USDA_ARS_SAWSRU_Davis_100__Bid_Set_Drawings_20190715_-_Full_Sized_-_2.pdf

PDF 12 MB Posted

Attached to
Davis Watershed Project Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Pacific West Area

About this file

Drawings 2

View the file

Other files for this federal contract opportunity

Other files attached to Davis Watershed Project, newest first.
File Type Posted
Question_correction_&_additional_information.pdf PDF
Questions__2.pdf PDF
Question_Answers__1.docx DOCX document
Contractor_Certification_Regarding_EMR.pdf PDF
Addendum_SOW_-Water_Mgmt_Unit-_UC_Davis_revised.pdf PDF
Contractor_Calculation_of_Self-Performed_Work.xlsx XLSX spreadsheet
Past_Performance_Capability_Information.docx DOCX document
RFI_FORM.pdf PDF
12905B19R0032.pdf PDF
ars372.pdf PDF
USDA_ARS_SAWSRU_Davis_100__Bid_Set_Specifications_Rev1_20190715_COR_3.pdf PDF
ars371.pdf PDF
USDA_ARS_SAWSRU_Davis_100__Bid_Set_Drawings_20190715_-_Full_Sized_-_1.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BOTTOM OF TRENCH EXCAVATION

SHALL NOT EXTEND BELOW THIS LINE

NOTE:

THE CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING,

SHEATHING OR OTHERWISE MAINTAINING THE SIDES OF

THE EXCAVATION FROM CAVE-INS UNTIL ALL BACKFILL

IS COMPLETED PER SPECIFICATIONS

COMPACTED

FILL 90%

DENSITY

BACKFILL

PER SPECS.

10'-0" MIN.

EXCAVATION

TRENCH

WIDTH

FOOTING

MIN.

1'-6"

NOTES:

1. FOR PIPES & CONDUITS 3'-0" OR LESS BELOW FTG, PROVIDE SLEEVES & CONC AS

SHOWN. MORE THAN 3'-0", COMPACT BACKFILL O/ PIPES & CONDUITS TO 90% AS

APPROVED BY SOILS ENGINEER.

2. CONDUITS & PIPES MAY NOT UNDER ANY CIRCUMSTANCES, RUN PARALLEL TO & WITHIN

FTGS. SKEWED CROSSINGS OF CONDUITS & PIPES THRU FTGS ARE PROHIBITED.

3. PIPES OR CONDUITS 4" DIA. MAY CROSS AT 90° IN PLAN THRU FTGS SUBJECT TO

SPACINGS SHOWN IN DETAIL & AT MIDDLE 1/3 DEPTH OF FTG.

PIPE THRU

FDN WALL

B.O. FTG.

D

"D"+ 1'-6"

S

EE

N O

TE

S

TH

A N

O .D O F P

IP

ES

S

LE

EV

ES

LA

R G

ER

S

EE

N O

TE

M A X

(2) #5 T&B EXTEND

BARS INTO FOOTING

2'-0" W/ BENT END

CONCRETE SLAB ON GRADE

1'-3"

1'-0"

#4 TIES @ 12" O.C.

FOOTING SCHEDULE

MARK

FOOTING SIZE REINFORCING

REMARKSLENGTH

B t

THICK. b

BARS

aWIDTH

A BARS

NOTE:

1. a AND b BARS ARE BOTT BARS TYP U.O.N. SEE FOOTING DETAIL 6/S1.3

2. "a" BARS PARALLEL TO TRANSVERSE (SHORT) DIRECTION

"b" BARS PARALLEL TO LONGITUDINAL (LONG) DIRECTION

3. SEE TYP WALL FTG DETAIL 8/S1.4

NOTE 1 TYPICAL

3-#6 COLUMN FOOTING3'-0" 3'-0" 2'-0" 3-#6

3-#5 COLUMN FOOTING2'-0" 2'-0" 3-#52'-0"

F3

F2

5-#6 COLUMN FOOTING5'-0" 5'-0" 2'-0" 5-#6

4-#6 COLUMN FOOTING4'-0" 4'-0" 4-#62'-0"

F5

F4

S THIS POINT SHOWN

ON PLAN THUS

TOP REINF WHERE OCCURSREINFORCING

SHALL MATCH

CONT BARS IN

SIZE & NUMBER

2'0" MIN

2 "H" OR

M A X

"H

2'-0" MIN

2 "H" OR

D

EP

TH

"D

FO

O

TI

N G

SPLICE

HORIZ LAP

"D" MIN

3" MIN BAR COVERAGE TYP.

LAP SPLICE

HORIZ

PEB FOOTING PER PLAN

PEB COL PER PEB DRAWINGS

S.O.G. SEE PLAN

TIE BEAM

#5 @ 18" O.C. E.W.#5 @ 18" O.C. E.W.

FINISHES, S.A.D.

3" CLEAR, TYP

PER PLAN & SCHEDULE 4/1.3

FOOTING WIDTH (A)

EDGE OF

BLDG SLAB

CL OF BASE PLATE & FOOTING

FOOTING

THICKNESS (t), PER PLAN &

SCHEDULE

FINISH GRADE OR

SURFACE, S.C.D.

'a' BARS

'b' BARS

SEE P.E.B. MFR

DWGS FOR A.B. DIA.

#3 TIES @ 3" O.C.

P

LA

N

P

ER

3"

N.T.S. S1.3

1EXCAVATIONS PARALLEL TO FOOTING

N.T.S. S1.3

2PIPE & CONDUITS PERPENDICULAR TO FTG

N.T.S. S1.3

3TIE BEAM DETAIL

N.T.S. S1.3

4FOOTING SCHEDULE

N.T.S. S1.3

5STEPPED FOOTING OR GRADE BEAM DETAIL

N.T.S. S1.3

6PEB FOOTING

GN

A

No. S4485

S

ET

AT

FO

Exp.

FILAC

I

RO

N

E

ER

T

IGER

S

NIOO SEF SR

D

P A

E

L

I

RE

EN

6/30/20

STRUCTURA

L

M I C

HA

EL J .

RO

S S

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

23'-8" 20'-3 1/2" 23'-8"

1'-1" FACE OF STEEL, TYP

1'-8"1'-8"

3 TYP

S1.3S2.1

6 TYP

S1.3S2.1

8 TYP

S1.2S2.1

GN

A

No. S4485

S

ET

AT

FO

Exp.

FILAC

I

RO

N

E

ER

T

IGER

S

NIOO SEF SR

D

P A

E

L

I

RE

EN

6/30/20

STRUCTURA

L

M I C

HA

EL J .

RO

S S

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

1/4" = 1'-0" S2.1

FOUNDATION PLAN 1

5" CONC SLAB ON GRADE W/

#4 @ 18" O.C. EW @ MID-

DEPTH O/ 15-MIL MOISTURE

BARRIER, O/ 4"-3/4"

CRUSHED ROCK (W/ 100%

PASSING A NO. 4 SIEVE. SEE

THE SOILS REPORT FOR MORE

SUB-SLAB PREPARATION

F3F4F4F3

F3F4F4F3

TYP

12"x15"

NORTH

DSD

(UNDER DIVISION 16)

DUCT MOUNTED SM OKE DETECTOR

ROOM TEMPERAT URE SENSOR

DOOR LOUVER (UNDER DOOR SECTION)

UNDERCUT DOOR (UNDER DOOR SECTION)

EQUIPMENT IDENTIFICATION: TYPE-NUMBER

U/C

D/L

EF

ACCESS PANELAP

EF-1

REF

PSIG

RA

QTY.

P.D.

POUNDS PER SQUARE INCH GAUGE

REFER ENCE

RETURN AIR

QUANTITY

PRESSURE DROP

FSD COMBINATION SMOKE & F IRE DAMPER

ROUND DUCT OR STACK - SECTION

ABBREV.

MECHANICAL SYMBOLS

S Y M B O L DESCRIPTION

POINT OF CONNECTION

POINT OF DISCONNECTION

P O C

P O D

ESP EXTERNAL STATIC PRESSURE

TYPICAL

TOTAL STATIC PRESSURE

UNLESS OT HERWISE NOTED

TYP

U O N

TSP

REVOLUTIONS PER MINUTER P M

VENT THROUGH ROOF

UP THROUGH ROOF

VT R

UTR

EFF

EA

D W G

EFFICIENCY

EXHAUST AIR

DRA WI NG

DEFL DEFLECTION

BUTTERFLY VALVE

CIRCUIT SETTER

CHECK VALVE

SAFETY OR RELIEF VALVERV

CH V

BALL VALVE

GATE VALVE

ABBREV.

MECHANICAL SYMBOLS

S Y M B O L DESCRIPTION

2-WAY ON/OFF VALVE

PRESSURE & TEMPERATURE TEST PLUG

EXPANSION JOINT 2 ' MINIMUM MOVEMENT

A N C H O R

PTTP

STRAINER

TEMPERAT URE GAGE

PRESSURE GAGE WITH COCK

2-WAY MODULATING VALVE

AUTOMATIC FLOW CONTROL VALVEAFV

MANUAL AIR VENTMAV

AUTOMATIC AIR VENTAAV

N C

M B H

LPS

THOUSAND BT U PER HOUR

NOISE CRITERIA

LOW PRESSURE STEAM

IN.W.C.

HZ

HP

H C

INCH WATER COL UMN

HERT Z

HEATING COIL

H O R S E P O W E R

FD FIRE DAMPER

(E) EXISTING

CWS

CWR

CONDENSOR WATER SUPPLY

CONDENSOR W ATER RETURN

ABOVE FINISHED FLOOR

ACCESS PANEL

BRITISH THERMAL UNIT PER HOURBT U H

AP

AFF

ABBREVIATIONS

ABBREV. DESCRIPT ION

D B

CV

DRY-BUL B

CONSTANT VOLUME

GENERAL SEISMIC NOTES

MEP COMPONEN T ANCH ORAGE

ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND

INSTALLED PER STRUCTURAL DETAILS ON THE CONSTRUCTION DOCUMENTS. WHERE NO

DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO

MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC,

SECTIONS 1616A.1.18 THROUGH 1616A.1 .26 AND ASCE 7-10 CHAPTER 13, 26 AND 30.

1 . ALL PERMANENT EQUIPMENT AND COMPONENTS.

2 . TEMPORARY OR MOVEABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (e .g .HARD WIRE)

TO THE BUILDING UTILITY SUCH AS ELECTRICITY, GAS OR WATER.

3 . MOVEABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND

HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY

ATTACHMENTS. THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL

COMPONENTS SHALL BE POSIT IVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE

DETAILED ON PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED

BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, P IPING, AND CONDUIT.

A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED

4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE

COMPON ENT.

B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED

SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR

OR HUNG FROM A WALL.

FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE

INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF

RECORD. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT

HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY

WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13 .3 AS DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2016 CBC, SECTIONS 1616A1.23, 1616A.1.24, 1616A.1.25 AND 1616A.1.26.

COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF

CHANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.

THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE

TO SUPPORT THE HANGER AND BRACE LOADS. RELOCATED UNIT(RL)

REMOVE AND RELOCATE EQUIPMENT(RR)

LBS P O U N D S

3-WAY ON/OFF VALVE

3-WAY MODULATING VALVE

GENERAL NOTES

CALGREEN HVAC COMPLIANCE

1. HVAC SYSTEM INSTALLERS SHALL BE TRAINED AND CERTIF IED IN THE PROPER

INSTALLATION OF HVAC SYSTEMS.

2. PROVIDE DOCUMENTATION TO SHOW COMPLIANCE WIT H CONSTRUCTION

DOCUMENTS, PLANS, INSTALLER CERTIFICATIONS, INSPECTION REPORTS, TO

DEMONSTRATE SUBSTANTIAL CONFORMANCE, WHEN SPECIF IC DOCUMENTATION OR

SPECIAL INSPECTION IS NECESSARY TO VERIFY COMPLIANCE, THAT METHOD OF

COMPLIANCE WILL BE SPECIFIED IN THE APPROPRIATE SECTION OR IDENTIF IED IN THE

APPLICATION CHECKLIST.

3. AABC COMPLIANCE: COMPLY WITH AABC'S MANUAL MN_1 "AABC NATIONAL

STANDARDS". AS APPLICABLE TO MECHANICAL AIR DISTRIBUTION SYSTEMS AND

ASSOCIATED, DEVELOP A WRITTEN PLAN OF PROCEDURES TO BE INCLUDED FOR

TESTING AND BALANCING. SUBMIT CERTIFIED TEST REPORTS SIGNED BY THE TEST

AND BALANCE SUPERVISOR WHO PERFORMED TESTING AND BALANCING WORK.

PROVIDE A COPY OF THE FINAL TEST REPORT TO THE ENFORCING AGENCY.

4. PROVIDE VENTILATION DURING CONSTRUCTION THRU OPENING IN THE BUILDING

SHELL USING TEMPORARY FANS TO PRODUCE A MINIMUM OF 3 AIR CHANGES PER

HOUR. DO NOT USE THE PERMANENT HVAC EQUIPMENT FOR THIS

PURPOSE.

5. COVER ALL DUCT OPENINGS WITH SHEET METAL OR PLASTIC DURING CONSTRUCTION

TO REDUCE DUST AND DEBRIS IN

DUC TW OR K.

6. ALL AIR FILTERS SHALL BE MINIMUM MERV 8 . A HIGHER MERV RATING MAY BE

REQUIRED ON SCHEDUL ES OR

SPECIF ICATIONS.

7. NO HVAC REF RIGERANT SYST EM USING HYDROCHOROFL UOROCARBONS SHALL BE

USED ON THE

PROJECT.

8. PROVIDE THE BUILDING OWNER WITH DETAILED OPERATION AND MAINTENANCE

INSTRUCTIONS AND COPIES OF GUARANTEES/WARRANTIES FOR EACH SYSTEM PRIOR

TO FINAL

INSPECTION.

1. ALL WORK SHALL CONFORM TO TITLE-24, CALIFORNIA CODE OF REGULATIONS(CCR) .

2. SEAL ALL OPENING AROUND PIPING AND DUCTWORK PENETRATING FIRE RESISTIVE

RATED WALLS AND FLOORS TO MAINTAIN RATING INTEGRITY.

3. PROVIDE ACCESS DOOR FOR ALL EQUIPMENT, VALVES AND CLEAN OUTS WHICH

REQUIRE ACCESS FOR ADJUSTMENT OR SERVICING, AND WHICH ARE LOCATED IN

OTHERWISE INACCESSIBLE LOCATIONS, PERMIT MAINTENANCE AND ADJUSTMENT OF

THE DEVICE.

4. PROVIDE 120V RECEPTACLE WITHIN 25 FT OF EQUIPMENT.

5. PITCH PIPELINES AS REQUIRED FOR PROPER DRAINAGE AND ELIMINATION OF AIR.

6. INSTALL ALL EQUIPMENT LEVEL AND PLUMB. PROVIDE BLOCKING AND HARDWARE AS

REQUIRED.

7. MANUFACTURERS NAMES FOR PRODUCTS L ISTED ON DRAWINGS ARE BASIS OF

DESIGN. SEE SPECIFICATIONS FOR EQUIVALENT MANUFACTURERS.

8. THE PROJECT DESIGN SHOWN ON THE DRAWINGS AND SPECIFIC ITEMS REFERENCED

IN THE SPECIFICATIONS IS IN COMPLIANCE WITH THE CODE AND ORDINANCES LISTED

IN DIVISION 23 OF SPECIFICATIONS.

9. PROVIDE SEISMIC ANCHORAGE AND BRACING FOR MECHANICAL EQUIPMENT, P IPING

AND DUCTWORK. SEE "GENERAL SEISMIC NOTES" FOR DETAIL REQUIREMENTS.

10. PROVIDE HANGER, SUPPORTS AND SWAY BRACES FOR ALL DUCTWORK, P IPING AND

EQUIPMENT AS REQUIRED BY THE LATEST EDITION OF THE SMANCA GUIDELINES.

11. INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER

RECOMMENDATION UNLESS SPECIF ICALLY INDICATED OTHERWISE OR WHERE THE

LOCAL CODES OR REGULATIONS TAKE PRECEDENCE.

12. PREPARE SHOP DRAWINGS FOR INSTALLATION OF ALL NEW WORK BEFORE

INSTALLATION TO VERIFY COORDINATION BETWEEN TRADES.

13. KEEP CUTTING TO THE MINIMUM REQUIRED FOR PROPER EXECUTION OF WORK. BE

RESPONSIBLE FOR ALL CUTTING AND PATCHING NECESSARY FOR THE COMPLETION

OF WORK. NO CUTTING SHALL BE PERFORMED WITHOUT THE APPROVAL OF THE

ARCHITECT.

14. PROVIDE OFFSETS, ELBOWS AND TRANSITIONS IN DUCTWORK AND PIPING AS

REQUIRED AT NO ADDITIONAL COST TO THE OWNER. VERIFY ALL CONNECTIONS WITH

MANUFACTURER'S CERTIFIED DRAWINGS. PROVIDE TRANSITION FOR FINAL

CONNECTION TO EQUIPMENT. F IELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION

OF

WORK .

15. ALL WORK AND MATERIAL SHALL BE IN COMPLIANCE WITH THE SPECIFICATIONS. IN

THE EVENT OF CONFLICT BETWEEN THE CONTRACT DRAWINGS AND THE

SPECIFICATIONS THE MOST STRINGER SHALL GOVERN.

16. INSTALL ALL PIPING AND DUCTWORK TO BEST SUIT F ILED CONDITIONS AND

COORDINATE WITH OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC AND SHALL

NOT BE SCALED TO DETERMINE THE EXACT LOCATION OF THE PIPING OR

DUC TW OR K.

17. DUCTS AND EQUIPMENTS STORED ON THE CONSTRUCTION S ITE SHALL BE

PROTECTED AND ISOLATED FROM DUST CONTAMINATION.

18. ALL DUCTWORK SHALL BE SEISMICALLY SUPPORTED PER SMACNA DUCTWORK

CONSTRU CTION

GUIDELINES.

19. ALL SIZES ARE IN INCH, U.O.N.

20. OUTSIDE OR RETURN AIR FOR A HEATING OR COOLING SYSTEM SHALL NOT BE TAKEN

FROM LESS THAN 10 FEET IN DISTANCE FROM AN APPLIANCE VENT OUTLET, VENT

OPENING OF A PLUMBING DRAINAGE SYSTEM, DISCHARGE OUTLET OF AN EXHAUST

FAN, UNLESS THE OUTLET IS 3 FEET ABOVE THE OUTSIDE AIR INLET. ALSO, THE

OUTSIDE OR RETURN AIR SHALL NOT BE TAKEN FROM LESS THAN 10 FEET ABOVE

THE SURFACE OF AN ABUTTING PUBLIC WAY, SIDEWALK, STREET, ALLEY, OR

DRIVEWAY, PER 2016 CMC SECTION 311.3 .

21. ENVIRONMENTAL AIR DUCT EXHAUST SHALL TERMINATE NOT LESS THAN 3 FEET

FROM A PROPERTY LINE, 10 FEET FROM A FORCED AIR INLET, AND 3 FEET FROM

OPENINGS INTO THE BUILDING. ENVIRON MENTAL EXHAUST DUCTS SHALL NOT

DISCHARGE ONTO A PUBLIC WALKWAY, PER 2016 CMC SECTION 502 .2.1 .

EXISTING PIPE OR EQUIPMENT TO REMAIN

(N) N E W W O R K

(R) EXIST ING WORK TO BE REMOVED

N E W W O R K

P U M P

CEILING DIFFUSER SUPPLY

CEILING GRILLE EXHAUST

CEILING GRILLE RETURN

(ER) EXISTING TO RELOCATE

VOLUME DAMPERVD

GENERAL NOTES (CONTINUED)

22. DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE VAPORS, FUMES, OR DUSTS SHALL

TERMINATE NOT LESS THAN 30 FEET FROM A PROPERTY LINE, 10 FEET FROM

OPENINGS INTO THE BUILDING, 6 FEET FROM EXTERIOR WALLS OR ROOFS, 30 FEET

FROM COMBUSTIBLE WALLS OR OPENINGS INTO THE BUILDING THAT ARE IN THE

DIRECTION OF THE EXHAUST DISCHARGE AND 10 FEET ABOVE THE ADJOINING GRADE,

PER 2016 CMC SECTION 502.2.2.

23. CONTRACTOR TO FOLLOW BASIS OF DESIGN REQUIREMENTS BASED ON DAVIS DESIGN

CONDITION.

24. CONTRACTOR TO FOLLOW ALL MECHANICAL COMMISSIONING REQUIREMENTS PER UC

DAVIS CAMPUS DESIGN GUIDE, PART IV STANDARD SPECIF ICATION.

APPLIED BUILDING CODES:

2016 CALIFORNIA MECHANICAL CODE (CMC)

2016 CALIFORNIA PLUMBING CODE (CPC)

2016 CALIFORNIA ELECTRICAL CODE (CEC)

2016 CALIFORNIA ENERGY CODE

2016 CALIFORNIA BUILDING CODE (CBC)

ACCESSIBILITY CODE-2016 CBC; CHAPTER 10, 11A, 11B

TITLE 19 CALIFORNIA ADMINISTRATION CODE

TITLE 24 CALIFORNIA

2016 CALIFORNIA ADMINISTRATION CODE

2016 EDITION, CALIFORNIA CODE OF REGULATIONS, TITLE 24, PART 9, CALIFORNIA FIRE

C O D E

(CFC)2016 EDITION, CALIFORNIA GREEN BUILDING STANDARDS CODE

2016 NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEM

NFPA 30 , FLAMMABLE AND COMBUSTIBLE L IQUIDS CODE 2018 EDIT ION, PER CFC CHAPTER 80

2016 NFPA 72,NATIONAL F IRE ALARM AND SIGNALING CODE

2016 NFPA 110, STANDARDS FOR EMERGENCY AND STANDBY POWER

2016 NFPA 415, STANDARDS ON AIRPORT TERMINAL BUILDINGS, FUELING RAMP DRAINAGE,

AND LOADING WALKWAYS

APPLICABLE REQUIREMENTS ENFORCED BY THE STATE, CITY, AND LOCAL AUTHORITIES

HAVING JURISDICTION.

EXISTING DUCT/PIPE OR EQUIPMENT

TO BE REMOVED

UNDER CUT (DOOR)U C

TUBULAR DAYLIGHTING DEVICETDD

SCOPE OF WORK

THE PROPOSED FACILITY WILL BE PROVIDED WITH DEDICATED HEATING, VENTILATING AND

AIR-CONDITIONING (HVAC) SYSTEM WITH PROGRAMMABLE CONTROL SYSTEMS TO ACHIEVE

THE DESIRED TEMPERATURE CONTROL AND VENTILATION REQUIREMENTS.

BASED ON THE GEOGRAPHICAL LOCATION OF THIS PROJECT (ZONE-12) AND LOAD

CALCULATION RESULTS, WE HAVE SELECTED AN ENERGY EFFICIENT VRV SYSTEM WITH HEAT

RECOVERY AND VARIABLE REFRIGERANT TEMPERATURE CONTROL THAT IMPROVES

SEASONAL COOLING EFFICIENCY. THIS VRV UNIT DEDICATEDLY SERVES THE OFFICE BUILDING

INCLUDING ALL OFFICE SPACES AND CONFERENCE ROOMS. WITH HEAT RECOVERY SYSTEM,

WE CAN HAVE HEATING AND COOLING IN A DIFFERENT ZONE DEPENDING ON EXPOSURE OF

THE BUILDING AND LOAD REQUIREMENTS. MINIMUM OUTSIDE AIR REQUIREMENTS ARE MET

USING DEDICATED OUTSIDE AIR SUPPLY FAN WITH MERV-13 F ILTER. THIS HVAC SYSTEM

COMPLIES WITH THE ARS FACILIT IES DESIGN STANDARD AND UC DAVIS CAMPUS DESIGN

SPECIFICATION/ GUIDE.

DEDICATED ENERGY EFFICIENT WALL MOUNTED SPLIT SYSTEM WITH SINGLE CONDENSER UNIT

IS PROVIDED FOR SERVER ROOM AND IDF ROOM FOR 24X7

COOLING.

MISCELLANEOUS EXHAUST FANS ARE PROVIDED FOR RESTROOMS, JANITOR CLOSET,

ELECTRICAL ROOM, ETC. THE BUILDING WILL BE KEPT SLIGHTLY UNDER POSITIVE PRESSURE.

A COUNTER BALANCE DAMPER IS PROVIDED IN THE COMMON AREA TO RELIEF ACCESS AIR VIA

GRAVITY VENT RELIEF (GVR).

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M0.1MECHANCIAL LEGEND,

ABBREV., SYMBOLS, &

GENERAL NOTES

MECHANICAL SHEET INDEX

Sheet Number Sheet Name

M0.1 MECHANCIAL LEGEND, ABBREV., SYMBOLS, & GENERAL NOTES

M0.2 MECHANICAL SCHEDULES

M0.3 MECHANICAL SCHEDULES

M2.1 MECHANICALFLOOR PLAN

M2.2 MECHANICAL ROOF PLAN

M3.1 MECHANICAL DETAILS

M3.2 REFRIGERANT PIPING ANE WIRING DIAGRAMS

1 05-17-2019 35% DESIGN SUBMITTAL

INDOOR FAN COIL UNIT SCHEDULE

CONDENSING UNIT SCHEDULE

BRANCH CONTROLLER SCHEDULE (BC)

1 UNITS SHALL BE COMPLETE WITH INDOOR FAN COIL UNITS. CONFIRM EQUIPMENT

SELECTION WITH MANUFACTURER PRIOR TO ORDERING EQUIPMENT.

REFRIGERANT TUBING SETS, PER INDOOR UNIT. SIZE TUBING TO ACCOMMODATE

MAXIMUM INDIVIDUAL AND TOTAL SYSTEM LENGTHS. CONFIRM WITH MANUFACTURER.

DISCONNECT SHALL BE PROVIDED BY DIVISION 26. THE DISCONNECT SHALL BE

ADJACENT TO AND IN SIGHT OF THE EQUIPMENT IT SERVES. 2016 CMC, SEC. 310.0

NOTES:

TAG

MANUFACTURER

AND

MODEL NO.

LOCATIONSERVICE

COOLING ELECTRICAL DATA

NOMINAL

TONS

CAPACITY

MBH

MCA

(A)

MOCP

(A) V/PH/Hz

REFRIG

TYPE

EER

IEER

DIMENSION

HXWXD

INCH

OPERATING

WEIGHT

LBS.

REMARKS

FCU-1, FCU-2, FCU-3, FCU-4, FCU-5, FCU-6 1 2 3 4 5GROUND

DAIKIN

REYQ120TATJU

10-TONS 125.2 43.0 208-230/3/60

12.3

22.6 70450.0 R-410A

INSTALL CONDENSING UNIT ON 6" HOUSEKEEPING PAD WITH 5/8" THICK NEOPRENE PAD.

REFRIGERANT-CONTAINING PARTS OF A SYSTEM THAT IS FIELD-ERECTED SHALL BE TESTED AND PROVED TIGHT TO THE AUTHORITY HAVING JURISDICTION AFTER COMPLETE INSTALLATION AND BEFORE OPERATION. CONTACT THE MECHANICAL INSPECTOR AT 650-821-5981 TO SCHEDULE AN INSPECTION. 2016 CMC SEC. 1124.2.

PROVIDE OIL SUMP HEATER, LOW AMBIENT CONTROL, AND HI AND LOW PRESSURE SAFETY SWITCHES.

1 MERV 13 FILTER TO BE MOUNTED ON FAN COIL RETURN AIR OPENING.

PROVIDE WITH ODP MOTOR.

LOW AMBIENT CONTROLS FIELD INSTALLED.

PROVIDE VIBRATION ISOLATOR, MASON TYPE 30N(TYP-4)

5 DISCONNECT SHALL BE PROVIDED BY DIVISION 26 AND SHALL BE ADJACENT TO AND IN

SIGHT OF EQUIPMENT SERVED PER CMC 2016 SECTION 310.

UNIT SHALL BE FURNISHED WITH MANUFACTURER THERMOSTAT.

PROVIDE MANUFACTURER CONDENSATE PUMP.

PROVIDE STANDARD MANUFACTURER FILTER.

NOTES:

MANUFACTURER

MODEL NO.

ANDTAG LOCATION

COOLING

V-PH-HZ

ELECTRICAL DATA

MBH

TOTAL WEIGHT

OPERATING

LBS.

REMARKS

SUPPLY AIR

SUPPLY

CFM (IN.W.G.)

ESP

HEATING

MBH

TOTAL

FILTER

FCU-1

MCA MOCP TYPE/MAX IPD

MBH

SENSIBLE (WxHxD)

DIMENSIONS

1 2 3 4

DAIKIN

FAQ18TAVJU

31N/A13.7 FACTORY/0.10"0.5 1518.0 41.4X11.4X9.2

SERVICE

ASSOCIATED

UNIT

CONDENSING

HP-1

WALL SERVER ROOM

500H 0.10

1 2 3

DAIKIN

MANUFACTURER

MODEL NO.

AND

BS8Q54TVJ

TAG

TECH CUBICLES

CEILING

LOCATION

V-PH-HZ

208-230V 1PH

ELECTRICAL DATA

0.8

WEIGHT

OPERATING

LBS.

REMARKS

NOTES: 1

SERVICE

REFRIG

TYPE

R-410A

MOCPMCA

BS-1 HP-1

OF

NUMBER

BRANCHES

1 2 3 422.8X11.7X18.9

WXHXD

DIMENSION

INCH

48.9X66.7X30.2

FCU-2

FCU-3

FCU-4

FCU-5

FCU-6

FCU-7

COMP/DATA-NW

DAIKIN

FXZQ09TAVJU

HP-1CEILING 317 0.25 35.310.56.3 FACTORY/0.10"0.3 159.5 22.6X10.2X22.6208-230V-1-60

AMP AMP

DAIKIN

FXMQ36PBVJU

10239.928.7 FACTORY/0.10"2.9 1536.0 55.1X11.8X27.6208-230V-1-60HP-1CEILING

ENCL OFF. 2, 3, 4

CORR. & RESTROOM

1,130 0.25

ECNL OFF 1/RECEIP.

DAIKIN

FXMQ09PBVJU

HP-1CEILING 317 0.25 5610.57.6 FACTORY/0.10"0.6 1512 21.7X11.8X27.6

BREAK ROOMDAIKIN

FXMQ12PBVJU

CEILING 6213.59.4 FACTORY/0.10"1.4 1512 27.6X11.8X27.6HP-1

HP-2

450 0.25

DAIKIN

FXMQ36PBVJU

10239.928.7 FACTORY/0.10"2.9 1536.0 55.1X11.8X27.6HP-1CEILING TECH CUBICLES 1,130 0.25

DAIKIN

FXMQ36PBVJU

10239.928.7 FACTORY/0.10"2.9 1536.0 55.1X11.8X27.6HP-1CEILING CONFERENCE ROOM 1,130 0.25

400L

1 2 3 4 5 6

1 2 3 4 5 6

1 2 3 4 5 6

1 2 3 4 5 6

1 2 3 4 5 6

FCU-7, FCU-8 1 2 3 4 5GROUND

DAIKIN

RXTQ36TAVJ9 3-TONS

VRV

36.2 16.5 208-230/1/60

12.0

18.0 17225.0 R-410AHP-2 39X37X12.6

CONFIRM EQUIPMENT SELECTION WITH MANUFACTURER PRIOR

TO ORDERING EQUIPMENT.

DISCONNECT SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR.

FAN COIL

WALL

CASSETTE

DUCTED

TYPE

MOUNTED

DUCTED

DUCTED

DUCTED

DUCTED

VRV

208-230V-1-60

208-230V-1-60

208-230V-1-60

208-230V-1-60

208-230V-1-60

DAIKIN

FAQ18TAVJU

31N/A13.7 FACTORY/0.10"0.5 1518.0 41.4X11.4X9.2WALL IT ROOM

500H 0.10 1 2 3 75 6FCU-8 HP-2

400L

WALL

MOUNTED 208-230V-1-60

9 CONTRACTOR TO MAKE SURE TO ORDER FAN COIL UNIT WITH FILTER

ACCESS ON THE SAME SIDE AS THE COIL SERVICE ACCESS.

RE-CIRCULATING UNIT FOR EQUIPMENT ROOM. NO OUTSIDE AIR

REQUIREMENTS.

8 10

75 6 8 10

MINIMUM

AIR

OUTSIDE

(CFM)

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M0.2MECHANICAL

SCHEDULES

DIFFUSERS AND REGISTERS SCHEDULE

EXHAUST/ OUTSIDE AIR SUPPLY FANS SCHEDULE GRAVITY VENT RELIEF SCHEDULE

PROVIDE SIZES AND LOCATIONS AS INDICATED IN DRAWING.

REFER TO ARCHITECTURAL DRAWINGS FOR CEILING/WALL/FLOOR

TYPE TO DETERMINE REQUIRED FRAME.

PROVIDE REMOTE CONTROL RODS FOR VOLUME DAMPER WHEN

REQUIRED.

NOTES:

SUPPLY

SERVICE

TYPE OF

RETURN/EXHAUST

RETURN/EXHAUST

DESIGNATION

CR-1 / CE-1

WR-1 /WE-1

TITUS 50F

TITUS 350RL

MODEL NO.

TITUS MCD

MFR.

CD-1 PERFORATED

PERFORATED

LOUVERED

SURFACE/LAY IN

SIDEWALL/SURFACE

BORDER

SURFACE/LAY IN

FACE

SEE PLANS

24x24

WHITE

WHITE

24x24

MODULE

WHITE

FINISH REMARKS

SUPPLYTITUS MCDCD-2 PERFORATEDSURFACE/LAY IN 12x12 WHITE

RETURN/EXHAUSTCR-2 / CE-2 TITUS 50F PERFORATEDSURFACE/LAY IN 12x12 WHITE

SUPPLYWS-1 TITUS 300RL LOUVEREDSIDEWALL/SURFACE SEE PLANS WHITE

1 52 3 4

1 52 3 4

1 52 3 4

1 52 3 4

1 52 3 4

1 52 3 4

PROVIDE SQUARE TO ROUND ADAPTER AS REQUIRED.

COORDINATE CUSTOM COLOR WITH ARCHITECT.

SONESUNIT

NO.

ESP

IN.

W.G.

MANUFACTURER

MODEL NO.

ROOM

SERVED AND

AIR

QUANT

CFM WATTS

FAN

RPM

V-PH-HZ

MOTOR

OPERATING

WEIGHT

UNIT

LBS.

REMARKS

NOTES:

EF-1 MEN 11

GREENHECK

SP-A200 175 0.30 37 120/1/60 1.5 26800 1 2 3

BACKDRAFT DAMPER

INTERLOCK WITH OCCUPANCY SENSOR.

FAN SHALL BE PROVIDED WITH STARTER AND DISCONNECT SWITCH.

PROVIDE LINE VOLTAGE THERMOSTAT.4

PROVIDE WITH MERV-13 FILTER.

INTERLOCK WITH FCU-1, FCU-2, FCU-3, FCU-4, FCU-5, FCU-6, FCU-7.

EF-2 WOMEN 10

EF-3 JANITOR CLOSET

GREENHECK

SP-A125 100 0.297 21 120/1/60 0.8 191100 1 2 3

EF-4 GREENHECK

SP-A250 250 0.286 83 120/1/60 3.0 261000 1 2 3ELECTRICAL ROOM

1 2 3

OAF-1

OUTSIDE AIR SUPPLY FAN FOR

ALL INDOOR FANCOIL UNITS

SERVING ALL ROOMS

GREENHECK

BSQ-100-4 800 0.5 (1/4) 208/1/60 9.5 1751418 1 3

(OR HP)

5 6

GREENHECK

SP-A200 175 0.30 37 120/1/60 1.5 26800

SERVED

AREA

NOTE:

NO.

ITEM

MODEL NO.

MANUFACTURER

AND

SIZE

CFM SERVICE

IN. WG

DROP

PRESSURE

REMARKS

PROVIDE ROOF CURB, BIRD SCREEN AND BACKDRAFT DAMPER.

PROVIDE FLASHING FLANGE.

AIR RELIEFGRSR

GREENHECKCORRIDOR

GVR

1 112 0.01200 2

(INCH)

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M0.3MECHANICAL

A B

FCU

FCU

FCU

HP

EF

FCU

OAF

C

D

FCU

T

HP

16"x12"

TT

FCU

UC

13 OA

T

BS

CD-1, 8"Ø

150 CFM

(3TYP)

CD-1, 6"Ø

100 CFM

CD-1, 6"Ø

50 CFM

12"x12"

CD-1, 8"Ø

160 CFM

(3TYP)

CD-1, 10"Ø

280 CFM

(4TYP)

T

16"x12"

FCU

10"ø OA

8"ø OA

12"x12"

CD-1, 10"Ø

225 CFM

(2TYP)

T

EF

EF

14"x12" OA

UC5

CD-1, 6"Ø

75 CFM

(2TYP)

CD-1, 10"Ø

280 CFM

(4TYP)

EF

(50)

5"ø OA

19 (165)

(280)

(280)

(280) (280)

8"ø OA

(75)

19(125)

(225)

(160)

(150)

(160)

(150)

19 (150)

19(60)

CD-1, 10"Ø

215 CFM

(280)(280)

(280)

COMP/DATA ANALYTICS

SERVER RM

CORRIDOR

MEN

WOMEN

TECH OPEN OFFICE

STORAGE

CONF/TRAINING RM

BREAK RM

15ELEC RM

JC

ENCL OFC

ENCL OFC

ENCL OFC

RL OFC

RECEP

8"ø

T

FCU

T

CR-1,22X22(TYP)

(FCU-3)

T 2

(FCU-2)(FCU-1) (FCU-7)

(FCU-8)

UC 5

(FCU-5)

(FCU-4)

(FCU-6)

6"ø OA

SEE REF. PIPING

DIAGRAM FOR SIZES.

(250)

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M2.1MECHANICALFLOOR

PLAN

SCALE: 1/4" = 1'-0"1 MECHANICAL FLOOR PLAN

CASSETTE TYPE FAN COIL UNIT TO BE MOUNTED IN THE CEILING PER MFR'S

INSTALLATION DETAIL. SEE SCHEDULE FOR TYPE AND SIZE.

MFR'S PROGRAMMABLE THERMOSTAT WITH RESET CAPABILITY.

CEILING MOUNTED EXHAUST FAN. SEE SCHEDULE FOR TYPE AND SIZE.

10"Ø EXHAUST UP THROUGH ROOF(UTR).

1" DOOR UNDERCUT(TYPICAL).

DUCTED FAN COIL UNIT TO BE HUNG FROM STRUCTURE ABOVE AS HIGH AS

POSSIBLE WITH VIBRATION ISOLATOR, MASON MODEL 30N WITH 1" DEFLECTION.

SEE SCHEDULE FOR PERFORMANCE.

8"Ø EXHAUST UP THROUGH ROOF(UTR).

WALL MOUNTED DUCTLESS FAN COIL UNIT TO BE MOUNTED PER MFR'S

INSTALLATION INSTRUCTION. PROVIDE ALL NECESSARY BRACKET KIT. SEE

SCHEDULE FOR PERFORMANCE.

REF. PIPING FROM WALL MOUNTED FAN COIL UNIT TO HP-2 OUTSIDE WITH

ARMAFLEX INSULATION. PIPE SIZE SHALL BE PER MFR'S RECOMMENDATIONS.

PUMPED CONDENSATE DRAIN. SEE PLUMBING DRAWINGS FOR CONDENSATE

DRAIN PIPE LAYOUT.

6"Ø EXHAUST UTR.

18X18 DOOR LOUVER. SEE ARCH'L DWGS.

24X14 OUTSIDE AIR LOUVER WITH 12" LONG FULL SIZE PLENUM. PROVIDE 10'

DISTANCE BETWEEN OUTSIDE AIR INTAKE AND EXHAUST. SEE ARCH'L DWGS. FOR

LOUVER EXACT SIZE AND LOCATION.

6" DEEP CONC. PAD FOR MECHANICAL EQUIPMENT. SEE ARCH'L DWGS. FOR

EXACT SIZE AND LOCATION OF THE CONCRETE PAD.

8 PORT MFR. BRANCH SELECTOR. SEE SCHEDULE FOR ELECTRICAL AND

PLUMBING REQUIREMENTS.

FLEXIBLE CONNECTION (TYP.).

1" INTERNAL ACOUSTICAL LINING(TYP.). FIBER FREE TYPE MATERIAL PER UCD

STANDARDS.

18" LONG FULL SIZE OPEN RETURN AIR PLENUM WITH 1" ACOUSTICAL LINING.

BALANCE MIN. OUTSIDE AIR PER INDICATED AIRFLOW CFM. OUTSIDE AIR DUCT

TERMINATION TO BE MAXIMUM 3'-0" FROM OPEN END OF RETURN AIR PLENUM.

RETURN AIR PLENUM ABOVE CEILING(TYP.).

PROVIDE LINE VOLTAGE THERMOSTAT AND SET AT 80°F.

MANUFACTURE PROGRAMMABLE REMOTE CONTROL THERMOSTAT TO BE

PERMANENTLY INSTALL ON THE WALL.

OUTSIDE AIR FAN TO BE HUNG FROM STRUCTURE ABOVE AS HIGH AS POSSIBLE

WITH VIBRATION ISOLATOR, MASON MODEL 30N WITH 1" DEFLECTION. SEE

SCHEDULE FOR PERFORMANCE.

12"Ø RELEIF AIR DUCT UP THROUGH ROOF TO GAVITY VENT RRELIEF WITH

COUNTER BALANCE DAMPER TO BE SET AT 0.05" WG.

REF. PIPING FROM HP-1 OUTSIDE WITH ARMAFLEX INSULATION TO INDOOR FAN

COIL UNITS . PIPE SIZE SHALL BE PER MFR'S RECOMMENDATIONS.

1- COORDINATE EXACT LOCATION OF AIR OUTLET WITH ARCH'L DWHS.

2-COORDINATE AIROUT LET LOCATIONS WIT LIGHT FIXTURES AND OTHER DEVICES IN THE CEILING.

3- FOR GENERAL NOTES SEE M0.1.

4- DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, ELBOWS, AND OTHER ELEMENT THAT MAYBE REQUIRED. THE DRAWING SHOW THE GENERAL ARRANGEMENT OF EQUIPMENT, DUCTWORK, ETC., AND SHALL BE FOLLOWED AS CLOSELY AS THE ACTUAL BUILDING CONSTRUCTION AND THE WORK FROM OTHER TRADES SHALL PERMIT.

CONTRACTOR WILL PROVIDE ALL NECESSARY ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION.

5- DUCT SIZE IS THE SAME AS THE ASOCIATED DIFFUER UNLESS OTHERWISE NOTED (TYP).

GENERAL NOTES:

SHEET NOTES:

C D

2 2

TTD(TYP).

SEE ARCH'L

DWGS.

GRV-1

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M2.2MECHANICAL ROOF

PLAN

SCALE: 1/8" = 1'-0"1 MECHANICAL ROOF PLAN

6"Ø EXHAUST TO BE TERMINATED 24" ABOVE ROOF WITH RAIN CAP. MIN. 10'-0"

AWAY FROM ANY OUTSIDE AIR INTAKE.

8"Ø EXHAUST TO BE TERMINATED 24" ABOVE ROOF WITH RAIN CAP. MIN. 10'-0"

AWAY FROM ANY OUTSIDE AIR INTAKE.

10"Ø EXHAUST TO BE TERMINATED 24" ABOVE ROOF WITH RAIN CAP. MIN. 10'-0"

AWAY FROM ANY OUTSIDE AIR INTAKE.

VENT THROUGH ROOF. SEE PLUMBING DWGS.

1- COORDINATE EXACT LOCATION OF AIR OUTLET WITH ARCH'L DWHS.

2-COORDINATE AIR OUTLETS' LOCATIONS WITH LIGHT FIXTURES AND OTHER DEVICES IN THE CEILING.

GENERAL NOTES:

SHEET NOTES:

T

H

46" MAX.

*46" MAX. IF NOT OVER OBSTRUCTION.

WHEN D>10"-24"MAX, H = 53.5" MAX.

FOR GIVEN DEPTHS:

CORRESPONDING REACH HEIGHTS

WHEN D = 10" OR LESS, H = 48" MAX.

MAXIMUM SIDE REACH OVER OBSTRUCTION

SIDE REACH

FIGURE 11B-5D

34" MAX.

30"

D

24" MAX.

THIS DIAGRAM (SIDE REACH FIGURE 11B-5D) ILLUSTRATES THE

SPECIFIC REQUIREMENTS OF THIS REGULATIONS AND IS

INTENDED ONLY AS AN AID FOR BUILDING DESIGN AND

CONSTRUCTION.

1"

NOTES:

INSIDE BUILDING SHALL BE

SEE DRAWING FOR SIZES.

THE REQUIREMENTS OF SECTION

ALL CONDENSATE DRAIN LINES

INSULATED IN ACCORDANCE WITH

15400, PLUMBING SPECIFICATIONS.

ON THE DRAIN PAN.

THE SAME SIZE AS THE NIPPLE

DRAIN LINE SHALL BE AT LEAST

BRASS CLEANOUT PLUG (THREADED)

UNION

DRAIN PAN

2"PLANS.

OF PIPING, SEE

FOR CONTINUATION

HVAC UNIT

VOLUME DAMPER DETAIL

2SCALE

NOT TO

5SCALE

NOT TO

1SCALE

NOT TO

6SCALE

NOT TO

7SCALE

NOT TO

3SCALE

NOT TO

4SCALE

NOT TO

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE

SIMILAR FOR MULTI-BLADE DAMPERS AND ROUND DAMPERS.

NOTES:

2.

1.

INSULATION

DAMPER BLADE

INSULATION

INSULATION

STAND-OFF

HANDLE WITH

QUADRANT

INSIDE END BEARING

LOCKING

SECTION

HANDLE WITH LOCKING

STIFFEN BLADE AS REQUIRED

SIDE ELEVATION

QUADRANT

DUCT

1/8" CLEARANCE ALL AROUND

OUTSIDE END BEARING

1/2" ROUND ROD PIN

DAMPER BLADE

DUCT

THERMOSTAT HEIGHT DETAIL

REFRIGERANT PIPING THRU WALL DETAIL

SCHEDULE 40 PIPESCHEDULE 40 PIPE

SLEEVE TYPICAL EACH

PIPE THRU WALL

CAULKING MATERIAL PACKED

INSULATION REQUIRED

FOR SUCTION LINE

TIGHTLY AROUND PIPE

TYPICAL

TYPICAL-REFRIGERANT PIPING AND

CONDENSATE PIPING PER PLAN

SEE PLANS FOR SIZES

SECURE TO WALL WITH

POLYURETHANE

(4)1/8"∅ SHOTS EACH

SEALANT- TYPICAL

LIGHT GAUGE FRAMED WALL

18 GA. SST. ESCUTCHEON.

SEE PLANS FOR

LOCATION

FLEXIBLE CONN. TO DIFFUSER DETAIL

CONNECT PLENUM TO CEILING

DIFFUSER WITH SHEET METAL

REFER TO FIG. 2-17 SMACNA

SCREWS, CANVAS & ARABOL-

INSTALL RIGID DUCT FOR ALL EXHAUST REGISTERS.

TYPICAL FOR RETURN REGISTERS.

NOTES:

OR APPROVED EQUAL

1.

2.

FOR PLENUM

DIFFUSER

CEILING

SUPPORT

FULL SIZE OF

LINED PLENUM

18" NO BENDS

FOR CONNECTION

ARABOL SEAL

BAND, CANVAS &

22 GA. PLATE-SAME DIA.

SEE PLANS FOR

DUCT COLLAR WITH DRAW

SQUARE, ROUND OR

RECTANGULAR DUCT

AS FLEXIBLE DUCT-

4'-0" O.C.-SEE PLAN

6"

SIZE

1"

FOR SIZE

CONN. (INSULATED) EQUIV. AREA

TO DUCT SIZE SHOWN-

(MAX. LENGTH 5'-0")

CIRCULAR FLEX DUCT CONNECTOR

SEE SPECIFICATIONS FOR DUCT

SCREWS (2) EACH SIDE

#10x1/2" LONG "TECO"

TO STRUCTURE

CEILING EXHAUST

FAN

FAN

GRILLE

FACTORY SUPPLIED

MOUNTING CLIP SECURED

TO FAN WITH SELF-

TAPPING SMS AND

BLOCKING WITH #10X3/4 SMS

CEILING EXHAUST FAN DETAIL

CEILING

16 GA. BLOCKING ON SIDES (TWO) OF

FAN. SECURE TO CEILING JOISTS W/MIN

2/10 S.M.S. EACH END OF BLOCK.

WALL MOUNTED FAN COIL UNIT DETAIL

INSTALLATION.

CEILING DIFFUSER

OPERATOR

COORDINATE EXACT LOCATION OF CEILING MOUNTED

CONCEALED REGULATOR WITH ARCHITECT PRIOR TO

COVER PLATE

1.

NOTE:

DIE CAST

MOUNTING CUP

SOCKET WRENCH

REGULATOR KIT

CONCEALED

AND WIRE (12'-0"

MAXIMUM)

FLEXIBLE CASING

RACK & PINION

ROUND DAMPER

FLEXIBLE DUCTWORKRIGID DUCTWORK

USE BOWDEN CABLE CONTROL BY " YOUNG REGULATORY COMP."2.

CEILING DIFFUSER

REMOTE VOLUME DAMPER CONTROL

8SCALE

NOT TO

9SCALE

NOT TO

REAR VIEW

UNIT OUTLINE

SECURE

FACTORY

MOUNTING

BRACKET TO

WALL W/ 2-#10

S.M.S. @ EA

CORNER, INTO

BLOCKING

1) VERIFY AND MAINTAIN MANUFACTURERS

RECOMMENCED MINIMUM CLEARANCES.

NOTES:

5" MIN.

6" MIN.

5" MIN.

TOP OF STRUCTURE

FRONT VIEW (MIN. CLEARANCE)

WALL MOUNTED

FAN COIL UNIT

2-#10 S.M.S. @

EA CORNER, INTO

BLOCKING

16GA. METAL STUD

BLOCKING IN EA STUD

BAY BEHIND UNIT

WALL

2) INSULATE BOTH REFRIGERANT LINES.

UNIT

NEOPRENE PAD

(TYPICAL)

6"

CONCRETE

GROUND

SEE ARCHITECTURAL

DRAWINGS

W/ 3/8" DIA. X1-1/2" EMBD HILTI

ANCHOR TO CONCRETE PAD

KWIK BOLT TZ EXPANSION @ 12"O.C.

ICC ESR 1917

HP-1

TYPICAL OF (4)

FLEX CONNECTION

AT DISCHARGE

FLEX CONNECTION AT INLET

FAN COIL UNIT

45°

1/2" HANGER ROD- SECURE

TO SPRING HANGER WITH

DOUBLE NUT & LOCK WASHERS

TYPICAL (4) PLACES

SPING VIBRATION ISOLATOR

BY FAN MANUFACTURER

LOCATION OF VIBRATION

ISOLATORS- TYPICAL

LOCATION OF VIBRATION

ISOLATORS- TYPICAL (4)

EXHAUST FAN

PLAN VIEW

BRACE TYPICAL (2)

LOCATION OF DIAGONAL

DISCHARGE

DUCT

1 1/2"x1 1/2"x16 GAUGE

DIAGONAL BRACE

FCU

FCU

FCU

FCU

FCU

10SCALE

NOT TO

11SCALE

NOT TO

12SCALE

NOT TO

ADD 4 OZ. OIL PER 10' OF PIPING OVER

PIPING PER SPECIFICATIONS.

50' MAXIMUM PIPE RUN. INSULATE

NOTE:

REFRIGERANT PIPING SCHEMATIC DIAGRAM

HP

HARD DRAWN ACR TUBING

SLOPE AT 1/4" PER 10' BACK

TO CONDENSING UNIT. SIZE

PER MFR RECOMMENDATIONS.

RS

SUCTION LINE

ACCUMULATOR

P-TRAP

GLASS

SIGHT

RL

EQUALIZING LINE

OF SUCTION LINE

SHALL BE CONNECTED

IN STRAIGHT SECTION

AFTER THERMAL BULB

PIECE FACTORY

MFR.

EXPANSION

VALVE

CONTROL CIRCUIT

P-TRAP ONE

RL

RS

SOLENOID VALVE

COMPRESSOR

WIRED IN

FCU

DUCTED FAN COIL UNIT DETAIL

CONDENSING UNIT DETAIL

CONDENSATE TRAP DETAIL

CONDENSING

&HP-2

PAD

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M3.1MECHANICAL DETAILS

5/8" 3/8 x

1/2" 1/4 x

1/2" 1/4 x

HP- 2

RXTQ36TAVJ9

KHRP26A22T9KHRP26A22T9

FCU- 7

FXAQ18TAVJU

FCU- 8

FXAQ18TAVJU

HP-2

RXTQ36TAVJ9

RXTQ36TAVJ9

FCU- 7

FXAQ18PVJU

BRC1E73 (1)

FCU- 8

FXAQ18PVJU

BRC1E73 (1)

OUT F1,F2

to centralized controller

L1, L2 16.5A 1ph L1, L2 0.4A 1ph

L1, L2 0.4A 1ph

IN F1,F2 F1,F2

F1,F2

P1,P2

P1,P2

3/4" 1 1/8 x

1/2 x

1/2" 1/4 x

5/8" 3/8 x

1/2" 1/4 x

1/2" 1/4 x

5/8" 3/8 x

5/8" 3/8 x

HP- 1

REYQ120TATJU

BS- 1BS- 1

BS8Q54TVJBS8Q54TVJ

AA

FCU- 1

Comp/Data An...Comp/Data Anly

FXZQ09TAVJUFXZQ09TAVJU

BB

FCU- 2

Encl Offices

FXMQ36PBVJUFXMQ36PBVJU

CC

FCU- 3

RL Encl Offices

FXMQ09PBVJUFXMQ09PBVJU

DD

FCU- 4

Break RoomBreak Room

FXMQ12PBVJUFXMQ12PBVJU

EE

FCU- 5

Tech Cubicle

FXMQ36PBVJU

FF

FCU- 6

ConferenceConference

FXMQ36PBVJU

GG

HH

HP-1

REYQ120TATJU

REYQ120TATJU

BS- 1

BS8Q54TVJ

A B C D E F G H

FCU- 1

FXZQ09TAVJU

BRC1E73 (1)

FCU- 2

FXMQ36PBVJU

BRC1E73 (1)

FCU- 3

FXMQ09PBVJU

BRC1E73 (1)

FCU- 4

FXMQ12PBVJU

BRC1E73 (1)

FCU- 5

FXMQ30PBVJU

BRC1E73 (1)

FCU- 6

FXMQ30PBVJU

BRC1E73 (1)

OUT F1,F2

to centralized controller

L1, L2, L3 43A 3ph L1, L2 0.8A 1ph L1, L2 0.3A 1ph

L1, L2 2.9A 1ph

L1, L2 0.6A 1ph

L1, L2 1.4A 1ph

L1, L2 2.8A 1ph

L1, L2 2.8A 1ph

IN F1,F2

OUT F1,F2

IN F1,F2 F1,F2

F1,F2

F1,F2

F1,F2

F1,F2

F1,F2

P1,P2

P1,P2

P1,P2

P1,P2

P1,P2

P1,P2

4SCALE

NOT TO

HP-2 WIRING DIAGRAM

3SCALE

NOT TO

HP-1 WIRING DIAGRAM 2SCALE

NOT TO

HP-2 REFRIGERANT PIPING DIAGRAM 1SCALE

NOT TO

HP-1 REFRIGERANT PIPING DIAGRAM

IDF Room

Server Room

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

M3.2REFRIGERANT PIPING

AND WIRING

DIAGRAMS

S

ALL PLUMBING PIPING/FITTINGS AND PLUMBING FIXTURES

INTENDED TO CONVEY OR DISPENSE WATER FOR DRINKING OR

COOKING SHALL BE "LEAD FREE" IN COMPLIANCE WITH AB 1953.

CONTRACTOR SHALL PROVIDE CERTIFICATION AS PART OF THE

PLUMBING SUBMITTALS THAT ALL PLUMBING PRODUCTS COMPLY

WITH AB 1953.

EXISTING PIPE ABOVE CEILING

VTR VENT THROUGH ROOF

W T

W/ W/O

W C W C O W H

WEIGHT

WITH OU T

WALL CLEANOUT

WATER HEATER

WATER CLOSET

WITH

FLOOR DRAIN

DIRECTION OF FLOW

BALANCING VALVE

HOSE BIBB

PIPE CONNECTION, TOP

PIPE CONNECTION, BOTTOM

PIPE DROP

UNION

SHEET NOTE DESIGNATION

DOMESTIC HOT WATER P IPING

WALL CLEANOUT

FLOOR CLEAN OUT

GATE VALVE

M ME TE R

PIPE RISE

DOMESTIC COLD WATER PIP ING

CONDENSATE DRAINAGE PIP ING

SOIL OR WASTE PIP ING BELOW FLOOR SLAB

SOIL WASTE PIPING ABOVE FLOOR

SANITARY VENT PIPING

L E G E N D

CD

CEILINGC L G

UNDERWRITER'S LABORATORY

S HO CK A BS OR BE R

TRAP PRIMER VALVE

UNLESS OTHERWISE NOTED

SANITARY VENT PIPING

SOIL OR WASTE PIPING

OVERFLOW DRAINAGE PIP ING

POUNDS PER SQUARE INCH

PRESSURE GAUGE

NORM ALLY CLOSED

PRESSURE DROP

NORMA LLY OPEN

S or W

U R

UL

U G U O N

V

SA

TP

TYP

SQ.FT.

URINAL

U N D E R G R O U N D

TYPICAL

SQUARE FEET

PD

P G

PH

PSI

R W

M A X (N) N C N O No.

OF D

PHASE

RECYCLED WATER

MAXIMUM

N U M B E R

N E W

P O U N D S

GALLON PER FLUSH

INVERT ELEVATION

DOMESTIC HOT WATER P IPING

FLOOR CLEAN OUT

GALLONS PER MINUTE

H W

LBS

I.E.

LAV OR L

IW

GP F

H B

G P M

LAVATORY

INDUSTRIAL WASTE

HOSE BIBB

FD

FLR

FS

GAL

FT

FP

D N

C O

DIA

F C O (E)

FLOOR DRAIN

FL OO R

FLOOR SINK

G A L L O N

FIRE WATER PUMP

FEET

D O W N

CLE AN O U T

DIAMETER

EXISTING

AIR CONDITIONING UNIT

DOMESTIC COLD WATER PIP ING

CONDENSATE DRAIN

B E L O W F L O O R

BALANCING VALVE

ABOVE F INISHED FLOOR

ABBREVIATIONS

AR C H

CFF

C W

C D

BF

BV

AC

AP

AFF

ARCHITECTURAL

ACCESS PANEL

GENERAL NOTES

P-1 PLUMBING FIXTURE IDENTIFICATION

DOMESTIC HOT WATER RETURN

WH

W&V

EQUIPMENT TAG

WASTE AND VENT RISER TAG

VR VENT RISER

T W TEMPERED WATER

OFCI

T W R TEMPERED WATER RETURN

P IPE MATERIAL SCHEDULE

CAST IR

ON SOIL PIPE & FITTING

OR COPPER DWV BRONZE FITTING

COPPER T

YPE L

SIL

VER S

OLDER

COPPER T

YPE L

95/5 S

OLDER

BLACK S

TEEL S

CH 40SPECIFICATION

MATERIA

L

OUTSIDE

OV E R F L O W

STORM &

WASTE &

SERVICE

VENT

DRAIN

W A T E R

INSIDE

(OD)

(SD)

(W) (V)

(DR)

OUTSIDE

INSIDE

OUTSIDE

INSIDE

(IRR)

(CW)(HW) INSIDE

OUTSIDE

"OUTSIDE" COLUMN IS TO 5' -0"

OUT SIDE BLDG. FOR CONT.

NOTE:

SEE CIVIL PLANS AND

COPPER T

YPE "L

" O 2 C

LEAN T

O A

STM

B-819, N

FPA 99, C

GA G

4.1, S

ILVER

SOLDER D

OUBLE W

ALL B

EL. G

RADE

ASTM B

-8

8, B -280 S

ILVER S

OLDER

COPPER T

YPE A

CR "L

" T

O

FOR CW & 5 FT/S FOR HW

7.76 PSI/100FT @ 8 FT/S VEL

RE M A R K S

G C O GRADE CLEANOUT

STORM DRAINSD

WATER SIZE CALCULATION

PIPE SIZE

G P M

FU

VEL(FPS)

LOSS (PSI)

1/2"

COLD WATER SIZING (FLUSH VALVES)

BASED ON 4/PSI/100 & 6 FT./SEC. MAX.

3/4"

1"

1-1/2"

6.0

5.0

2"

6.0

2.7

2-1/2"

6.0

2.2

3"

6.0

1.8

4"

6.0

1.5

PIPE SIZE

G P M

FU

VEL(FPS)

LOSS (PSI)

1/2"

1.5

4.0

4.0

COLD WATER SIZ ING

BASED ON 4/PSI/100 & 6 FT./SEC. MAX.

3/4"

6.0

7.0

4.0

5.0

1"

5.0

5.0

1-1/4"

6.0

5.0

1-1/2"

6.0

4.0

2"

6.0

3.0

2-1/2"

6.0

2.0

3"

6.0

1.8

4"

6.0

1.1

PIPE SIZE

G P M

FU

VEL(FPS)

LOSS (PSI)

1/2"

1.8

2.3

2.7

HOT WATER SIZ ING

BASED ON 5/PSI/100 & 5 FT./SEC. MAX.

3/4"

4.5

2.8

2.7

1"

3.3

2.7

1-1/4"

4.1

2.7

1-1/2"

4.7

2.7

2"

2.2

2-1/2"

1.8

3"

1.4

4"

1.0SOLENOID VALVE

VENT BELOW FLOOR

EXISTING P IPE BELOW GRADE

IN CEILINGI.C.

BE LOW GR AD EB G

BELOW FINISH FLOORBFF

ROOF DRAIN

PRV

R D

PRESSURE REDUCING VALVE

CALGREEN PLUMBING COMPLIANCE

IN ACCORDANCE WITH CAL GREEN REQUIREMENTS, ALL PLUMBING F IXTURES

SHALL COMPLY WITH THE FOLLOWING MINIMUM REQUIREMENTS. NOTE ACTUAL

DESIGN MAY EXCEED THE MINIMUMS NOTED BELOW. SEE PLANS AND

SPECIFICATIONS FOR ACTUAL FIXTURE SPECIFICATIONS.

A. WATER CLOSETS(TOILETS) - THE EFFECTIVE FLUSH VOLUME OF ALL WATER

CLOSETS SHALL NOT EXCEED 1.28 GALLON PER FLUSH.

TANK TYPE: U.S. EPA WATERSENSE TANK-TYPE HIGH EFFICIENCY TOILET

SPECIFICATION.

B. PUBLIC LAVATORY FAUCETS: MAXIMUM FLOW RATE - 0 .5 GPM (1.9L/MIN) ,

ASME A 112,18,1/CSA B125.1

C. URINALS- WALL MOUNTED URINAL- THE EFFECTIV FLUSH VOLUME OF

WALL MOUNTED URINALS SHALL NOT EXCEED 0.125 GALLON PER FLUSH.

THE EFFECTIVE FLUSH VOLUME OF FLOOR MOUNTED OR OTHER URINALS

SHALL NOT EXCEED 0.5 GALLON PER FLUSH.

1.

NOTE:

1. TYPE "K" COPPER PIPE BELOW GROUND WITH PIPE WRAP.

FD C FIRE DEPARTMENT CONNECTION

(RW)

LEAD-FREE NOTE

MANUAL WETTED STAND PIPEM W S P

BEAM PENETRATION

FSFDC

BUILDINGB L D G

FF FINISH FLOOR

FIXTURE

FIXTURE UNIT VALUE (2016 CPC)

W/V

TABLE 702.1

TOTL CW

TABLE A-103.1

CW (3/4 OF

TOTAL CW)

HW(3/4 OF

TOTAL CW)

WATER CLOSET

LAVATORY

SINK

1.5

.75

1,25

.75

1.25

FLOOR SINK 2 0.5 - -

NOTES:

(1) WATER SUPPLY UNIT FIXTURE UNITS ARE BASED ON 2016 CPC, TABLE A-103.1.

(2) DRAINAGE FIXTURE UNITS ARE BASED ON 2016 CPC, TABLE 702.1.

FLOOR DRAIN 2 - - -

DRINKING FOUNTAIN 0.5 0.5 - -

JANITOR SINK 3 1.5 1.25 1.25

HOSE BIBB - 2.5 2.25 -

GENERAL SEISMIC NOTES

MP COMPONENT ANCHORAGE

ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND

INSTALLED PER THE DETAILS ON THE APPROVED CONSTRUCTION DOCUMENTS. WHERE

NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR

BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE

2013 CBC, SECTIONS 1616A.1.18 THROUGH 1616A.1.20 AND 1.26, AND ASCE 7-10 CHAPTER

13, 26 AND 30.

1. ALL PERMANENT EQUIPMENT AND COMPONENTS.

2. TEMPORARY OR MOVEABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED

(e.g.HARDWIRE) TO THE BUILDING UTILITY SUCH AS ELECTRICITY, GAS OR WATER.

3. MOVEABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS

AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY

ATTACHMENTS.

THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS

SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON

PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN

THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.

A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS

LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY

SUPPORT THE COMPONENT.

B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED

SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR

FLOOR OR HUNG FROM A WALL.

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO

COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION

13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2013 CBC, SECTIONS

1616A1.23, 1616A.1.24, 1616A.1.25 AND 1616A.1.26.

COPIES OF THE DRAWINGS AND SPECIFICATION SHALL BE AVAILABLE ON THE JOBSITE

PRIOR TO THE START OF CHANGING AND BRACING OF THE PIPE, DUCTWORK, AND

ELECTRICAL DISTRIBUTION SYSTEMS.

THE STRUCTURAL ENGINEER OF RECORD HAS VERIFIED THE ADEQUACY OF THE

STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. PIPE HANGER SUPPORT

DETAILS HAVE BEEN REVIEWED AND APPROVED BY THE PLUMBING ENGINEER.

1. ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE 2016

CALIFORNIA PLUMBING CODE, 2016 CALIFORNIA BUILDING CODE, NATIONAL FIRE

PROTECTION CODES, BUILDING EDITION DESIGN CRITERIA, AND ALL OTHER LOCAL

APPLICABLE CODES AND REGULATIONS.

2. COORDINATE PLUMBING SYSTEMS WITH WORK OF OTHER TRADES PRIOR TO ANY

FABRICATION OR INSTALLATION. PROVIDE ALL FITTINGS, OFFSETS, AND TRANSITIONS AS

REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

3. COORDINATE LOCATIONS OF ALL ROOF OPENINGS WITH STRUCTURAL, MECHANICAL

AND ARCHITECTURAL PLANS PRIOR TO ANY INSTALLATION.

4. PLATFORMS, CURBS, AND FLASHING FOR PLUMBING EQUIPMENT SHALL BE AS

INDICATED ON THE ARCHITECTURAL PLANS AND METAL BUILDING SYSTEM SHOP

DRAWINGS, UNLESS NOTED OTHERWISE. COORDINATE EXACT SIZES OF REQUIRED

OPENINGS AND SUPPORTS FOR FURNISHED EQUIPMENT.

5. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT

MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL

FITTINGS, TRANSITIONS, VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE

WORKABLE INSTALLATION.

6. MAINTENANCE LABEL SHALL BE AFFIXED TO ALL PLUMBING EQUIPMENT AND A

MAINTENANCE MANUAL SHALL BE PROVIDED TO GOVERNMENT'S REP.

7. PIPES SHALL BE SUPPORTED AND BRACED PER STRUCTURAL ENGINEER APPROVED

DETAIL.

8. HORIZONTAL PIPING THRU METAL STUDS IS PROHIBITED.

9. WATER PIPING SHALL BE TYPE "L" HARD DRAWN COPPER.

10. SOIL, WASTE, DRAIN, AND VENT PIPING BELOW AND INSIDE BUILDING, USE NO HUB CAST

IRON PIPE WITH 24 GA. STAINLESS STEEL COUPLING AND NEOPRENE GASKETS.

11. INSTALL DIELECTRIC FITTING BETWEEN FERROUS AND NON-FEROUS MATERIALS.

12. PROVIDE STOP VALVES IN EACH WATER SUPPLY AT EACH PLUMBING FIXTURE.

13. HORIZONTAL WASTE PIPING SHALL HAVE MINIMUM SLOPE OF (1/4" PER FOOT AND 1/8"

PER FOOT FOR STORM DRAIN) UNLESS NOTED OTHERWISE ON THE PLANS.

14. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF PLUMBING FIXTURES.

15. VENT PIPE SHALL TERMINATE VERTICALLY NOT LESS THAN 6 INCHES ABOVE ROOF NOR

12 INCHES FROM ANY VERTICAL SURFACES. EACH VENT SHALL TERMINATE NOT LESS

THAN 10 FEET FROM OR AT LEAST 3 FEET ABOVE ANY OPERABLE WINDOW, DOOR,

OPENING AIR INTAKE, OR VENT SHAFT.

16. INSULATE ALL HOT WATER SUPPLY PIPING TO RUN-OUTS IN WALLS.

17. PIPE PROTECTION: PENETRATION OF RATED ASSEMBLIES SHALL BE FIRE STOPPED.

18. PROVIDE U.L. LISTED FIRE RATED "MOLDABLE PUTTY" AND/OR CAULKING AROUND

RECESSED VALVE BOXES IN RATED WALLS OR CEILING, AS REQUIRED BY CODE.

19. FLUSH VALVE FOR ACCESSIBLE WATER CLOSET FLUSH MECHANISM SHALL BE

PROVIDED ON THE OPEN SIDE OF STALL.

20. PROVIDE ADA COMPLIANT COVERS OVER P-TRAP AND WATER SUPPLY LINES AND STOPS

AT ALL LAVATORIES AND OTHER ADA SINKS "TRAP WRAP" INSULATION KIT BY

BROCAR-PRODUCTS INC.

21. ALL SERVICE SHUT-DOWN AND START-UPS SHALL BE SCHEDULED IN ADVANCE AND

SUPERVISED OR PERFORMED BY FACILITY MANAGEMENT STAFF.

22. ALL WORK IN OCCUPIED AREAS SHALL BE SCHEDULED DURING OFF-HOURS AND

COORDINATED WITH THE FACILITY, SO THAT SUCH WORK IS COMPLETED, AREA

CLEANED AND ALL SERVICES RESTORED AND CODE COMPLAINT PRIOR TO RETURNING

TO NORMAL FACILITY OPERATION HOURS.

23. PLUMBING FIXTURES AND FITTINGS SHALL COMPLY WITH CALGREEN TABLE 5.303.6.

24. TRAP PRIMER SYSTEM SHALL CONSIST OF A STAINLESS STEEL SERVICE ACCESS PANEL,

12"X12", BRONZE LEAD-FREE BALL VALVE UPSTREAM AND A COPPER X FIP (FEMALE IRON

PIPE) UNION DOWN STREAM. BRONZE BALL VALVE SHALL BE MANUFACTURED BY NIBCO

OR APPROVED EQUAL.

25. PROVIDE ISOLATION VALVE W/AP FOR ALL FIXTURES FOR SERVICE & MAINTENANCE.

26. ALL CLEANOUTS SHALL BE ACCESSIBLE FOR REGULAR MAINTENANCE.

27. THE AVAILABLE WATER PRESSURE IS IN THE RANGE OF 120-125 PSI. DOMESTIC WATER SYSTEM PRESSURE SHALL BE LIMITED TO 65 PSI THROUGH AN EXISTING PRESSURE REDUCING STATION

ON THE EXISTING INCOMING COLD WATER MAIN. EXISTING PRESSURE REDUCING STATION TO

REMAIN AS IS.

28. WATER FLOW VELOCITY: TO AVOID ANY EROSION, CORROSION AND EXCESSIVE NOISE

GENERATION, THE DOMESTIC COLD WATER PIPING SHALL BE SIZED FOR A MAXIMUM FLOW

VELOCITY OF 4 FEET PER SECOND (FPS) FOR PIPES TWO INCHES AND SMALLER; AND 6 FEET PER

SECOND (FPS) FOR LARGER PIPES.

EXISTING PIPE TO BE REMOVED

PIPE>4"GRAVITY @ 2% STANDARD FOR

PIPE<4" 4"GRAVITY @ 1%

1.5"/HR RAIN FALL. 3"/HR RAINFALL FOR

COMBINED SYSTEM. 1% SLOPE

FIRE SPRINKLER FIRE DEPARTMENT

CONNECTION

PIP ING CAPPED FOR FUTURE

CONNECTION

OWNER FURNISH ED CONTRACTOR

INSTALLED

URINAL 2 3 - -

PIPE SIZE

INSULATION

THICKNESS

1/2"

1"

PIPE INSULATION PER 2016 CPC 609.11 & T-24

3/4"

1"

1"

1-1/2"

1-1/4" 1-1/2" 2"

2"

2-1/2"

2"

3" 4" 5" 6"

1-1/2" 1-1/2" 2" 2" 2" 2"

PIPE SIZE VERTICAL

TABLE 702.1

HORIZONTAL

1/4" SLOPE

HORIZONTAL

1/8" SLOPE

NA

NA

172.8

48 35 NA

600 428 342.8

1380 720 576

3600 2640 2112

5600 4680 3744

8400 8200 6560

MAXIMUM DRAINAGE F IXTURE UNITS ALLOWED FOR

EACH SIZE OF PIPE PER CPC 2016

2"

2-1/2"

3"

4"

5"

6"

8"

10"

12"

NOTES:

1- DRAINAGE FIXTURE UNITS ARE BASED ON 2016 CPC, TABLE 703.2.

2- VENT FIXTURE UNITS AND LENGTH ARE BASED ON 2016 TABLE 703.2 . NOT TO

EXCEED ONE-THIRD OF THE TOTAL PERMITTED LENGTH OF A VENT SHALL

PERMITTED TO BE INSTALLED IN A HORIZONTAL POSITION. WHERE VENTS ARE

INCREASED ONE PIPE SIZE FOR THEIR ENTIRE LENGTH, THE MAXIMUM LENGTH

LIMITATION SPECIFIED IN THIS TABLE DO NOT APPLY.

VENT PIPING

MAX. UNIT / MAX. LENGTH - FEET

24/120

256/300

84/21

600/390

1380/510

3600/750

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECTONICS

SUSTAINABLE AGRICULTURAL WATER

SYSTEM RESEARCH UNIT

UC DAVIS, CA

Architects Planners Engineers 1500 Park Ave

EMERYVILLE, CA 94608

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER EPM

A D

USDA S

U

NO. DATE BY

SHEET OF

REVISIONS

DESCRIPTION

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET CONTENTS

UNITED STATES

DEPARTMENT OF

AGRICULTURE

07/15/2019

A - E FIRM

BID SET SUBMITTAL

P0.1PLUMBING LEGEND,

ABBREVIATIONS, AND

GENRAL NOTES

PLUMBING SHEET INDEX

Sheet Number Sheet Name

P0.1 PLUMBING LEGEND, ABBREVIATIONS,

AND GENRAL NOTES

P0.2 PLUMBING SCHEDULES

P2.1 PLUMBING FLOOR PLAN

P3.1 PLUMBING RISER DIAGRAMS

P4.1 PLUMBING DETAIL

BRADLEY MODEL S 59-400 W/ INTEGRAL CHECK

VALVE AND STRAINER. PROVIDE AT EACH FIXTURE

SET AT 95°.

VENT

PLUMBING F IXTURE AND CONNECTION SCHEDULE

FLOOR CLEAN OUTFCO-1 -

WA S T E TRAP

C W H W

J.R. SMITH FLOOR CLEANOUT, MODEL 4020

DIR. INDIR.CAP(MBH) CONN.

-TRAP PRIMERTP-1 - 1/2" -

-4"

J.R. SMITH 2699 ANSI-112.26, CAST BRONZE

WITH 1/2"CONNECTION

1- ALL HOT WATER AND DRAIN PIPES SHALL BE INSULATED.

2- THERE SHALL BE NO SHARP OR ABRASIVE SURFACE UNDER

LAVATORIES/SINKS.

3- FORCE TO ACTIVATE FAUCET CONTROLS SHALL BE NO GREATER

THAN 5 LBS.

4- REPLACE FAUCET AERATOR WITH AERATOR PROVIDED BY

CHRONOMITE FOR FAUCET WITH CHRONOMITE INSTANTANEOUS

ELECTRIC WATER HEATER.

RE M A R K S

WALL CLEANOUTWCO-1 - -J.R. SMITH MODEL 4420 -4"

- - SEE PLAN FOR PIPE SIZE

WAT E R H AM M E RWHA-1 J.R. SMITH MODEL 5005 WATER HAMMER

ARRESTOR. INSTALL PER MANUFACTURE'S

RECOMMENDATION.

--- - -- -AR R E S T O R

-- 3/4" -- -

PROVIDE WITH VACUUM

BREA KER

INDUST.

WA S T E

FD-1 FLOOR DRAIN

ZURN MODEL Z415B FLOOR DRAIN, DURA-COATED

CAST IRON WITH BOTTOM OUTLET, -- 1/2" -- 2" --

JS-1

URINAL WALL HUNGUR-1 TOTO HIGH EFFICIENCY URINAL (TOP SPUD).

SLOAN 186-0.125 MANUAL FLUSH VALVE 0.125 GPF.

WATTS CA-321 CARRIER MOUNTED PER ADA

REQUIREMENTS.

1-1/2"1-1/2"- 3/4" -- 2"-

1-1/2"

LAVATORY - WALL

L-1 1-1/2"- 1/2" 1/2"- - 2"

MOU NT-ADU LT

WALL HUNG LAVATORY TOTO, MODEL TL307(A) WITH

SINGLE HOLE FOR FAUCET. FAUCET TOTO MODEL HELIX

ECO POWERED SENSORED FAUCET TEL115-D10#CP,

WITH 0.35 GPM AERATOR. WATTS TCA-411 CARRIER,

DEARBORN BRASS 704-1 P-TRAP, TOTO THP5067#CP

GRID DRAIN, TRUEBRO LAV GUARD #101-F-7.

ADA HEIGHT

- - - 3" - - 2" 1/2" -

2"- 1" -INT.- - 4"TOTO MODEL CT705ULNGX VITREOUS CHINA, 1 .0 GPF,

ELONGATED BOWL WITH TOTO FLUSH VALVE MODEL

TET1UAX32#CP. ADA-HEIGHT.

TMV-1 THERMOSTATIC MIX ING

VALVE 1/2"1/2"

ADA HEIGHT

JANITOR SINK

FL O O R M O U N T E D 1/2"

C O D E

EWH-1

LOCATION

B O C K

M A N UF A C TU R E R

NO.

M O D E L G A L L O N

CAPACITY

K W

ELECTRIC

VOLT PHASE

RE M A R K SWEIGHT

LBS

MECH. ROOM 50F 50 9 208 3 535 FLOOR MOUNT

M A N UF A C TU R E R

NEAR WATER HEATERET-1

C O D E LOCATION

CAPACITY

GA LL ON S

PTA-5BELL & GOSSETT 2.1

M O D E L

NO. PRE-CHARGE

AIR

RE M A R K S

NOTES:

1- INSTALL ON HOLDRITE DRAIN PAN MODEL QP AND 30" FLOOR MOUNT QUICK STAND MODEL 40-S-30 PAN AND STAND SIZE TO MATCH WATER HEATER

SIZE.

2- SET TEMPERATURE FOR 120°F. TERMINATE RELIEFE DRAIN AND PAN DRAIN OVER JANITOR SINK.

1/2" TP

C O D E

WC-1 WATER CLOSET

FL O O R M O U N T

FLUSH VALVE - ADA

DESCRIPTION M O D E L GAS

ELECTRIC WATER HEATER SCHEDULE

EXPANSION TANK SCHEDULE

2"- 1" -INT.- - 4"SAME AS WC-1, EXCEPT IS NON-ADA HEIGHT

WC-2 WATER CLOSET

FL O O R M O U N T

FLUSH VALVE

HB-2

WOODFORD MODEL B75 WALL BOX SERIES

WITH INTEGRAL VACUUM BREAKER & HOSE

THREADED NOZZLE

EXTERIOR

WALL HOSE BIBB

HB-1 WOODFORD MODEL 24 SERIES WITH INTEGRAL

VACUUM BREAKER & HOSE THREADED NOZZLE

INTERIOR

HOSE BIBB

-- 3/4" -- -

PROVIDE WITH VACUUM

BREA KER-- -

SK-1 1-1/2"1-1/2"- 1/2" 1/2"- - 2" BREAK ROOM SINK

ELKAY MODEL LRAD 191855(19"X18"X5-1/2" DEEP)

STAINLESS STEEL 18 GAUGE, SINGLE HOLE

CENTERED

WITH FAUCET CHICAGO ELECTRONIC EBPS SENSOR

OPERATED FAUCET, MODEL 116.683.AB.1. PROVIDE

PLUG-IN S INGLE USE CLASS 2A TRANSFORMER FOR

DUAL POWER. 120V HARDWIRED NORMAL POWER

AND BATTERY BACK UP FOR SECONDARY SOURCE

OF POWER. PROVIDE ALL NECESSARY PARTS FOR

DUAL POWER OPERATION. PROVIDE WITH

NON-AERATOR LAMINAR FLOW. SEE ARCH'L DWGS.

FOR MOUNTING HEIGHT. PROVIDE WITH MIXING

VALVE.

COUNTER MOUNT

Exp.06/30/21

I

L

No. M33664

I

CINHC

EM

SSEFORP

ACFO

ET

DERETSI

GE R

AT

S

ASALHA

HS A

LA

RE

EN

I

GN

E

LA

NO

AINROFI

I

ND

I

A

TECT…