Questions_and_Answers_0001.pdf

PDF 670 KB Posted

Attached to
Fire and Intrusion Alarms Replacement Federal contract opportunity
Solicitation number
140P6425B0009
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document is a Questions and Answers (Q&A) addendum for Solicitation #140P6425B0009, a Fire and Intrusion Alarm Replacement project for the Dayton Aviation Heritage National Historic Site. The Q&A covers technical details for installing new fire and security alarm systems across multiple buildings (16, 22, 26, 30, and 277), including specifics on wireless and wired device requirements, camera systems, network configurations, and installation parameters. Key details include wireless fire alarm devices for conditioned buildings, wired devices for unconditioned spaces, a requirement to maintain existing systems during installation, 30-day video storage, motion-activated camera recording, and the need to integrate new systems with Milestone camera platforms. The project allows equipment substitutions provided they meet salient characteristics, and work is generally to be performed during standard business hours with prior approval required for after-hours work.

View the file

Other files for this federal contract opportunity

Other files attached to Fire and Intrusion Alarms Replacement, newest first.
File Type Posted
Sol_140P6425B0009_Amd_0001.pdf PDF
Drawings.pdf PDF
Sol_140P6425B0009.pdf PDF
Specifications.pdf PDF
Bid_Schedule.xlsx XLSX spreadsheet
Bid_Schedule.pdf PDF
Alarms_Product_File.pdf PDF
DOL_Wage_Determination.pdf PDF
Submittal_List.pdf PDF
Limitations_on_Subcontracting_Report.xlsx XLSX spreadsheet

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation #: 140P6425B0009

Amendment #: P0001

Fire and Intrusion Alarm Replacement – DAAV

Questions and Answers listed below:

QUESTIONS:

Question # Question Answer/Response

1. The specs and drawings call for wireless devices, are wireless devices mandatory, or can we use wired devices if we deem it possible?

Sheet E0 1: FIRE ALARM MANUAL PULL STATIONS, SMOKE DETECTORS, AND HEAT DETECTORS TO BE THE

FIRE ALARM MANUAL PULL STATIONS, SMOKE

DETECTORS, AND HEAT DETECTORS TO BE THE WIRELESS

TYPE IN THE FOLLOWING CONDITIONED BUILDINGS 16,

22, 26, 30. IF THERE ARE SPACES IN THESE BUILDINGS

THAT ARE UNCONDITIONED SUCH AS ATTIC SPACES THAN

THOSE DEVICES SHALL BE THE WIRED TYPE. 2. FIRE

ALARM MANUAL PULL STATIONS, SMOKE DETECTORS,

AND HEAT DETECTORS TO BE THE FIRE ALARM MANUAL

PULL STATIONS, SMOKE DETECTORS, AND HEAT

DETECTORS TO BE THE WIRED TYPE IN THE FOLLOWING

UNCONDITIONED BUILDING 277. 3. FIRE ALARM

HORN/STROBE LIGHTS AND STROBE LIGHTS TO BE WIRED.

FIRE ALARM HORN/STROBE LIGHTS AND STROBE LIGHTS

TO BE WIRED. 4. FIRE ALARM DUCT DETECTORS TO BE

WIRED. FIRE ALARM DUCT DETECTORS TO BE WIRED. No changes without CO/COR/Engineer Approval.

2. Is all fire alarm and security wire required to be in conduit, or can it be open ran in concealed spaces (attics & basements)?

Sheet E, Note 5: FIRE ALARM WIRING SHALL BE IN

CONDUIT

3. Do the existing fire alarm systems need to remain active until the new systems are operational?

Sheet E0, Note 13: THE EXISTING FIRE ALARM AND

INTRUSION DETECTION SYSTEMS SHALL STAY

OPERATIONAL THE EXISTING FIRE ALARM AND

INTRUSION DETECTION SYSTEMS SHALL STAY

OPERATIONAL AS LONG AS POSSIBLE AND TO KEEP

DOWN TIME TO A MINIMUM. COORDINATE ANY DOWN

TIME WITH THE CONTRACTING OFFICER OR

CONTRACTING OFFICER REPRESENTATIVE COR

4. In building 16 there is a metal drop in ceiling, does the owner have any spare/replacement tiles for this space, or know the make/model of the existing metal ceiling tiles?

Yes the facility does have a minimal supply of those tiles.

5121 MW Torsion Spring CAT_225

5. Is there any asbestos, lead paint or any other hazardous materials present within any of the buildings?

With the age of the facility there is assumed lead-based paint encapsulated in the walls.

6. There is a security connex/building next to building 227, does any work need to be performed in the connex or is it not a part of the project?

Demo existing Cameras only

7. Per the drawings & scope of work, we are to tie the new cameras into the existing Milestone camera system.

Will the owner be providing licenses for new cameras?

For Milestone you typically have to transfer the main SLC license to the new Milestone distributor before they can install/purchase new licenses.

There is no Existing Milestone server at DAAV

Sheet E1C: THE NATIONAL PARK SYSTEM SHALL PAY FOR

THE LICENSE FEES AND MAINTENANCE FEES TO SUPPORT

THE VIDEO SURVEILLANCE CAMERA SYSTEM

8. Building 16 has existing Avigilon camera equipment, is the Avigilon equipment going away and being converted to the Milestone?

converted to the Milestone

9. Will we be allowed to work within the buildings during normal business hours, or will we have to perform any afterhours work?

Division 1 Section 3.2: On-site work hours: Work shall be generally performed during normal business working hours of 8 a.m. to 5 p.m., Monday through Friday, except when otherwise indicated. Work on Saturdays, Sundays, Federal holidays, early morning, or at night may not be performed without prior consent from the CO and COR.

Submit requests for work outside of the stated normal business hours to the CO and COR for approval at least 48 hours in advance of the work.

10. Are the buildings connected to the same network?

Yes, Buildings 16-22-26-30 are on one system and B 277 is a standalone system.

11. Is any new fiber optic cable that we need to run?

Yes, Multiple locations, See 100% Construction Document Drawings for exact Locations

12. Is there to be a camera server in each building?

During the walkthrough they stated the two houses are connected. So, would there be 3 servers total or will they all connect over the same network? (See question 1

Sheets E2C, E3C, E6C Buildings 16,22, B 277 is a standalone system.

13. Are the cameras to be terminated to a patch panel or directly to the switches?

Sheet E2C Flag Notes 1-7: PROVIDE NEW CAMERA, AND INDOOR PLENUM-RATED CATEGORY 6A

CABLING IN EXISTING CONDUIT TO COPPER PATCH

PANEL IN EXISTING COMMUNICATIONS RACK IN

BASEMENT.

14. How many viewing client stations are needed for the camera system?

What are the locations of the viewing stations?

How many remote viewing stations are there, if any?

Sheets E2C, E3C, E6C: Office B277, Basements of B 22 and 16

None, however, need the capability of logging in through the network to view remotely

15. Are the existing P2P systems to be replaced or utilized in any way? Will any point to point wireless points need to be added?

Existing P2P cameras are to be removed and not replaced.

16. Building #4 had a maintenance shed area?

Are there to be cameras installed there? if so, what are the locations? is that building connected to the larger building or would point to point devices be needed ?

Sheet E6C, No additional Cameras to be installed on buildings other than B277 at the Maintenance area

17. How many days of storage are expected for footage review?

30 Days

18. Are all cameras to be set on motion record or constant? Or is there a recording schedule?

set on motion record

19. Will we have keys for the installers? or will we have to contact someone to unlock doors as needed?

Keys will be available by contacting staff each morning

20. If floor pass throughs are full or cannot be used for some reason, are we allowed to make new ones?

Yes, with park CO/ COR approval

21. Can we get exact device counts to verify against the drawings/prints?

You are welcome to schedule another walk through to verify counts with the 100% drawings.

22. Are the existing pole cams to be left alone and removed by others

Sheet ED01C Existing Pole Cameras are to be removed by the winning contractor.

23. I am interested; however, it looks like this project requires specific manufacturer products (Honeywell, and Bosch) that I am not certified for installation. My system products would be Kidde and 2GIG/Alarm.com - it does not look like substitutions are allowed (correct me if that is not the case).

Substitutes are allowed as long as they meet the salient characteristics provided.