USDA_ARS_SAWSRU_Davis_100__Bid_Set_Drawings_20190715_-_Full_Sized_-_2.pdf
PDF 12 MB Posted
- Attached to
- Davis Watershed Project Federal contract opportunity
- Solicitation number
- Not on record
About this file
Drawings 2
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Question_correction_&_additional_information.pdf | ||
| Questions__2.pdf | ||
| Question_Answers__1.docx | DOCX document | |
| Contractor_Certification_Regarding_EMR.pdf | ||
| Addendum_SOW_-Water_Mgmt_Unit-_UC_Davis_revised.pdf | ||
| Contractor_Calculation_of_Self-Performed_Work.xlsx | XLSX spreadsheet | |
| Past_Performance_Capability_Information.docx | DOCX document | |
| RFI_FORM.pdf | ||
| 12905B19R0032.pdf | ||
| ars372.pdf | ||
| USDA_ARS_SAWSRU_Davis_100__Bid_Set_Specifications_Rev1_20190715_COR_3.pdf | ||
| ars371.pdf | ||
| USDA_ARS_SAWSRU_Davis_100__Bid_Set_Drawings_20190715_-_Full_Sized_-_1.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOTTOM OF TRENCH EXCAVATION
SHALL NOT EXTEND BELOW THIS LINE
NOTE:
THE CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING,
SHEATHING OR OTHERWISE MAINTAINING THE SIDES OF
THE EXCAVATION FROM CAVE-INS UNTIL ALL BACKFILL
IS COMPLETED PER SPECIFICATIONS
COMPACTED
FILL 90%
DENSITY
BACKFILL
PER SPECS.
10'-0" MIN.
EXCAVATION
TRENCH
WIDTH
FOOTING
MIN.
1'-6"
NOTES:
1. FOR PIPES & CONDUITS 3'-0" OR LESS BELOW FTG, PROVIDE SLEEVES & CONC AS
SHOWN. MORE THAN 3'-0", COMPACT BACKFILL O/ PIPES & CONDUITS TO 90% AS
APPROVED BY SOILS ENGINEER.
2. CONDUITS & PIPES MAY NOT UNDER ANY CIRCUMSTANCES, RUN PARALLEL TO & WITHIN
FTGS. SKEWED CROSSINGS OF CONDUITS & PIPES THRU FTGS ARE PROHIBITED.
3. PIPES OR CONDUITS 4" DIA. MAY CROSS AT 90° IN PLAN THRU FTGS SUBJECT TO
SPACINGS SHOWN IN DETAIL & AT MIDDLE 1/3 DEPTH OF FTG.
PIPE THRU
FDN WALL
B.O. FTG.
D
"D"+ 1'-6"
S
EE
N O
TE
S
TH
A N
O .D O F P
IP
ES
S
LE
EV
ES
LA
R G
ER
S
EE
N O
TE
M A X
(2) #5 T&B EXTEND
BARS INTO FOOTING
2'-0" W/ BENT END
CONCRETE SLAB ON GRADE
1'-3"
1'-0"
#4 TIES @ 12" O.C.
FOOTING SCHEDULE
MARK
FOOTING SIZE REINFORCING
REMARKSLENGTH
B t
THICK. b
BARS
aWIDTH
A BARS
NOTE:
1. a AND b BARS ARE BOTT BARS TYP U.O.N. SEE FOOTING DETAIL 6/S1.3
2. "a" BARS PARALLEL TO TRANSVERSE (SHORT) DIRECTION
"b" BARS PARALLEL TO LONGITUDINAL (LONG) DIRECTION
3. SEE TYP WALL FTG DETAIL 8/S1.4
NOTE 1 TYPICAL
3-#6 COLUMN FOOTING3'-0" 3'-0" 2'-0" 3-#6
3-#5 COLUMN FOOTING2'-0" 2'-0" 3-#52'-0"
F3
F2
5-#6 COLUMN FOOTING5'-0" 5'-0" 2'-0" 5-#6
4-#6 COLUMN FOOTING4'-0" 4'-0" 4-#62'-0"
F5
F4
S THIS POINT SHOWN
ON PLAN THUS
TOP REINF WHERE OCCURSREINFORCING
SHALL MATCH
CONT BARS IN
SIZE & NUMBER
2'0" MIN
2 "H" OR
M A X
"H
2'-0" MIN
2 "H" OR
D
EP
TH
"D
FO
O
TI
N G
SPLICE
HORIZ LAP
"D" MIN
3" MIN BAR COVERAGE TYP.
LAP SPLICE
HORIZ
PEB FOOTING PER PLAN
PEB COL PER PEB DRAWINGS
S.O.G. SEE PLAN
TIE BEAM
#5 @ 18" O.C. E.W.#5 @ 18" O.C. E.W.
FINISHES, S.A.D.
3" CLEAR, TYP
PER PLAN & SCHEDULE 4/1.3
FOOTING WIDTH (A)
EDGE OF
BLDG SLAB
CL OF BASE PLATE & FOOTING
FOOTING
THICKNESS (t), PER PLAN &
SCHEDULE
FINISH GRADE OR
SURFACE, S.C.D.
'a' BARS
'b' BARS
SEE P.E.B. MFR
DWGS FOR A.B. DIA.
#3 TIES @ 3" O.C.
P
LA
N
P
ER
3"
N.T.S. S1.3
1EXCAVATIONS PARALLEL TO FOOTING
N.T.S. S1.3
2PIPE & CONDUITS PERPENDICULAR TO FTG
N.T.S. S1.3
3TIE BEAM DETAIL
N.T.S. S1.3
4FOOTING SCHEDULE
N.T.S. S1.3
5STEPPED FOOTING OR GRADE BEAM DETAIL
N.T.S. S1.3
6PEB FOOTING
GN
A
No. S4485
S
ET
AT
FO
Exp.
FILAC
I
RO
N
E
ER
T
IGER
S
NIOO SEF SR
D
P A
E
L
I
RE
EN
6/30/20
STRUCTURA
L
M I C
HA
EL J .
RO
S S
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
23'-8" 20'-3 1/2" 23'-8"
1'-1" FACE OF STEEL, TYP
1'-8"1'-8"
3 TYP
S1.3S2.1
6 TYP
S1.3S2.1
8 TYP
S1.2S2.1
GN
A
No. S4485
S
ET
AT
FO
Exp.
FILAC
I
RO
N
E
ER
T
IGER
S
NIOO SEF SR
D
P A
E
L
I
RE
EN
6/30/20
STRUCTURA
L
M I C
HA
EL J .
RO
S S
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
1/4" = 1'-0" S2.1
FOUNDATION PLAN 1
5" CONC SLAB ON GRADE W/
#4 @ 18" O.C. EW @ MID-
DEPTH O/ 15-MIL MOISTURE
BARRIER, O/ 4"-3/4"
CRUSHED ROCK (W/ 100%
PASSING A NO. 4 SIEVE. SEE
THE SOILS REPORT FOR MORE
SUB-SLAB PREPARATION
F3F4F4F3
F3F4F4F3
TYP
12"x15"
NORTH
DSD
(UNDER DIVISION 16)
DUCT MOUNTED SM OKE DETECTOR
ROOM TEMPERAT URE SENSOR
DOOR LOUVER (UNDER DOOR SECTION)
UNDERCUT DOOR (UNDER DOOR SECTION)
EQUIPMENT IDENTIFICATION: TYPE-NUMBER
U/C
D/L
EF
ACCESS PANELAP
EF-1
REF
PSIG
RA
QTY.
P.D.
POUNDS PER SQUARE INCH GAUGE
REFER ENCE
RETURN AIR
QUANTITY
PRESSURE DROP
FSD COMBINATION SMOKE & F IRE DAMPER
ROUND DUCT OR STACK - SECTION
ABBREV.
MECHANICAL SYMBOLS
S Y M B O L DESCRIPTION
POINT OF CONNECTION
POINT OF DISCONNECTION
P O C
P O D
ESP EXTERNAL STATIC PRESSURE
TYPICAL
TOTAL STATIC PRESSURE
UNLESS OT HERWISE NOTED
TYP
U O N
TSP
REVOLUTIONS PER MINUTER P M
VENT THROUGH ROOF
UP THROUGH ROOF
VT R
UTR
EFF
EA
D W G
EFFICIENCY
EXHAUST AIR
DRA WI NG
DEFL DEFLECTION
BUTTERFLY VALVE
CIRCUIT SETTER
CHECK VALVE
SAFETY OR RELIEF VALVERV
CH V
BALL VALVE
GATE VALVE
ABBREV.
MECHANICAL SYMBOLS
S Y M B O L DESCRIPTION
2-WAY ON/OFF VALVE
PRESSURE & TEMPERATURE TEST PLUG
EXPANSION JOINT 2 ' MINIMUM MOVEMENT
A N C H O R
PTTP
STRAINER
TEMPERAT URE GAGE
PRESSURE GAGE WITH COCK
2-WAY MODULATING VALVE
AUTOMATIC FLOW CONTROL VALVEAFV
MANUAL AIR VENTMAV
AUTOMATIC AIR VENTAAV
N C
M B H
LPS
THOUSAND BT U PER HOUR
NOISE CRITERIA
LOW PRESSURE STEAM
IN.W.C.
HZ
HP
H C
INCH WATER COL UMN
HERT Z
HEATING COIL
H O R S E P O W E R
FD FIRE DAMPER
(E) EXISTING
CWS
CWR
CONDENSOR WATER SUPPLY
CONDENSOR W ATER RETURN
ABOVE FINISHED FLOOR
ACCESS PANEL
BRITISH THERMAL UNIT PER HOURBT U H
AP
AFF
ABBREVIATIONS
ABBREV. DESCRIPT ION
D B
CV
DRY-BUL B
CONSTANT VOLUME
GENERAL SEISMIC NOTES
MEP COMPONEN T ANCH ORAGE
ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND
INSTALLED PER STRUCTURAL DETAILS ON THE CONSTRUCTION DOCUMENTS. WHERE NO
DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO
MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC,
SECTIONS 1616A.1.18 THROUGH 1616A.1 .26 AND ASCE 7-10 CHAPTER 13, 26 AND 30.
1 . ALL PERMANENT EQUIPMENT AND COMPONENTS.
2 . TEMPORARY OR MOVEABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (e .g .HARD WIRE)
TO THE BUILDING UTILITY SUCH AS ELECTRICITY, GAS OR WATER.
3 . MOVEABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND
HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY
ATTACHMENTS. THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL
COMPONENTS SHALL BE POSIT IVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE
DETAILED ON PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED
BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, P IPING, AND CONDUIT.
A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED
4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE
COMPON ENT.
B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED
SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR
OR HUNG FROM A WALL.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE
INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF
RECORD. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT
HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY
WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13 .3 AS DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2016 CBC, SECTIONS 1616A1.23, 1616A.1.24, 1616A.1.25 AND 1616A.1.26.
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF
CHANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE
TO SUPPORT THE HANGER AND BRACE LOADS. RELOCATED UNIT(RL)
REMOVE AND RELOCATE EQUIPMENT(RR)
LBS P O U N D S
3-WAY ON/OFF VALVE
3-WAY MODULATING VALVE
GENERAL NOTES
CALGREEN HVAC COMPLIANCE
1. HVAC SYSTEM INSTALLERS SHALL BE TRAINED AND CERTIF IED IN THE PROPER
INSTALLATION OF HVAC SYSTEMS.
2. PROVIDE DOCUMENTATION TO SHOW COMPLIANCE WIT H CONSTRUCTION
DOCUMENTS, PLANS, INSTALLER CERTIFICATIONS, INSPECTION REPORTS, TO
DEMONSTRATE SUBSTANTIAL CONFORMANCE, WHEN SPECIF IC DOCUMENTATION OR
SPECIAL INSPECTION IS NECESSARY TO VERIFY COMPLIANCE, THAT METHOD OF
COMPLIANCE WILL BE SPECIFIED IN THE APPROPRIATE SECTION OR IDENTIF IED IN THE
APPLICATION CHECKLIST.
3. AABC COMPLIANCE: COMPLY WITH AABC'S MANUAL MN_1 "AABC NATIONAL
STANDARDS". AS APPLICABLE TO MECHANICAL AIR DISTRIBUTION SYSTEMS AND
ASSOCIATED, DEVELOP A WRITTEN PLAN OF PROCEDURES TO BE INCLUDED FOR
TESTING AND BALANCING. SUBMIT CERTIFIED TEST REPORTS SIGNED BY THE TEST
AND BALANCE SUPERVISOR WHO PERFORMED TESTING AND BALANCING WORK.
PROVIDE A COPY OF THE FINAL TEST REPORT TO THE ENFORCING AGENCY.
4. PROVIDE VENTILATION DURING CONSTRUCTION THRU OPENING IN THE BUILDING
SHELL USING TEMPORARY FANS TO PRODUCE A MINIMUM OF 3 AIR CHANGES PER
HOUR. DO NOT USE THE PERMANENT HVAC EQUIPMENT FOR THIS
PURPOSE.
5. COVER ALL DUCT OPENINGS WITH SHEET METAL OR PLASTIC DURING CONSTRUCTION
TO REDUCE DUST AND DEBRIS IN
DUC TW OR K.
6. ALL AIR FILTERS SHALL BE MINIMUM MERV 8 . A HIGHER MERV RATING MAY BE
REQUIRED ON SCHEDUL ES OR
SPECIF ICATIONS.
7. NO HVAC REF RIGERANT SYST EM USING HYDROCHOROFL UOROCARBONS SHALL BE
USED ON THE
PROJECT.
8. PROVIDE THE BUILDING OWNER WITH DETAILED OPERATION AND MAINTENANCE
INSTRUCTIONS AND COPIES OF GUARANTEES/WARRANTIES FOR EACH SYSTEM PRIOR
TO FINAL
INSPECTION.
1. ALL WORK SHALL CONFORM TO TITLE-24, CALIFORNIA CODE OF REGULATIONS(CCR) .
2. SEAL ALL OPENING AROUND PIPING AND DUCTWORK PENETRATING FIRE RESISTIVE
RATED WALLS AND FLOORS TO MAINTAIN RATING INTEGRITY.
3. PROVIDE ACCESS DOOR FOR ALL EQUIPMENT, VALVES AND CLEAN OUTS WHICH
REQUIRE ACCESS FOR ADJUSTMENT OR SERVICING, AND WHICH ARE LOCATED IN
OTHERWISE INACCESSIBLE LOCATIONS, PERMIT MAINTENANCE AND ADJUSTMENT OF
THE DEVICE.
4. PROVIDE 120V RECEPTACLE WITHIN 25 FT OF EQUIPMENT.
5. PITCH PIPELINES AS REQUIRED FOR PROPER DRAINAGE AND ELIMINATION OF AIR.
6. INSTALL ALL EQUIPMENT LEVEL AND PLUMB. PROVIDE BLOCKING AND HARDWARE AS
REQUIRED.
7. MANUFACTURERS NAMES FOR PRODUCTS L ISTED ON DRAWINGS ARE BASIS OF
DESIGN. SEE SPECIFICATIONS FOR EQUIVALENT MANUFACTURERS.
8. THE PROJECT DESIGN SHOWN ON THE DRAWINGS AND SPECIFIC ITEMS REFERENCED
IN THE SPECIFICATIONS IS IN COMPLIANCE WITH THE CODE AND ORDINANCES LISTED
IN DIVISION 23 OF SPECIFICATIONS.
9. PROVIDE SEISMIC ANCHORAGE AND BRACING FOR MECHANICAL EQUIPMENT, P IPING
AND DUCTWORK. SEE "GENERAL SEISMIC NOTES" FOR DETAIL REQUIREMENTS.
10. PROVIDE HANGER, SUPPORTS AND SWAY BRACES FOR ALL DUCTWORK, P IPING AND
EQUIPMENT AS REQUIRED BY THE LATEST EDITION OF THE SMANCA GUIDELINES.
11. INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER
RECOMMENDATION UNLESS SPECIF ICALLY INDICATED OTHERWISE OR WHERE THE
LOCAL CODES OR REGULATIONS TAKE PRECEDENCE.
12. PREPARE SHOP DRAWINGS FOR INSTALLATION OF ALL NEW WORK BEFORE
INSTALLATION TO VERIFY COORDINATION BETWEEN TRADES.
13. KEEP CUTTING TO THE MINIMUM REQUIRED FOR PROPER EXECUTION OF WORK. BE
RESPONSIBLE FOR ALL CUTTING AND PATCHING NECESSARY FOR THE COMPLETION
OF WORK. NO CUTTING SHALL BE PERFORMED WITHOUT THE APPROVAL OF THE
ARCHITECT.
14. PROVIDE OFFSETS, ELBOWS AND TRANSITIONS IN DUCTWORK AND PIPING AS
REQUIRED AT NO ADDITIONAL COST TO THE OWNER. VERIFY ALL CONNECTIONS WITH
MANUFACTURER'S CERTIFIED DRAWINGS. PROVIDE TRANSITION FOR FINAL
CONNECTION TO EQUIPMENT. F IELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION
OF
WORK .
15. ALL WORK AND MATERIAL SHALL BE IN COMPLIANCE WITH THE SPECIFICATIONS. IN
THE EVENT OF CONFLICT BETWEEN THE CONTRACT DRAWINGS AND THE
SPECIFICATIONS THE MOST STRINGER SHALL GOVERN.
16. INSTALL ALL PIPING AND DUCTWORK TO BEST SUIT F ILED CONDITIONS AND
COORDINATE WITH OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC AND SHALL
NOT BE SCALED TO DETERMINE THE EXACT LOCATION OF THE PIPING OR
DUC TW OR K.
17. DUCTS AND EQUIPMENTS STORED ON THE CONSTRUCTION S ITE SHALL BE
PROTECTED AND ISOLATED FROM DUST CONTAMINATION.
18. ALL DUCTWORK SHALL BE SEISMICALLY SUPPORTED PER SMACNA DUCTWORK
CONSTRU CTION
GUIDELINES.
19. ALL SIZES ARE IN INCH, U.O.N.
20. OUTSIDE OR RETURN AIR FOR A HEATING OR COOLING SYSTEM SHALL NOT BE TAKEN
FROM LESS THAN 10 FEET IN DISTANCE FROM AN APPLIANCE VENT OUTLET, VENT
OPENING OF A PLUMBING DRAINAGE SYSTEM, DISCHARGE OUTLET OF AN EXHAUST
FAN, UNLESS THE OUTLET IS 3 FEET ABOVE THE OUTSIDE AIR INLET. ALSO, THE
OUTSIDE OR RETURN AIR SHALL NOT BE TAKEN FROM LESS THAN 10 FEET ABOVE
THE SURFACE OF AN ABUTTING PUBLIC WAY, SIDEWALK, STREET, ALLEY, OR
DRIVEWAY, PER 2016 CMC SECTION 311.3 .
21. ENVIRONMENTAL AIR DUCT EXHAUST SHALL TERMINATE NOT LESS THAN 3 FEET
FROM A PROPERTY LINE, 10 FEET FROM A FORCED AIR INLET, AND 3 FEET FROM
OPENINGS INTO THE BUILDING. ENVIRON MENTAL EXHAUST DUCTS SHALL NOT
DISCHARGE ONTO A PUBLIC WALKWAY, PER 2016 CMC SECTION 502 .2.1 .
EXISTING PIPE OR EQUIPMENT TO REMAIN
(N) N E W W O R K
(R) EXIST ING WORK TO BE REMOVED
N E W W O R K
P U M P
CEILING DIFFUSER SUPPLY
CEILING GRILLE EXHAUST
CEILING GRILLE RETURN
(ER) EXISTING TO RELOCATE
VOLUME DAMPERVD
GENERAL NOTES (CONTINUED)
22. DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE VAPORS, FUMES, OR DUSTS SHALL
TERMINATE NOT LESS THAN 30 FEET FROM A PROPERTY LINE, 10 FEET FROM
OPENINGS INTO THE BUILDING, 6 FEET FROM EXTERIOR WALLS OR ROOFS, 30 FEET
FROM COMBUSTIBLE WALLS OR OPENINGS INTO THE BUILDING THAT ARE IN THE
DIRECTION OF THE EXHAUST DISCHARGE AND 10 FEET ABOVE THE ADJOINING GRADE,
PER 2016 CMC SECTION 502.2.2.
23. CONTRACTOR TO FOLLOW BASIS OF DESIGN REQUIREMENTS BASED ON DAVIS DESIGN
CONDITION.
24. CONTRACTOR TO FOLLOW ALL MECHANICAL COMMISSIONING REQUIREMENTS PER UC
DAVIS CAMPUS DESIGN GUIDE, PART IV STANDARD SPECIF ICATION.
APPLIED BUILDING CODES:
2016 CALIFORNIA MECHANICAL CODE (CMC)
2016 CALIFORNIA PLUMBING CODE (CPC)
2016 CALIFORNIA ELECTRICAL CODE (CEC)
2016 CALIFORNIA ENERGY CODE
2016 CALIFORNIA BUILDING CODE (CBC)
ACCESSIBILITY CODE-2016 CBC; CHAPTER 10, 11A, 11B
TITLE 19 CALIFORNIA ADMINISTRATION CODE
TITLE 24 CALIFORNIA
2016 CALIFORNIA ADMINISTRATION CODE
2016 EDITION, CALIFORNIA CODE OF REGULATIONS, TITLE 24, PART 9, CALIFORNIA FIRE
C O D E
(CFC)2016 EDITION, CALIFORNIA GREEN BUILDING STANDARDS CODE
2016 NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEM
NFPA 30 , FLAMMABLE AND COMBUSTIBLE L IQUIDS CODE 2018 EDIT ION, PER CFC CHAPTER 80
2016 NFPA 72,NATIONAL F IRE ALARM AND SIGNALING CODE
2016 NFPA 110, STANDARDS FOR EMERGENCY AND STANDBY POWER
2016 NFPA 415, STANDARDS ON AIRPORT TERMINAL BUILDINGS, FUELING RAMP DRAINAGE,
AND LOADING WALKWAYS
APPLICABLE REQUIREMENTS ENFORCED BY THE STATE, CITY, AND LOCAL AUTHORITIES
HAVING JURISDICTION.
EXISTING DUCT/PIPE OR EQUIPMENT
TO BE REMOVED
UNDER CUT (DOOR)U C
TUBULAR DAYLIGHTING DEVICETDD
SCOPE OF WORK
THE PROPOSED FACILITY WILL BE PROVIDED WITH DEDICATED HEATING, VENTILATING AND
AIR-CONDITIONING (HVAC) SYSTEM WITH PROGRAMMABLE CONTROL SYSTEMS TO ACHIEVE
THE DESIRED TEMPERATURE CONTROL AND VENTILATION REQUIREMENTS.
BASED ON THE GEOGRAPHICAL LOCATION OF THIS PROJECT (ZONE-12) AND LOAD
CALCULATION RESULTS, WE HAVE SELECTED AN ENERGY EFFICIENT VRV SYSTEM WITH HEAT
RECOVERY AND VARIABLE REFRIGERANT TEMPERATURE CONTROL THAT IMPROVES
SEASONAL COOLING EFFICIENCY. THIS VRV UNIT DEDICATEDLY SERVES THE OFFICE BUILDING
INCLUDING ALL OFFICE SPACES AND CONFERENCE ROOMS. WITH HEAT RECOVERY SYSTEM,
WE CAN HAVE HEATING AND COOLING IN A DIFFERENT ZONE DEPENDING ON EXPOSURE OF
THE BUILDING AND LOAD REQUIREMENTS. MINIMUM OUTSIDE AIR REQUIREMENTS ARE MET
USING DEDICATED OUTSIDE AIR SUPPLY FAN WITH MERV-13 F ILTER. THIS HVAC SYSTEM
COMPLIES WITH THE ARS FACILIT IES DESIGN STANDARD AND UC DAVIS CAMPUS DESIGN
SPECIFICATION/ GUIDE.
DEDICATED ENERGY EFFICIENT WALL MOUNTED SPLIT SYSTEM WITH SINGLE CONDENSER UNIT
IS PROVIDED FOR SERVER ROOM AND IDF ROOM FOR 24X7
COOLING.
MISCELLANEOUS EXHAUST FANS ARE PROVIDED FOR RESTROOMS, JANITOR CLOSET,
ELECTRICAL ROOM, ETC. THE BUILDING WILL BE KEPT SLIGHTLY UNDER POSITIVE PRESSURE.
A COUNTER BALANCE DAMPER IS PROVIDED IN THE COMMON AREA TO RELIEF ACCESS AIR VIA
GRAVITY VENT RELIEF (GVR).
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M0.1MECHANCIAL LEGEND,
ABBREV., SYMBOLS, &
GENERAL NOTES
MECHANICAL SHEET INDEX
Sheet Number Sheet Name
M0.1 MECHANCIAL LEGEND, ABBREV., SYMBOLS, & GENERAL NOTES
M0.2 MECHANICAL SCHEDULES
M0.3 MECHANICAL SCHEDULES
M2.1 MECHANICALFLOOR PLAN
M2.2 MECHANICAL ROOF PLAN
M3.1 MECHANICAL DETAILS
M3.2 REFRIGERANT PIPING ANE WIRING DIAGRAMS
1 05-17-2019 35% DESIGN SUBMITTAL
INDOOR FAN COIL UNIT SCHEDULE
CONDENSING UNIT SCHEDULE
BRANCH CONTROLLER SCHEDULE (BC)
1 UNITS SHALL BE COMPLETE WITH INDOOR FAN COIL UNITS. CONFIRM EQUIPMENT
SELECTION WITH MANUFACTURER PRIOR TO ORDERING EQUIPMENT.
REFRIGERANT TUBING SETS, PER INDOOR UNIT. SIZE TUBING TO ACCOMMODATE
MAXIMUM INDIVIDUAL AND TOTAL SYSTEM LENGTHS. CONFIRM WITH MANUFACTURER.
DISCONNECT SHALL BE PROVIDED BY DIVISION 26. THE DISCONNECT SHALL BE
ADJACENT TO AND IN SIGHT OF THE EQUIPMENT IT SERVES. 2016 CMC, SEC. 310.0
NOTES:
TAG
MANUFACTURER
AND
MODEL NO.
LOCATIONSERVICE
COOLING ELECTRICAL DATA
NOMINAL
TONS
CAPACITY
MBH
MCA
(A)
MOCP
(A) V/PH/Hz
REFRIG
TYPE
EER
IEER
DIMENSION
HXWXD
INCH
OPERATING
WEIGHT
LBS.
REMARKS
FCU-1, FCU-2, FCU-3, FCU-4, FCU-5, FCU-6 1 2 3 4 5GROUND
DAIKIN
REYQ120TATJU
10-TONS 125.2 43.0 208-230/3/60
12.3
22.6 70450.0 R-410A
INSTALL CONDENSING UNIT ON 6" HOUSEKEEPING PAD WITH 5/8" THICK NEOPRENE PAD.
REFRIGERANT-CONTAINING PARTS OF A SYSTEM THAT IS FIELD-ERECTED SHALL BE TESTED AND PROVED TIGHT TO THE AUTHORITY HAVING JURISDICTION AFTER COMPLETE INSTALLATION AND BEFORE OPERATION. CONTACT THE MECHANICAL INSPECTOR AT 650-821-5981 TO SCHEDULE AN INSPECTION. 2016 CMC SEC. 1124.2.
PROVIDE OIL SUMP HEATER, LOW AMBIENT CONTROL, AND HI AND LOW PRESSURE SAFETY SWITCHES.
1 MERV 13 FILTER TO BE MOUNTED ON FAN COIL RETURN AIR OPENING.
PROVIDE WITH ODP MOTOR.
LOW AMBIENT CONTROLS FIELD INSTALLED.
PROVIDE VIBRATION ISOLATOR, MASON TYPE 30N(TYP-4)
5 DISCONNECT SHALL BE PROVIDED BY DIVISION 26 AND SHALL BE ADJACENT TO AND IN
SIGHT OF EQUIPMENT SERVED PER CMC 2016 SECTION 310.
UNIT SHALL BE FURNISHED WITH MANUFACTURER THERMOSTAT.
PROVIDE MANUFACTURER CONDENSATE PUMP.
PROVIDE STANDARD MANUFACTURER FILTER.
NOTES:
MANUFACTURER
MODEL NO.
ANDTAG LOCATION
COOLING
V-PH-HZ
ELECTRICAL DATA
MBH
TOTAL WEIGHT
OPERATING
LBS.
REMARKS
SUPPLY AIR
SUPPLY
CFM (IN.W.G.)
ESP
HEATING
MBH
TOTAL
FILTER
FCU-1
MCA MOCP TYPE/MAX IPD
MBH
SENSIBLE (WxHxD)
DIMENSIONS
1 2 3 4
DAIKIN
FAQ18TAVJU
31N/A13.7 FACTORY/0.10"0.5 1518.0 41.4X11.4X9.2
SERVICE
ASSOCIATED
UNIT
CONDENSING
HP-1
WALL SERVER ROOM
500H 0.10
1 2 3
DAIKIN
MANUFACTURER
MODEL NO.
AND
BS8Q54TVJ
TAG
TECH CUBICLES
CEILING
LOCATION
V-PH-HZ
208-230V 1PH
ELECTRICAL DATA
0.8
WEIGHT
OPERATING
LBS.
REMARKS
NOTES: 1
SERVICE
REFRIG
TYPE
R-410A
MOCPMCA
BS-1 HP-1
OF
NUMBER
BRANCHES
1 2 3 422.8X11.7X18.9
WXHXD
DIMENSION
INCH
48.9X66.7X30.2
FCU-2
FCU-3
FCU-4
FCU-5
FCU-6
FCU-7
COMP/DATA-NW
DAIKIN
FXZQ09TAVJU
HP-1CEILING 317 0.25 35.310.56.3 FACTORY/0.10"0.3 159.5 22.6X10.2X22.6208-230V-1-60
AMP AMP
DAIKIN
FXMQ36PBVJU
10239.928.7 FACTORY/0.10"2.9 1536.0 55.1X11.8X27.6208-230V-1-60HP-1CEILING
ENCL OFF. 2, 3, 4
CORR. & RESTROOM
1,130 0.25
ECNL OFF 1/RECEIP.
DAIKIN
FXMQ09PBVJU
HP-1CEILING 317 0.25 5610.57.6 FACTORY/0.10"0.6 1512 21.7X11.8X27.6
BREAK ROOMDAIKIN
FXMQ12PBVJU
CEILING 6213.59.4 FACTORY/0.10"1.4 1512 27.6X11.8X27.6HP-1
HP-2
450 0.25
DAIKIN
FXMQ36PBVJU
10239.928.7 FACTORY/0.10"2.9 1536.0 55.1X11.8X27.6HP-1CEILING TECH CUBICLES 1,130 0.25
DAIKIN
FXMQ36PBVJU
10239.928.7 FACTORY/0.10"2.9 1536.0 55.1X11.8X27.6HP-1CEILING CONFERENCE ROOM 1,130 0.25
400L
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
FCU-7, FCU-8 1 2 3 4 5GROUND
DAIKIN
RXTQ36TAVJ9 3-TONS
VRV
36.2 16.5 208-230/1/60
12.0
18.0 17225.0 R-410AHP-2 39X37X12.6
CONFIRM EQUIPMENT SELECTION WITH MANUFACTURER PRIOR
TO ORDERING EQUIPMENT.
DISCONNECT SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR.
FAN COIL
WALL
CASSETTE
DUCTED
TYPE
MOUNTED
DUCTED
DUCTED
DUCTED
DUCTED
VRV
208-230V-1-60
208-230V-1-60
208-230V-1-60
208-230V-1-60
208-230V-1-60
DAIKIN
FAQ18TAVJU
31N/A13.7 FACTORY/0.10"0.5 1518.0 41.4X11.4X9.2WALL IT ROOM
500H 0.10 1 2 3 75 6FCU-8 HP-2
400L
WALL
MOUNTED 208-230V-1-60
9 CONTRACTOR TO MAKE SURE TO ORDER FAN COIL UNIT WITH FILTER
ACCESS ON THE SAME SIDE AS THE COIL SERVICE ACCESS.
RE-CIRCULATING UNIT FOR EQUIPMENT ROOM. NO OUTSIDE AIR
REQUIREMENTS.
8 10
75 6 8 10
MINIMUM
AIR
OUTSIDE
(CFM)
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M0.2MECHANICAL
SCHEDULES
DIFFUSERS AND REGISTERS SCHEDULE
EXHAUST/ OUTSIDE AIR SUPPLY FANS SCHEDULE GRAVITY VENT RELIEF SCHEDULE
PROVIDE SIZES AND LOCATIONS AS INDICATED IN DRAWING.
REFER TO ARCHITECTURAL DRAWINGS FOR CEILING/WALL/FLOOR
TYPE TO DETERMINE REQUIRED FRAME.
PROVIDE REMOTE CONTROL RODS FOR VOLUME DAMPER WHEN
REQUIRED.
NOTES:
SUPPLY
SERVICE
TYPE OF
RETURN/EXHAUST
RETURN/EXHAUST
DESIGNATION
CR-1 / CE-1
WR-1 /WE-1
TITUS 50F
TITUS 350RL
MODEL NO.
TITUS MCD
MFR.
CD-1 PERFORATED
PERFORATED
LOUVERED
SURFACE/LAY IN
SIDEWALL/SURFACE
BORDER
SURFACE/LAY IN
FACE
SEE PLANS
24x24
WHITE
WHITE
24x24
MODULE
WHITE
FINISH REMARKS
SUPPLYTITUS MCDCD-2 PERFORATEDSURFACE/LAY IN 12x12 WHITE
RETURN/EXHAUSTCR-2 / CE-2 TITUS 50F PERFORATEDSURFACE/LAY IN 12x12 WHITE
SUPPLYWS-1 TITUS 300RL LOUVEREDSIDEWALL/SURFACE SEE PLANS WHITE
1 52 3 4
1 52 3 4
1 52 3 4
1 52 3 4
1 52 3 4
1 52 3 4
PROVIDE SQUARE TO ROUND ADAPTER AS REQUIRED.
COORDINATE CUSTOM COLOR WITH ARCHITECT.
SONESUNIT
NO.
ESP
IN.
W.G.
MANUFACTURER
MODEL NO.
ROOM
SERVED AND
AIR
QUANT
CFM WATTS
FAN
RPM
V-PH-HZ
MOTOR
OPERATING
WEIGHT
UNIT
LBS.
REMARKS
NOTES:
EF-1 MEN 11
GREENHECK
SP-A200 175 0.30 37 120/1/60 1.5 26800 1 2 3
BACKDRAFT DAMPER
INTERLOCK WITH OCCUPANCY SENSOR.
FAN SHALL BE PROVIDED WITH STARTER AND DISCONNECT SWITCH.
PROVIDE LINE VOLTAGE THERMOSTAT.4
PROVIDE WITH MERV-13 FILTER.
INTERLOCK WITH FCU-1, FCU-2, FCU-3, FCU-4, FCU-5, FCU-6, FCU-7.
EF-2 WOMEN 10
EF-3 JANITOR CLOSET
GREENHECK
SP-A125 100 0.297 21 120/1/60 0.8 191100 1 2 3
EF-4 GREENHECK
SP-A250 250 0.286 83 120/1/60 3.0 261000 1 2 3ELECTRICAL ROOM
1 2 3
OAF-1
OUTSIDE AIR SUPPLY FAN FOR
ALL INDOOR FANCOIL UNITS
SERVING ALL ROOMS
GREENHECK
BSQ-100-4 800 0.5 (1/4) 208/1/60 9.5 1751418 1 3
(OR HP)
5 6
GREENHECK
SP-A200 175 0.30 37 120/1/60 1.5 26800
SERVED
AREA
NOTE:
NO.
ITEM
MODEL NO.
MANUFACTURER
AND
SIZE
CFM SERVICE
IN. WG
DROP
PRESSURE
REMARKS
PROVIDE ROOF CURB, BIRD SCREEN AND BACKDRAFT DAMPER.
PROVIDE FLASHING FLANGE.
AIR RELIEFGRSR
GREENHECKCORRIDOR
GVR
1 112 0.01200 2
(INCH)
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M0.3MECHANICAL
A B
FCU
FCU
FCU
HP
EF
FCU
OAF
C
D
FCU
T
HP
16"x12"
TT
FCU
UC
13 OA
T
BS
CD-1, 8"Ø
150 CFM
(3TYP)
CD-1, 6"Ø
100 CFM
CD-1, 6"Ø
50 CFM
12"x12"
CD-1, 8"Ø
160 CFM
(3TYP)
CD-1, 10"Ø
280 CFM
(4TYP)
T
16"x12"
FCU
10"ø OA
8"ø OA
12"x12"
CD-1, 10"Ø
225 CFM
(2TYP)
T
EF
EF
14"x12" OA
UC5
CD-1, 6"Ø
75 CFM
(2TYP)
CD-1, 10"Ø
280 CFM
(4TYP)
EF
(50)
5"ø OA
19 (165)
(280)
(280)
(280) (280)
8"ø OA
(75)
19(125)
(225)
(160)
(150)
(160)
(150)
19 (150)
19(60)
CD-1, 10"Ø
215 CFM
(280)(280)
(280)
COMP/DATA ANALYTICS
SERVER RM
CORRIDOR
MEN
WOMEN
TECH OPEN OFFICE
STORAGE
CONF/TRAINING RM
BREAK RM
15ELEC RM
JC
ENCL OFC
ENCL OFC
ENCL OFC
RL OFC
RECEP
8"ø
T
FCU
T
CR-1,22X22(TYP)
(FCU-3)
T 2
(FCU-2)(FCU-1) (FCU-7)
(FCU-8)
UC 5
(FCU-5)
(FCU-4)
(FCU-6)
6"ø OA
SEE REF. PIPING
DIAGRAM FOR SIZES.
(250)
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M2.1MECHANICALFLOOR
PLAN
SCALE: 1/4" = 1'-0"1 MECHANICAL FLOOR PLAN
CASSETTE TYPE FAN COIL UNIT TO BE MOUNTED IN THE CEILING PER MFR'S
INSTALLATION DETAIL. SEE SCHEDULE FOR TYPE AND SIZE.
MFR'S PROGRAMMABLE THERMOSTAT WITH RESET CAPABILITY.
CEILING MOUNTED EXHAUST FAN. SEE SCHEDULE FOR TYPE AND SIZE.
10"Ø EXHAUST UP THROUGH ROOF(UTR).
1" DOOR UNDERCUT(TYPICAL).
DUCTED FAN COIL UNIT TO BE HUNG FROM STRUCTURE ABOVE AS HIGH AS
POSSIBLE WITH VIBRATION ISOLATOR, MASON MODEL 30N WITH 1" DEFLECTION.
SEE SCHEDULE FOR PERFORMANCE.
8"Ø EXHAUST UP THROUGH ROOF(UTR).
WALL MOUNTED DUCTLESS FAN COIL UNIT TO BE MOUNTED PER MFR'S
INSTALLATION INSTRUCTION. PROVIDE ALL NECESSARY BRACKET KIT. SEE
SCHEDULE FOR PERFORMANCE.
REF. PIPING FROM WALL MOUNTED FAN COIL UNIT TO HP-2 OUTSIDE WITH
ARMAFLEX INSULATION. PIPE SIZE SHALL BE PER MFR'S RECOMMENDATIONS.
PUMPED CONDENSATE DRAIN. SEE PLUMBING DRAWINGS FOR CONDENSATE
DRAIN PIPE LAYOUT.
6"Ø EXHAUST UTR.
18X18 DOOR LOUVER. SEE ARCH'L DWGS.
24X14 OUTSIDE AIR LOUVER WITH 12" LONG FULL SIZE PLENUM. PROVIDE 10'
DISTANCE BETWEEN OUTSIDE AIR INTAKE AND EXHAUST. SEE ARCH'L DWGS. FOR
LOUVER EXACT SIZE AND LOCATION.
6" DEEP CONC. PAD FOR MECHANICAL EQUIPMENT. SEE ARCH'L DWGS. FOR
EXACT SIZE AND LOCATION OF THE CONCRETE PAD.
8 PORT MFR. BRANCH SELECTOR. SEE SCHEDULE FOR ELECTRICAL AND
PLUMBING REQUIREMENTS.
FLEXIBLE CONNECTION (TYP.).
1" INTERNAL ACOUSTICAL LINING(TYP.). FIBER FREE TYPE MATERIAL PER UCD
STANDARDS.
18" LONG FULL SIZE OPEN RETURN AIR PLENUM WITH 1" ACOUSTICAL LINING.
BALANCE MIN. OUTSIDE AIR PER INDICATED AIRFLOW CFM. OUTSIDE AIR DUCT
TERMINATION TO BE MAXIMUM 3'-0" FROM OPEN END OF RETURN AIR PLENUM.
RETURN AIR PLENUM ABOVE CEILING(TYP.).
PROVIDE LINE VOLTAGE THERMOSTAT AND SET AT 80°F.
MANUFACTURE PROGRAMMABLE REMOTE CONTROL THERMOSTAT TO BE
PERMANENTLY INSTALL ON THE WALL.
OUTSIDE AIR FAN TO BE HUNG FROM STRUCTURE ABOVE AS HIGH AS POSSIBLE
WITH VIBRATION ISOLATOR, MASON MODEL 30N WITH 1" DEFLECTION. SEE
SCHEDULE FOR PERFORMANCE.
12"Ø RELEIF AIR DUCT UP THROUGH ROOF TO GAVITY VENT RRELIEF WITH
COUNTER BALANCE DAMPER TO BE SET AT 0.05" WG.
REF. PIPING FROM HP-1 OUTSIDE WITH ARMAFLEX INSULATION TO INDOOR FAN
COIL UNITS . PIPE SIZE SHALL BE PER MFR'S RECOMMENDATIONS.
1- COORDINATE EXACT LOCATION OF AIR OUTLET WITH ARCH'L DWHS.
2-COORDINATE AIROUT LET LOCATIONS WIT LIGHT FIXTURES AND OTHER DEVICES IN THE CEILING.
3- FOR GENERAL NOTES SEE M0.1.
4- DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, ELBOWS, AND OTHER ELEMENT THAT MAYBE REQUIRED. THE DRAWING SHOW THE GENERAL ARRANGEMENT OF EQUIPMENT, DUCTWORK, ETC., AND SHALL BE FOLLOWED AS CLOSELY AS THE ACTUAL BUILDING CONSTRUCTION AND THE WORK FROM OTHER TRADES SHALL PERMIT.
CONTRACTOR WILL PROVIDE ALL NECESSARY ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION.
5- DUCT SIZE IS THE SAME AS THE ASOCIATED DIFFUER UNLESS OTHERWISE NOTED (TYP).
GENERAL NOTES:
SHEET NOTES:
C D
2 2
TTD(TYP).
SEE ARCH'L
DWGS.
GRV-1
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M2.2MECHANICAL ROOF
PLAN
SCALE: 1/8" = 1'-0"1 MECHANICAL ROOF PLAN
6"Ø EXHAUST TO BE TERMINATED 24" ABOVE ROOF WITH RAIN CAP. MIN. 10'-0"
AWAY FROM ANY OUTSIDE AIR INTAKE.
8"Ø EXHAUST TO BE TERMINATED 24" ABOVE ROOF WITH RAIN CAP. MIN. 10'-0"
AWAY FROM ANY OUTSIDE AIR INTAKE.
10"Ø EXHAUST TO BE TERMINATED 24" ABOVE ROOF WITH RAIN CAP. MIN. 10'-0"
AWAY FROM ANY OUTSIDE AIR INTAKE.
VENT THROUGH ROOF. SEE PLUMBING DWGS.
1- COORDINATE EXACT LOCATION OF AIR OUTLET WITH ARCH'L DWHS.
2-COORDINATE AIR OUTLETS' LOCATIONS WITH LIGHT FIXTURES AND OTHER DEVICES IN THE CEILING.
GENERAL NOTES:
SHEET NOTES:
T
H
46" MAX.
*46" MAX. IF NOT OVER OBSTRUCTION.
WHEN D>10"-24"MAX, H = 53.5" MAX.
FOR GIVEN DEPTHS:
CORRESPONDING REACH HEIGHTS
WHEN D = 10" OR LESS, H = 48" MAX.
MAXIMUM SIDE REACH OVER OBSTRUCTION
SIDE REACH
FIGURE 11B-5D
34" MAX.
30"
D
24" MAX.
THIS DIAGRAM (SIDE REACH FIGURE 11B-5D) ILLUSTRATES THE
SPECIFIC REQUIREMENTS OF THIS REGULATIONS AND IS
INTENDED ONLY AS AN AID FOR BUILDING DESIGN AND
CONSTRUCTION.
1"
NOTES:
INSIDE BUILDING SHALL BE
SEE DRAWING FOR SIZES.
THE REQUIREMENTS OF SECTION
ALL CONDENSATE DRAIN LINES
INSULATED IN ACCORDANCE WITH
15400, PLUMBING SPECIFICATIONS.
ON THE DRAIN PAN.
THE SAME SIZE AS THE NIPPLE
DRAIN LINE SHALL BE AT LEAST
BRASS CLEANOUT PLUG (THREADED)
UNION
DRAIN PAN
2"PLANS.
OF PIPING, SEE
FOR CONTINUATION
HVAC UNIT
VOLUME DAMPER DETAIL
2SCALE
NOT TO
5SCALE
NOT TO
1SCALE
NOT TO
6SCALE
NOT TO
7SCALE
NOT TO
3SCALE
NOT TO
4SCALE
NOT TO
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE
SIMILAR FOR MULTI-BLADE DAMPERS AND ROUND DAMPERS.
NOTES:
2.
1.
INSULATION
DAMPER BLADE
INSULATION
INSULATION
STAND-OFF
HANDLE WITH
QUADRANT
INSIDE END BEARING
LOCKING
SECTION
HANDLE WITH LOCKING
STIFFEN BLADE AS REQUIRED
SIDE ELEVATION
QUADRANT
DUCT
1/8" CLEARANCE ALL AROUND
OUTSIDE END BEARING
1/2" ROUND ROD PIN
DAMPER BLADE
DUCT
THERMOSTAT HEIGHT DETAIL
REFRIGERANT PIPING THRU WALL DETAIL
SCHEDULE 40 PIPESCHEDULE 40 PIPE
SLEEVE TYPICAL EACH
PIPE THRU WALL
CAULKING MATERIAL PACKED
INSULATION REQUIRED
FOR SUCTION LINE
TIGHTLY AROUND PIPE
TYPICAL
TYPICAL-REFRIGERANT PIPING AND
CONDENSATE PIPING PER PLAN
SEE PLANS FOR SIZES
SECURE TO WALL WITH
POLYURETHANE
(4)1/8"∅ SHOTS EACH
SEALANT- TYPICAL
LIGHT GAUGE FRAMED WALL
18 GA. SST. ESCUTCHEON.
SEE PLANS FOR
LOCATION
FLEXIBLE CONN. TO DIFFUSER DETAIL
CONNECT PLENUM TO CEILING
DIFFUSER WITH SHEET METAL
REFER TO FIG. 2-17 SMACNA
SCREWS, CANVAS & ARABOL-
INSTALL RIGID DUCT FOR ALL EXHAUST REGISTERS.
TYPICAL FOR RETURN REGISTERS.
NOTES:
OR APPROVED EQUAL
1.
2.
FOR PLENUM
DIFFUSER
CEILING
SUPPORT
FULL SIZE OF
LINED PLENUM
18" NO BENDS
FOR CONNECTION
ARABOL SEAL
BAND, CANVAS &
22 GA. PLATE-SAME DIA.
SEE PLANS FOR
DUCT COLLAR WITH DRAW
SQUARE, ROUND OR
RECTANGULAR DUCT
AS FLEXIBLE DUCT-
4'-0" O.C.-SEE PLAN
6"
SIZE
1"
FOR SIZE
CONN. (INSULATED) EQUIV. AREA
TO DUCT SIZE SHOWN-
(MAX. LENGTH 5'-0")
CIRCULAR FLEX DUCT CONNECTOR
SEE SPECIFICATIONS FOR DUCT
SCREWS (2) EACH SIDE
#10x1/2" LONG "TECO"
TO STRUCTURE
CEILING EXHAUST
FAN
FAN
GRILLE
FACTORY SUPPLIED
MOUNTING CLIP SECURED
TO FAN WITH SELF-
TAPPING SMS AND
BLOCKING WITH #10X3/4 SMS
CEILING EXHAUST FAN DETAIL
CEILING
16 GA. BLOCKING ON SIDES (TWO) OF
FAN. SECURE TO CEILING JOISTS W/MIN
2/10 S.M.S. EACH END OF BLOCK.
WALL MOUNTED FAN COIL UNIT DETAIL
INSTALLATION.
CEILING DIFFUSER
OPERATOR
COORDINATE EXACT LOCATION OF CEILING MOUNTED
CONCEALED REGULATOR WITH ARCHITECT PRIOR TO
COVER PLATE
1.
NOTE:
DIE CAST
MOUNTING CUP
SOCKET WRENCH
REGULATOR KIT
CONCEALED
AND WIRE (12'-0"
MAXIMUM)
FLEXIBLE CASING
RACK & PINION
ROUND DAMPER
FLEXIBLE DUCTWORKRIGID DUCTWORK
USE BOWDEN CABLE CONTROL BY " YOUNG REGULATORY COMP."2.
CEILING DIFFUSER
REMOTE VOLUME DAMPER CONTROL
8SCALE
NOT TO
9SCALE
NOT TO
REAR VIEW
UNIT OUTLINE
SECURE
FACTORY
MOUNTING
BRACKET TO
WALL W/ 2-#10
S.M.S. @ EA
CORNER, INTO
BLOCKING
1) VERIFY AND MAINTAIN MANUFACTURERS
RECOMMENCED MINIMUM CLEARANCES.
NOTES:
5" MIN.
6" MIN.
5" MIN.
TOP OF STRUCTURE
FRONT VIEW (MIN. CLEARANCE)
WALL MOUNTED
FAN COIL UNIT
2-#10 S.M.S. @
EA CORNER, INTO
BLOCKING
16GA. METAL STUD
BLOCKING IN EA STUD
BAY BEHIND UNIT
WALL
2) INSULATE BOTH REFRIGERANT LINES.
UNIT
NEOPRENE PAD
(TYPICAL)
6"
CONCRETE
GROUND
SEE ARCHITECTURAL
DRAWINGS
W/ 3/8" DIA. X1-1/2" EMBD HILTI
ANCHOR TO CONCRETE PAD
KWIK BOLT TZ EXPANSION @ 12"O.C.
ICC ESR 1917
HP-1
TYPICAL OF (4)
FLEX CONNECTION
AT DISCHARGE
FLEX CONNECTION AT INLET
FAN COIL UNIT
45°
1/2" HANGER ROD- SECURE
TO SPRING HANGER WITH
DOUBLE NUT & LOCK WASHERS
TYPICAL (4) PLACES
SPING VIBRATION ISOLATOR
BY FAN MANUFACTURER
LOCATION OF VIBRATION
ISOLATORS- TYPICAL
LOCATION OF VIBRATION
ISOLATORS- TYPICAL (4)
EXHAUST FAN
PLAN VIEW
BRACE TYPICAL (2)
LOCATION OF DIAGONAL
DISCHARGE
DUCT
1 1/2"x1 1/2"x16 GAUGE
DIAGONAL BRACE
FCU
FCU
FCU
FCU
FCU
10SCALE
NOT TO
11SCALE
NOT TO
12SCALE
NOT TO
ADD 4 OZ. OIL PER 10' OF PIPING OVER
PIPING PER SPECIFICATIONS.
50' MAXIMUM PIPE RUN. INSULATE
NOTE:
REFRIGERANT PIPING SCHEMATIC DIAGRAM
HP
HARD DRAWN ACR TUBING
SLOPE AT 1/4" PER 10' BACK
TO CONDENSING UNIT. SIZE
PER MFR RECOMMENDATIONS.
RS
SUCTION LINE
ACCUMULATOR
P-TRAP
GLASS
SIGHT
RL
EQUALIZING LINE
OF SUCTION LINE
SHALL BE CONNECTED
IN STRAIGHT SECTION
AFTER THERMAL BULB
PIECE FACTORY
MFR.
EXPANSION
VALVE
CONTROL CIRCUIT
P-TRAP ONE
RL
RS
SOLENOID VALVE
COMPRESSOR
WIRED IN
FCU
DUCTED FAN COIL UNIT DETAIL
CONDENSING UNIT DETAIL
CONDENSATE TRAP DETAIL
CONDENSING
&HP-2
PAD
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M3.1MECHANICAL DETAILS
5/8" 3/8 x
1/2" 1/4 x
1/2" 1/4 x
HP- 2
RXTQ36TAVJ9
KHRP26A22T9KHRP26A22T9
FCU- 7
FXAQ18TAVJU
FCU- 8
FXAQ18TAVJU
HP-2
RXTQ36TAVJ9
RXTQ36TAVJ9
FCU- 7
FXAQ18PVJU
BRC1E73 (1)
FCU- 8
FXAQ18PVJU
BRC1E73 (1)
OUT F1,F2
to centralized controller
L1, L2 16.5A 1ph L1, L2 0.4A 1ph
L1, L2 0.4A 1ph
IN F1,F2 F1,F2
F1,F2
P1,P2
P1,P2
3/4" 1 1/8 x
1/2 x
1/2" 1/4 x
5/8" 3/8 x
1/2" 1/4 x
1/2" 1/4 x
5/8" 3/8 x
5/8" 3/8 x
HP- 1
REYQ120TATJU
BS- 1BS- 1
BS8Q54TVJBS8Q54TVJ
AA
FCU- 1
Comp/Data An...Comp/Data Anly
FXZQ09TAVJUFXZQ09TAVJU
BB
FCU- 2
Encl Offices
FXMQ36PBVJUFXMQ36PBVJU
CC
FCU- 3
RL Encl Offices
FXMQ09PBVJUFXMQ09PBVJU
DD
FCU- 4
Break RoomBreak Room
FXMQ12PBVJUFXMQ12PBVJU
EE
FCU- 5
Tech Cubicle
FXMQ36PBVJU
FF
FCU- 6
ConferenceConference
FXMQ36PBVJU
GG
HH
HP-1
REYQ120TATJU
REYQ120TATJU
BS- 1
BS8Q54TVJ
A B C D E F G H
FCU- 1
FXZQ09TAVJU
BRC1E73 (1)
FCU- 2
FXMQ36PBVJU
BRC1E73 (1)
FCU- 3
FXMQ09PBVJU
BRC1E73 (1)
FCU- 4
FXMQ12PBVJU
BRC1E73 (1)
FCU- 5
FXMQ30PBVJU
BRC1E73 (1)
FCU- 6
FXMQ30PBVJU
BRC1E73 (1)
OUT F1,F2
to centralized controller
L1, L2, L3 43A 3ph L1, L2 0.8A 1ph L1, L2 0.3A 1ph
L1, L2 2.9A 1ph
L1, L2 0.6A 1ph
L1, L2 1.4A 1ph
L1, L2 2.8A 1ph
L1, L2 2.8A 1ph
IN F1,F2
OUT F1,F2
IN F1,F2 F1,F2
F1,F2
F1,F2
F1,F2
F1,F2
F1,F2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
4SCALE
NOT TO
HP-2 WIRING DIAGRAM
3SCALE
NOT TO
HP-1 WIRING DIAGRAM 2SCALE
NOT TO
HP-2 REFRIGERANT PIPING DIAGRAM 1SCALE
NOT TO
HP-1 REFRIGERANT PIPING DIAGRAM
IDF Room
Server Room
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
M3.2REFRIGERANT PIPING
AND WIRING
DIAGRAMS
S
ALL PLUMBING PIPING/FITTINGS AND PLUMBING FIXTURES
INTENDED TO CONVEY OR DISPENSE WATER FOR DRINKING OR
COOKING SHALL BE "LEAD FREE" IN COMPLIANCE WITH AB 1953.
CONTRACTOR SHALL PROVIDE CERTIFICATION AS PART OF THE
PLUMBING SUBMITTALS THAT ALL PLUMBING PRODUCTS COMPLY
WITH AB 1953.
EXISTING PIPE ABOVE CEILING
VTR VENT THROUGH ROOF
W T
W/ W/O
W C W C O W H
WEIGHT
WITH OU T
WALL CLEANOUT
WATER HEATER
WATER CLOSET
WITH
FLOOR DRAIN
DIRECTION OF FLOW
BALANCING VALVE
HOSE BIBB
PIPE CONNECTION, TOP
PIPE CONNECTION, BOTTOM
PIPE DROP
UNION
SHEET NOTE DESIGNATION
DOMESTIC HOT WATER P IPING
WALL CLEANOUT
FLOOR CLEAN OUT
GATE VALVE
M ME TE R
PIPE RISE
DOMESTIC COLD WATER PIP ING
CONDENSATE DRAINAGE PIP ING
SOIL OR WASTE PIP ING BELOW FLOOR SLAB
SOIL WASTE PIPING ABOVE FLOOR
SANITARY VENT PIPING
L E G E N D
CD
CEILINGC L G
UNDERWRITER'S LABORATORY
S HO CK A BS OR BE R
TRAP PRIMER VALVE
UNLESS OTHERWISE NOTED
SANITARY VENT PIPING
SOIL OR WASTE PIPING
OVERFLOW DRAINAGE PIP ING
POUNDS PER SQUARE INCH
PRESSURE GAUGE
NORM ALLY CLOSED
PRESSURE DROP
NORMA LLY OPEN
S or W
U R
UL
U G U O N
V
SA
TP
TYP
SQ.FT.
URINAL
U N D E R G R O U N D
TYPICAL
SQUARE FEET
PD
P G
PH
PSI
R W
M A X (N) N C N O No.
OF D
PHASE
RECYCLED WATER
MAXIMUM
N U M B E R
N E W
P O U N D S
GALLON PER FLUSH
INVERT ELEVATION
DOMESTIC HOT WATER P IPING
FLOOR CLEAN OUT
GALLONS PER MINUTE
H W
LBS
I.E.
LAV OR L
IW
GP F
H B
G P M
LAVATORY
INDUSTRIAL WASTE
HOSE BIBB
FD
FLR
FS
GAL
FT
FP
D N
C O
DIA
F C O (E)
FLOOR DRAIN
FL OO R
FLOOR SINK
G A L L O N
FIRE WATER PUMP
FEET
D O W N
CLE AN O U T
DIAMETER
EXISTING
AIR CONDITIONING UNIT
DOMESTIC COLD WATER PIP ING
CONDENSATE DRAIN
B E L O W F L O O R
BALANCING VALVE
ABOVE F INISHED FLOOR
ABBREVIATIONS
AR C H
CFF
C W
C D
BF
BV
AC
AP
AFF
ARCHITECTURAL
ACCESS PANEL
GENERAL NOTES
P-1 PLUMBING FIXTURE IDENTIFICATION
DOMESTIC HOT WATER RETURN
WH
W&V
EQUIPMENT TAG
WASTE AND VENT RISER TAG
VR VENT RISER
T W TEMPERED WATER
OFCI
T W R TEMPERED WATER RETURN
P IPE MATERIAL SCHEDULE
CAST IR
ON SOIL PIPE & FITTING
OR COPPER DWV BRONZE FITTING
COPPER T
YPE L
SIL
VER S
OLDER
COPPER T
YPE L
95/5 S
OLDER
BLACK S
TEEL S
CH 40SPECIFICATION
MATERIA
L
OUTSIDE
OV E R F L O W
STORM &
WASTE &
SERVICE
VENT
DRAIN
W A T E R
INSIDE
(OD)
(SD)
(W) (V)
(DR)
OUTSIDE
INSIDE
OUTSIDE
INSIDE
(IRR)
(CW)(HW) INSIDE
OUTSIDE
"OUTSIDE" COLUMN IS TO 5' -0"
OUT SIDE BLDG. FOR CONT.
NOTE:
SEE CIVIL PLANS AND
COPPER T
YPE "L
" O 2 C
LEAN T
O A
STM
B-819, N
FPA 99, C
GA G
4.1, S
ILVER
SOLDER D
OUBLE W
ALL B
EL. G
RADE
ASTM B
-8
8, B -280 S
ILVER S
OLDER
COPPER T
YPE A
CR "L
" T
O
FOR CW & 5 FT/S FOR HW
7.76 PSI/100FT @ 8 FT/S VEL
RE M A R K S
G C O GRADE CLEANOUT
STORM DRAINSD
WATER SIZE CALCULATION
PIPE SIZE
G P M
FU
VEL(FPS)
LOSS (PSI)
1/2"
COLD WATER SIZING (FLUSH VALVES)
BASED ON 4/PSI/100 & 6 FT./SEC. MAX.
3/4"
1"
1-1/2"
6.0
5.0
2"
6.0
2.7
2-1/2"
6.0
2.2
3"
6.0
1.8
4"
6.0
1.5
PIPE SIZE
G P M
FU
VEL(FPS)
LOSS (PSI)
1/2"
1.5
4.0
4.0
COLD WATER SIZ ING
BASED ON 4/PSI/100 & 6 FT./SEC. MAX.
3/4"
6.0
7.0
4.0
5.0
1"
5.0
5.0
1-1/4"
6.0
5.0
1-1/2"
6.0
4.0
2"
6.0
3.0
2-1/2"
6.0
2.0
3"
6.0
1.8
4"
6.0
1.1
PIPE SIZE
G P M
FU
VEL(FPS)
LOSS (PSI)
1/2"
1.8
2.3
2.7
HOT WATER SIZ ING
BASED ON 5/PSI/100 & 5 FT./SEC. MAX.
3/4"
4.5
2.8
2.7
1"
3.3
2.7
1-1/4"
4.1
2.7
1-1/2"
4.7
2.7
2"
2.2
2-1/2"
1.8
3"
1.4
4"
1.0SOLENOID VALVE
VENT BELOW FLOOR
EXISTING P IPE BELOW GRADE
IN CEILINGI.C.
BE LOW GR AD EB G
BELOW FINISH FLOORBFF
ROOF DRAIN
PRV
R D
PRESSURE REDUCING VALVE
CALGREEN PLUMBING COMPLIANCE
IN ACCORDANCE WITH CAL GREEN REQUIREMENTS, ALL PLUMBING F IXTURES
SHALL COMPLY WITH THE FOLLOWING MINIMUM REQUIREMENTS. NOTE ACTUAL
DESIGN MAY EXCEED THE MINIMUMS NOTED BELOW. SEE PLANS AND
SPECIFICATIONS FOR ACTUAL FIXTURE SPECIFICATIONS.
A. WATER CLOSETS(TOILETS) - THE EFFECTIVE FLUSH VOLUME OF ALL WATER
CLOSETS SHALL NOT EXCEED 1.28 GALLON PER FLUSH.
TANK TYPE: U.S. EPA WATERSENSE TANK-TYPE HIGH EFFICIENCY TOILET
SPECIFICATION.
B. PUBLIC LAVATORY FAUCETS: MAXIMUM FLOW RATE - 0 .5 GPM (1.9L/MIN) ,
ASME A 112,18,1/CSA B125.1
C. URINALS- WALL MOUNTED URINAL- THE EFFECTIV FLUSH VOLUME OF
WALL MOUNTED URINALS SHALL NOT EXCEED 0.125 GALLON PER FLUSH.
THE EFFECTIVE FLUSH VOLUME OF FLOOR MOUNTED OR OTHER URINALS
SHALL NOT EXCEED 0.5 GALLON PER FLUSH.
1.
NOTE:
1. TYPE "K" COPPER PIPE BELOW GROUND WITH PIPE WRAP.
FD C FIRE DEPARTMENT CONNECTION
(RW)
LEAD-FREE NOTE
MANUAL WETTED STAND PIPEM W S P
BEAM PENETRATION
FSFDC
BUILDINGB L D G
FF FINISH FLOOR
FIXTURE
FIXTURE UNIT VALUE (2016 CPC)
W/V
TABLE 702.1
TOTL CW
TABLE A-103.1
CW (3/4 OF
TOTAL CW)
HW(3/4 OF
TOTAL CW)
WATER CLOSET
LAVATORY
SINK
1.5
.75
1,25
.75
1.25
FLOOR SINK 2 0.5 - -
NOTES:
(1) WATER SUPPLY UNIT FIXTURE UNITS ARE BASED ON 2016 CPC, TABLE A-103.1.
(2) DRAINAGE FIXTURE UNITS ARE BASED ON 2016 CPC, TABLE 702.1.
FLOOR DRAIN 2 - - -
DRINKING FOUNTAIN 0.5 0.5 - -
JANITOR SINK 3 1.5 1.25 1.25
HOSE BIBB - 2.5 2.25 -
GENERAL SEISMIC NOTES
MP COMPONENT ANCHORAGE
ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND
INSTALLED PER THE DETAILS ON THE APPROVED CONSTRUCTION DOCUMENTS. WHERE
NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR
BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE
2013 CBC, SECTIONS 1616A.1.18 THROUGH 1616A.1.20 AND 1.26, AND ASCE 7-10 CHAPTER
13, 26 AND 30.
1. ALL PERMANENT EQUIPMENT AND COMPONENTS.
2. TEMPORARY OR MOVEABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED
(e.g.HARDWIRE) TO THE BUILDING UTILITY SUCH AS ELECTRICITY, GAS OR WATER.
3. MOVEABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS
AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY
ATTACHMENTS.
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS
SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON
PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN
THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS
LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY
SUPPORT THE COMPONENT.
B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED
SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR
FLOOR OR HUNG FROM A WALL.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO
COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION
13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2013 CBC, SECTIONS
1616A1.23, 1616A.1.24, 1616A.1.25 AND 1616A.1.26.
COPIES OF THE DRAWINGS AND SPECIFICATION SHALL BE AVAILABLE ON THE JOBSITE
PRIOR TO THE START OF CHANGING AND BRACING OF THE PIPE, DUCTWORK, AND
ELECTRICAL DISTRIBUTION SYSTEMS.
THE STRUCTURAL ENGINEER OF RECORD HAS VERIFIED THE ADEQUACY OF THE
STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. PIPE HANGER SUPPORT
DETAILS HAVE BEEN REVIEWED AND APPROVED BY THE PLUMBING ENGINEER.
1. ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE 2016
CALIFORNIA PLUMBING CODE, 2016 CALIFORNIA BUILDING CODE, NATIONAL FIRE
PROTECTION CODES, BUILDING EDITION DESIGN CRITERIA, AND ALL OTHER LOCAL
APPLICABLE CODES AND REGULATIONS.
2. COORDINATE PLUMBING SYSTEMS WITH WORK OF OTHER TRADES PRIOR TO ANY
FABRICATION OR INSTALLATION. PROVIDE ALL FITTINGS, OFFSETS, AND TRANSITIONS AS
REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.
3. COORDINATE LOCATIONS OF ALL ROOF OPENINGS WITH STRUCTURAL, MECHANICAL
AND ARCHITECTURAL PLANS PRIOR TO ANY INSTALLATION.
4. PLATFORMS, CURBS, AND FLASHING FOR PLUMBING EQUIPMENT SHALL BE AS
INDICATED ON THE ARCHITECTURAL PLANS AND METAL BUILDING SYSTEM SHOP
DRAWINGS, UNLESS NOTED OTHERWISE. COORDINATE EXACT SIZES OF REQUIRED
OPENINGS AND SUPPORTS FOR FURNISHED EQUIPMENT.
5. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT
MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL
FITTINGS, TRANSITIONS, VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE
WORKABLE INSTALLATION.
6. MAINTENANCE LABEL SHALL BE AFFIXED TO ALL PLUMBING EQUIPMENT AND A
MAINTENANCE MANUAL SHALL BE PROVIDED TO GOVERNMENT'S REP.
7. PIPES SHALL BE SUPPORTED AND BRACED PER STRUCTURAL ENGINEER APPROVED
DETAIL.
8. HORIZONTAL PIPING THRU METAL STUDS IS PROHIBITED.
9. WATER PIPING SHALL BE TYPE "L" HARD DRAWN COPPER.
10. SOIL, WASTE, DRAIN, AND VENT PIPING BELOW AND INSIDE BUILDING, USE NO HUB CAST
IRON PIPE WITH 24 GA. STAINLESS STEEL COUPLING AND NEOPRENE GASKETS.
11. INSTALL DIELECTRIC FITTING BETWEEN FERROUS AND NON-FEROUS MATERIALS.
12. PROVIDE STOP VALVES IN EACH WATER SUPPLY AT EACH PLUMBING FIXTURE.
13. HORIZONTAL WASTE PIPING SHALL HAVE MINIMUM SLOPE OF (1/4" PER FOOT AND 1/8"
PER FOOT FOR STORM DRAIN) UNLESS NOTED OTHERWISE ON THE PLANS.
14. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF PLUMBING FIXTURES.
15. VENT PIPE SHALL TERMINATE VERTICALLY NOT LESS THAN 6 INCHES ABOVE ROOF NOR
12 INCHES FROM ANY VERTICAL SURFACES. EACH VENT SHALL TERMINATE NOT LESS
THAN 10 FEET FROM OR AT LEAST 3 FEET ABOVE ANY OPERABLE WINDOW, DOOR,
OPENING AIR INTAKE, OR VENT SHAFT.
16. INSULATE ALL HOT WATER SUPPLY PIPING TO RUN-OUTS IN WALLS.
17. PIPE PROTECTION: PENETRATION OF RATED ASSEMBLIES SHALL BE FIRE STOPPED.
18. PROVIDE U.L. LISTED FIRE RATED "MOLDABLE PUTTY" AND/OR CAULKING AROUND
RECESSED VALVE BOXES IN RATED WALLS OR CEILING, AS REQUIRED BY CODE.
19. FLUSH VALVE FOR ACCESSIBLE WATER CLOSET FLUSH MECHANISM SHALL BE
PROVIDED ON THE OPEN SIDE OF STALL.
20. PROVIDE ADA COMPLIANT COVERS OVER P-TRAP AND WATER SUPPLY LINES AND STOPS
AT ALL LAVATORIES AND OTHER ADA SINKS "TRAP WRAP" INSULATION KIT BY
BROCAR-PRODUCTS INC.
21. ALL SERVICE SHUT-DOWN AND START-UPS SHALL BE SCHEDULED IN ADVANCE AND
SUPERVISED OR PERFORMED BY FACILITY MANAGEMENT STAFF.
22. ALL WORK IN OCCUPIED AREAS SHALL BE SCHEDULED DURING OFF-HOURS AND
COORDINATED WITH THE FACILITY, SO THAT SUCH WORK IS COMPLETED, AREA
CLEANED AND ALL SERVICES RESTORED AND CODE COMPLAINT PRIOR TO RETURNING
TO NORMAL FACILITY OPERATION HOURS.
23. PLUMBING FIXTURES AND FITTINGS SHALL COMPLY WITH CALGREEN TABLE 5.303.6.
24. TRAP PRIMER SYSTEM SHALL CONSIST OF A STAINLESS STEEL SERVICE ACCESS PANEL,
12"X12", BRONZE LEAD-FREE BALL VALVE UPSTREAM AND A COPPER X FIP (FEMALE IRON
PIPE) UNION DOWN STREAM. BRONZE BALL VALVE SHALL BE MANUFACTURED BY NIBCO
OR APPROVED EQUAL.
25. PROVIDE ISOLATION VALVE W/AP FOR ALL FIXTURES FOR SERVICE & MAINTENANCE.
26. ALL CLEANOUTS SHALL BE ACCESSIBLE FOR REGULAR MAINTENANCE.
27. THE AVAILABLE WATER PRESSURE IS IN THE RANGE OF 120-125 PSI. DOMESTIC WATER SYSTEM PRESSURE SHALL BE LIMITED TO 65 PSI THROUGH AN EXISTING PRESSURE REDUCING STATION
ON THE EXISTING INCOMING COLD WATER MAIN. EXISTING PRESSURE REDUCING STATION TO
REMAIN AS IS.
28. WATER FLOW VELOCITY: TO AVOID ANY EROSION, CORROSION AND EXCESSIVE NOISE
GENERATION, THE DOMESTIC COLD WATER PIPING SHALL BE SIZED FOR A MAXIMUM FLOW
VELOCITY OF 4 FEET PER SECOND (FPS) FOR PIPES TWO INCHES AND SMALLER; AND 6 FEET PER
SECOND (FPS) FOR LARGER PIPES.
EXISTING PIPE TO BE REMOVED
PIPE>4"GRAVITY @ 2% STANDARD FOR
PIPE<4" 4"GRAVITY @ 1%
1.5"/HR RAIN FALL. 3"/HR RAINFALL FOR
COMBINED SYSTEM. 1% SLOPE
FIRE SPRINKLER FIRE DEPARTMENT
CONNECTION
PIP ING CAPPED FOR FUTURE
CONNECTION
OWNER FURNISH ED CONTRACTOR
INSTALLED
URINAL 2 3 - -
PIPE SIZE
INSULATION
THICKNESS
1/2"
1"
PIPE INSULATION PER 2016 CPC 609.11 & T-24
3/4"
1"
1"
1-1/2"
1-1/4" 1-1/2" 2"
2"
2-1/2"
2"
3" 4" 5" 6"
1-1/2" 1-1/2" 2" 2" 2" 2"
PIPE SIZE VERTICAL
TABLE 702.1
HORIZONTAL
1/4" SLOPE
HORIZONTAL
1/8" SLOPE
NA
NA
172.8
48 35 NA
600 428 342.8
1380 720 576
3600 2640 2112
5600 4680 3744
8400 8200 6560
MAXIMUM DRAINAGE F IXTURE UNITS ALLOWED FOR
EACH SIZE OF PIPE PER CPC 2016
2"
2-1/2"
3"
4"
5"
6"
8"
10"
12"
NOTES:
1- DRAINAGE FIXTURE UNITS ARE BASED ON 2016 CPC, TABLE 703.2.
2- VENT FIXTURE UNITS AND LENGTH ARE BASED ON 2016 TABLE 703.2 . NOT TO
EXCEED ONE-THIRD OF THE TOTAL PERMITTED LENGTH OF A VENT SHALL
PERMITTED TO BE INSTALLED IN A HORIZONTAL POSITION. WHERE VENTS ARE
INCREASED ONE PIPE SIZE FOR THEIR ENTIRE LENGTH, THE MAXIMUM LENGTH
LIMITATION SPECIFIED IN THIS TABLE DO NOT APPLY.
VENT PIPING
MAX. UNIT / MAX. LENGTH - FEET
24/120
256/300
84/21
600/390
1380/510
3600/750
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECTONICS
SUSTAINABLE AGRICULTURAL WATER
SYSTEM RESEARCH UNIT
UC DAVIS, CA
Architects Planners Engineers 1500 Park Ave
EMERYVILLE, CA 94608
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER EPM
A D
USDA S
U
NO. DATE BY
SHEET OF
REVISIONS
DESCRIPTION
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET CONTENTS
UNITED STATES
DEPARTMENT OF
AGRICULTURE
07/15/2019
A - E FIRM
BID SET SUBMITTAL
P0.1PLUMBING LEGEND,
ABBREVIATIONS, AND
GENRAL NOTES
PLUMBING SHEET INDEX
Sheet Number Sheet Name
P0.1 PLUMBING LEGEND, ABBREVIATIONS,
AND GENRAL NOTES
P0.2 PLUMBING SCHEDULES
P2.1 PLUMBING FLOOR PLAN
P3.1 PLUMBING RISER DIAGRAMS
P4.1 PLUMBING DETAIL
BRADLEY MODEL S 59-400 W/ INTEGRAL CHECK
VALVE AND STRAINER. PROVIDE AT EACH FIXTURE
SET AT 95°.
VENT
PLUMBING F IXTURE AND CONNECTION SCHEDULE
FLOOR CLEAN OUTFCO-1 -
WA S T E TRAP
C W H W
J.R. SMITH FLOOR CLEANOUT, MODEL 4020
DIR. INDIR.CAP(MBH) CONN.
-TRAP PRIMERTP-1 - 1/2" -
-4"
J.R. SMITH 2699 ANSI-112.26, CAST BRONZE
WITH 1/2"CONNECTION
1- ALL HOT WATER AND DRAIN PIPES SHALL BE INSULATED.
2- THERE SHALL BE NO SHARP OR ABRASIVE SURFACE UNDER
LAVATORIES/SINKS.
3- FORCE TO ACTIVATE FAUCET CONTROLS SHALL BE NO GREATER
THAN 5 LBS.
4- REPLACE FAUCET AERATOR WITH AERATOR PROVIDED BY
CHRONOMITE FOR FAUCET WITH CHRONOMITE INSTANTANEOUS
ELECTRIC WATER HEATER.
RE M A R K S
WALL CLEANOUTWCO-1 - -J.R. SMITH MODEL 4420 -4"
- - SEE PLAN FOR PIPE SIZE
WAT E R H AM M E RWHA-1 J.R. SMITH MODEL 5005 WATER HAMMER
ARRESTOR. INSTALL PER MANUFACTURE'S
RECOMMENDATION.
--- - -- -AR R E S T O R
-- 3/4" -- -
PROVIDE WITH VACUUM
BREA KER
INDUST.
WA S T E
FD-1 FLOOR DRAIN
ZURN MODEL Z415B FLOOR DRAIN, DURA-COATED
CAST IRON WITH BOTTOM OUTLET, -- 1/2" -- 2" --
JS-1
URINAL WALL HUNGUR-1 TOTO HIGH EFFICIENCY URINAL (TOP SPUD).
SLOAN 186-0.125 MANUAL FLUSH VALVE 0.125 GPF.
WATTS CA-321 CARRIER MOUNTED PER ADA
REQUIREMENTS.
1-1/2"1-1/2"- 3/4" -- 2"-
1-1/2"
LAVATORY - WALL
L-1 1-1/2"- 1/2" 1/2"- - 2"
MOU NT-ADU LT
WALL HUNG LAVATORY TOTO, MODEL TL307(A) WITH
SINGLE HOLE FOR FAUCET. FAUCET TOTO MODEL HELIX
ECO POWERED SENSORED FAUCET TEL115-D10#CP,
WITH 0.35 GPM AERATOR. WATTS TCA-411 CARRIER,
DEARBORN BRASS 704-1 P-TRAP, TOTO THP5067#CP
GRID DRAIN, TRUEBRO LAV GUARD #101-F-7.
ADA HEIGHT
- - - 3" - - 2" 1/2" -
2"- 1" -INT.- - 4"TOTO MODEL CT705ULNGX VITREOUS CHINA, 1 .0 GPF,
ELONGATED BOWL WITH TOTO FLUSH VALVE MODEL
TET1UAX32#CP. ADA-HEIGHT.
TMV-1 THERMOSTATIC MIX ING
VALVE 1/2"1/2"
ADA HEIGHT
JANITOR SINK
FL O O R M O U N T E D 1/2"
C O D E
EWH-1
LOCATION
B O C K
M A N UF A C TU R E R
NO.
M O D E L G A L L O N
CAPACITY
K W
ELECTRIC
VOLT PHASE
RE M A R K SWEIGHT
LBS
MECH. ROOM 50F 50 9 208 3 535 FLOOR MOUNT
M A N UF A C TU R E R
NEAR WATER HEATERET-1
C O D E LOCATION
CAPACITY
GA LL ON S
PTA-5BELL & GOSSETT 2.1
M O D E L
NO. PRE-CHARGE
AIR
RE M A R K S
NOTES:
1- INSTALL ON HOLDRITE DRAIN PAN MODEL QP AND 30" FLOOR MOUNT QUICK STAND MODEL 40-S-30 PAN AND STAND SIZE TO MATCH WATER HEATER
SIZE.
2- SET TEMPERATURE FOR 120°F. TERMINATE RELIEFE DRAIN AND PAN DRAIN OVER JANITOR SINK.
1/2" TP
C O D E
WC-1 WATER CLOSET
FL O O R M O U N T
FLUSH VALVE - ADA
DESCRIPTION M O D E L GAS
ELECTRIC WATER HEATER SCHEDULE
EXPANSION TANK SCHEDULE
2"- 1" -INT.- - 4"SAME AS WC-1, EXCEPT IS NON-ADA HEIGHT
WC-2 WATER CLOSET
FL O O R M O U N T
FLUSH VALVE
HB-2
WOODFORD MODEL B75 WALL BOX SERIES
WITH INTEGRAL VACUUM BREAKER & HOSE
THREADED NOZZLE
EXTERIOR
WALL HOSE BIBB
HB-1 WOODFORD MODEL 24 SERIES WITH INTEGRAL
VACUUM BREAKER & HOSE THREADED NOZZLE
INTERIOR
HOSE BIBB
-- 3/4" -- -
PROVIDE WITH VACUUM
BREA KER-- -
SK-1 1-1/2"1-1/2"- 1/2" 1/2"- - 2" BREAK ROOM SINK
ELKAY MODEL LRAD 191855(19"X18"X5-1/2" DEEP)
STAINLESS STEEL 18 GAUGE, SINGLE HOLE
CENTERED
WITH FAUCET CHICAGO ELECTRONIC EBPS SENSOR
OPERATED FAUCET, MODEL 116.683.AB.1. PROVIDE
PLUG-IN S INGLE USE CLASS 2A TRANSFORMER FOR
DUAL POWER. 120V HARDWIRED NORMAL POWER
AND BATTERY BACK UP FOR SECONDARY SOURCE
OF POWER. PROVIDE ALL NECESSARY PARTS FOR
DUAL POWER OPERATION. PROVIDE WITH
NON-AERATOR LAMINAR FLOW. SEE ARCH'L DWGS.
FOR MOUNTING HEIGHT. PROVIDE WITH MIXING
VALVE.
COUNTER MOUNT
Exp.06/30/21
I
L
No. M33664
I
CINHC
EM
SSEFORP
ACFO
ET
DERETSI
GE R
AT
S
ASALHA
HS A
LA
RE
EN
I
GN
E
LA
NO
AINROFI
I
ND
I
A
TECT…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.