Drawings.pdf
PDF 9 MB Posted
- Attached to
- Dock Lift Replacement Federal contract opportunity
- Solicitation number
- 12505B25R0003
About this file
This document is a solicitation issued by the United States Department of Agriculture (USDA) Agricultural Research Service (ARS) for dock lift repairs at the National Center for Agricultural Utilization Research Center in Peoria, Illinois. The solicitation is a Request for Proposals (RFP) that will result in a firm-fixed price order. The requirement is a Total Small Business Set Aside with a NAICS code of 238990, Building and Property Specialty Trade Services, and a size standard of $19.0 million. The magnitude of construction is between $100,000 and $250,000 with a period of performance of 60 days after the notice to proceed. The solicitation requires the use of biobased products. Interested vendors must attend a site visit on November 19 or 20, 2024, and submit written questions by November 27, 2024. The solicitation and any amendments will be available only through the SAM.gov website.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign In 11202024.pdf | ||
| RFIs.pdf | ||
| Site Visit Sign In 11192024.pdf | ||
| SF30 - Amendment 01.pdf | ||
| SF-1442.pdf | ||
| Attachments.pdf | ||
| Specifications.pdf | ||
| ARS-371.pdf | ||
| ARS-372.pdf | ||
| Wage Determination.pdf | ||
| Statement of Work.pdf | ||
| Past Performance Questionnaire.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCOPE INCLUDES MODIFICATION OR REMOVAL TO THE EXISTING WORK PLATFORM
ON BOILER #3, INSTALLATION OF A NEW WORKING PLATFORM SYSTEM ON BOILER #
3, AND INSTALLATION OF A NEW RAILING ALONG THE PERIMETER OF THE BOILER
PLATFORM TO MEET OSHA REGULATIONS.
STRUCTURAL ENGINEER
2882 106TH STREET
DES MOINES, IA 50322
T: 515.334.9906
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMPORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)
PC/LS
KS
/1
/2
:2
:0
A
M
H
P ro je c t F ile s \0
-0
-0
U
S D
A N
C A
U R
S H
IP
P
IN
G
A N
D R
E C
E
IV
IN
G
I M
P R
O V
E M
E N
T S
\0 C
A D
\R E
V
IT
\R U
S D
A N
C A
U R
S h ip p in g a n d R e c e iv in g I m p ro v e m e n ts
.r v t
02/20/2024
COVER
SR-G000
1815 N UNIVERSITY ST PEORIA, IL 61604
SHIPPING / RECEIVING
IMPROVEMENTS
LOCATION MAP
SCOPE OF WORK SUMMARY
Sheet
Number Sheet Name
GENERAL
SR-G000 COVER
SR-G001 ABBREVIATIONS AND SYMBOLS
SR-G003 GENERAL AND ARCH PROJECT NOTES
SR-G101 SITE PLAN
SR-G102 AREA PLAN
STRUCTURAL
SR-S000 GENERAL NOTES
SR-S001 GENERAL NOTES
SR-S002 GENERAL NOTES
SR-S003 GENERAL NOTES
SR-S004 GENERAL NOTES
SR-S005 TESTING AND INSPECTION
SR-S006 TESTING AND INSPECTION
SR-S100 DEMOLITION PLAN
SR-S101 FOUNDATION PLAN
SR-S300 CONCRETE DETAILS
SR-S301 CONCRETE DETAILS
ARCHITECTURAL
SR-D101 DEMO PLAN
SR-A101 CONSTRUCTION PLAN
SR-A800 CONSTRUCTION DETAILS
SR-A801 MANUFACTURER DETAILS
SR-A802 MANUFACTURER DETAILS
SITE
ISSUE FOR 100% DESIGN SUBMITTAL 07/11/2024
Revision Schedule
NO. DESCRIPTION DATE
95% DESIGN SUBMITTAL 06/12/24
1 100% DESIGN SUBMITTAL 07/11/24
Sheet Number Sheet Name
ELECTRICAL
SR-E000 ELECTRICAL COVERSHEET
SR-E001 ELECTRICAL COVERSHEET
SR-E101 DEMO PLAN - POWER
SR-E201 CONSTRUCTION PLAN - POWER
SR-E600 ELECTRICAL SCHEDULES
SR-E700 ELECTRICAL SPECIFICATIONS
SR-E701 ELECTRICAL SPECIFICATIONS
PLUMBING
SR-P000 PLUMBING COVERSHEET
SR-P001 PLUMBING COVERSHEET
SR-P002 PLUMBING COVERSHEET
SR-P101 PIT DEMO PLAN - PLUMBING
SR-P102 DEMO PLAN - PLUMBING
SR-P200 PIT PLAN - PLUMBING
SR-P201 CONSTRUCTION PLAN - PLUMBING
SR-P700 PLUMBING SPECIFICATIONS
SR-P701 PLUMBING SPECIFICATIONS
SR-P702 PLUMBING SPECIFICATIONS
NORTH
WALL TAG
SECTION
TAG
GRID LINE
ELEVATION
TAG
DETAIL
TAG
EQUIPMENT
TAG
DETAIL
TAG
DETAIL
NUMBER
SHEET
NUMBER
INTERIOR
ELEVATIO
N
TAG
DIMENSION
STRING
NORTH ARROW
KEYNOTE
X X.X
XX
XX
X X.X
X X.X
X X.X
X X.X
B
1"
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMPORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)
PC/LS
KS
/1
/2
:2
:0
A
M
H
P ro je c t F ile s \0
-0
-0
U
S D
A N
C A
U R
S H
IP
P
IN
G
A N
D R
E C
E
IV
IN
G
I M
P R
O V
E M
E N
T S
\0 C
A D
\R E
V
IT
\R U
S D
A N
C A
U R
S h ip p in g a n d R e c e iv in g I m p ro v e m e n ts
.r v t
02/20/2024
ABBREVIATIONS AND SYMBOLS
SR-G001
A
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
B
BSMT BASEMENT
BTTM/ BOTTOM OF
C
C/C CENTER TO CENTER
CIP CAST IN PLACE
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
CONST JT CONSTRUCTION JOINT
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
D
DBL DOUBLE
DEMO DEMOLISH
DIA DIAMETER
DIMS DIMENSIONS
DN DOWN
DTL DETAIL
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR / ELEVATION
EPDM ETHYLENE PROPYLENE DIENE ROOFING
EQ EQUAL
EXIST EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISHED FLOOR ELEVATION
FIN FINISH
FLR FLOOR
FND FOUNDATION
FO FACE OF
FTG FOOTING
G
GA GAUGE
GALV GALVANIZED
GWB GYPSUM WALL BOARD
H
HC HOLLOW CORE
HM HOLLOW METAL
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
I
INSUL INSULATION / INSULATED
INT INTERIOR
IRGWB IMPACT RESISTANT GYPSUM WALLBOARD
L
LAV LAVATORY
M
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MO MASONRY OPENING
MRGWB MOISTURE-RESISTANT GYPSUM WALL BOARD
MTD MOUNTED
MTL METAL
N
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
O
OC ON CENTER
OH OPPOSITE HAND
OZ OUNCE
P
PCC PRE-CAST CONCRETE
PLUMB PLUMBING
PNT PAINT/PAINTED
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PVC POLYVINYL CHLORIDE
R
R RADIUS
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REINF REINFORCED
REQD REQUIRED
RM ROOM
S
SF SQUARE FOOT
SIM SIMILIAR
SOG SLAB ON GRADE
SPEC SPECIFIED OR SPECIFICATION
SPK SPRINKLER
SQ SQUARE
SSTL STAINLESS STEEL
STC SOUND TRANSMISSION COEFFICIENT
STL STEEL
STRUCT STRUCTURAL
T
T&G TONGUE & GROOVE
T/ TOP OF
T/D TELEPHONE/DATA
TELE TELEPHONE
TLT TOILET
TOC TOP OF CONCRETE
TOS TOP OF STEEL / STRUCTURE
TOW TOP OF WALL
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
VIF VERIFY IN FIELD
VP VISION PANEL
W
W/ WITH
WD WOOD
WWF WELDED WIRE FABRIC
ABBREVIATIONS SYMBOLS LEGEND
Revision Schedule
NO. DESCRIPTION DATE
95% DESIGN SUBMITTAL 06/12/24
1 100% DESIGN SUBMITTAL 07/11/24
• THE EXISTING SHIPPING AND RECEIVING AREA IS LOCATED ON THE WEST SIDE OF THE EXISTING BUILDING 1
SOUTH WING.
• THE OCCUPANCY CLASSIFICATION/USE OF BUILDING 1 IS GROUP B (BUSINESS) LABORATORIES: TESTING AND
RESEARCH PER THE INTERNATIONAL BUILDING CODE - IBC CHAPTER 3.
• THE SCOPE OF THIS PROJECT WILL BE CONSIDERED LEVEL 1 ALTERATIONS PER THE INTERNATIONAL EXISTING BUILDING CODE - IEBC CHAPTER 6. LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES USING NEW MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES THAT SERVE THE SAME PURPOSE.
• THE NEW LOADING DOCK LIFT WILL COMPLY WITH ALL APPLICABLE OSHA STANDARDS RELATING TO, BUT NOT
LIMITED TO, FALL PROTECTION.
• STRUCTURAL DESIGN WORK SHALL COMPLY WITH IBC CHAPTER 16.
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMPORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)
PC/LS
KS
/1
/2
:2
:0
A
M
H
P ro je c t F ile s \0
-0
-0
U
S D
A N
C A
U R
S H
IP
P
IN
G
A N
D R
E C
E
IV
IN
G
I M
P R
O V
E M
E N
T S
\0 C
A D
\R E
V
IT
\R U
S D
A N
C A
U R
S h ip p in g a n d R e c e iv in g I m p ro v e m e n ts
.r v t
02/20/2024
GENERAL AND ARCH PROJECT NOTES
SR-G003
GENERAL PROJECT NOTES
1. THESE DRAWINGS INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF THE ARCHITECTURAL DESIGN CONCEPT, DIMENSIONS, MAJOR ELEMENTS AND MATERIALS. THESE DRAWINGS DO NOT NECESSARILY INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL COMPLETION OF THE PROJECT. ALL CONTRACTORS SHALL FURNISH ALL OF THOSE ITEMS AND LABOR REQUIRED FOR THE FULL
COMPLETION OF THIS PROJECT IN A FIRST CLASS WORKMANSHIP-LIKE MANNER.
2. ALL WORK IS TO BE PERFORMED FROM FINAL CONSTRUCTION DOCUMENTS ONLY AND A COPY OF THE APPROVED FINAL SET MUST BE LOCATED ON THE SITE AT ALL TIMES. ALL CONTRACTOR'S SUBCONTRACTORS SHALL BE GIVEN FULL SETS OF FINAL CONSTRUCTION
DOCUMENTS WITH NO SHEETS EXCLUDED.
3. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS HOLD PRIORITY OVER APPARENT SCALE. ANY DISCREPANCIES SHOULD BE BROUGHT TO
THE ATTENTION OF THE ARCHITECT IN WRITING.
4. EXISTING CONDITIONS AND DIMENSIONS SHOWN ON THE DRAWINGS HAVE BEEN COMPILED BY THE ARCHITECT FROM EXISTING DRAWINGS PROVIDED BY THE OWNER AND FIELD MEASURING AND SHALL BE USED BY THE CONTRACTOR ONLY AS A GUIDE. ALL CONTRACTORS SHALL BE RESPONSIBLE FOR FIELD VERIFICATION OF ALL DIMENSIONS AND CONDITIONS AND SHALL REPORT ANY DISCREPANCIES IN THE SITE
CONDITIONS OR THE DOCUMENTS TO THE ARCHITECT IN WRITING.
5. CONTRACTORS SHALL BE HELD RESPONSIBLE FOR THE ADHERENCE AND COMPLIANCE TO ALL APPLICABLE CITY, STATE AND NATIONAL CODES, ORDINANCES, AND ACCESSIBILITY REQUIREMENTS, INCLUDING BUT NOT LIMITED TO THOSE OF THE STATE ADA. ANY
DISCREPANCIES SHOULD BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN WRITING.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL UTILITIES AFFECTED BY PROJECT.
7. THE PROJECT SHALL BE ENTIRELY CLEANED BY THE GENERAL CONTRACTOR BEFORE OWNER OCCUPATION INCLUDING ALL FLOORS, WALL
TILES AND ELECTRICAL PLATES.
8. THE WORK AREAS SHALL BE KEPT IN BROOM-SWEPT FINISH CONDITION. ALL CONTRACTORS AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR CLEANING UP AND DISPOSING OF THEIR LITTER AND LEFT OVER MATERIALS ON A REGULAR BASIS AND BE RESPONSIBLE FOR LEAVING THE PROJECT IN A BROOM SWEPT FINISH CONDITIONS UPON COMPLETION OF THEIR PORTION OF THE PROJECT.
9. THE PLUMBING, ELECTRICAL AND HVAC CONTRACTORS SHALL VERIFY VISIBLE EQUIPMENT LOCATIONS AND REPORT ANY DISCREPANCIES OR CONFLICTS TO THE OWNER PRIOR TO SUBMITTING HIS / HER BID. UNLESS THE OWNER AND THE ARCHITECT ARE NOTIFIED IN WRITING OF THE CONFLICTS OR ADDITIONAL SPACE REQUIREMENTS BEFORE THE START OF CONSTRUCTION, ALL CORRECTIVE MEASURES WILL BE MADE
BY THE CONTRACTORS AT NO ADDITIONAL COST TO THE OWNER.
10. THE OWNER'S WRITTEN AUTHORIZATION MUST BE OBTAINED PRIOR TO THE ORDERING OF ANY MATERIAL, AWARDING OF ANY CONTRACTS
OR THE EXECUTION OF ANY WORK WHICH INVOLVES EXTRA COST.
11. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR ADDITIONAL INFORMATION AND COORDINATION OF WORK.
12. DETAILS SHOWN ARE INDICATIVE OF THE CHARACTER, PROFILES, MATERIALS AND SYSTEMS REQUIRED FOR THE WORK INCLUDING THOSE
CONDITIONS NOT COVERED BY SPECIFIC DETAILS.
13. WHERE THE DESIGN INTENT CANNOT BE DETERMINED FROM THE DRAWINGS OR KEYNOTES. CONSULT THEARCHITECT BEFORE PROCEEDING
WITH THE WORK.
14. DIMENSIONS SHALL GOVERN. DO NOT SCALE DRAWINGS. WHERE THERE APPEARS TO BE A CONFLICT BETWEEN DIMENSIONS OR WHERE DIMENSIONS CANNOT BE DETERMINED FROM THE DRAWINGS, CONSULT THE ARCHITECT BEFORE PROCEEDING WITH THE WORK.
15. FOLLOWING DEMOLITION OF THE INTERIOR FINISHES AND THE CEILINGS, THE CONTRACTOR SHALL MAKE A DIGITAL VIDEO RECORDING OF THE EXISTING CONDITIONS AND PROVIDE ACCESS FOR THE OWNER'S AND THE OWNER'S CONSULTANT'S REVIEW OF EXISTING CONDITIONS.
THE OWNER MAY, AT THE OWNER'S OPTION, CONTRACT WORK TO OTHERS OUTSIDE OF THIS CONTRACT. CONFIRM WITH THE ARCHITECT
PRIOR TO PROCEEDING.
16. PENETRATION OPENINGS AND FIRESTOPPING IN OPENINGS SMALLER THAN OR EQUAL TO 4" SHALL BE MADE BY THE TRADE MAKING THE
PENETRATION.
ARCHITECTURAL GENERAL PROJECT NOTES
1. THE FOLLOWING GENERAL NOTES APPLY TO ALL ARCHITECTURAL DRAWINGS
2. THE ARCHITECTURAL DRAWINGS ARE PART OF A LARGER SET OF DRAWINGS WHICH, WHEN COMPLETE, CONSIST OF SPECIFICATIONS AND ALL DRAWINGS LISTED BY THE INDEX OF DRAWINGS. THE WORK DESCRIBED BY THE DRAWINGS OF ANY ONE DISCIPLINE MAY BE AFFECTED BY THE WORK DESCRIBED ON DRAWINGS OF ANOTHER DISCIPLINE AND MAY REQUIRE REFERENCE TO DRAWINGS OF ANOTHER DISCIPLINE.
3. THE ARCHITECTURAL DRAWINGS ESTABLISH AND COORDINATE THE FINISHED APPEARANCE AND EXACT LOCATION OF ALL EXPOSED ELEMENTS OF THE WORK, INCLUDING THAT WORK WHICH IS ILLUSTRATED PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES. LOCATIONS SHOWN ON OTHER DRAWINGS ARE SCHEMATIC, UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS. THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE FOR THE FINISHED APPEARANCE AND EXACT LOCATION OF ALL PARTS OF THE WORK. EXCEPTION:
DIMENSIONED LOCATIONS SHOWN ON DRAWINGS OF OTHER DRAWINGS ARE SCHEMATIC, UNLESS OTHERWISE NOTED ON THE ARCHITECTURE DRAWINGS. THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE FOR THE FINISHED APPEARANCE AND EXACT LOCATION OF ALL PARTS OF THE WORK. EXCEPTION: DIMENSIONED LOCATIONS SHOWN ON DRAWINGS OF OTHER DISCIPLINES:
SHALL GOVERN ONLY WHERE:
1. SPECIFICALLY AND INDIVIDUALLY INDICATED BY SYMBOL, KEYED NOTE, OR NOTATION ON THE ARCHITECTURAL DRAWINGS.
2. OCCURRING WITHIN A ROOM OR OTHER IDENTIFIED SPACE FOR WHICH ARCH SHEET OR SCHEDULE NOTES INDICATE THAT DIMENSIONS
PROVIDED ELSEWHERE SHALL GOVERN.
4. THE ARCHITECTURAL FLOOR PLANS, REFLECTED CEILING PLANS, SECTIONS, AND ELEVATIONS SHOW THE EXACT LOCATION OF MANY – BUT NOT ALL – EXPOSED PARTS OF THE WORK. FOR ITEMS NOT LOCATED EXACTLY, APPLY THE RULES INDICATED BY TYPICAL INSTALLATION DRAWINGS FOR DETERMINING MOUNTING HEIGHTS AND LOCATIONS TO DETERMINE THE EXACT LOCATION OF EACH EXPOSED PART OF THE
WORK.
5. DESIGN REFERENCE ELEVATION +0’-0” AS SHOWN ON THE ARCHITECTURAL DRAWINGS CORRESPONDS TO THE FINISH FLOOR ELEVATION OF
THE FLOOR ILLUSTRATED.
6. FOR NOTES APPLICABLE TO THE SCOPE OR WORK INDICATED ON INDIVIDUAL SHEETS, REFER TO SHEET NOTES ON THAT SHEET.
7. FOR GENERAL NOTES AND SYMBOLS APPLICABLE ONLY TO THE DRAWINGS OF DISCIPLINES OTHER THAN ARCHITECTURE, REFER TO THE
SPECIFIC DRAWINGS OF THAT DISCIPLINE.
8. JOC IS RESPONSIBLE FOR COORDINATING THE WORK OF ALL SUBCONTRACTORS, ASSIGNED SUBCONTRACTORS, TRADES, AND SUPPLIERS.
THE CONTRACTOR SHALL ENDEAVOR TO IDENTIFY AND NOTIFY THE OWNER OF ANY CONFLICTS BETWEEN THE WORK OF DIFFERENT PARTIES AT THE EARLIEST POSSIBLE DATE SO AS TO ALLOW REASONABLE AND ADEQUATE TIME FOR THE CONFLICT TO BE RESOLVED WTIHOUT DELAYING THE WORK. ALL DEVIATIONS FROM THAT WHICH IS REQUIRED BY THE CONTRACT DOCUMENTS MUST BE APPROVED IN
ADVACE BY THE OWNER.
9. REFERENCES TO MECHANICAL, ELECTRICAL. HEATING., ELEC., & FP, ETC. DRAWINGS REFER TO THE HEATING VENTILATION, ELECTRICAL, PLUMBING AND DRAWINGS.
EXISTING CONDITIONS AND APPLICABLE CODES
Revision Schedule
NO. DESCRIPTION DATE
2 3
CONTRACTOR
PARKING
SOUTH WING
CENTER WING
NORTH WING
N O
R T
H A
D M
IN
S O
U T
H A
D M
IN
VISITOR'S PARKING
NORTH PARKING LOT
SOUTH PARKING LOT
RESEARCH
FIELD
PLOT
RESEARCH
FIELD
PLOT
RESEARCH
FIELD
PLOT
RESEARCH
FIELD
PLOT
RESEARCH
FIELD
PLOT
RESEARCH
FIELD
PLOT
PEOPLE'S
GARDEN
MAIN
ENTRANCE
SR-G102
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMPORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)
PC/LS
KS
/1
/2
:2
:0
A
M
H
P ro je c t F ile s \0
-0
-0
U
S D
A N
C A
U R
S H
IP
P
IN
G
A N
D R
E C
E
IV
IN
G
I M
P R
O V
E M
E N
T S
\0 C
A D
\R E
V
IT
\R U
S D
A N
C A
U R
S h ip p in g a n d R e c e iv in g I m p ro v e m e n ts
.r v t
02/20/2024
SITE PLAN
SR-G101
NOT TO SCALE
SITE PLAN
Revision Schedule
NO. DESCRIPTION DATE
C O
R R
ID
O
R C
O R
R
ID
O R
ASU-A3
ASU-A2
EMERGENCY
GENERATOR
RECEIVING
LOADING
DOCK
SR-A101
AREA NOT IN SCOPE OF WORK
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMPORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)
PC/LS
KS
/1
/2
:2
:0
A
M
H
P ro je c t F ile s \0
-0
-0
U
S D
A N
C A
U R
S H
IP
P
IN
G
A N
D R
E C
E
IV
IN
G
I M
P R
O V
E M
E N
T S
\0 C
A D
\R E
V
IT
\R U
S D
A N
C A
U R
S h ip p in g a n d R e c e iv in g I m p ro v e m e n ts
.r v t
02/20/2024
AREA PLAN
SR-G102
3/32" = 1'-0"
AREA PLAN
0 8' 16'
AREA PLAN LEGEND
Revision Schedule
NO. DESCRIPTION DATE
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S000
PC/LS
KS
02/20/24
GENERAL NOTES
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/24
DESIGN CRITERIA
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
IBC 2018
IEBC 2018
ASCE 7-16
ACI 318-14
AISC 360-16
AWS D1.1 AND D1.3
2. RISK CATEGORY II
3. LIVE LOADS:
TYPICAL LIFT 100 PSF (NON REDUCIBLE)
4. ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE BUILDING IN THE COMPLETED
STRUCTURE IS PROVIDED BY THE EXISTING BUILDING IN EACH ORTHOGONAL DIRECTION.
GENERAL
1. DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SAFETY OF PERSONNEL AND PROPERTY ON AND AROUND THE JOBSITE. THE
CONTRACTOR SHALL PROVIDE ADEQUATE SHORING, BRACING, GUYS, ETC. IN
ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
3. STRUCTURAL SUBSTITUTIONS MAY BE ALLOWED WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER. SUPPLIER SHALL PROVIDE SEALED DESIGN CALCULATIONS OR
SUITABLE PRODUCT LITERATURE FOR THE COMPONENTS.
4. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
5. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT OF
NEW WORK.
6. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
7. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
8. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
9. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DO NOT IN ANY WAY
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
10. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
11. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
12. NO HOLES, NOTCHES, BLOCK-OUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
1 100% DESIGN SUBMITTAL 07/11/24
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S001
PC/LS
KS
02/20/24
GENERAL NOTES
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/24
SUBMITTALS
1. SUBMITTALS ARE:
a. CONCRETE MIX DESIGNS
b. CONCRETE REINFORCING
2. SUBMITTALS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
3. SUBMITTALS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DOES NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS.
4. FOR ADDITIONAL INFORMATION ON REQUIRED SUBMITTALS, SEE INDIVIDUAL MATERIAL
SECTIONS.
EXISTING CONDITIONS / DEMOLITION
1. EXISTING CONDITIONS:
a. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM EXISTING
DRAWINGS DATED MAY 13, 1966 BY LANKTON, ZIEGELE, TERRY AND ASSOCIATES AND
FROM FIELD TAKE-OFF BY IMEG.
b. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS
GIVEN AS THE BEST PRESENT KNOWLEDGE. CONTRACTOR TO VERIFY EXISTING
INFORMATION, DIMENSIONS AND SIZES AS REQUIRED TO COMPLETE THEIR WORK.
WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE
REPORTED TO THE ARCHITECT OR STRUCTURAL ENGINEER SO PROPER
CLARIFICATION MAY BE MADE. MODIFICATION OF CONSTRUCTION DETAILS SHALL NOT
BE MADE WITHOUT WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL
ENGINEER.
2. ALL DEMOLITION SHALL BE CARRIED OUT IN SUCH A WAY SO AS TO NOT DAMAGE
EXISTING ELEMENTS WHICH ARE TO REMAIN.
3. ALL ELEMENTS WHICH ARE TO REMAIN AND WHICH ARE DAMAGED DURING DEMOLITION
WORK SHALL BE REPLACED AT NO ADDED COST. EXISTING ELEMENTS ARE TO BE
PROTECTED TO THE FULLEST EXTENT POSSIBLE TO REDUCE SUCH DAMAGE TO A
MINIMUM.
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE
AMERICAN CONCRETE INSTITUTE “ACI DETAILING MANUAL” (SP-066) EXCEPT AS
OTHERWISE SHOWN, NOTED OR SPECIFIED.
2. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL
CONFORMING TO THE FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR 60 Fy = 60 KSI
WELDED WIRE REINFORCING ASTM A1064 Fy = 65 KSI
DEFORMED BAR ANCHORS ASTM A1064 Fy = 70 KSI
3. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE OUTERMOST
REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3”
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2”
#5 BARS OR SMALLER 1 1/2”
4. WELDING OF REINFORCING BARS TO BE IN ACCORDANCE WITH AWS D1.4.
5. DEFORMED BAR ANCHORS (DBA) SHALL BE AUTOMATICALLY END WELDED WITH SUITABLE
WELDING EQUIPMENT IN THE SHOP OR IN THE FIELD. WELDING SHALL BE IN ACCORDANCE
WITH THE MANUFACTURER.
6. SUPPORTS FOR REINFORCEMENT SHALL HAVE CLASS 2 PROTECTION AS DEFINED IN THE
CRSI MANUAL OF STANDARD PRACTICE, UNLESS OTHERWISE NOTED.
7. ALL WELDED WIRE REINFORCING (WWR) SHALL BE LAPPED 2 PANELS AT EDGES AND
ENDS.
8. CONTINUOUS HORIZONTAL REINFORCING SHALL BE LAPPED AT MIDSPAN FOR TOP BARS
AND DIRECTLY OVER SUPPORTS FOR BOTTOM BARS. AT DISCONTINUOUS ENDS, THE TOP
STEEL SHALL BE BENT DOWN 12 BAR DIAMETERS OR 12” MINIMUM, WHICHEVER IS
GREATER.
9. WHERE REINFORCEMENT LENGTH IS SPECIFIED, NO SPLICES ARE PERMITTED WITHIN THE
SPECIFIED LENGTH WITHOUT APPROVAL BY THE STRUCTURAL ENGINEER.
10. DOWELS BETWEEN WALLS SHALL BE THE SAME GRADE, SIZE AND SPACING OR NUMBER
AS THE VERTICAL REINFORCING, RESPECTIVELY, UNLESS OTHERWISE NOTED. PROVIDE
FOUNDATION DOWELS TO MATCH SIZE AND SPACING OF WALL REINFORCEMENT. EXTEND
DOWELS A LAP SPLICE LENGTH INTO WALL AND TERMINATE WITH STANDARD HOOK AT
BOTTOM OF FOOTING, UNLESS OTHERWISE NOTED.
1 100% DESIGN SUBMITTAL 07/11/24
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S002
PC/LS
KS
02/20/24
GENERAL NOTES
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/24
11. CUTTING OF REINFORCING WHICH CONFLICTS WITH EMBEDDED OBJECTS OR SLEEVES IS
NOT ACCEPTABLE.
12. REINFORCING BARS SHALL BE BENT COLD, AND NO METHOD OF FABRICATION SHALL BE
USED WHICH WOULD BE INJURIOUS TO THE MATERIAL. HEATING OF BARS FOR BENDING IS
NOT PERMITTED.
13. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED EXCEPT AS INDICATED
ON THE DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER.
14. USE TEMPLATES TO SET ALL EMBEDDED ANCHOR BOLTS, LEVELING PLATES, AND DOWEL
BARS AS REQUIRED OR INDICATED ON THE DRAWINGS.
15. SUBMIT SHOP DRAWINGS FOR FABRICATION AND PLACEMENT OF REINFORCING STEEL.
INCLUDE SCHEDULES AND DIAGRAMS OF BENT BARS AND SHOW ARRANGEMENT OF
REINFORCEMENT, INCLUDING CONCRETE COVER. STRUCTURAL ENGINEER’S REVIEW WILL
BE FOR COMPLIANCE WITH DESIGN REQUIREMENTS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING DIMENSIONS AND QUANTITIES.
16. ALL CONCRETE NOT OTHERWISE SPECIFIED SHALL BE REINFORCED TO THE MINIMUM
REQUIREMENT OF ACI 318.
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE CORRESPONDING EDITION OF THE
AMERICAN CONCRETE INSTITUTE PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI
308.1, ACI 318 AND SP-066, UNLESS OTHERWISE NOTED.
2. CONCRETE MATERIALS SHALL CONFORM TO:
CEMENT ASTM C150, TYPE I OR II
FLY ASH ASTM C618, TYPE C OR F
FINE AND COARSE AGGREGATE ASTM C33
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER REDUCING ADMIXTURE ASTM C494
CONCRETE STRENGTHS SHALL CONFORM TO:
INTENDEDUSE STRENGTH(PSI) EXPOSURE
CLASS
FOUNDATIONS 4000 F3, S0, W0, C1
SLAB ON GRADE 4000 F3, S0, W0, C1
UNLESS OTHERWISE NOTED 4000 F3, S0, W0, C1
NORMAL-WEIGHT 28-DAY STRENGTH UNLESS OTHERWISE NOTED.
4. LIGHTWEIGHT CONCRETE SHALL HAVE A DRY DENSITY OF 107-116 PCF.
5. DRYPACK OR GROUT SHALL HAVE A MINIMUM 28-DAY STRENGTH OF 7000 PSI.
6. SLAB-ON-GRADE CONSTRUCTION: LOCATE SAW-CUT CONTROL JOINTS ALONG COLUMN
LINES WITH INTERMEDIATE JOINTS SPACED PER THE TABLE BELOW, UNLESS OTHERWISE
NOTED. SLAB PANELS SHALL HAVE A MAXIMUM LENGTH TO WIDTH RATIO OF 1.5:1.
PROVIDE ADDITIONAL CONTROL JOINTS AT ALL RE-ENTRANT CORNERS. SEE PLAN FOR
SPECIAL CASES.
THICKNESS (IN) MAXIMUM JOINT SPACING EACH WAY (FT)
8 18
7. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ENSURE PROPER
DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS, NOTCHES, AND EDGES
OF WALLS/FOUNDATIONS PRIOR TO PLACING CONCRETE.
8. CONSTRUCTION JOINTS SHALL BE THOROUGHLY ROUGHENED TO 1/4” AMPLITUDE BY
SAND BLASTING OR MECHANICAL MEANS. CLEAN BEFORE POUR. LOCATION TO BE
APPROVED BY THE STRUCTURAL ENGINEER. SUBMIT LOCATION PLAN OF ALL PROPOSED
JOINTS NOT INDICATED ON DRAWINGS FOR APPROVAL PRIOR TO BEGINNING WORK.
9. PRIOR TO PLACING CONCRETE, THE CONTRACTOR SHALL ENSURE ALL REINFORCING AND
EMBEDMENTS, INCLUDING COLUMN ANCHOR BOLTS, ARE PROPERLY LOCATED AND
SECURELY TIED IN PLACE.
10. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL PENETRATIONS THROUGH
CONCRETE BEFORE PLACING. SECURE SLEEVES TO PREVENT MOVEMENT DURING
PLACING OPERATIONS. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS.
11. CONFIRM WITH ARCHITECT THAT MATERIALS TO BE EMBEDDED ARE SUITABLE FOR
EMBEDMENT IN CONCRETE.
12. CONDUIT, PIPES, AND SLEEVES EMBEDDED IN CONCRETE SHALL CONFORM TO
REQUIREMENTS OF ACI 318, SECTIONS 20.7 AND 26.8.
13. NO ALUMINUM SHALL BE ALLOWED IN THE CONCRETE WORK UNLESS COATED TO
PREVENT ALUMINUM-CONCRETE REACTION.
14. WATERSTOPS SHALL BE A [ENGR NOTE: SELECT ONLY ONE OF THE FOLLOWING TWO
TYPES, BENTONITE OR PVC.] FLEXIBLE BENTONITE PVC PRODUCT. ACCEPTABLE
PRODUCTS INCLUDE: [ENGR NOTE: KEEP FOLLOWING IF USING BENTONITE] CETCO
WATERSTOP-RX AND GREENSTREAK SWELLSTOP WESTIC BARRIER TECHNOLOGIES TPE-
R WATERSTOP AND GREENSTREAK PVC WATERSTOP.
15. PROJECTING CORNERS OF WALLS SHALL BE FORMED WITH A 3/4 INCH CHAMFER, UNLESS
OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
1 100% DESIGN SUBMITTAL 07/11/24
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S003
PC/LS
KS
02/20/24
GENERAL NOTES
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/24
16. SLOPE SLABS TO DRAINS OR FOR POSITIVE DRAINAGE IF NO DRAINS ARE PRESENT AND
PROVIDE DEPRESSIONS WHERE SHOWN ON THE STRUCTURAL AND/OR ARCHITECTURAL
DRAWINGS WITHOUT REDUCING THE THICKNESS OF SLAB INDICATED. FOR SLAB-ON-
GRADE DEPRESSIONS GREATER THAN 1 INCH, SEE DETAILS FOR ADDITIONAL
REINFORCING.
17. INTERNALLY VIBRATE ALL CAST-IN-PLACE CONCRETE EXCEPT SLABS-ON-GRADE WHICH
NEED ONLY BE VIBRATED AROUND UNDER FLOOR DUCTS AND OTHER EMBEDDED ITEMS.
VIBRATE TOPS OF COLUMNS.
18. PROVIDE VERTICAL CONTROL JOINTS IN EXPOSED CONCRETE WALLS AT A MINIMUM
UNIFORM SPACING NOT TO EXCEED 25 FEET PER ACI 224.3. COORDINATE JOINT
LOCATIONS WITH ARCHITECTURAL DRAWINGS.
19. CONCRETE SHALL NOT BE PERMITTED TO DROP MORE THAN 5 FEET.
20. IF CONCRETE IS PLACED BY PUMPING, SUPPORT SHALL BE PROVIDED FOR THE HOSE. THE
HOSE SHALL NOT BE ALLOWED TO RIDE ON THE REINFORCING AND OTHER EMBEDDED
ITEMS.
21. CONCRETE SLABS SHALL BE CURED BY KEEPING CONTINUOUSLY WET FOR 7 DAYS.
FORMS FOR CONCRETE WALLS SHALL BE LEFT IN PLACE FOR 7 DAYS OR MAY BE
STRIPPED AFTER 3 DAYS AND COATED WITH AN APPROVED CURING COMPOUND.
22. NO LOADS SHALL BE PLACED ON STRUCTURAL CONCRETE SLABS WITHIN 7 DAYS AFTER
CONCRETE IS PLACED. AFTER CONCRETE IS PLACED, IN NO CASE SHALL THE
SUPERIMPOSED CONSTRUCTION LOADS BE GREATER THAN SPECIFIED DESIGN LIVE
LOADS, UNLESS THE WORK IS SHORED.
23. NOTIFY THE ARCHITECT/STRUCTURAL ENGINEER 48 HOURS MINIMUM PRIOR TO ALL
POURS.
24. CONTRACTOR SHALL SURVEY ALL CONCRETE WORK WITHIN 48 HOURS OF PLACING
CONCRETE TO ENSURE PLACEMENT IS IN ACCORDANCE WITH PROJECT REQUIREMENTS.
25. THE DESIGN AND ENGINEERING OF FORMWORK, SHORING AND RESHORING, AS WELL AS
THEIR CONSTRUCTION, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. FORMS
SHALL BE DESIGNED TO HAVE SUFFICIENT STRENGTH TO SAFELY WITHSTAND THE LOADS
RESULTING FROM PLACEMENT AND VIBRATION OF THE CONCRETE AND SHALL ALSO BE
DESIGNED FOR SUFFICIENT RIGIDITY TO MAINTAIN SPECIFIED TOLERANCES. CONTRACTOR
SHALL SUBMIT DETAILED FORMWORK SHOP DRAWINGS TO THE ARCHITECT TO BE
REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN CONCEPT ONLY.
26. CORING OF CONCRETE IS NOT PERMITTED UNLESS APPROVED BY THE STRUCTURAL
ENGINEER.
27. NO CONCRETE SHALL BE PLACED ONTO OR AGAINST SUBGRADES CONTAINING FREE
WATER, FROST, ICE OR SNOW.
28. DURING WINTER CONSTRUCTION, ALL FOOTINGS SHALL BE PROTECTED FROM FROST
PENETRATION UNTIL THE BUILDING IS ENCLOSED AND TEMPORARY HEAT IS PROVIDED.
29. GENERAL CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR SIZE, LOCATION AND HEIGHT
OF MECHANICAL EQUIPMENT PADS ON CONCRETE SLAB ON STEEL DECK AND SLAB-ON-
GRADE.
30. THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND
REVIEWED BY THE TESTING AGENCY. RESPONSIBILITY FOR OBTAINING THE REQUIRED
DESIGN STRENGTH IS THE CONTRACTOR’S. SUBMIT TEST DATA ON EACH PROPOSED MIX
FOR REVIEW IN ACCORDANCE WITH THE APPLICABLE CODE. MIX DESIGNS SUBMITTED
WITHOUT THE REQUIRED TEST DATA WILL BE RETURNED WITHOUT REVIEW.
STEEL
1. STRUCTURAL STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE AMERICAN INSTITUTE
OF STEEL CONSTRUCTION (AISC) “DETAILING FOR STEEL CONSTRUCTION” AND
FABRICATED AND ERECTED IN ACCORDANCE WITH THE “SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS”.
2. STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:
OTHER ROLLED SHAPES ASTM A36 Fy = 36 KSI
PIPE SECTIONS ASTM A53, GR B Fy = 35 KSI
3. SPLICING OF STEEL MEMBERS WHERE NOT DETAILED ON THE DRAWINGS IS PROHIBITED
WITHOUT THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER AS TO LOCATION, TYPE
OF SPLICE AND CONNECTION TO BE MADE.
4. ALL STEEL EXPOSED TO WEATHER OR AS NOTED ON PLAN SHALL BE HOT-DIP GALVANIZED
AFTER FABRICATION IN ACCORDANCE WITH ASTM A123 G60. ABRADED AREAS TO BE
TOUCHED UP WITH COLD GALVANIZING COMPOUND IN ACCORDANCE WITH ASTM A780.
14. ALL GALVANIZED HOLLOW SECTIONS SHALL HAVE WELDED CAP PLATES TO SEAL
EXPOSED ENDS.
15. CUTS, HOLES, OPENINGS, ETC., REQUIRED IN STRUCTURAL STEEL MEMBERS FOR THE
WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS. BURNING OF
HOLES AND CUTS IN THE FIELD SHALL NOT BE ALLOWED, EXCEPT BY WRITTEN
AUTHORIZATION FROM THE STRUCTURAL ENGINEER.
16. FURNISH AND INSTALL MISCELLANEOUS STEEL (CURBS, HANGERS, EXPANSION JOINT
ANGLES, STRUTS, ETC.) AS CALLED FOR OR AS NECESSARY PER ARCHITECTURAL AND
MECHANICAL/ELECTRICAL DRAWINGS.
17. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL
STRUCTURAL STEEL FOR ARCHITECT/STRUCTURAL ENGINEER’S REVIEW BEFORE
FABRICATION.
1 100% DESIGN SUBMITTAL 07/11/24
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S004
Designer
Checker
07/11/24
GENERAL NOTES
POST-INSTALLED ANCHORS
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/24
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS.
ACCEPTABLE ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY AND
CONFIGURATION MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY AND
CONFIGURATION. ANY ALTERNATES ARE TO BE SUBMITTED TO THE STRUCTURAL
ENGINEER FOR REVIEW. INSTALL IN ACCORDANCE WITH MANUFACTURER’S WRITTEN
INSTRUCTIONS. BELOW SUMMARIZES EACH ANCHOR TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
a. EXPANSION ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
GROUTED
MASONRY
HILTI KB3 (ESR-1385) DEWALT POWER STUD+ SD1 (ESR-2966)
SIMPSON WEDGE-ALL (ESR-1396)
UNCRACKED
CONCRETE
HILTI KB3 (ESR-2302) DEWALT POWER STUD+ SD2 (ESR-2502) RED
HEAD TRUBOLT+ (ESR-2427) SIMPSON STRONG
BOLT 2 (ESR-3037)
CRACKED
CONCRETE
HILTI KBTZ (ESR-1917) DEWALT POWER STUD+ SD2 (ESR-2502) RED
HEAD TRUBOLT+ (ESR-2427) SIMPSON STRONG
BOLT 2 (ESR-3037)
b. THREADED SCREW ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
GROUTED
MASONRY
HILTI KWIK HUS-EZ
(ESR-3056)
DEWALT WEDGE-BOLT+ (ESR-1678) SIMPSON
TITEN HD (ESR-1056)
UNCRACKED
CONCRETE
HILTI KWIK HUS-EZ
(ESR-3027)
DEWALT POWER SCREW-BOLT+ (ESR-3889)
SIMPSON TITEN HD (ESR-2713)
CRACKED
CONCRETE
HILTI KWIK HUS-EZ
(ESR-3027)
DEWALT POWER SCREW-BOLT+ (ESR-3889)
SIMPSON TITEN HD (ESR-2713)
3. ADHESIVE ANCHORS: SHALL CONSIST OF DEFORMED REINFORCING BARS OR ASTM A193
GRADE B7 RODS, HEAVY DUTY NUTS AND WASHERS AND A TWO COMPONENT
STRUCTURAL ADHESIVE. WHERE ANCHORING INTO HOLLOW MASONRY, A SCREEN TUBE
SHALL BE PROVIDED.
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HOLLOW
MASONRY
HILTI HIT-HY 270
(ESR-4143)
DEWALT AC 100+ GOLD (ESR-3200) SIMPSON
SET-XP (ESR-0265)
GROUTED
MASONRY
HILTI HIT-HY 270
(ESR-4143)
DEWALT AC 100+ GOLD (ESR-3200) RED HEAD A7
ACRYLIC (ESR-3951) SIMPSON SET-XP (ESR-0265)
CONCRETE HILTI HIT-HY 200
(ESR-3187)
DEWALT AC 200+ (ESR-4027) SIMPSON SET-3G
(ESR-4057)
4. CRACKED CONCRETE REPRESENTS ALL CONCRETE FOR PROJECTS LOCATED IN SEISMIC
DESIGN CATEGORY C OR HIGHER, TENSILE ZONES SUCH AS BOTTOMS OF BEAMS AND
SLABS, OR WHERE NOTED ON THE DRAWINGS.
1 100% DESIGN SUBMITTAL 07/11/24
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S005
PC/LS
KS
02/20/24
TESTING AND INSPECTION
TESTING, INSPECTIONS, AND OBSERVATIONS
1. THE STRUCTURAL ENGINEER DOES NOT PROVIDE INSPECTIONS OF CONSTRUCTION. STRUCTURAL ENGINEER MAY MAKE PERIODIC OBSERVATIONS OF THE CONSTRUCTION. SUCH OBSERVATIONS SHALL NOT REPLACE REQUIRED INSPECTIONS BY THE GOVERNING AUTHORITIES OR SERVE AS “SPECIAL INSPECTIONS” AS MAY BE REQUIRED BY CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE.
2. SEE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION
REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
a. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK.
b. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND INSPECTION PROGRAM.
c. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT, STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE COMPLETED AND FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
d. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION
AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS.
4. SPECIAL INSPECTIONS AND TESTS ARE REQUIRED FOR MATERIALS AND SYSTEMS REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL MANUFACTURER’S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT CONTAINED IN CHAPTER 17 OF THE IBC OR IN STANDARDS REFERENCED BY
THE IBC. THESE ITEMS INCLUDE:
a. POST-INSTALLED ANCHORS - INSPECTION
5. THE FOLLOWING WORK SHALL BE INSPECTED BY THE SPECIAL INSPECTOR UNLESS SPECIFICALLY WAIVED BY THE BUILDING OFFICIAL.
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/241 100% DESIGN SUBMITTAL 07/11/24
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S006
PC/LS
KS
02/20/24
TESTING AND INSPECTION
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
CONCRETE CONSTRUCTION
1. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING TENDONS, AND VERIFY
PLACEMENT
X ACI 318: CH 20,
25.2, 25.3, 26.2.1-26.6.3
1908.4
2. MATERIAL IDENTIFICATION OF REINFORCING (TYPE/GRADE) X AISC 341: TABLE
J9.1
3. REINFORCING STEEL HAS NOT BEEN REBENT IN THE FIELD X AISC 341: TABLE
J9.1
4. REINFORCING STEEL HAS BEEN TIED AND SUPPORTED AS REQUIRED X AISC 341: TABLE
J9.1
5. REINFORCING STEEL CLEARANCES HAVE BEEN PROVIDED X AISC 341: TABLE
J9.1
6. COMPOSITE STEEL MEMBERS HAVE REQUIRED SIZE X AISC 341: TABLE
J9.1
7. REINFORCING BAR WELDING:
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706 X AWS D1.4
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16”; AND X ACI 318: 26.6.4
c. INSPECTS ALL OTHER WELDS X
8. INSPECT ANCHORS CAST IN CONCRETE X ACI 318: 17.8.2
9. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS:
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
X ACI 318: 17.8.2.4
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a X ACI 318: 17.8.2
10. VERIFY USE OF REQUIRED DESIGN MIX X ACI 318: CH 19,
26.4.2, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
11. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF
THE CONCRETE
X ASTM C172, ASTM
C31, ACI 318: 26.5,
26.12
1907.10
12. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES
X ACI 318: 26.5 1908.6, 1908.7,
1908.8
13. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES X ACI 318:
26.5.3-26.5.5
1908.9
14. INSPECT PRESTRESSED CONCRETE FOR:
a. APPLICATION OF PRESTRESSING FORCES; AND X ACI 318: 26.11.2
b. GROUTING OF BONDED PRESTRESSING TENDONS X
15. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS X ACI 318: 26.9
16. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF TENDONS IN POST-
TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS
AND STRUCTURAL SLABS
X ACI 318: 26.11.2
17. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE
MEMBER BEING FORMED
X ACI 318: 26.11.2(b)
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/241 100% DESIGN SUBMITTAL 07/11/24
C
D
15 16
18'-0"
(E) 8" CONC SLAB
T.O. SLAB ELEVATION (+7'-6")
(E) CONCRETE PIER.
DEMO TO BE FLUSH
WITH TOP OF SLAB
(E) 8" SLAB ON GRADE
SLOPED TO DRAIN.
TOP OF SLAB AT EDGE (0'-0")
W A
L L
T
Y P
(E
C O
N C
F D
N
1'-4" 2'-0" 2'-0" 1'-4"
2'-1" 8'-0"
12'-2"
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/2
/2
:2 :3
P
M
C
R e vi t L o c a l F ile s \S
.0
U
S D
A -P e o ri a -I
L -N
C A
U R
U p g ra d e s C
S u jit k u m a r.
N .P a d h a n .r v t
SR-S100
PC/LS
KS
02/20/24
DEMOLITION PLAN
N O R
HT
1/4" = 1'-0"1
EXISTING DOCK PIT
NOTES:
1. VERIFY ALL EXISTING CONDITIONS IN FIELD. NOTIFY EOR IF
EXISTING CONDITIONS DEVIATE FROM WHAT IS SHOWN ON PLAN.
2. SEE ARCH AND MEP DRAWINGS FOR DIMENSIONS NOT GIVEN
HERE.
Revision Schedule
NO. DESCRIPTION DATE
KEYNOTES:
1. DEMO SLAB AS NEEDED TO INSTALL PIER AND BOLLARDS. SEE
1/SR-S101 AND ARCH DRAWINGS FOR BOLLARD LOCATION.
REPLACE DEMOED SLAB WITH SLAB OF SAME THICKNESS. SEE
1/SR-S301.
1 100% DESIGN SUBMITTAL 07/11/24
NOTES:
1. SEE SR-S300 FOR SLAB ON GRADE CONSTRUTION DETAILS.
2. SEE ARCH AND MEP DRAWINGS FOR DIMENSIONS NOT GIVEN
HERE.
KEYNOTES:
1. 8" CONCRETE SLAB ON GRADE WITH #5 @ 12" OC, EACH WAY. TOP
OF SLAB (3'-10") FOR BASE BID AND (3'-8") FOR BID OPTION. VERIFY
SLAB ELEVATION WITH EQUIPMENT SUPPLIER. INFILL PIT WITH #57
CRUSHED STONE TO BOTTOM OF SLAB.
2. CONCRETE PIER. SEE 4/SR-S300.
3. SUMP PIT, SEE DETAIL 2/SR-S301. COORDINATE WITH PLUMBING
DRAWINGS.
C
D
15 16
18'-0"
(E) 8" CONC SLAB
T.O. SLAB ELEVATION (+7'-6")
W A
L L
T
Y P
(E
C O
N C
F D
N
12'-2"
SR-S300
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:2 :5
P
M
C
R e vi t L o c a l F ile s \S
.0
U
S D
A -P e o ri a -I
L -N
C A
U R
U p g ra d e s C
S u jit k u m a r.
N .P a d h a n .r v t
SR-S101
PC/LS
KS
02/20/24
FOUNDATION PLAN
N O R
HT
1/4" = 1'-0"1
DOCK PIT FOUNDATION PLAN
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/241 100% DESIGN SUBMITTAL 07/11/24
BACKER ROD AND
SEALANT - SEE SPECS
SAWCUT JOINT WITHIN
24 HOURS OF CONCRETE
PLACEMENT
SLAB ON GRADE
SEE PLAN
S E
E P
L A
N
T H
IC
K
N E
S S t)
1/4" t/ M
IN
IM
U M
ENGINEERED FILL
VAPOR RETARDER
NOTE 2
NOTES:
1. COMPACT ALL FILL MATERIAL TO 95% OF THE MAXIMUM
DRY DENSITY PER ASTM D1557.
2. VAPOR RETARDER TO MEET ASTM E1745, CLASS A AND
BE NOT LESS THAN 15 MILS THICK.
SLAB ON GRADE - SEE PLAN
REINFORCING - SEE PLAN
/3 t)
S E
E P
L A
N T
H
IC
K N
E S
S t)
S E
E P
L A
N
(E) CONT L4x4x3/8 WITH 5/8"Ø x 6" BOLT @ 2'-0" OC
EL (0'-0")
T.O. (E) SLAB
6"
PIPE 8 STD WITH CONCRETE INFILL
SEE ARCH FOR LOCATION
ROUND OFF TOP OF CONCRETE INFILL
CONCRETE PIER
SEE 4/SR-S300
EL (5'-0")
T.O. LIFT
CONCRETE SLAB SEE PLAN
COORDINATE TOP OF SLAB WITH
DOCK LIFT MANUFACTURER
DOCK LIFT SEE ARCH
WATERSTOP
SEE - GENERAL NOTES
#4 TIES @6" OC. DOWEL
INTO EXITING
FOUNDATION WALL
WITH HILTI HIT-HY 200
EPOXY, MIN 4" EMBED
(7) #4 VERT
EMBED
BOLLARD SEE 1/SR-S300
2'-0" DIAMETER CONCRETE PIER
(E) CONCRETE WALL
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S300
PC/LS
KS
02/20/24
CONCRETE DETAILS
3/4" = 1'-0"2
TYPICAL CONTROL JOINT
3/4" = 1'-0"3
TYPICAL SLAB SECTION
1/4" = 1'-0"1
DOCK PIT SECTION
1/2" = 1'-0"4
PIER PLAN VIEW
Revision Schedule
NO. DESCRIPTION DATE
1 95% DESIGN SUBMITTAL 06/12/241 100% DESIGN SUBMITTAL 07/11/24
6"
SMOOTH DOWEL BARS - SEE
SCHEDULE. DRILL INTO
EXISTING
EXISTING CONCRETE SLAB
UNBONDED
SLAB ON GRADE
SEE TYPICAL
DETAILS
SLAB
THICKNESS
4"
SMOOTH DOWEL
BAR
5"
6"
> 6"
1/2"Ø x 1'-4" @ 18" OC
1"Ø x 1'-4" @ 12" OC
3/4"Ø x 1'-4" @ 12" OC
PLAN
#4
1'-6"
@ 12" EA WAY
COORD WITH PLUMBING
& ARCH FOR DIMENSION
8" SLAB ON GRADE WITH
#5 @ 12" OC EACH WAY
SLAB ON GRADE
SEE PLAN
EL (SEE PLAN)
T.O. SLAB
(5) #4 TIES
Expiration Date of Seal: 11-30-2024
Drawing Sheet / RFI No. Reference:
BE Project Name:
t 312.440.2300 f 312.440.2303 www.baileyedward.com 35 East Wacker Dr Suite 800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
D A
U S
Agricultural Research Service
COPYRIGHT BAILEY EDWARD DESIGN 2024 - BED# 24001
DWG. NO.
SHEET OF
BE DESIGN
CO:
FACILITY ENGINEER:
DESIGNER:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
GREG KENNEDY
DEBORAH WELLS
CRAIG TIEZZIMP
PEORIA, IL 61604
1815 N UNIVERSITY ST
NATIONAL CENTER
FOR AGRICULTURAL
UTILIZATION
RESEARCH (NCAUR)ORDER DATE:
TASK ORDER NO.:
24001
SHIPPING / RECEIVING
IMPROVEMENTS
/1
/2
:5
:1
A
M
C R e v it L o c a l F ile s \S
.0
U S
D A
-P e o ri a
-I L -N
C A
U R
U p g ra d e s C
A u tu m n
.N .B u e s k in g .r v t
SR-S301
PC/LS
KS
06/20/24
CONCRETE DETAILS
Revision Schedule
NO. DESCRIPTION DATE
3/4" = 1'-0"1
NEW TO EXISTING SLAB DETAIL
NO SCALE2
SUMP PIT
AREA NOT IN SCOPE OF WORK
EXISTING…