TO ANY SYMBOL

INDICATES WEATHERPROOF NEMA TYPE 4

OR EQUIVALENT

SUBSCRIPT "EP" APPLIED TO ANY SYMBOL

INDICATES EXPLOSION PROOF,

CLASS, GROUP AND DIVISION AS NOTED

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

SECURITY

WALL MOUNT MOTION SENSOR

CEILING MOUNT MOTION SENSOR

WIRELESS WALL MOUNT MOTION DETECTOR

WIRELESS CEILING MOUNT MOTION DETECTOR

POINT OF CONNECTION FOR 120VAC BY

ELECTRICAL CONTRACTOR

GLASS BREAK SENSOR

INTERCOM STATION

("S" SUBSTATION, "M" MASTER STATION)

JUNCTION BOX FOR SPECIALTY SECURITY SENSOR

DOME CAMERA

("#" INDICATES NUMBER IN SPECIFICATIONS)

SECURITY KEYPAD DEVICE

REMOTE ANNUNCIATOR DEVICE

DOOR LOCK POWER SUPPLY

PTZ DOME CAMERA

("#" INDICATES NUMBER IN SCHEDULE)

SECURITY EQUIPMENT CABINET(S), TYPE AND

QUANTITY MAY VARY FROM WALL MOUNTED,

FREE STANDING RACKS, OR EXTERIOR RATED,

REFER TO DETAILS

KEY SWITCH

REQUEST TO EXIT DEVICE

("M" MOTION SENSOR, "P" PUSH BUTTON)ACCESS CONTROL DEVICE LOCATION

"M" INDICATES MULLION MOUNT

ELECTRONICALLY CONTROLLED AND

MONITORED DOOR LOCATION

(REFER TO ACCESS CONTROL OPENING SCHEDULE)

DOOR POSITION SWITCH

AUTOMATIC OPERATOR CONNECTION POINT

('G' GATE, 'D' DOOR)

SECURITY PUSH BUTTON - ("P" INDICATES

PANIC ALARM)

M

P

J S

IC S,M

GB

E

G,D

PS

RA

KP

KS

RQE M,P

SEC

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

LIGHTING AND POWER

BRANCH CIRCUIT EXPOSED

BRANCH CIRCUIT -

CONCEALED IN CEILING OR WALL

BRANCH CIRCUIT - CONCEALED IN FLOOR

(UNDERGROUND IF EXTERIOR)

SPECIAL PURPOSE HOMERUN AS INDICATED

HOMERUN TO PANEL (NUMBER OF ARROWS

INDICATES NUMBER OF CIRCUITS)

CIRCUIT DOWN

SIMPLEX RECEPTACLE

CORD AND PLUG

PULL BOX

CEILING MOUNTED DUPLEX RECEPTACLE

POLE LUMINAIRE(S)

(# INDICATES FIXTURE NUMBER IN SCHEDULE)

ABOVE GRADE FIXTURE

(# INDICATES FIXTURE NUMBER IN SCHEDULE)

LIGHTING PANEL - FLUSH MOUNTED

TRANSFORMER

ENCLOSED CIRCUIT BREAKER

SAFETY SWITCH

(FUSED UNLESS OTHERWISE NOTED)

WALL MOUNTED JUNCTION BOX

JUNCTION BOX

("F" INDICATES FLOOR, "C" INDICATES CEILING)

T

PB J

J XCIRCUIT BREAK

CIRCUIT UP

CONDUIT STUB OUT

STRIP LIGHT

(# INDICATES FIXTURE NUMBER IN SCHEDULE)

LIGHTING PANEL - SURFACE MOUNTED

SINGLE POLE SWITCH

G,T,U

DUPLEX RECEPTACLE

"G" SUBSCRIPT INDICATES GFCI, "T" SUBSCRIPT

INDICATES TAMPER RESISTANT TYPE, "U" SUBSCRIPT

INDICATES COMBINATION USB CHARGING STATION

SYMBOLS INDICATED HERE AND NOT USED IN THE

CONTRACT DOCUMENTS DO NOT APPLY TO THIS

PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS

MAY BE INDICATED IN THE CONTRACT DOCUMENTS.

FIRE ALARM MONITOR MODULE

FIRE ALARM HORN AND LIGHT COMBINATION

P

R

CO

GATEWAYF

WIRELESS FIRE ALARM MANUAL STATION R RESIDENTIAL BATTERY SMOKE DETECTOR

FS FIRE ALARM LOW FREQUENCY SOUNDER

H20 WATER DETECTOR

F WIRELESS FIRE ALARM SMOKE DETECTOR

AutoCAD SHX Text

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

%%uGENERAL NOTES

BUILDING 30

BUILDING 26

BUILDING 22

BUILDING 16

PB

PB

PB

T

- S . W

ILL

IA

MS

S

TR

EE

T

- - SANFORD CT. -

- C

HU

RC

HI

LL

LA

NE

- W 3RD STREET -

E01

SITE PLAN

ELECTRICAL

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ma y 0

6, :34 am

E

.dw g lqu ick

SITE PLAN - ELECTRICAL

SCALE: 1" = 20'-0"

20 40 60 80 100

FLAG NOTES

REMOVE EXISTING BURIED WATER IRRIGATION TYPE BOXES AND REPLACE WITH A

NEW FLUSH-IN GROUND PULL BOX. REFER TO DETAIL 1/E9.

EXISTING UNDERGROUND 6" CONDUIT SLEEVE WITH A 3" CONDUIT. REFER TO

DETAIL 1/E2A FOR CABLE TYPE.

EXISTING UNDERGROUND 2" CONDUIT WITH 12 STRAND FIBER OPTIC CABLE.3

TO NEW FIBER FIRE OPTIC TERMINAL ENCLOSURE.4

EXISTING UNDERGROUND CONDUIT AND CABLE TO SECURITY CAMERA ON OUTHOUSE.5

EXISTING OUTHOUSE.6

EXISTING UNDERGROUND 2" CONDUIT WITH 12 STRAND FIBER OPTIC CABLE.7

EXISTING AMERITECH COMMUNICATION PEDESTAL.8

EXISTING 25 KVA, 240/120 VOLT PAD MOUNTED TRANSFORMER.9

EXISTING SPECTRUM COMMUNICATION PEDESTAL.10

EXISTING AT&T COMMUNICATION PEDESTAL.11

STORAGE

STORAGE

STORAGE

STAIR

S5

DN

DN

DN UP

F F F

F F

F

F

F

F

EXHIBITS

EXHIBITS

EXHIBITS

F

F

F

F

F

F F

F

F

F F F

F

FF

EXHIBITS

EXHIBITS

FOYER

EXHIBITS

PRINTSHOP

SUITE

PRINTSHOP

SUITE

PRINTSHOP

SUITE

CORRIDOR

EXHIBITS

EXHIBITS

EXHIBITS

EXHIBITS

STAIR

HALL

STAIR

S4

CORRIDOR

F

F

F

F

OFFICE

LIBRARY

WORKROOM

STAIR

HALL

STAIR

S4

1 (TYP)

(TYP)

2(TYP)

1 (TYP)

(TYP)6(TYP) 5

(TYP)

(TYP)

(TYP)

4 (TYP)

5 (TYP)3

(TYP)

BASEMENT - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SECOND FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

THIRD FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

ED1

16 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

DEMOLITION

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :01 pm

6E D1

.dw g lqu ick

FLAG NOTES

REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM MANUAL PULL STATION AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM STROBE LIGHT AND WIRING. EXISTING CONCEALED

CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM DOOR CONTACT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

DEMOLITION NOTES

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

THE PARK SHALL HAVE FIRST SALVAGE RIGHTS TO ALL DEVICES AND EQUIPMENT REMOVED.

AutoCAD SHX Text REMOVE FIRE ALARM AND INTRUSION ALARM CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS BACK TO THE SOURCE.

AutoCAD SHX Text

ABANDON CONCEALED CONDUITS INSIDE WALLS.

AutoCAD SHX Text COORDINATE AND SCHEDULE FIRE ALARM SYSTEM AND INTRUSION ALARM SYSTEM OUTAGES WITH THE CONTRACTING OFFICER OR CONTRACTING OFFICER REPRESENTATIVE.

AutoCAD SHX Text COORDINATE DEMOLITION WITH THE CONTRACTING OFFICER OR CONTRACTING OFFICER REPRESENTATIVE. WORK WITH NPS TO ALLOW THE PARK TO OCCUPY THE SPACE.

AutoCAD SHX Text REMOVE EXISTING FIRE ALARM DEVICES, INTRUSION ALARM DEVICES, AND WIRING. SEE PROJECT MANUAL AND NEW WORK DRAWINGS.

AutoCAD SHX Text

REMOVE DEMOLISHED ITEMS FROM PROJECT SITE. PROPERLY DISPOSE OF ITEMS.

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text 5.

AutoCAD SHX Text 6.

AutoCAD SHX Text 8.

AutoCAD SHX Text 7.

DEMOLITION DRAWINGS INDICATE EXISTING FIRE ALARM AND EXISTING INTRUSION ALARM EQUIPMENT AND EXISTING DEVICES WHICH ARE TO BE REMOVED. REMOVE INDICATED ITEMS AND ASSOCIATED ITEMS SUCH AS PARTYLINE EVENT TRANSCEIVER (PET) PANELS, OTHER ASSOCIATED EQUIPMENT, ABANDONED PANELS/EQUIPMENT BOXES AND CONDUITS NOT INDICATED BUT WHICH MUST BE REMOVED TO ACCOMMODATE REMODELING. SEE PROJECT MANUAL "WORK IN EXISTING BUILDINGS" FOR ADDITIONAL INFORMATION.

F

F

F

CRAWL

SPACE

STORAGE

001ELEV.

EQ.

PASSAGE

WAY

STAIR

S1

STAIR

S2

FACP

1 (TYP)

DN

UP

DN

UP

115 117 119

EXHIBIT

THEATER

EQUIP.

RM

KITCHNT.

MEN

WOMEN

J.C.

COM.

CLOSET

ATRIUM

STAIR

S3

STAIR

S1

BOOKSTORE

GIFTSHOP

STAIR

S2

VESTIBULE

F

F

F

F

F

F

F

F

(TYP)

2(TYP)

5 (TYP)

1 (TYP)

FA

A

UP

DN

DN

EXHIBIT

KITCHNT.

CONF.

RM.

COAT

RM.

CONF.

RM.

OFFICE

201A

MEN

WOMEN

STAIR

S1

J.C.

CORRIDOR

ATRIUM

STAIR

S3

F

F

F

F

F

F

F

F

F

2 (TYP)

1 (TYP)

(TYP)

DN

ROOF

R1

BREAK

RM.

BOILER

RM.

CORRIDOR

MEN

J.C.

WOMEN

STAIR

S1

F

F

F

F

(TYP)

(TYP)

BASEMENT - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

ED2

16 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

DEMOLITION

FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SECOND FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

THIRD FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ma y 0

6, :34 am

E D2

.dw g lqu ick

FLAG NOTES

REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM MANUAL PULL STATION AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM STROBE LIGHT AND WIRING. EXISTING CONCEALED

CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM DOOR CONTACT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM CONTROL PANEL AND WIRING.7

REMOVE EXISTING INTRUSION ALARM CONTROL PANEL AND WIRING.8

REMOVE EXISTING FIRE ALARM REMOTE ANNUNCIATOR AND WIRING.9

REMOVE EXISTING BATTERIES.10

REMOVE EXISTING BOX, PATCH AND PAINT WALL.11

EXISTING ELEVATOR DISCONNECT SWITCH WITH SHUNT TRIP. REMOVE FIRE ALARM

WIRING INTERFACE.

REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING. EXISTING CONDUIT

TO REMAIN.

CRAWL

SPACE

002STAIR

S0

F F FACP

REMOVE EXISTING FIRE ALARM / INTRUSION

ALARM CONTROL PANEL AND WIRING REMOVE EXISTING BATTERY

F F

FSHOP

RR

STAIR

S1

OFFICE

HALLWAY

STAIR

S0

F

STAIR

S2

OPEN

OFFICE

COPY

OFFICE

OFFICE

OFFICE

RR

IN ATTIC

IN ATTIC

4 (TYP)

(TYP)

(TYP)

(TYP)

(TYP)

BASEMENT - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

ED3

22 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

DEMOLITION

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :02 pm

6E D3

.dw g lqu ick

FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SECOND FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

FLAG NOTES

REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM MANUAL PULL STATION AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM DOOR CONTACT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

PARLOR

101 DINING

RM

HALLWAY

KITCHEN

RR

CONFERENCE

OFFICE

OFFICE

RR

CLOSET

HALL

OFFICE

CLOSET

CLOSET

KPKP

F

F F

IN ATTIC

F

IN ATTIC

(TYP)

(TYP)

2 (TYP)

F F F F

7 6

(TYP) (TYP)

5 (TYP)

ED4

26 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

DEMOLITION

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :02 pm

6E D4

.dw g lqu ick

SECOND FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

BASEMENT - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

FLAG NOTES

REMOVE EXISTING FIRE ALARM SMOKE DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING FIRE ALARM HORN/STROBE LIGHT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM DOOR CONTACT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING KEYPAD AND WIRING.5

REMOVE FIRE ALARM WIRING TO EXISTING FIRE SPRINKLER TAMPER SWITCH.

EXISTING TAMPER SWITCH TO REMAIN.

REMOVE FIRE ALARM WIRING TO EXISTING FIRE SPRINKLER FLOW SWITCH.

EXISTING FLOW SWITCH TO REMAIN.

STAIR

S0

UP

CRAWL

SPACE

CRAWL

SPACE

003 CONFERENCE

RR

FRONT

ENTRY/WAITING

OFFICE

CORRIDOR

REAR

ENTRY

STAIR

S1

RECEPT.

STAIR

S2

UP DN

OPEN

OFFICE

RR

OFFICE

OFFICE

CORRIDOR

WORK

ROOM

STAIR

S1

DN

F F

F

KP

KP

R

IN ATTIC

R1

IN ATTIC

EXISTING FIRE

SPRINKLER MAIN

(TYP)

ED5

30 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

DEMOLITION

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :02 pm

6E D5

.dw g lqu ick

SECOND FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

BASEMENT - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

FLAG NOTES

REMOVE EXISTING RESIDENTIAL STYLE LINE VOLTAGE SMOKE DETECTOR.

DISCONNECT AND REMOVE OR ABANDON EXISTING 120V. CONDUCTORS AND PATCH

AND PAINT CEILING.

REMOVE EXISTING FIRE ALARM HEAT DETECTOR AND WIRING.2

REMOVE EXISTING FIRE ALARM DUCT DETECTOR, WIRING AND CONDUIT.3

REMOVE EXISTING FIRE ALARM WIRING AND CONDUIT TO EXISTING FIRE SPRINKLER

FLOW SWITCHES.

REMOVE EXISTING FIRE ALARM WIRING AND CONDUIT TO EXISTING FIRE SPRINKLER

TAMPER SWITCH.

REMOVE EXISTING FIRE ALARM WIRING AND CONDUIT TO EXISTING FIRE SPRINKLER

ALARM BELL.

REMOVE EXISTING INTRUSION ALARM DOOR CONTACT AND WIRING.7

REMOVE EXISTING FIRE ALARM CONTROL PANEL, FIRE ALARM WIRING, AND 120V.

WIRING.

REMOVE EXISTING KEYPAD AND WIRING.9

OFFICE

WORK

RM.

STORAGE

STORAGE

MEZZANINE

(ABOVE)

REMOVE EXISTING INTRUSION

ALARM CONTROL PANEL AND

WIRING

KPREMOVE EXISTING

KEYPAD AND WIRING

REMOVE EXISTING CELLULAR

DEVICE AND WIRING

1 (TYP)

FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

ED6

277 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

DEMOLITION

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :03 pm

6E D6

.dw g lqu ick

FLAG NOTES

REMOVE EXISTING INTRUSION ALARM MOTION DETECTOR AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

REMOVE EXISTING INTRUSION ALARM DOOR CONTACT AND WIRING. EXISTING

CONCEALED CONDUIT TO REMAIN.

STORAGE

STORAGE

STORAGE

STAIR

S5

DN

DN

DN UP

F F F

F F

F

F

F

F

EXHIBITS

EXHIBITS

EXHIBITS

F

F

F

F

F

F F

F

F

F F

F

FF

EXHIBITS

EXHIBITS

FOYER

EXHIBITS

PRINTSHOP

SUITE

PRINTSHOP

SUITE

PRINTSHOP

SUITE

CORRIDOR

EXHIBITS

EXHIBITS

EXHIBITS

EXHIBITS

STAIR

HALL

STAIR

S4

CORRIDOR

F

F

110CD

F

F

OFFICE

LIBRARY

WORKROOM

STAIR

HALL

STAIR

S4

F

F

F 1

F

FP

F

WPF

F1

FF

F F

F

BASEMENT - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

FIRST FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SECOND FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

THIRD FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

E1

16 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :58 pm

6E 1.d wg lq uic k

FLAG NOTES

NEW FIRE ALARM DEVICE IN NEW LOCATION.1

COORDINATE MOUNTING HEIGHT WITH CONTRACTING OFFICER OR CONTRACTING

OFFICER REPRESENTATIVE.

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

F

F

F

CRAWL

SPACE

STORAGE

001ELEV.

EQ.

PASSAGE

WAY

STAIR

S1

STAIR

S2

FACP

F

E2AATS

F R

F

DN

UP

DN

UP

115 117 119

EXHIBIT

THEATER

EQUIP.

RM

KITCHNT.

MEN

WOMEN

J.C.

COM.

CLOSET

ATRIUM

STAIR

S3

STAIR

S1

BOOKSTORE

GIFTSHOP

STAIR

S2

VESTIBULE

F

F

F

F

F

F

F

F

F1

F

F

FA

A

NEW REMOTE FIRE ALARM

ANNUNCIATOR PANEL

P

F

P

PANIC BUTTON UP

DN

DN

EXHIBIT

KITCHNT.

CONF.

RM.

COAT

RM.

CONF.

RM.

OFFICE

201A

MEN

WOMEN

STAIR

S1

J.C.

CORRIDOR

ATRIUM

STAIR

S3

F

F

F

F

F

F

F

F

F 21

F 21

F

P

F1F

P

F

DN

ROOF

R1

BREAK

RM.

BOILER

RM.

CORRIDOR

MEN

J.C.

WOMEN

STAIR

S1

F

F

F

F

F 1 F1

F1

F

P

BASEMENT - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

E2

16 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

FIRST FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SECOND FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

THIRD FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :59 pm

6E 2.d wg lq uic k

FLAG NOTES

PROVIDE A NEW FIRE ALARM DEVICE IN A NEW LOCATION.1

COORDINATE MOUNTING LOCATION WITH CONTRACTING OFFICER OR

CONTRACTING OFFICER REPRESENTATIVE.

PAINT ANY NEW CEILING MOUNTED CONDUITS AND BOXES BLACK TO MATCH

EXISTING CEILING.

MOUNT 24" A.F.F. IN PIT.4

EXISTING ELEVATOR DISCONNECT WITH SHUNT TRIP.5

STAIR

S1

STAIR

S2

FACP

ATS

NEW FIRE ALARM CONTROL PANEL

EXISTING ATS

EXISTING PANEL LP-AA

EXISTING PANEL LP-EM

NEW INTRUSION ALARM PANEL

EXISTING COMMUNICATIONS BOARD

EXISTING SWITCHBOARD

EXISTING

COMMUNICATION

CABINET

EXISTING COMMUNICATION RACK

FIVE EXISTING CONDUITS

SEE DETAIL 1/E2A

EXISTING METER

F

F

F R

NEW FIBER OPTIC

TERMINATION ENCLOSURE

NEW DIALER

NEW FIBER OPTIC

TERMINATION ENCLOSURE

REFER TO DETAIL 4/E8 FOR

INTERSYSTEM CONNECTIONS

LP-EM

LP-EM

NEW FIRE INTERSYSTEM GROUND BAR

EXISTING 12-STRAND FIBER OPTIC

CABLE WITH (6) SPARE FIBER STRANDS

EXISTING 'ARUBA' FIBER CONVERSION SWITCH

EXISTING COMMUNICATIONS RACK

EXISTING FIVE-WAY SPLITTER

SPECTRUM

SPECTRUM 911

UBEE

AT&T

EXISTING FIBER MODEM

EXISTING FIBER OPTIC CABLES:

62.5 / 125 μm OFNR

EXISTING UNUSED TELEPHONE

UTILITY CABLE

EXISTING UTILITY CONNECTION DEVICE

EXISTING COMMUNICATION BOARD

EXISTING UTILITY TELEPHONE CABLE

EXISTING:

ONE (1) UTILITY TELEPHONE CABLE

TWO (2) TELEPHONE CABLES TO BUILDINGS 22 AND 30

TWO (2) FIBER OPTIC CABLES TO BUILDINGS 22 AND 30 ALL IN ONE 3" C.

EM

PT

Y 4"

NA

TU

RA

L G

AS

6" S

LE

EV

E W

/ 3 " C

ON

DU

IT

4" NA

TU

RA

L G

AS

PROVIDE NEW FIBER OPTIC

TERMINATION ENCLOSURE

PROVIDE (2) NEW FIBER OPTIC

STRANDS TO FIRE ALARM SYSTEM

PROVIDE (2) NEW FIBER OPTIC STRANDS

TO INTRUSION ALARM SYSTEM

BASEMENT - ELECTRICAL ENLARGED

SCALE: 1/4" = 1'-0"

2 6 8 124 16 20

E2A

16 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

ENLARGED PLAN

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :59 pm

6E 2A

.dw g lqu ick

BUILDING 16 EXISTING UTILITY ENTRANCE DIAGRAM

NOT TO SCALE

E2A

FLAG NOTES

PROVIDE TWO NEW 20/1 BREAKERS AND PROVIDE A NEW UPDATED TYPED CIRCUIT

DIRECTORY.

F F FACP

NEW FIRE ALARM ALARM CONTROL PANEL

F F

SHOP

RR

STAIR

S1

OFFICE

HALLWAY

102STAIR

S0

F

STAIR

S2

OPEN

OFFICE

COPY

OFFICE

OFFICE

OFFICE

RR

IN ATTIC

IN ATTIC

F

F

F

F

F F

F

F

F

NEW INTRUSION ALARM

CONTROL PANEL

F

EXISTING PANEL

F

BASEMENT

CRAWL

SPACE

STAIR

S0 F

R

WPF

1 3

NEW FIBER OPTIC TERMINATION ENCLOSURE

NEW INTERSYSTEM GROUND BAR

PANIC BUTTON BEHIND COUNTER

F

P

F

P

BASEMENT - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

E3

22 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2025C

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239956

Ja nu ar y 2

3, :59 pm

6E 3.d wg lq uic k

FIRST FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

SECOND FLOOR - ELECTRICAL

SCALE: 1/8" = 1'-0"

8 16 24 32 4042

FLAG NOTES

PROVIDE TWO NEW 20/1 BREAKERS AND PROVIDE A NEW UPDATED TYPED CIRCUIT

DIRECTORY.

PROVIDE A 120V. 20 AMP CIRCUIT TO EXISTING PANEL. 2 #12, 1 #12 GROUND IN 3/4" C.2

PROVIDE A HANDLE LOCK ON THE 20/1 BREAKER SERVING THE FIRE ALARM PANEL.3

PARLOR

101 DINING

RM

HALLWAY

KITCHEN

RR

CONFERENCE

KPKP

F

F F

IN ATTIC

F

IN ATTIC

F

F

FF

F

F F F F F

EXISTING FIRE

SPRINKLER MAIN EXISTING COMMUNICATION BOARD

EXISTING 1 1/4", 1 1/2", 4"

CONDUITS TO BUILDING #22

EXISTING 4" CONDUITS

TO BUILDING #30

EXISTING ELECTRICAL PANEL

BASEMENT

NEW INTRUSION ALARM

CONTROL PANEL

NEW FIBER OPTIC

TERMINATION ENCLOSURE

F F

EXISTING

FURNACE

F3

OFFICE

OFFICE

RR

CLOSET

HALL

OFFICE

CLOSET

CLOSET

F

R

REMOTE FIRE ALARM

ANNUNCIATOR PANEL

F

F

R

IN ATTIC

WP

F

NEW FIRE ALARM

CONTROL PANEL

NEW INTERSYSTEM GROUND BAR

P

E4

26 S. WILLIAMS

FIRE ALARM/INTRUSION ALARM

SUB SHEET NO.

OF

DESIGNED:

RCF

PARK-WIDE REPLACEMENT OF FIRE & INTRUSION ALARMS

DAYTON AVIATION HERITAGE NHP

DAYTON, OHIO

362/80015

227811

DRAWN BY:

TECH. REVIEW:

DATE:

01/31/2025

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

VG

GAN

100% CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .