Drawings .pdf
PDF 4 MB Posted
- Attached to
- Y1DA--756-16-110 NRM Upgrade Underground Feeder
- Solicitation number
- 36C25722B0001
About this file
This document is a pre-solicitation notice for an invitation for bid to upgrade underground feeders at the VA El Paso Healthcare System in El Paso, Texas. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17 anticipates awarding a firm-fixed-price construction contract with a projected bid due date of November 2, 2021. The project includes demolishing existing structures and furnishing labor, materials, and work to replace existing utility transformers and switches. This requirement is set aside 100% for Service-Disabled Veteran Owned Small Businesses. The applicable NAICS code is 238210 and the estimated construction cost range is $1,000,000 to $2,000,000. Apparent successful offerors must be verified and visible in the Department of Veterans Affairs Center for Veterans Enterprises database prior to submitting a proposal.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25722B0001 0005.docx | DOCX document | |
| Attachment 1-ADD. #1 SPECIFICATIONS.pdf | ||
| 36C25722B0001 0004.docx | DOCX document | |
| Attachment 3-E6_07.pdf | ||
| Consolidated RFI for Underground feeder Responses.pdf | ||
| Attachment 2-ADD 1 - DESIGN PRIMARY POWER.pdf | ||
| 36C25722B0001 0003.docx | DOCX document | |
| 36C25722B0001 0002.docx | DOCX document | |
| 36C25722B0001 0001.docx | DOCX document | |
| 36C25722B0001_3.docx | DOCX document | |
| Specifications.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NUMBER:
ISSUE DATE:
EA #:
CLIENT #:
PROJECT DIRECTORY:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
A-000
DESIGN PRIMARY POWER, SECONDARY SIDE
ISSUE FOR CONSTRUCTION
D E
S
IG
N P
R
IM
A R
Y P
O W
E R
, S E
C O
N D
A R
Y S
ID
E
IS
S
U E
F O
R C
O N
S T
R U
C T
IO
N
E A
.0
756-16-110
EA03.0111
5001 N. PIEDRAS / EL PASO, TEXAS 79930
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
03-31-2021 2021-02-12
March 31, 2021
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:DESCRIPTION:
EA:CLIENT:
1 2 3 4 5 6 7 8
S
D ZIP
FORCE PROTECTION STREET ADDRESS
FORCE PROTECTION CITY AND ZIP
FORCE PROTECTION NAME
FORCE PROTECTION PH AND FAX
MEP STREET ADDRESS
MEP CITY AND ZIP
MEP ENGINEERS
MEP PH AND FAX
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CONSULTANT 01 NAME
CONSULTANT 01 PH AND FAX
FORCE PROTECTION CONTACT
ENAPAY, LLC
MEP CONTACT
ENAPAY, LLC
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
REVISION SCHEDULE
No. DESCRIPTION DATE
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
PROJECT NUMBER:
BUILDING NUMBER:
EA:CLIENT:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
SYMBOLS AND NOTES
DESIGN PRIMARY POWER
SECONDARY SIDE
5001 N. PIEDRAS / EL PASO, TEXAS 79930
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
756-16-110 EA03.0111
D
ES
IG
N
P R
IM
A
R Y
PO
W
ER
. S
EC
O
N D
A R
Y
SI
D E
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
PR
O
JE
C T
N U
M B
ER
: E
A
.0
E-0
A
H1A-1 CIRCUIT NUMBER
LIGHT FIXTURE TYPE
XX/XX/XX/XX
FUSE SIZE
POLE(S)
FRAME SIZE
NEMA RATING
a
SWITCHING
CONFIGURATION
E
VERTICALVERT
SWGR SWITCHGEAR
MEDIUM VOLTAGEMV
MOUNTEDMTD
MEZZ MEZZANINE
MECHANICALMECH
LOW POWER FACTORLPF
INSTRUMENT/INSTRUMENTATIONINST
HORIZONTALHORIZ
HPF HIGH POWER FACTOR
FUTUREFUT
EQUIPMENTEQPT
ES ENERGY SAVING
ELECTRIC/ELECTRICALELEC
ELECTRICAL WATER HEATEREWH
EXH EXHAUST
CND CONDUCTOR
CONTINUATIONCONT
CATALOG NUMBERCAT NO.
BOTTOM OF TRAYBOT
BOD BOTTOM OF DUCT
LIGHTING SYMBOL LEGEND
(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)
NIC
NFS
NO
POLE(S)
OVERHEADOH
NTS
P
PA
PL
PVC
PNL
RC
RCP
PF
SWITCH
REC
RVSS
RGS
SF
SPDT
SW
SS
SWBD
TA
TAS
SPST
SINGLE-POLE, DOUBLE-THROW
TRIP AMPERE(S)
SINGLE-POLE, SINGLE-THROW
SWITCHBOARD
START-STOP
RECEPTACLES(S)
SQUARE FOOT OR FEET
REDUCED VOLTAGE, SOLID STATE
RIGID GALVANIZED STEEL
REFLECTED CEILING PLAN
POLYVINYL CHLORIDE
REMOTE CONTROL
PUBLIC ADDRESS SYSTEM
POWER FACTOR
PANELBOARD
PILOT LIGHT
NOT TO SCALE
NORMALLY OPEN
NON-FUSIBLE SAFETY SWITCH
NOT IN CONTRACT
TEXAS ACCESSIBILITY STANDARDS
TYPICAL
TU
TEMP
TEL
TYP
TV
UL
UNO
UPS
V
VA
UG
WITH
WITHOUT
WATT(S)
DELTA
PHASE(S)
NUMBER
W
VFD
WP
W/ W/O
XP
XFMR
EXPLOSION-PROOF
TRANSFORMER
WEATHERPROOF
VOLTAGE OR VOLT(S)
VARIABLE FREQUENCY DRIVE
VOLT-AMPERE(S)
UNLESS NOTED OTHERWISE
UNINTERRUPTIBLE POWER SUPPLY
UNDERWRITERS LABORATORIES, INC.
TEXAS UTILITIES ELECTRIC
UNDERGROUND
TELEVISION
TEMPORARY
TELEPHONE
FS
FLEX
HERTZ
G
HVAC
HPS
HID
HP
HOA
GFI
FVR
FVNR
GS
HZ
KV
KWH
KW
KA
JBOX
IMC
IG
IES
KVA
AC
ACCU
A
AFC
AFF
ADA
AIC
AHU
ALT
ARCH
APPROX
AFG
ATS
AUX
AWG
BFG
BFC
C
CATV
CCTV
CB
CKT
BLDG
CLOSED-CIRCUIT TELEVISION
CIRCUIT BREAKER
CABLE TELEVISION
CONDUIT OR TUBING
BUILDING
BELOW FINISHED GRADE
AUTOMATIC TRANSFER SWITCH
APPROXIMATE OR APPROXIMATELY
AMPERE INTERRUPTING CAPACITY(ROOT
AMERICANS WITH DISABILITIES ACT
AIR-COOLED CONDENSING UNIT
BELOW FINISHED CEILING
AUXILIARY
AMERICAN WIRE GAGE
ARCHITECT
ALTERNATE
MEAN SQUARE ALTERNATE)
ABOVE FINISHED CEILING
AIR HANDLING UNIT
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
ALTERNATING CURRENT
AMPERE(S)
CIRCUIT
m
MIC
MAX
MH
MCP
MCC
MCB
LTG
LPS
KVAR
MIN
NEMA
NEC
NC
MVAR
MW
MVA
MTS
MMS
mm
MLO
NFPA
PANELBOARD, SWITCHBOARD OR MOTOR CONTROL CENTER
CLG
CT(S)
DC
DISC
DIV
COMM
DPDT
DPST
EGS
EC
EHH
DWG(S)
ELEV
EMH
EWC
EX
EMT
EMERG
F
FACP
FAAP
FBO
FLA
FL
CONDUIT ABOVE CEILING
BRANCH CIRCUIT HOMERUN TO PANELBOARD. EGC TO BE RUN WITH ALL CIRCUITS
LB-3
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
ELECTRICAL WATER COOLER
ELECTRICAL METALLIC TUBING
EMPTY CONDUIT OR TUBING
DOUBLE POLE, SINGLE THROW
DOUBLE-POLE, DOUBLE THROW
ENGINE-GENERATOR SET
FULL LOAD AMPERE(S)
FLOOR
FURNISHED BY OWNER
FUSE(S)
EXISTING
ELECTRICAL MANHOLE
EMERGENCY
ELEVATION
ELECTRICAL HANDHOLE
DRAWING(S)
DISCONNECT
CURRENT TRANSFORMER(S)
DIRECT CURRENT
COMMUNICATIONS
CEILING
DIVISION
CONDUIT UNDERGROUND
DESIGNATION
MICROPHONE
ELECTRICAL CONVENTIONS
NATIONAL FIRE PROTECTION ASSOCIATION
ASSOCIATION
NATIONAL ELECTRICAL MANUFACTURER'S
NATIONAL ELECTRICAL CODE
NORMALLY CLOSED
MEGAWATT(S)
MEGAVOLT-AMPERE(S) REACTIVE
MEGAVOLT-AMPERE(S)
MANUAL TRANSFER SWITCH
MANUAL MOTOR STARTER
MILLIMETER(S)
MAIN LUGS ONLY
MINIMUM
METAL HALIDE
MOTOR CIRCUIT PROTECTOR
MOTOR CONTROL CENTER
MAIN CIRCUIT BREAKER
LOW PRESSURE SODIUM
MAXIMUM
METER(S)
LIGHTING
KILOVOLT-AMPERE(S) REACTIVE
KILOVOLT-AMPERE(S)
KILOWATT-HOUR(S)
KILOWATTS(S)
KILOAMPERE(S)
JUNCTION BOX
KILOVOLT(S)
INTERMEDIATE METALLIC CONDUIT
ISOLATED GROUND
OF NORTH AMERICA
ILLUMINATING ENGINEERING SOCIETY
CONDITIONING
HEATING, VENTILATION AND AIR
HIGH PRESSURE SODIUM
HORSEPOWER
HAND-OFF-AUTOMATIC
HIGH INTENSITY DISCHARGE
GROUND FAULT CIRCUIT INTERRUPT
FULL VOLTAGE, REVERSING
FULL VOLTAGE, NON-REVERSING
GROUND
FUSIBLE SAFETY SWITCH/FUSIBLE SWITCH
(ALL ABBREVIATIONS MAY NOT APPEAR ON DRAWINGS.)
ELECTRICAL ABBREVIATIONS
FLEXIBLE
GALVANIZED STEEL
SIZED IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC)
MTR MOTOR
CONDUIT IN WALL
CONDUIT CAPPED OFF
CONDUIT CONTINUED
CONDUIT RUN UP
CONDUIT RUN DOWN
GROUND WIRE CONCEALED
GROUND SYSTEM
DOWNLIGHT FIXTURE
2X2 LIGHT FIXTURE
2X4LIGHT FIXTURE
CEILING MOUNTED CAMERA
CEILING MOUNTED SPEAKER
TELEVISION DEVICE JUNCTION BOX WITH 1" C. TO
ABOVE ACCESSIBLE CEILING
ELECTRIC HEATING COIL
RECEPTACLE ON EMERGENCY CIRCUIT. PROVIDE RED
OUTLET AND COVERPLATE
MOTOR
NON-FUSED DISCONNECT SWITCH (AMPS/POLES/NEMA
RATING)
TRANSFORMER
GROUND OR GROUND ROD AS NOTED
GROUND BAR
TELECOMMUNICATIONS TERMINAL BOARD
E3.01
AREA OF ENLARGED PLAN OR DETAIL
SHEET NO. ON
WHICH
ENLARGED
DETAIL IS DRAWN
DETAIL NUMBER
GRAPHIC SYMBOLS
SPECIAL PURPOSE RECEPTACLE - WALL MOUNTED
NEW CONSTRUCTION
EXISTING
DEMOLISHED
CEILING MTD VOICE/DATA DEVICE
CEILING MTD DUPLEX RECEPTACLE ON EMERGENCY
CIRCUIT. PROVIDE RED OUTLET AND COVERPLATEE
STRIP LIGHT FIXTURE
WALL MOUNT LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
CLG MTD EXIT LIGHT - SHADING INDICATEDS NUMBER OF
FACES. ARROWS INDICATE ORIENTATION
WALL MTD EXIT LIGHT - SHADING INDICATEDS NUMBER
OF FACES. ARROWS INDICATE ORIENTATION
POLE MTD SITE LIGHTING FIXTURE
BOLLARD LIGHT FIXTURE
GENERAL
NO HATCH INDICATES NORMAL POWER LIGHT FIXTURE
HALF SOLID INDICATES LIFE SAFETY LIGHT FIXTURE
ENTIRE STRIPED HATCH INDICATES CRITICAL LIGHT FIXTURE
LIGHTING SYMBOL LEGEND
(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)
GENERAL
a
- SUPERSCRIPT DENOTES FIXTURE BEING
CONTROLLED
- K - KEY OPERATED SWITCH
- T- TIMER SWITCH
- WP - WEATHERPROOF SWITCH
PHOTOCELL (MATCH CONTACTOR COIL VOLTAGE
AS REQUIRED)
PC
TC DIGITAL PROGRAMMABLE TIME CLOCK
OS WALL MTD OCCUPANCY SENSOR/SWITCH
CLG MTD OCCUPANCY SENSOROS
VS
CLG MTD VACANCY SENSORVS
WALL MTD VACANCY SENSOR/SWITCH
TOGGLE SWITCH - SPST
DIMMER SWITCH
WALL
ABOVE COUNTER
WP WEATHER PROOF
WHILE IN USE COVER
L1-10
PANEL NAME - CIRCUIT NUMBER
ELECTRICAL SYMBOL LEGEND
(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)
M
MOTOR RATED SWITCH
MS
MANUAL MOTOR STARTER
MAGNETIC STARTER OR CONTACTOR
JUNCTION BOXJ
PULLBOX PB
TELEPOWER/COMMUNICATIONS POLE
CEILING MOUNTED DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
GROUND FAULT INTERRUPTION RECEPTACLE
ELECTRICAL SYMBOL LEGEND
(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)
DOUBLE DUPLEX RECEPTACLE
GROUND FAULT INTERRUPTION DOUBLE DUPLEX
RECEPTACLE
SPECIAL PURPOSE RECEPTACLE - FLOOR MOUNTED
DUPLEX RECEPTACLE PROTECTED BY GFI CIRCUIT
BREAKER
W TELECOMMUNICATIONS WALL MTD OUTLET WITH MINIMUM 1"
C. TO ABOVE CEILING, 48" AFF TO CENTER
TELECOMMUNICATIONS/DATA WALL OUTLET WITH
MINIMUM 1" C. TO ABOVE CEILING 18" TO CENTER UNO
TELEVISION DEVICE JUNCTION BOX WITH 1" C. TO ABOVE
ACCESSIBLE CEILING
TV
COMBINATION DISCONNECT SWITCH/MOTOR STARTER
(AMPS/POLES/FUSE RATING/NEMA RATING/STARTER SIZE)
FUSED DISCONNECT SWITCH (AMPS/POLES/FUSE
RATING/NEMA RATING)
30/3/1
30/3/25/3R
30/3/25/3R/00
VFD VARIABLE FREQUENCY DRIVE
ELECTRICAL PANEL ( SURFACE OR FLUSH MOUNTED AS
NOTED ON PANEL SCHEDULE AND DRAWINGS)
MISC. CONTROL PANEL (SURFACE OR FLUSH MOUNTED AS
NOTED ON DRAWINGS)
T
PUSH BUTTON MTD AT 48" TO CENTER UNO
WIREMOLD
CT
March 31, 2021
2 7 2021-03-31
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:DESCRIPTION:
EA:CLIENT:
1 2 3 4 5 6 7 8
S
D ZIP
FORCE PROTECTION STREET ADDRESS
FORCE PROTECTION CITY AND ZIP
FORCE PROTECTION NAME
FORCE PROTECTION PH AND FAX
MEP STREET ADDRESS
MEP CITY AND ZIP
MEP ENGINEERS
MEP PH AND FAX
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CONSULTANT 01 NAME
CONSULTANT 01 PH AND FAX
FORCE PROTECTION CONTACT
ENAPAY, LLC
MEP CONTACT
ENAPAY, LLC
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
REVISION SCHEDULE
No. DESCRIPTION DATE
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
PROJECT NUMBER:
BUILDING NUMBER:
EA:CLIENT:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
SITE PLAN AND LOCATION
DESIGN PRIMARY POWER
SECONDARY SIDE
5001 N. PIEDRAS / EL PASO, TEXAS 79930
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
756-16-110 EA03.0111
D
ES
IG
N
P R
IM
A
R Y
PO
W
ER
. S
EC
O
N D
A R
Y
SI
D E
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
PR
O
JE
C T
N U
M B
ER
: E
A
.0
E-1
F4F1
C1
PROJECT LOCATION
PROJECT SITE PLAN - DEMOLITION PROJECT SITE PLAN
MAIN ELECTRICAL ENTRANCE
AT CENTRAL PLANT
N PIEDRAS ST
T T
T
UGE UGE UGE
E U
EUEU
E U
E U
KEY NOTES
1. EXISTING RIO GRANDE ELECTRIC UTILITY TRANSORMERS TO BE
REMOVED.
2. EXISTING RIO GRANDE ELECTRIC UTILITY SWITCHGEAR TO BE REMOVED.
3. EXISTING BACKUP GENERATOR ROOM.
4. MAIN ELECTRICAL ROOM LOCATED IN BUILDING.
5. REMOVE AND RELOCATE LIGHT POLE.
6. EXISTING ELECTRICAL VAULT UNDER REMOVED TRANSFORMERS.
7. PROPOSED LOCATION OF EL PASO ELECTRIC 15 KV SWITCHGEAR.
8. PROPOSED LOCATION OF EL PASO ELECTRIC 2500 KVA TRANSFORMER.
9. 13.2 KV PRIMARY FEEDER FROM EL PASO ELECTRIC.
10. 13.2 KV PRIMARY FEED FROM SWITCH TO TRANSFORMER.
11. 480Y/277V SECONDARY SERVICE 8-4" CONDUITS IN DUCTBANK.
12. 480Y/277V SECONDARY SERVICE 16-4" CONDUITS IN DUCTBANK.
13. NEW UNDERGROUND ELECTRICAL MANHOLE.
14. REMOVE EXISTING WIRING AND REUSE EXISTING SERVICE CONDUITS TO
SWITCHBOARDS IN BUILDING.
15. RELOCATE ELECTRICAL SERVICE FOR CONDENSING UNIT TO ROOF; RE:
MECHANICAL.
16. MANHOLE FOR ELEVATION CHANGE.
17. PROVIDE 120 VAC/20 AMP CIRCUIT TO SUMP PUMP. PROVIDE 2#10,1#10,
3/4C FROM SPARE CIRCUIT IN PANEL IDCLA OR ICLLA IN EMERGENCY
DISTRIBUTION ROOM. UPDATE THE PANEL SCHEDULE AND USE
PHENOLIC TAG FOR CIRCUIT ID.
18. PROPOSED RELOCATED LIGHT POLE LOCATION.
19. ROUTING OF ELECTRICAL LINES HIGH VOLTAGE OR SECONDARY SHALL
MAINTAIN A MINIMUM DISTANCE OF 11'-6" FEET FROM THE CENTER OF
THE FUEL OIL ACCESS COVER.
SHEET NOTES
A. UNDERGROUND SECONDARY CONDUITS TO BE SCHEDULE 40 PVC MINIMUM WALL THICKNESS ENCASED IN A CONCRETE DUCTBANK WITH RED DYE ON TOP. FOR PRIMARY CONDUIT REQUIREMENTS CONTACT
EL PASO ELECTRIC.
B. COORDINATE ELECTRICAL UNDERGROUND WITH CROSSING UTILITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE VERTICAL AND HORIZONTAL LOCATION OF ANY EXISTING UTILITIES
PRIOR TO BEGINNING CONSTRUCTION ACTIVITIES.
C. UNDERGROUND ELECTRICAL PRIMARY (UGE) MEDIUM VOLTAGE DUCTBANKS AND SECONDARY
VOLTAGE (EU) DUCTBANKS SHALL BE INSTALLED BELOW GRADE AS INDICATED.
D. SECONDARY VOLTAGE MANHOLES SHALL BE TRAFFIC RATED H-20 LOADING WITH CAST IRON COVERS
AND CONDUIT TERMINATORS AS REQUIRED.
E. COORDINATE WITH EL PASO ELECTRIC FOR NEW PRIMARY FEEDER, SWITCHGEAR PAD, AND
TRANSFORER PAD REQUIREMENTS.
F. COORDINATE REMOVAL OF EXISTING TRANSFORMERS AND EXISTING SWITCHGEAR WITH RIO GRANDE
ELECTRIC.
G. FOR ANY DUCT BANKS TO REMAIN AND BE REUSED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR UTILIZING METHODS TO CAREFULLY REMOVE THE WIRING WITHOUT DAMAGING THE DUCT BANK. THE CONTRACTOR SHALL PROVIDE THE VA WITH A HAZARD ANALYSIS PLAN TO REMOVE THE WIRING. THE
PLAN SHALL BE APPROVED BY THE EOR AND VA PRIOR TO STARTING WORK.
H. PROVIDE AS-BUILT DRAWINGS PRIOR TO ENERGIZING THE NEW TRANSFORMERS AND WIRING.
I. THE CONTRACTOR SHALL PROVIDE A UTILITY SURVEY PLAN PRIOR TO STARTING WORK.
J. CONTRACTOR TO PERFORM A SITE EXPLORATION AND A SURVEY FOR GRADING PLAN. CONTRACTOR
SHALL PREPARE GRADING PLAN PRIOR TO COMMENCING WORK.
K. CONTRACTOR TO PULL SITE PERMIT FROM FORT BLISS DPW
L. CONTRACTOR TO COMPLY WITH ANY FORT BLISS DPW COMMENTS MADE ON PROPRIETARY WORK
ORDER AND EXCAVATION PERMIT.
M. CONTRACTOR TO OBTAIN HOT WORK PERMIT ON A DAILY BASIS THROUGH VA SAFETY OFFICE.
50'
SCALE
~100'
SCALE
T
S
E U
16 7
4 3
3 7
U G
E
U G
E U
G E
BLD 7781-B
BLD 7781
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:DESCRIPTION:
EA:CLIENT:
1 2 3 4 5 6 7 8
S
D ZIP
FORCE PROTECTION STREET ADDRESS
FORCE PROTECTION CITY AND ZIP
FORCE PROTECTION NAME
FORCE PROTECTION PH AND FAX
MEP STREET ADDRESS
MEP CITY AND ZIP
MEP ENGINEERS
MEP PH AND FAX
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CONSULTANT 01 NAME
CONSULTANT 01 PH AND FAX
FORCE PROTECTION CONTACT
ENAPAY, LLC
MEP CONTACT
ENAPAY, LLC
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
REVISION SCHEDULE
No. DESCRIPTION DATE
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
PROJECT NUMBER:
BUILDING NUMBER:
EA:CLIENT:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
ONE LINE DRAWINGS DESIGN PRIMARY POWER
SECONDARY SIDE
5001 N. PIEDRAS / EL PASO, TEXAS 79930
756-16-110 EA03.0111
D
ES
IG
N
P R
IM
A
R Y
PO
W
ER
. S
EC
O
N D
A R
Y
SI
D E
E-2
3000A3000A
SHEET NOTES
A. COORDINATE WITH EL PASO ELECTRIC FOR SERVICE AND METER
REQUIREMENTS. INSTALLATION SHALL CONFORM WITH EL PASO
ELECTRIC UTILITY GUIDELINES, THE NATIONAL ELECTRICAL CODE (NEC),
AND THE AUTHORITY HAVING JURISDICTION (AHJ).
B. GROUNDING AND BONDING SHALL CONFORM WITH ARTICLE 250 OF THE
NEC.
C. THE LAYOUT OF NEW AND EXISTING EQUIPMENT TO BE REUSED IS
DIAGRAMMATIC. FIELD VERIFY DISTANCES, SITE CONDITIONS, THE
LOCATION OF EXISTING EQUIPMENT AND THE LOCATION AND SPACING
OF NEW EQUIPMENT PRIOR TO BID AND PERFORMING WORK. PROVIDE
ALL LABOR AND MATERIALS FOR A COMPLETE INSTALLATION.
D. VERIFY LOCATION OF ALL EXISTING UNDERGROUND UTILITIES. HAND DIG
TO IDENTIFY EXISTING UTILITIES PRIOR TO DEMOLITION OR
INSTALLATION. USE CAUTION DURING EXCAVATION TO NOT DAMAGE OR
DISRUPT EXISTING UTILITIES.
E. COORDINATE WITH EL PASO ELETRIC FOR FINAL TERMINATIONS ON
SECONDARY SIDE OF UTILITY TRANSFORMERS.
KEY NOTES
1. 15 KV FEEDER BY EL PASO ELECTRIC. PROVIDE CONDUITS AS REQUIRED
BY EL PASO ELECTRIC.
2. EIGHT (8) SETS OF 4#500 KCMIL IN 4"C
3. EIGHT (8) SETS OF 4#500 KCMIL IN EXISTING CONDUIT
4. VERIFY SERVICE ENTRANCE AT EXISTING SWITCHBOARD AND CONNECT
NEUTRAL TO GROUND.
13.2 KV EL PASO
ELECTRIC FEEDER
EL PASO ELECTRIC
15 KV SWITCHGEAR
2000 KVA
13.2 KV TO 480Y/277V
EL PASO ELECTRIC
TRANSFORMER 1
2000 KVA
13.2 KV TO 480Y/277V
EL PASO ELECTRIC
TRANSFORMER 2
ELECTRICAL
MANHOLE
(NEW)
ELECTRICAL
MANHOLE
(NEW)
ELECTRICAL
MANHOLE
(NEW)
ELECTRICAL
VAULT
(EXISTING)
3000A/3P3000A/3P
MAIN SWITCHBOARD MSB 480Y/277V 3000A
(EXISTING)
MAIN SWITCHBOARD MSA 480Y/277V 3000A
(EXISTING)
ONE LINE DIAGRAM
F3
2 2
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
PR
O
JE
C T
N U
M B
ER
: E
A
.0
4 7
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:DESCRIPTION:
EA:CLIENT:
1 2 3 4 5 6 7 8
S
D ZIP
FORCE PROTECTION STREET ADDRESS
FORCE PROTECTION CITY AND ZIP
FORCE PROTECTION NAME
FORCE PROTECTION PH AND FAX
MEP STREET ADDRESS
MEP CITY AND ZIP
MEP ENGINEERS
MEP PH AND FAX
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CONSULTANT 01 NAME
CONSULTANT 01 PH AND FAX
FORCE PROTECTION CONTACT
ENAPAY, LLC
MEP CONTACT
ENAPAY, LLC
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
REVISION SCHEDULE
No. DESCRIPTION DATE
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
PROJECT NUMBER:
BUILDING NUMBER:
EA:CLIENT:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
SCHEDULES AND DETAILS DESIGN PRIMARY POWER
SECONDARY SIDE
5001 N. PIEDRAS / EL PASO, TEXAS 79930
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
756-16-110 EA03.0111
D
ES
IG
N
P R
IM
A
R Y
PO
W
ER
. S
EC
O
N D
A R
Y
SI
D E
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
PR
O
JE
C T
N U
M B
ER
: E
A
.0
E-3
C5
POWER MANHOLE DETAILS
NTS
F7
UNDERGROUND CONCRETE
PULLBOX - PAVED AREAS
NTSF5
MANHOLE GROUNDING DETAIL
NTSF3
DUCT BANK DETAILS
NTSF1
GROUNDING BAR DETAIL
NTS
5 7
GENERAL NOTES:
1. HARDWARE SHALL BE STAINLESS STEEL. GROUND BAR SHALL BE COPPER (CU)
AS NOTED ABOVE.
2. PROVIDE 1 MOUNTING POINT PER 305mm (12") OF BAR LENGTH.
3. HOLES MAY BE ADDEDD IF REQUIRED.
GRADE
LIGHTING CIRCUIT UP POLE
(TYPICAL ALL CONDUCTORS).
BOND SYSTEM GROUND TO
GROUNDING LUG INSIDE.
No.6 GROUND CONDUCTOR.
GROUT POLE BASE.
1" CHAMFER.
PVC CONDUITS.
#6 AWG
CADWELD CONNECTION
TO GROUND ROD.
PVC CONDUIT FOR CIRCUIT
CONTINUATION.
COPPERWELD GROUND
ROD, 5/8" x 8'-0".
FOUNDATION DESIGNED BY
STRUCTURAL ENGINEER,
REFERENCE STRUCTURAL
PLANS
PVC CONDUIT FOR CIRCUIT
CONTINUATION.
ANCHOR BOLTS (4).
LEVELING NUT.
2'-6" MINIMUM
REUSE EXISTING LUMINAIRE
REUSE EXISTING LUMINAIRE POLE
NOTES:
1. DO NOT CAST GROUND CONDUCTOR IN CONCRETE BASE WITHOUT RACEWAY.
2. LEVELING NUTS SHALL BE USED. POLE BEARING PLATE SHALL NOT BE SHIMMED AGAINST PIER CONCRETE.
3. FOR LIGHT POLES LOCATED ON HERB KELLEHER LOCATE THE RECEPTACLE ON THE NORTH SIDE OF THE POLE WHEN DRIVING TOWARD THE TERMINAL. LOCATE THE RECEPTACLE ON THE SOUTH SIDE OF THE POLE WHEN DRIVING FROM THE TERMINAL. PROVIDE RECEPTACLES FOR LIGHT POLES CIRCUITED FROM ELECTRICAL
PANELS 2 AND 3. REFER TO ELECTRICAL PLANS AND SCHEDULES ON SHEET E6.01.
POLE BASE TO EXTEND
6" ABOVE GRADE.
PVC CONDUITS
6"
3"
C3
POLE BASE DETAIL
NTS
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:DESCRIPTION:
EA:CLIENT:
1 2 3 4 5 6 7 8
S
D ZIP
FORCE PROTECTION STREET ADDRESS
FORCE PROTECTION CITY AND ZIP
FORCE PROTECTION NAME
FORCE PROTECTION PH AND FAX
MEP STREET ADDRESS
MEP CITY AND ZIP
MEP ENGINEERS
MEP PH AND FAX
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CONSULTANT 01 NAME
CONSULTANT 01 PH AND FAX
FORCE PROTECTION CONTACT
ENAPAY, LLC
MEP CONTACT
ENAPAY, LLC
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
REVISION SCHEDULE
No. DESCRIPTION DATE
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
PROJECT NUMBER:
BUILDING NUMBER:
EA:CLIENT:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
MECHANICL SYMBOLS AND
GENERAL NOTES
DESIGN PRIMARY POWER
SECONDARY SIDE
5001 N. PIEDRAS / EL PASO, TEXAS 79930
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
756-16-110 EA03.0111
D
ES
IG
N
P R
IM
A
R Y
PO
W
ER
. S
EC
O
N D
A R
Y
SI
D E
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
PR
O
JE
C T
N U
M B
ER
: E
A
.0
N
SCALE:
COCO
S
MM
S S
M M
M M
H
T
CO2
M
R
CO
VFD
R D R D
FD
FSD
SD
FD
SD
BDD
BDD
FSD
SP
SP
S S
M M
T T
H H
CO2
CO2
B B
DP
DP
DPS
DPS
AF
AF
CRD
SHEET 1/8" = 1'-0"
TOP TITLE
BOTTOM TITLE
F&T F&T
DUCTWORK SYMBOLSVALVE SYMBOLS
GATE VALVE
PIPE & FITTING SYMBOLS
MANUAL VOLUME DAMPER
GRAPHIC SYMBOLS
CONTROL SYMBOLS
VERTICAL RUN ON PLAN
READ LEFT TO RIGHT
4" CWS
H W
R C
W R
H W
S
2" HWS
2" HWR
4" CWR
READ TOP TO BOTTOM
4" CHWS
3" PCD(F) *
2" HPS
2" LPS
4" CHWR
C W
S
3" PCD(F) *
2" HPS
2" LPS
4" CHWR
4" CHWS
L P
S C
H W
R C
H W
S P
C D
(F
CHWS
CHWR
LPS
PCD(F) *
HWS
HWR
CWR
H P
S
HPS
CWS
PIPING DESIGNATION
2" CHWS
XXX-1
SYSTEM SERVICE ABBREVIATION
NOMINAL PIPE SIZE
MISCELLANEOUS SYMBOLS
EQUIPMENT DESIGNATION
(IN INCHES)
SINGLE LINE PIPE/DUCTWORK BREAK
KEYED NOTE
POINT OF DISCONNECTION
POINT OF CONNECTION (NEW TO EXISTING)
HORIZONTAL RUN ON PLAN
MULTI-LINE KEY
4" CWR
4" CWS
2" HWS
2" HWR
(D)
(R)
(E)
(N)
LIMIT OF EXISTING ITEMS TO BE REMOVED
NEW ITEM (NOTATION SHOWN AS NECESSARY
FOR CLARIFICATION)
EXISTING ITEM TO REMAIN (NOTATION
SHOWN AS NECESSARY FOR CLARIFICATION)
EXISTING ITEM TO BE RELOCATED (NOTATION
SHOWN AS NECESSARY FOR CLARIFICATION)
EXISTING ITEM TO BE DEMOLISHED (NOTATION
SHOWN AS NECESSARY FOR CLARIFICATION)
EXISTING ITEMS TO BE DEMOLISHED
EXISTING ITEMS TO REMAIN
NEW ITEMS (PIPING/DUCTWORK/EQUIPMENT)
RECTANGULAR DUCT/STANDARD BREAK
* - (F) INDICATES FUTURE PIPING ON RACK
BOP 12'-6"
AFF
LOWER
PIPE RACK
BOP 13'-6"
AFF UPPER
PIPE RACK
BOP 12'-6"
AFF
LOWER
PIPE RACK
BOP 13'-6"
AFF UPPER
PIPE RACK
SINGLE LINEDOUBLE LINE
PIPE
WELDED JOINT
SCREWED JOINT
GROOVED END JOINT
FLANGED JOINT
GROOVED END ADAPTER FLANGE
FLANGED COUPLING ADAPTER
UNION
TEE FITTING
REDUCER - ECCENTRIC
REDUCER - CONCENTRIC
CAP
ANCHOR
BLIND FLANGE
FLOW ORIFICE PLATE
ELBOW, 90 DEGREE -
CHANGE IN
DIRECTION
TOWARD VIEWER
ELBOW, 90 DEGREE -
CHANGE IN
DIRECTION
AWAY FROM VIEWER
LATERAL
NOTE:
WELDED FITTINGS ARE SHOWN FOR DOUBLE LINE PIPING.
FITTINGS WITH OTHER END CONDITIONS ARE SIMILAR.
PRESSURE GAUGE
WITH
GAUGE COCK
STEAM TRAP, TYPE AS NOTED
IB = INVERTED BUCKET
F&T = FLOAT &
THERMOSTATIC
TH = THERMODYNAMIC
BP = BALANCED PRESSURE
AIR SEPARATOR
ELBOW, 90 DEGREE
(LONG RADIUS
UON)
ELBOW, 45 DEGREE
(LONG RADIUS
UON)
VENTURI FLOW METER
CONTROL VALVES
CLEANOUT
(F) FUTURE ITEM (NOTATION SHOWN AS
NECESSARY FOR CLARIFICATION)
2"
SECTION NO.
DIRECTION OF CUTTING PLANE
SHEET NO. ON WHICH
THE SECTION IS
DRAWN
A
M5.01
DRAWING TITLE
DETAIL NO. AND SHEET NO.
SCALE OF FLOOR PLAN,
SECTION OR DETAIL
M3.01
AREA OF ENLARGED PLAN
OR
DETAIL
SHEET NO. ON
WHICH
ENLARGED
DETAIL IS DRAWN
CHWS
DOUBLE LINE PIPE/ROUND DUCTWORK BREAK
NEW CONNECTION TO EXISTING ITEM
1 REVISION DELTA
STUB END OR FLANGE
ADAPTER W/ FLANGE RING
GENERIC FLEXIBLE
COUPLING
(REFER TO SPECIFICATIONS)
2"CHWS
- OR -
TEE FITTING,
BRANCH TOWARD VIEWER
TEE FITTING,
BRANCH AWAY FROM VIEWER
PIPING WITH INSULATION
(WHEN SHOWN FOR
CLARITY)
THERMOWELL
WITH
THERMOMETER
STRAINER - "Y"
TYPE
WITH BLOW DOWN
WATER METER
PUMP, ARROW INDICATES FLOW
SINGLE LINEDOUBLE LINEDESCRIPTION DESCRIPTION
CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
DIAPHRAGM VALVE
GLOBE VALVE
PLUG VALVE
PRESSURE REDUCING VALVE
BALANCING VALVE
DIRECTION OF FLOW / SLOPE
PRESSURE RELIEF VALVE
AUTOMATIC AIR VENT
MANUAL AIR VENT
SINGLE LINEDOUBLE LINE DESCRIPTION
TWO-WAY, TWO POSITION
CONTROL VALVE W/ SOLENOID
TWO-WAY, MODULATING
CONTROL VALVE
TWO-WAY, TWO POSITION
CONTROL VALVE
THREE-WAY, TWO POSITION
CONTROL VALVE
THREE-WAY, MODULATING
CONTROL VALVE
WALL MOUNTED DEVICES
HUMIDITY SENSOR/HUMIDISTAT
TEMPERATURE SENSOR/THERMOSTAT
CARBON DIOXIDE SENSOR
MOTION SENSOR
OVERRIDE SWITCH
CARBON MONOXIDE SENSOR
VARIABLE FREQUENCY DRIVE
EQUIPMENT SYMBOLS
ROOFTOP EXHAUST FAN (ROOF PLAN VIEW)
ROOFTOP EXHAUST FAN (ROOF PLAN VIEW)
WALL LOUVER WITH POSITIVE OR NEGATIVE AIRFLOW
DOOR UNDERCUT (SPECIFY CFM IF REQUIRED)UC
DOOR LOUVER (SPECIFY CFM IF REQUIRED)
LD
AxB
RECTANGULAR OR SQUARE DUCT,
DIMENSIONS ARE IN INCHES, MIN.
INSIDE CLEAR, A = WIDTH, B= HEIGHT
AxB
A"Ø
ROUND DUCT DIMENSIONS ARE IN
INCHES, MIN. INSIDE CLEAR,
A = DIAMETER
A"Ø
AxBØ
FLAT OVAL DUCT DIMENSIONS ARE
IN INCHES, MIN. INSIDE CLEAR,
A = WIDTH, B= HEIGHT
AxBØ
DUCTWORK RISE (R) OR DROP (D)
RELATIVE TO DIRECTION OF
AIRFLOW
DIRECTION OF AIR FLOW
SUPPLY AIR OR POSITIVE
PRESSURE DUCTWORK, SECTION
TOWARDS/AWAY VIEWER
RETURN AIR OR NEGATIVE
PRESSURE DUCTWORK, AIRFLOW
TOWARDS VIEWER
EXHAUST AIR DUCTWORK,
AIRFLOW TOWARDS VIEWER
RIGID ROUND DUCTWORK,
AIRFLOW TOWARDS VIEWER
FIRE DAMPER
FIRE/SMOKE DAMPER
SMOKE DAMPER
BACKDRAFT DAMPER
SMOKE DETECTOR
STATIC PRESSURE SENSOR
MOTORIZED DAMPER
TEMPERATURE SENSOR
DESCRIPTIONSINGLE LINEDOUBLE LINE
HUMIDITY SENSOR
CARBON DIOXIDE SENSOR
BAROMETRIC DAMPER
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE
SAFETY SHUT-DOWN
RELAY
AIRFLOW PROOF SWITCH
ACCESS PANEL/CLEANOUT
SUPPLY AIR OR POSITIVE
PRESSURE DUCTWORK, AIRFLOW
AWAY FROM VIEWER
RETURN AIR OR NEGATIVE
PRESSURE DUCTWORK, AIRFLOW
AWAY FROM VIEWER
EXHAUST AIR DUCTWORK,
AIRFLOW AWAY FROM VIEWER
RIGID ROUND DUCTWORK,
AIRFLOW AWAY FROM
VIEWER
TRANSITION - ECCENTRIC REDUCER
TRANSITION - CONCENTRIC REDUCER
TRANSITION - SQUARE TO ROUND
90° ELBOW WITHOUT TURNING
VANES (RETURN OR EXHAUST
DUCTWORK ONLY)
90° ELBOW WITH TURNING VANES
(REQUIRED ON SUPPLY
DUCTWORK)
45° ELBOW WITHOUT TURNING
VANES (RETURN OR EXHAUST
DUCTWORK ONLY)
45° ELBOW WITH TURNING VANES
(REQUIRED ON SUPPLY DUCTWORK)
RADIUS 90° ELBOW (R = 1.5W)
RW
RADIUS 45° ELBOW (R = 1.5W)
RW
SPIN-IN FITTING WITH FLEXIBLE
DUCTWORK, DIMENSIONS ARE IN
INCHES, MIN. INSIDE CLEAR,
A = DIAMETER
AIR DISTRIBUTION
CEILING RADIATION DAMPER
LINEAR SLOT DIFFUSER
ROUND SUPPLY AIR DIFFUSER
SIDEWALL REGISTER
8"Ø
TYP OF 2
AIR DISTRIBUTION CALLOUT
RETURN AIR OR TRANSFER AIR GRILLE
A"ØA"Ø
INLINE EXHAUST FAN (EF), AIR HANDLING UNIT
(AHU), CONDENSING UNIT (CU)
BRANCH TAKE-OFF WITH MVD
CONICAL TAKE-OFF WITH MVD
DUCTWORK SYMBOLS
SINGLE LINEDOUBLE LINE DESCRIPTION
SUPPLY AIR DIFFUSER
EXHAUST AIR GRILLE
REFER TO SCHEDULE FOR ADDITIONAL INFORMATION
DUCT MOUNTED GRILLE
DETAIL NUMBER
MECHANICAL SYMBOL LEGEND
THIS IS A STANDARD LEGEND SHEET. SOME INFORMATION ON
THIS SHEET MAY NOT NECESSARILY APPLY TO THIS PROJECT.
S1
MECHANICAL GENERAL NOTES
1. ISOLATION VALVES SHALL BE PROVIDED IN ALL BRANCH PIPING AND AT EQUIPMENT CONNECTIONS.
2. PIPING CONNECTIONS TO ALL EQUIPMENT SHALL BE FABRICATED WITH THE ISOLATION VALVES, FLANGES AND/OR UNIONS
POSITIONED TO ALLOW REMOVAL AND SERVICE OF THE COMPONENT PARTS.
3. INSTALL MANUAL AIR VENTS AT THE HIGH POINTS OF THE PIPING SYSTEMS.
4. ROUTE PIPING IN AN ORDERLY MANNER AND MAINTAIN PROPER GRADES. INSTALL TO CONSERVE HEADROOM AND TO CREATE
MINIMUM INTERFERENCE WITH USE OF SPACE. ROUTE ALL PIPING PARALLEL TO BUILDING LINES UON. GROUP PIPING AT COMMON
BOP ELEVATIONS WHENEVER PRACTICAL. PIPES LOCATED IN CONCEALED SPACES SHALL BE ROUTED CLOSE TO BUILDING
STRUCTURE UON.
5. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT STRESSING PIPE OR EQUIPMENT CONNECTED.
6. INSTALL VALVES WITH STEMS UPRIGHT OR HORIZONTAL, NOT INVERTED.
7. INSTALL VALVES AND EQUIPMENT IN ACCESSIBLE LOCATIONS. INSTALL ACCESS DOORS IN PARTITIONS OR CEILINGS WHERE VALVES
AND EQUIPMENT WOULD OTHERWISE BE INACCESSIBLE.
8. WHEN SOCKET WELD OR SOLDER END VALVES ARE INSTALLED, SPECIAL CARE SHALL BE TAKEN TO AVOID OVERHEATING AND
DAMAGING THE VALVE BODY, TRIM OR PACKING. DAMAGED VALVES SHALL BE REPLACED AT CONTRACTOR'S EXPENSE.
9. IDENTIFY EACH PIPE WITH LABELING AS REQUIRED BY SPECIFICATIONS.
10. SLEEVE ALL PIPING THAT PENETRATES FIRE RATED WALLS, FLOORS AND PARTITIONS. PENETRATIONS SHALL BE SEALED WITH A U.L.
LISTED ASSEMBLY TO PROVIDE A RATING EQUAL TO OR GREATER THAN THAT OF THE PENETRATED WALL, FLOOR OR PARTITION.
11. SLEEVE ALL PIPING THAT PENETRATES EXTERIOR BUILDING WALLS AND GRADE BEAMS. SEAL PENETRATIONS WATERTIGHT.
12. COORDINATE WITH OTHER TRADES BEFORE FABRICATION OR INSTALLATION OF ANY SYSTEMS.
13. EXISTING DUCTWORK, PIPING AND EQUIPMENT SHOWN ON THESE DRAWINGS INDICATES THE GENERAL LOCATION AND ROUTING. THE
ACTUAL LOCATION SHALL BE DETERMINED BY THE CONTRACTOR WHO SHALL COORDINATE ALL WORK WITH ALL TRADES NECESSARY
TO INSTALL NEW DUCTWORK, PIPING OR EQUIPMENT AS SHOWN ON THE DRAWING.
14. THESE DRAWINGS DO NOT NECESSARILY SHOW ALL OFFSETS OR ELEVATION DIFFERENCES WHICH MAY BE NECESSARY FOR THE
COMPLETE INSTALLATION. THESE SHALL BE PROVIDED AS REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM AT NO
ADDITIONAL COST TO THE CONTRACT.
15. ALL NEW DUCTWORK SHALL BE EXTERNALLY INSULATED AS SPECIFIED.
16. WHERE REMOVAL OF EXISTING DUCTWORK OR PORTIONS OF ANY AIR SYSTEM IS NECESSARY, THE DUCT SHALL BE PATCHED AND
SEALED AIRTIGHT USING PATCH OF SAME MATERIAL AND EQUAL OR GREATER THICKNESS AS EXISTING. PATCHES SHALL BE
ATTACHED WITH SHEET METAL SCREWS OR OTHER MEANS OF POSITIVE ATTACHMENT (WELDING, BONDING, ETC.) AS SPECIFIED FOR
THE PARTICULAR DUCT SYSTEM. NEW INSULATION SHALL BE EQUAL TO OR BETTER THAN EXISTING AND SHALL BE PATCHED AND
SEALED TO MATCH EXISTING INSULATION AND MAINTAIN VAPOR BARRIER.
17. COORDINATE ALL REMODEL WORK WITH NEW CONSTRUCTION AND OTHER TRADES.
18. THE CONTRACTOR SHALL ADJUST AND BALANCE ALL MECHANICAL SYSTEMS TO DESIGN SETTINGS AS SHOWN AND SHALL
REBALANCE TO RESTORE SETTINGS OF SYSTEMS TEMPORARILY ALTERED FOR THE PURPOSES OF COMPLETING THE WORK OF THIS
PROJECT.
19. NOTIFY AND COORDINATE WITH THE OWNER AT LEAST SEVEN DAYS PRIOR TO SHUTDOWN OF ANY BUILDING SERVICES OR
EQUIPMENT. SHUTDOWN TIME SHALL BE KEPT TO A MINIMUM.
20. ANY ITEMS DAMAGED DURING DEMOLITION SHALL BE REPLACED WITH NEW MATERIALS TO MATCH EXISTING.
21. CONTRACTOR SHALL PROVIDE TEMPORARY DUCTWORK, ELECTRICAL SERVICE, PIPING OR OTHER BUILDING SERVICES AS REQUIRED
TO KEEP OTHER AREAS IN OPERATION DURING REMODELING. NOTIFY OWNER PRIOR TO SHUT-DOWN FOR ANY TEMPORARY SERVICE
REQUIREMENTS. ALL TEMPORARY WORK SHALL BE COMPLETELY REMOVED ONLY AFTER NEW SERVICES ARE COMPLETELY
INSTALLED AND FUNCTIONAL.
22. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS OF CEILING-MOUNTED HVAC DEVICES AND EQUIPMENT.
23. DUCT ROUTING CHANGES MADE BY THE CONTRACTOR FOR THE PURPOSE OF ACCOMMODATING FIELD CONDITIONS SHALL INCLUDE
FIRE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS IN RATED PARTITIONS AS SHOWN IN ORIGINAL ROUTING ARRANGEMENTS.
24. FURNISH AND INSTALL ACCESS DOORS (AD) IN THE DUCTWORK IMMEDIATELY ADJACENT TO EACH FIRE DAMPER AND EACH
FIRE/SMOKE DAMPER. PARTITIONS SHALL BE PROVIDED WITH ACCESS DOORS TO PROVIDE SERVICE AND ACCESS TO DAMPER
ACCESS DOORS.
25. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE REQUIRED BY CODE. FIRE, SMOKE, AND COMBINATION FIRE/SMOKE
DAMPERS SHALL BE UL LISTED, SHALL BEAR THE UL LABEL AND SHALL COMPLY WITH NFPA BULLETIN NO. 90A. FULLY-OPEN DAMPERS
SHALL NOT HAVE ANY PROJECTIONS INTO THE AIRSTREAM.
26. ABANDONED DUCT SHALL BE REMOVED WHERE INDICATED ON THE DRAWINGS. DUCT REMAINING IN PLACE SHALL BE CAPPED, SEALED AIR TIGHT AT POINT(S) OF DEMOLITION, AND INSULATED TO MATCH EXISTING..
27. NEW HOLES THROUGH EXISTING FLOORS SHALL BE CORE DRILLED. ALL CORES SHALL BE X-RAYED PRIOR TO CORING.
28. ALL DUCT SIZES SHOWN HEREIN REPRESENT INSIDE CLEAR DIMENSIONS. EXTERNAL SHEET METAL DIMENSIONS OF DUCTWORK
THAT IS SPECIFIED TO BE INTERNALLY LINED SHALL BE ADJUSTED BY THE CONTRACTOR TO ALLOW FOR THICKNESS OF LINING.
29. THE OWNER SHALL HAVE THE OPTION TO DESIGNATE ANY MATERIALS REMOVED OR DEMOLISHED DURING THIS WORK AS
"RECYCLABLE" AND SHALL HAVE FINAL DISPOSITION OVER THE DISPOSAL OF THESE MATERIALS. ALL MATERIALS
REMOVED/DEMOLISHED BY THE CONTRACTOR FOR THIS JOB AND NOT RETAINED BY THE OWNER FOR RECYCLING OR OTHER
PURPOSES SHALL BE DISPOSED OFF-SITE BY THE CONTRACTOR.
30. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ANY EQUIPMENT DESIGNATED FOR REMOVAL. THE OWNER SHALL PROVIDE A
LIST OF ITEMS THEY REQUIRE TO BE SALVAGED PRIOR TO THE START OF DEMOLITION. THE CONTRACTOR SHALL REMOVE THESE
ITEMS USING REASONABLE CARE TO MINIMIZE DAMAGE.
31. ANY AND ALL WATER CONNECTIONS MADE FOR THE PURPOSE OF CLEANING TOOLS OR THE WORK AREA OR FOR ANY OTHER
CONSTRUCTION-RELATED PURPOSES SHALL BE MADE ONLY TO DOMESTIC WATER HOSE BIBBS OR TO CONTRACTOR-SUPPLIED
WATER SOURCES. APPROVED BACKFLOW PREVENTION DEVICES SHALL BE USED AS REQUIRED BY THE AUTHORITY HAVING
JURISDICTION. CONNECTIONS SHALL NOT BE MADE TO FIRE WATER, CHILLED WATER, CONDENSER WATER, HEATING HOT WATER, DOMESTIC HOT WATER OR ANY OTHER TREATED WATER SOURCE UNLESS REQUIRED AS PART OF WORK ON THESE SYSTEMS.
32. EXCEPT WHERE REQUIRED AT EQUIPMENT NOZZLES, FLANGES SHALL BE RAISED FACE WELD-NECK.
33. INSTALL DIELECTRIC FITTINGS AT ALL FERROUS PIPE CONNECTIONS TO NON-FERROUS METALLIC PIPE OR EQUIPMENT.
34. BULLHEAD TEES SHALL NOT BE USED TO JOIN CONVERGING (RETURN) FLOWS, REGARDLESS OF ARRANGEMENT SHOWN ON PLANS.
35. PROVIDE ESCUTCHEON PLATES WHERE PIPES EXPOSED TO VIEW PENETRATE FINISHED WALLS, FLOORS AND CEILINGS. SPLIT-RING
ESCUTCHEON PLATES SHALL NOT BE USED UON.
36. PROVIDE CAPPED DRAIN VALVES AT LOW POINTS OF PIPING SYSTEMS AND AT EQUIPMENT CONNECTIONS. PROVIDE HOSE BIBB
CONNECTIONS WITH CAPS AT DRAIN VALVES WHICH DO NOT DISCHARGE DIRECTLY OVER OR ARE NOT PIPED DIRECTLY TO AN
APPROPRIATE DRAIN.
37. PIPING, DUCTWORK OR EQUIPMENT CONNECTIONS OPENED BY DEMOLITION OR RENOVATION SHALL BE TEMPORARILY SEALED TO
KEEP OUT FOREIGN MATTER UNTIL SUCH TIME AS RECONNECTIONS ARE MADE.
M-1 6 7
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:DESCRIPTION:
EA:CLIENT:
1 2 3 4 5 6 7 8
S
D ZIP
FORCE PROTECTION STREET ADDRESS
FORCE PROTECTION CITY AND ZIP
FORCE PROTECTION NAME
FORCE PROTECTION PH AND FAX
MEP STREET ADDRESS
MEP CITY AND ZIP
MEP ENGINEERS
MEP PH AND FAX
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CONSULTANT 01 NAME
CONSULTANT 01 PH AND FAX
FORCE PROTECTION CONTACT
ENAPAY, LLC
MEP CONTACT
ENAPAY, LLC
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
REVISION SCHEDULE
No. DESCRIPTION DATE
1331 RIVER BEND DRIVE
DALLAS, TEXAS 75247
MR. FRED C. CRABTREE, JR., P.E.
T. 214.696.6291
1255 CORPORATE DRIVE - SUITE 200
IRVING, TEXAS 75038
MR. MICHAEL BURCH
T. 469.242.4707
207 WEST MAIN STREET
MESQUITE, TX 75149
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
CAMPOS ENGINEERING
ENAPAY, LLC
HILL INTERNATIONAL
PROJECT NUMBER:
BUILDING NUMBER:
EA:CLIENT:
207 WEST MAIN STREET
MESQUITE, TX 75149
T. 214.607.0247
WWW.ENAPAYLLC.COM
MECHANICAL FLOOR PLAN DESIGN PRIMARY POWER
SECONDARY SIDE
5001 N. PIEDRAS / EL PASO, TEXAS 79930
VA EL PASO
5001 N. PIEDRAS
EL PASO, TEXAS 79930
MR. KEVIN ANGELES
756-16-110 EA03.0111
D
ES
IG
N
P R
IM
A
R Y
PO
W
ER
. S
EC
O
N D
A R
Y
SI
D E
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
PR
O
JE
C T
N U
M B
ER
: E
A
.0
M-2
F1
MECHANICAL PLAN
50'
SCALE
KEY NOTES
1. DISCONNECT EXISTING YORK CONDENSING UNIT AND RELOCATE TO
ROOF AS SHOWN. COORDINATE WITH ELECTRICAL. REPAIR EXISTING
CONDENSATE AND OVERFLOW DRAIN LINES.
2. RELOCATED YORK CONDENSING UNIT.
3. 4" SCH. 80 PVC DRAIN ROUTED OVER TO SUMP PUMP. ROUTE PIPING
BELOW ELECTRICAL DUCT BANK.
4. SUMP PUMP; LITTLE GIANT 6EC-CIA-RF, 1/3HP, 115 VAC OR EQUIVALENT.
5. 2" DISCHARGE CUT OFF ABOVE GRADE IN SIDE WALL OF SIDE WALK CURB.
6. 2" VENT UP ALONG EDGE OF VERTICAL RISE TERMINATE WITH
GOOSENECK. ANCHOR WITH TWO HOLE STRAPS.
B1
PIPING SUPPORT DETAIL
NO SCALE
D1
ROOF PENETRATION DETAIL
NO SCALE
ANCHOR EQUIPMENT TO ROOF
CURB WITH 3/8" STAINLESS
BOLTS W/WASHERS @ 2'-0"
MAX. SPACING, MINIMUM 3
PER SIDE.
#14 S/M STAINLESS SCREWS
@ 1'-0" SPACING MINIMUM
THREE PER SIDE.
1/4" BOLT WITH
WASHERS AND
NUT @ 2'-0"
SPACING MAXIMUM
ONE EVERY
CORNER MINIMUM.
PREFABRICATED
METAL SUPPORT.
(SEE CONDENSING
UNTI SUPPORT
DETAIL.)
F1
ROOF CONDENSING UNIT
ANCHOR DETAIL
NO SCALE
UGE
U G
E U
G E
E U
EUEU
E U
E U
T
S
U G
E
E U
S
S
S S S S S
3 5
B3
PIPING SUPPORT DETAIL
NO SCALE
S
S
S
S
S
SS S
V
V
V
V
V
PUMP
2" DISHARGE IN
CURB WALL
2" VENT ROUTED UP WALL
AND TERMINATED WITH
GOOSENECK WITH
INSECT SCREEN
4" DRAIN IN DUCT BANK
PULL BOX. PROVIDE
WITH 1/4"X1/4" SCREEN
4" DRAIN IN DUCT BANK
PULL BOX. PROVIDE
WITH 1/4"X1/4" SCREEN
SUMP PIT. SEE DETAIL
D3
SUMP ISOMETRIC
NO SCALE
7 7
| COVER SHEET |
| E-0 |
| E-1 |
| E-2 |
| E-3 |
| [4] FA-101-2 FIRE ALARM - BUILDING 1 SECOND FLOOR PLAN |
| M-1 |
| FA-101-2 FIRE ALARM - BUILDING 1 SECOND FLOOR PLAN |
| M-2 |
| FA-101-2 FIRE ALARM - BUILDING 1 SECOND FLOOR PLAN |
File details come from the government source that posted it. Updated .