Cole Rivers Service Substation Product Description Draft.pdf
PDF 152 KB Posted
- Solicitation number
- W9127N25Q17LC
About this file
This document is a detailed technical specification for a dry-type service transformer as part of an electrical substation for the Cole Rivers Hatchery. The specification requires a 2000kVA, 3-phase, 60-Hz transformer with 13,800-480/277 volt ratings and delta-wye winding configuration. The transformer is to be designed, assembled, and tested by a single manufacturer following IEEE standards, with a final design subject to government approval. Key technical requirements include a NEMA Class FFA rating with 220°C insulation, self-cooled operation, five voltage taps, 5.75% impedance, a basic lightning impulse insulation level of 95kV for high voltage and 30kV for low voltage, and compliance with Category II short-circuit requirements.
The specification provides extensive details on construction requirements, including copper windings, tinned or silver-plated bus connections, a ground bus, ventilated dead-front enclosure, and specific mounting and wiring guidelines. The transformer is to be designed for outdoor use with an ambient temperature range of 0-110 degrees F. The manufacturer must submit comprehensive documentation including shop drawings, product data, test reports, and operation and maintenance manuals. The substation is intended to be shipped to the Cole Rivers Hatchery site in Oregon, potentially in sections due to shipping restrictions, with minimal on-site assembly required. The specification is part of a larger project involving 480V switchgear and medium-voltage metal-enclosed switch-breakers.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 26 12 16.00 25
DRY-TYPE SERVICE TRANSFORMER
PART 1 GENERAL
1.1 GENERAL INFORMATION
The Cole Rivers Hatchery electrical substation is to be designed, assembled and tested by one manufacturer. The Substation Manufacturer is to use these drawings and specifications as a guideline to complete their design, assembly and testing. The final design is to be approved by the Government.
The substation is to be completely designed, assembled and tested at the Substation Manufacturer's factory and shipped to the Cole Rivers site as a complete unit or as factory designed modules that the Substation Manufacturer is to assemble on the Government supplied concrete pad. The Substation Manufacturer's scope of work ends after the substation is unloaded from the Substation Manufacturer's delivery truck, craned on to the Government supplied concrete pad or if in modular pieces is connected together yielding a complete ready to use substation. The Government realizes size of the equipment and realizes that it may have to be shipped in sections due to shipping restrictions on the Oregon highway systems using standard trucking. The Substation Manufacturer is to minimize the amount of assembly at the site.
This section specifies the design, fabrication, assembly, wiring, and factory testing of the 13.8kV to 480 volt station service transformer. This transformer is one part of three sections that make up the Cole Rivers Substation.
The two other associated sections of this substation are:
262310.0026 480 VOLT SWITCHGEAR
261301.0025 MEDIUM-VOLTAGE, METAL-ENCLOSED SWITCH-BREAKERS
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-10 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B1.1 (2003; R 2018) Unified Inch Screw Threads (UN and UNR Thread Form)
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 693 (2018) IEEE Recommended Practice for Seismic Design of Substations g2ct9nws Cross-Out
IEEE C37.20.1A (2020) Metal-Enclosed Low-Voltage (1000 Vac and below, 3200 Vdc and below) Power Circuit-Breaker Switchgear Amendment 1:
Control and Secondary Circuits and Devices, and All Wiring
IEEE C57.12.01 (2020) General Requirements for Dry-Type Distribution and Power Transformers Including Those with Solid-Cast and/or Resin-Encapsulated Windings
IEEE C57.12.51 (2019) IEEE Guide for Mechanical Interchangeability of Ventilated Dry-Type Transformers
IEEE C57.12.91 (2011) Standard Test Code for Dry-Type Distribution and Power Transformers
IEEE C57.13 (2016) Standard Requirements for Instrument Transformers
IEEE C57.13.3 (2014) IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases
IEEE C57.32 (2015) IEEE Standard for Requirements, Terminology, and Test Procedures for Neutral Grounding Devices
IEEE C62.11 (2020) Standard for Metal-Oxide Surge Arresters for Alternating Current Power Circuits (>1kV)
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2021) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA TR 1 (2013) Transformers, Regulators, and Reactors
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. Submit the following in accordance with Section 01 33 00, SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Electrical Equipment Drawings; G
SD-03 Product Data
Transformer; G
Nameplates; G
Surge Protection; G
Temperature Monitor; G
SD-06 Test Reports
Factory Acceptance Test Report; G
Acceptance Checks and Tests; G
SD-05 Design Data
Structural Design Criteria and Seismic Calculations; G
SD-08 Manufacturer's Instructions
Factory Test Procedure; G
Transformer Shipping Plan; G
SD-10 Operation and Maintenance Data
Operation and Maintenance Data; G
1.4 PRODUCT DATA
Provide Substation Manufacturer's catalog cuts composed of catalog cuts, brochures, circulars, specifications, product data, and printed information in sufficient detail and scope to verify compliance with the requirements of the Contract documents. Submit product data within 90 days after receipt of Notice to Proceed.
1.5 ELECTRICAL EQUIPMENT DRAWINGS
Provide detailed electrical drawings showing physical arrangement, construction details, connections, wiring diagrams, materials used in fabrication, access requirements for installation and maintenance, physical size, electrical characteristics, mounting and support details, and equipment weight. Provide drawings drawn to scale and dimensioned.
Optional items are to be clearly identified as included or excluded.
Submit drawings within 90 days after receipt of Notice to Proceed.
PART 2 PRODUCTS
2.1 GENERAL
a. The transformer supplied as part of this Contract is to meet all applicable industry standards and requirements as listed in IEEE C57.12.01 and IEEE C57.12.51.
b. The transformer is to be included as an integral section of the substation assembly. The substation assembly is to be manufactured and tested as one unit by the Substation Manufacturer at their factory. The substation is arrive at the site with minimal assembly of the sectional blocks. These blocks are only to be separated for ease of highway shipping by freight truck.
2.2 SERVICE CONDITIONS
2.2.1 General
Unless specified below, units are to be built for operation outdoors, ventilated enclosures in a non-hazardous environment meeting the usual service conditions outlined in Paragraph 4.1 of IEEE C57.12.01.
2.3 TRANSFORMER
2.3.1 Type and Rating
Transformer is to be outdoor ventilated dry-type, self-cooled, NEMA Class FFA, with 220 degrees C insulation and is to conform to the applicable requirements of IEEE C57.12.01, IEEE C57.12.51, IEEE C57.12.91, and NEMA TR 1. The transformer is to be rated 2000kVA, 3-phase, 60-Hz, 13,800-480/277 volts, and the windings are to be connected delta-wye. The Substation Manufacturer is to design the transformer to carry rated load continuously without exceeding 80 degrees temperature rise above 40 degrees C ambient temperature when installed in it's ventilated sheet metal enclosure and cooled by ambient air with provisions for fan forced air circulation (240VAC fan voltage).
2.3.2 Winding taps
Supply the transformer with de-energized, high-voltage full-capacity taps.
Provide five taps total, with two at +2.5 percent each above nominal voltage, normal and two at -2.5 percent each below nominal voltage.
2.3.3 Impedance
The transformer impedance is to be 5.75 percent subject to ANSI standard tolerance.
2.3.4 Basic Lightning Impulse Insulation Level
The transformer's high voltage winding is to have a basic lightning impulse insulation level (BIL) of at least 95kV. The transformer's low voltage winding is to have a basic lightning impulse insulation level (BIL) of at least 30kV.
2.3.5 Short-Circuit Characteristics
The transformer supplied is to be built to Category II short circuit requirements as defined in IEEE C57.12.01.
2.3.6 Sound Level
The sound level is not exceed the class AA, three phase ratings listed in Table 8 of IEEE C57.12.01.
2.4 CONSTRUCTION
2.4.1 Insulation System
Transformer coils are to be impregnated using a VPI or VPE process. Coils are to be pre-heated before application of resin. Resin is to be pressure impregnated under vacuum followed by positively pressurized dry-air or nitrogen to assure complete impregnation free of voids or air pockets.
Windings are to be completely cured via oven. After landing the coils on the core and completing final adjustments, treat the entire assembly with resin and oven-baked until fully cured.
2.4.2 Windings
Windings are to be copper.
2.4.3 Bus Connections
The bus connections are to be tinned or silver-plated.
2.4.4 Core and Coils
Rigidly attach the core, coils, and metal enclosure of the transformer to a structural steel base suitable for moving the complete transformer by the use of rollers. Provide jacking facilities and removable lifting eyes on the core and coil assembly. The core laminations are to be free from burrs which may puncture the insulation between laminations and are to be securely fastened to prevent excessive vibration in normal service or displacement under short-circuit conditions. The terminal board is to be accessible through a door or removable panel in the enclosure. All transformer leads and taps are to be securely braced to prevent displacement or injury during transit or installation and under short-circuit condition.
2.4.5 Ground Bus
Install a continuous ground bus inside the transformer enclosure including the transition and termination compartments. It is to be copper not less than 2 inch by 1/4 inch. Mechanically connect the ground bus to the core, frame and enclosure. The use of ground cables in lieu of bus is not allowed. In the medium voltage compartment the bus is to be installed up the wall to allow close connection of the medium voltage cable shields.
2.4.6 Enclosures and Mounting
2.4.6.1 General
Enclosures are to be of a ventilated, dead-front, freestanding construction. All enclosures are to be constructed to prevent inadvertent access to energized parts and the ingress of solid foreign objects.
Enclosures are to be constructed to a minimum of Type 3R as defined in NEMA 250, or equivalent. The enclosure are to be constructed such that all points are solidly bonded to the cubicle ground connection. All bolts, studs, machine screws, nuts, and tapped holes are to be in accordance with ASME B1.1. Ventilating openings are to be provided as required for proper ventilation. The openings are to be of the grille type, and are to be provided with corrosion-resistant insect-proof screens on the inside.
Interior surfaces are to receive not less than one coat of corrosion-resisting paint in accordance with the manufacturer's standard practice. Paint the enclosure the same color as the other sections of the substation.
2.4.6.2 Incoming Sections
Provide a metal-enclosed high voltage transition compartment for terminating the incoming medium voltage shielded cables. Ground bus and support for cable bracing are to be included in this Section. Provide access to the interior of the through removable bolted panels or bolted hinged doors. Heavy-duty clamp type terminal lugs are to be provided for connecting the medium voltage cables to the transformer medium voltage bus. The design is to allow adequate space for bending and bracing of medium voltage shielded cable. Install ground ball studs on all three phases for use by maintenance personnel to install safety grounds.
2.4.7 Outgoing Section
A metal-enclosed low voltage transition compartment is to be provided for connecting the transformer bus to the low voltage cable bus. Access to the interior of the compartment is to be through removable bolted panels or bolted hinged doors. The connections are to be made of copper bus with not less than 3200amps continuous current-carrying capacity and 65kA symmetrical amperes momentary current rating. Install ground ball studs on all three phases for use by maintenance personnel to install safety grounds.
2.4.8 Structural Design Criteria and Seismic Calculations
Submit Structural design criteria and seismic calculations for approval within 180 calendar days after date of award. Design criteria and calculations are to be performed by qualified structural engineers who are presently registered Professional Engineers (PE). A cover sheet for the submittal is to be provided and stamped or sealed and signed by a PE.
Provide structural design criteria and seismic calculations for the transformer design.
2.4.8.1 Structural Design Criteria
Structural design criteria is to include the following:
a. Indicate the industry design standards and allowable stresses or capacities to which steel plate, structural steel shapes, welds, bolts and studs are to conform.
b. Indicate the industry standards used in developing the seismic forces and analysis techniques used in design of the transformer and transformer components.
c. Seismic design for equipment restraint is to be in accordance with Chapter 13 "Seismic Design Requirements for Nonstructural Components", of ASCE 7-10 with the seismic design force computed as per Section 13.3 "Seismic Demands on Nonstructural Components". Electrical equipment restraint is to be designed in accordance with the provisions in IEEE 693 Annex D or Section 13.3 of ASCE 7-10 whichever produces the more adverse seismic effects. For ASCE 7-10, use a spectral response acceleration SDS=0.146, component importance factor IP=1.5, and z=h=1.
For IEEE 693, the seismic qualification level is to be moderate.
2.4.8.2 Seismic Calculations
Seismic calculations are to include the following:
a. Derivation of seismic forces and load cases. Load cases used for developing seismic anchorage of the complete transformer is to account for the effect of the righting force of the weight of the transformer.
b. Calculations for use in the design of anchorage to resist overturning and base shear. The maximum uplift and shear force per anchor bracket bolt is to be provided in pounds or kips.
c. A schematic depicting the location of the center of gravity, the applied seismic forces relative to the base, and the location of seismic anchors.
d. Calculations for individual components and their attachment to the transformer.
2.4.8.3 Anchorage to Concrete for Seismic Restraint
For the purposes of performing seismic calculations and for transformer design for anchorage to the transformer equipment pad, at least four removable seismic brackets are to be provided. These brackets are to be bolted to a steel channel foundation which is to be seismically anchored to the concrete.
2.5 SURGE PROTECTION
2.5.1 Surge Protection Capacitors
Mount three single phase surge capacitors for each phase in the transformer medium voltage terminal compartment. The surge capacitors are to be 0.25 microfarad rated 13.8 kV. If capacitors are not mounted near the base of the enclosure, a ground bus is to be run to close proximity of the capacitors so that cable is not run along the equipment housing to the enclosure ground bus.
2.6 NAMEPLATES
The transformer is to be provided with a cast bronze, stainless steel, or anodized aluminum nameplate conforming to the requirements of IEEE C57.12.01, Table 13. In addition to the requirements of Table 13, the nameplate is to also include the following information:
a. Date of Manufacture
b. Manufacturing plant location and address
c. Government Contract number
2.7 TEMPERATURE MONITOR
2.7.1 General
Provide each transformer with a temperature monitor mounted on a side panel such that it is easily read during normal operation. The temperature monitor is to be rated for outdoor use.
2.7.2 Inputs
The transformer temperature monitor is to utilize two inputs: multiple windings temperature and ambient temperature. Input resistance temperature detectors (RTDs) or thermocouples are to be placed in the anticipated hottest spot of each winding assembly. RTDs or thermocouples are be of the type recommended for the selected monitor. The monitor is to operate off of a 120 VAC supply.
2.7.3 Outputs
At a minimum, two programmable Form C contacts, rated for operation on a 120 VAC system, are to be supplied for hi-hi temperature and hi-temperature. Set the hi-hi temperature at the shut down trip point and the alarm, hi-temperature, at 15 degrees lower.
2.8 WIRING
Wiring for accessories is to be adequately supported to prevent damaging the conductors due to vibration or maintenance activities and is to be connected to accessible terminal blocks. The frame members and conduit are to be utilized to protect exposed wiring from damage and all wiring on the base are to be protected from stepping on during maintenance activities.
Entrance of wiring and raceways into cabinet enclosures are to be by bushings designed for the purpose and all cabinets and conduit are to be adequately bonded to ground by bonding jumpers or fitting approved for grounding. Insulation and jackets of wiring are to be non-PVC.
2.9 CONTROL CABINET
A control cabinet is to be provided with terminal blocks and control equipment as specified or required. This control cabinet is to be used for terminating the external control and power cables, temperature relay, control fuses, circuit breakers, instrumentation wires and current transformer secondary wiring. The control cabinet is to have a door to allow access from the front of the transformer enclosure. Doors with mounted equipment are to have a minimum bonding jumper of No. 10 AWG across panel hinges.
2.10 HIGH RESISTANCE GROUND EQUIPMENT
High Resistance Ground (HRG) equipment is to be installed in a suitable transformer section as determined by the transformer manufacturer. The HRG is to be a regular catalog off-the-shelf equipment of a manufacturer regularly engaged in the design, manufacture, and testing of neutral grounding systems and is to be designed for use on this type of equipment with no less than five years of successful operation. A device assembled of discrete parts is not acceptable.
2.10.1 Grounding Equipment
a. The grounding equipment is to include a grounding resistor and all associated controls and wiring. All connections and leads are to be insulated for 600 volts ac.
b. The grounding resistors are to be sized to provide one to five amperes of ground current in the event a single-line-to-ground fault.
The resistors are to be tapped with taps wired out to a convenient accessible terminal block. Taps are to provide one to five amperes of ground current in one ampere increments. The resistors are to be rated for continuous duty. The resistors are to be heavy duty industrial stamped steel design. The resistors are to conform to IEEE C57.32 except that they are to be insulated for not less than 600 volts AC and the rated maximum temperature of the resistors are not to exceed 415 degrees C when mounted inside the transformer with natural air cooling.
The resistors are to have mounting brackets for mounting in the transformer. All steel support materials are to be corrosion-resistant steel or hot-dipped galvanized.
c. The unit is to be enclosed inside the transformer, completely wired in the factory, in a location that will not interfere with the installation, operation, repair and maintenance of the transformer.
Manufacturer's standard ventilating openings are to be provided as required for proper ventilation. Intake vents are to be filtered, and both intake and exhaust vents are to be provided with corrosion-resistant insect-proof screens on the inside.
d. Provide engraved nameplates for all devices mounted within the assembly corresponding to appropriate designation on manufacturer's drawings.
e. Submit with the transformer drawings: outline drawings, connection and assembly drawings, and schematic diagram of high resistance grounding system. Drawings is to include overall dimensions, size and location of cable entrances, details for bolting equipment to the transformer, data for all equipment, nameplate schedule, wiring diagrams. Wiring diagrams are to be the wire-less type and are to be shown from the front as seen by the observer.
2.11 OPERATION AND MAINTENANCE DATA
The Substation Manufacturer is to provide an Operations and Maintenance manual. Operation and Maintenance (O&M) data is to comply with the requirements of Section 01 33 00, SUBMITTAL PROCEDURES and are to include complete operating, maintenance, and storage data regarding the transformer and it's related equipment and are to be included the O&M Manual. The data is to include the manufacturer's name, model number, catalog cuts, parts list, service manual, drawings, and a brief description of all equipment and their basic operating features. The data is to list routine maintenance procedures, possible breakdowns and repairs, and a trouble-shooting guide including detailed instructions for removal, overhaul, reconditioning, and reinstallation of replaceable components. In addition, the data is to also contain recommended frequency of inspections and cleaning.
PART 3 EXECUTION
Electrical installation and commissioning will be done at a later time.
Under this contract the Substation Manufacturer is not responsible for the installation and commissioning of the substation.
-- End of Section --
SECTION 26 13 01.00 25
MEDIUM-VOLTAGE METAL-ENCLOSED SWITCH-BREAKERS
PART 1 GENERAL
The Cole Rivers Hatchery electrical substation is to be designed, assembled and tested by one manufacturer. The Substation Manufacturer is to use these drawings and specifications as a guideline to complete their design, assembly and testing. The final design is to be approved by the Government.
The substation is to be completely designed, assembled and tested at the Substation Manufacturer's factory and shipped to the Cole Rivers site as a complete unit or as factory designed modules that the Substation Manufacturer is to assemble on the Government supplied concrete pad. The Substation Manufacturer's scope of work ends after the substation is unloaded from the Substation Manufacturer's delivery truck, craned on to the Government supplied concrete pad or if in modular pieces is connected together yielding a complete ready to use substation. The Government realizes size of the equipment and realizes that it may have to be shipped in sections due to shipping restrictions on the Oregon highway systems using standard trucking. The Substation Manufacturer is to minimize the amount of assembly at the site.
This section specifies the design, fabrication, assembly, wiring, and factory testing of the 13.8kV medium voltage switchgear. This switchgear is one part of three sections that make up the Cole Rivers Substation.
The two other associated sections of this substation are:
261216.0025 DRY-TYPE SERVICE TRANSFORMERS
262310.0026 480 VOLT SWITCHGEAR
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-10 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures
ASTM INTERNATIONAL (ASTM)
ASTM A780/A780M (2020) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM D1535 (2014; R 2018) Standard Practice for Specifying Color by the Munsell System
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE C2 (2023) National Electrical Safety Code
IEEE C37.20.3 (2013) Standard for Metal-Enclosed Interrupter Switchgear
IEEE C37.90 (2005; R 2011) Standard for Relays and Relay Systems Associated With Electric Power Apparatus
IEEE C57.13 (2016) Standard Requirements for Instrument Transformers
IEEE C57.13.1 (2006; R 2012) Guide for Field Testing of Relaying Current Transformers
IEEE C57.13.3 (2014) IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases
IEEE C57.98 (2011) Guide for Transformer Impulse Tests
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2021) International Building Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2021) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023) National Electrical Code
NFPA 70E (2021) Standard for Electrical Safety in the Workplace
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are to be as defined in
IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Switch-Breaker Drawings; G
SD-03 Product Data
Spare Parts List; G
Medium Voltage Metal Enclosed Switch-Breaker; G
SD-06 Test Reports
Metal Enclosed Switch-Breaker Production Tests; G
SD-10 Operation and Maintenance Data
Operation and Maintenance Data; G
SD-11 Closeout Submittals
Warranty; G
1.4 QUALITY ASSURANCE
1.4.1 Switch-Breaker Drawings
Substation Manufacturer's drawings are to include, but are not limited to the following:
a. An outline drawing, with front, top, section, and side views showing incoming medium voltage connection and outgoing connection to the close-coupled transformer.
b. One-line diagram showing metal enclosed switch-breaker, switchboard breakers, transformer and ampere rating of bus bars. Include control schematics for the medium voltage circuit breaker.
c. Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, accessories, and other items that are to be shown to ensure a coordinated installation.
Wiring diagrams are to identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Include control schematics and external connections. Point to point connection and wiring diagrams are to show all terminal blocks and connections between blocks and equipment.
Drawings are to indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices. Submittals are to include the nameplate data, size, and capacity. Submittals are to also include applicable federal, military, industry, and technical society publication references.
1.4.2 Test Reports
Submit all factory test reports and procedures.
1.4.3 Regulatory Requirements
Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting
Officer. Equipment, materials, installation, and workmanship are to be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.4.4 Standard Products
Provide materials and equipment from the Manufacturer that are currently in production. Products are to have been in satisfactory commercial or industrial use for five years prior to bid opening. The five year period is to include applications of equipment and materials under similar circumstances and of similar size. The product is to have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the five year period. Where two or more items of the same class of equipment are required, these are to be products of the same manufacturer.
1.4.5 Material and Equipment Manufacturing Date
Products manufactured more than three years prior to date of delivery to site are not to be used, unless specified otherwise.
1.4.6 Qualifications
The Manufacturer of the substation is to have a minimum of twenty years continuous experience in the design, production and testing of equipment of the same type and rating. The switchgear, power circuit breakers, ATS controller, and medium voltage switchgear contained therein are all to be from the same Manufacturer.
1.5 MAINTENANCE
1.5.1 Operation and Maintenance Data
Submit operation and maintenance data in accordance with Section 01 78 23.00 25, OPERATION AND MAINTENANCE DATA and as specified herein.
Contents are to at a minimum include:
a. Include Substation Manufacturer's schedule for routine preventive maintenance, inspections, tests, and adjustments required to ensure proper and economical operation and to minimize corrective maintenance.
Provide Substation Manufacturer's projection of preventive maintenance work-hours on a daily, weekly, monthly, and annual basis including craft requirements by type of craft. For periodic calibrations, provide Manufacturer's specified frequency and procedures for each separate operation.
b. Catalog data required by the paragraph entitled, SD-03 PRODUCT DATA.
c. Drawing required by the paragraph entitled, SD-02 SHOP DRAWINGS.
d. Price for spare parts and supply list.
e. Routine and field acceptance test reports.
1.6 SPARE PARTS
The Substation Manufacturer is to supply the spare parts as specified herein. Spare parts are to be duplicates of the original parts furnished, and are to be interchangeable therewith.
a. Four indicating lamps of same color as indicated on the drawings and any other lamps the Substation Manufacturer has included in there design.
b. Two ARMS selector switches and any other switches the Substation Manufacturer has included in there design.
c. One 15kV medium voltage breaker identical to the one provided in the finish substation.
d. One current transformer of each type and rating.
e. One cabinet space heater and associated circuit breaker.
f. Two optional auxiliary operating coils of each type used in the Manufacturers design (an example would be the optional shunt trip relay part).
g. One spring-charging motor or solenoid.
h. One complete auxiliary switch.
i. One breaker weather protective cover for the medium voltage circuit breaker, the same as installed on the finished product.
1.7 SEISMIC REQUIREMENTS
Provide seismic tested equipment as follows:
a. The equipment, it's anchorage and major components are to be suitable for, and certified to meet, all applicable seismic requirements of ICC IBC and ASCE 7-10, Minimum Design Loads for Buildings and Other Structures. A design spectral response acceleration parameter at short periods (SDS) of 0.49g, Risk Category IV and a Seismic Design Category D is to be used.
b. Mounting recommendations are to be provided by the Substation Manufacturer based upon approved shake table tests used to verify the seismic design of the equipment.
c. The Substation Manufacturer is to certify that the equipment can withstand, that is, function following the seismic event, including both vertical and lateral required response spectra as specified in above codes.
d. The Substation Manufacturer is to document the requirements necessary for proper seismic mounting of the equipment. Seismic qualification is to be considered achieved when the capability of the equipment, meets or exceeds the specified response spectra.
1.8 WARRANTY REPAIR
The equipment is to be be supported by the Substation Manufacturer providing satisfactory service to the equipment on a regular and emergency basis during the warranty period of the Contract.
PART 2 PRODUCTS
2.1 General
The medium voltage switchgear is to be included as an integral section of the substation assembly. The substation assembly is to be manufactured and tested as one unit by the Substation Manufacturer at their factory. The substation is arrive at the site with minimal assembly of the sectional blocks. These blocks are only to be separated for ease of highway shipping by freight truck.
2.2 MEDIUM VOLTAGE METAL ENCLOSED SWITCH-BREAKER AND ENCLOSURE
The metal enclosed switch-breaker is to consist of a deadfront, completely metal enclosed vertical section with a non-fused load interrupter switch in series with a fixed mounted medium voltage vacuum circuit breaker. The 15kV switch-breaker is to have a continuous current rating of 1200A at 13.8kV, circuit breaker short circuit rating of momentary 40kA asymmetrical RMS, 2 second current 25kA Sym. BIL is to be 95kV. Overcurrent protection is to use an electronic trip unit integrated into the medium voltage breaker. The three phase current transformers are also integrated into the medium voltage breaker. The following features are to be supplied with each switch-breaker:
a. A minimum 8-inch x 16-inch high-impact viewing window that permits full view of the position of all three switch blades through the closed door. The window is not be more than 58-inches above the switch pad level to allow ease of inspection.
b. High voltage parts within the circuit breaker compartment is to be isolated with grounded metal barriers.
c. A grounded metal barrier bolted closed in front of the switch to prevent inadvertent contact with any live part, yet allow for a full-view inspection on the switch blade.
d. Provisions for padlocking the switch in the open or closed position.
e. Green OPEN, Red CLOSED switch position indicators to be panel mounted LED lights above the breaker. See contract drawings.
f. A hinged cover with rustproof quarter turn nylon latches over the switch operating mechanism to discourage casual tampering.
g. The primary switch is to be removable from the structure as a complete operational component.
h. Vertical section construction is to be of the universal frame type using die-formed and bolted parts. All enclosing covers and doors are to be fabricated from steel whose thickness is to be equal to or greater than those specified in IEEE C37.20.3. No owner removable hardware for covers or doors are to be thread-forming type. To facilitate installation and maintenance of cables and bus in each vertical section, a split removable top cover is to be provided.
i. Eccentric or concentric knockouts are not allowed in the enclosure.
All holes for conduits need to be drilled and punched in the field.
j. Provide grounding switch on the load side of the disconnect that interlocks with the breaker cell door for breaker access.
k. Finish enclosure to be same color as the other components of the substation.
l. Enclosure to be outdoor rated, NEMA 3R, as is the transformer and low voltage sections. Provide ventilating openings as required for proper ventilation. The openings are to be of the grille type, and are to be provided with corrosion-resistant insect-proof screens on the inside.
m. Infra-red (IR) viewing windows are to be provided on the rear of the enclosures. Windows are to feature a removable steel or aluminum security cover over a four inch crystal sightglass and be outdoor rated. The IR windows are to be the equipment manufacturer's standard product, or a third party product that is UL certified and arc-flash tested to the kA rating of the breakers or higher, and installed with the coordination and approval of the switchgear manufacturer.
n. Install ground ball studs on all three phases, on the line side of the disconnect, for use by maintenance personnel to install safety grounds.
o. 13.8KV surge suppressors are to be installed on the medium voltage cables coming into the substation, upstream of the switch in the medium voltage cabinet.
p. 13.8KV surge capacitors are to be installed on the bus that leaves the medium voltage section and connects to the transformer (see transformer specification 261216.0025).
2.2.1 SURGE ARRESTERS
2.2.1.1 Medium Voltage Incoming Surge Arresters
Mount surge arresters for each phase in the medium voltage compartment.
Surge arresters are to be metal-oxide, station class, with a MCOV of 15.3kV for a 13.8 kV winding. Surge arresters are to be constructed in accordance with the requirements of IEEE C62.11. Submit the surge arrester design test results for each type of arrester provided and the surge arrester conformance test results is to be submitted for each arrester provided. If surge arresters are not mounted near the base of the enclosure, a ground bus is to be run to close proximity of the surge arrester so that cable is not run along the equipment housing to the enclosure ground bus. All tests are to be performed in accordance with IEEE C62.11.
2.2.2 Medium Voltage Bus
a. All buses are to be silver-plated copper.
b. Ground bus is to be directly fastened to a galvanized metal surface of each vertical section, and be of a size sufficient to carry the rated (2-second) current of the switchgear assembly.
c. All bus are to be supported utilizing a high strength and high creep support providing 10.5-inch of creep between phases and ground. The molded fins are to be constructed of high track resistant aramid nylon or cycloaliphatic epoxy.
d. All standoff insulators on the primary switches mounts are to be glass polyester or cycloaliphatic epoxy.
2.2.3 Wiring/Terminations
a. One terminal pad per phase is to be provided for attaching cable terminal lugs for a maximum of two conductors per phase of the sizes indicated on the drawings. Sufficient space is to be allowed for electrical stress relief termination devices.
2.2.4 Medium Voltage Circuit Breaker
a. Each circuit breaker is to be operated by a motor-charged spring stored energy mechanism. The spring is to be able to be charged manually in an emergency or during maintenance procedures.
b. Each circuit breaker is to have three vacuum interrupter assemblies.
Each vacuum interrupter is to have a contact wear indicator to indicate the contact wear. The breaker front panel is to be removable when the bolts are removed for ease of inspection and maintenance of the mechanism.
c. Remote control of the breaker is to be from a 120VAC control voltage. This voltage is to control functions such as the shunt trip coil and other similar circuitry inside of the breaker.
d. Primary stabs are to be silver plated.
e. to have a 3 cycle (50ms) interrupting time
f. to have dimensions of 20x25x18 inches WxHxD, fixed, non-drawout
g. The breaker tripping device is to be a microprocessor based internal electronic trip unit (ETU), factory installed and integral to the breaker.
2.2.5 Medium Voltage Circuit Breaker Electronic Trip Unit (ETU)
The ETU is to be integral to the circuit breaker and is to have the following:
a. Medium voltage switchgear 3 phase currents nominal range are between 0 to 84 amps. Trip unit to accurately measure currents below 200 amps
RMS.
b. ETU not to require a separately installed trip rating plug.
c. Long delay protection: delay setting = 0.4-1.0 In, delay time I2t at 6xIr = 2-24 seconds, to have delay thermal memory
d. Short delay protection: delay pickup = 200-1000% x Ir, delay time I2t at 8xIr = 100-500 milliseconds, delay time FLAT = 100-500 milliseconds, to have delay time zone selective interlock
e. Instantaneous protection: instantaneous pickup = 200-1000% x In, to have OFF position, to have making current release
f. ARMS maintenance mode
g. System Diagnostics (LEDs or panel display): long pickup indication, high load alarm contact output, cause of trip indication, magnitude of trip current display
h. System metering: panel display
i. USB remote communications for laptop connection. ETU to communicate to laptop software the following: breaker status open/closed/tripped;
Measured current values; ETU settings = long delay trip, short delay trip, instantaneous trip, overtemperature trip, making current release trip, high instantaneous trip;
j. ETU to be from same manufacturer as the circuit breaker
2.2.6 Arc Reduction Maintenance Switch (ARMS)
a. The metal enclosed switch-breaker section is to have one ARMS switch, for load side protection. The load side ARMS will activate the instantaneous-only setting of the circuit breaker for downstream protection.
b. The ARMS is to have a blue lamp for indication when maintenance mode is on, and a two position maintained selector switch for turning the maintenance mode on and off. The ARMS indication light is to be driven by a relay output, indicating that the relay has changed settings, in lieu of being driven from a contact in the ARMS switch.
2.2.7 Instrument Transformers
2.2.7.1 General
The medium voltage circuit breaker is to have an on-board trip unit, hence instrument transformers are not needed in the design shown in the drawings as they are incorporated into the breaker. Although, it is the responsibility of the Substation Manufacturer to supply the final design, components and assembly of the substation. If the final design is to include instrument transformers then the transformers are to conform to the following:
a. All instrument transformers are to conform to the applicable grounding requirements of IEEE C57.13. Thermal rating of instrument transformers are to be 1.33.
b. All leads from each individual instrument transformer are to be brought out to terminal blocks. All instrument transformer secondary circuits are to be grounded together at the switchgear terminal blocks.
All secondary leads are to be grounded together at the instrument transformer for shipping.
2.2.7.2 Current Transformers
2.2.7.2.1 General
The medium voltage circuit breaker is to have an on-board trip unit, hence current transformers are not needed in the design shown in the drawings as they are incorporated into the breaker. Although, it is the responsibility of the Substation Manufacturer to supply the final design, components and assembly of the substation. If the final design is to include current transformers then the transformers are to conform to the following:
a. The quantity, ratios, and functions of the current transformers are to be as shown on the drawings. If ratios are changed, then these changes are to be approved by the COR. Current transformers, except as otherwise specified, are to conform to the applicable requirements of IEEE C37.20.3, IEEE C57.13, and IEEE C57.13.3. Current transformers are to be of the dry or compound-insulated type revenue grade, and are to be provided with a suitable means of mounting and for grounding the frame. The polarity of the current transformers are to be plainly marked. All current transformers are to be suitable for continuous operation at the full-rated voltage and current at a frequency of 60 Hz. All current transformers are to be designed to withstand, without damage, the thermal and mechanical stresses resulting from short-circuit currents corresponding to ratings of the breakers in the circuits to which they are connected. Current transformers are to have a continuous thermal current rating factor based on 30 deg C average ambient air temperature of a minimum of 1.33. Current transformer secondary leads are not to be smaller than No. 10 AWG. Each current transformer secondary lead are to be connected to a terminal block of the short-circuiting type in the low voltage compartment and are to be conveniently located to permit short-circuiting the secondary windings without requiring access to the primary bus compartments. The current transformers are to be shorted at the terminals of each of the current transformers for shipping.
b. Current transformers installed are to be window or bushing type current transformers unless otherwise noted. Window or bushing type current transformer is to have a minimum full-wave insulation level of equipment voltage rating. The current transformers are to meet the requirements for a 95kV BIL rating for 15kV equipment as listed in Table 2 of IEEE C57.13 for test voltage applied between the bus and transformer secondary terminals.
2.3 MANUFACTURER'S NAMEPLATES
Each item of equipment is to have a nameplate bearing, as a minimum, the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable. Include additional information as applicable to fully identify the equipment. Nameplates is to be made of non-corrosive metal. As a minimum, provide nameplates for transformers, circuit breakers, switches, and switchboards.
2.4 EQUIPMENT NAMEPLATES
ASTM D709. Provide laminated plastic nameplates for each switch-breaker, equipment enclosure, relay, switch, and device; as specified in this Section or as indicated on the drawings. Each nameplate inscription is to identify the function and, when applicable, the position. Nameplates are to be melamine plastic, 0.125 inch thick, black with white center core.
Surface is to be matte finish. Corners are to be square. Accurately align lettering and engrave into the core. Minimum size of nameplates is to be one by two and a half inches. Lettering is to be a minimum of 0.25 inch high normal block style.
2.5 FACTORY INSPECTION AND TESTS
Each item of equipment supplied under this Contract is to be given the Manufacturer's routine factory tests and also other tests, as specified below, to insure successful operation of all parts of the assemblies. All tests required are to be witnessed by the Contracting Officer Representative (COR), unless waived in writing, and no equipment is to be shipped until it has been approved for shipment. The factory test equipment and test methods used are to conform to the applicable requirements of ANSI, IEEE and NEMA standards, and are to be subject to approval. The witnessing representatives of the Substation Manufacturer and the COR is to sign all test reports.
2.5.1 Equipment Test Schedule
The Government reserves the right to witness tests. Provide equipment test schedules for tests to be performed at the manufacturer's test facility.
Submit required test schedule and location, and notify the Contracting Officer 60 calendar days before scheduled test date.
2.5.2 Test Instrument Calibration
a. The Manufacturer is to have a calibration program which assures that all applicable test instruments are maintained within rated accuracy.
b. The accuracy is to be directly traceable to the National Institute of Standards and Technology.
c. Instrument calibration frequency schedule is not to exceed 12 months for both test floor instruments and leased specialty equipment.
d. Dated calibration labels is to be visible on all test equipment.
e. Calibrating standard is to be of higher accuracy than that of the instrument tested.
f. Keep up-to-date records that indicate dates and test results of instruments calibrated or tested. For instruments calibrated by the manufacturer on a routine basis, in lieu of third party calibration, include the following:
(1) Maintain up-to-date instrument calibration instructions and procedures for each test instrument.
(2) Identify the third party/laboratory calibrated instrument to verify that calibrating standard is met.
2.5.3 Metal Enclosed Switch-Breaker Production Tests
a. IEEE C37.20.3. Furnish reports of production tests performed on the actual equipment for this project. Required tests are to be as follows:
b. Production Tests
(1) Dielectric
(2) Mechanical operation
(3) Circuit breaker operated over the range of minimum to maximum control voltage.
(4) Electrical operation and control wiring
(5) Factory setting of contact gap
PART 3 EXECUTION
Electrical installation and commissioning will be done at a later time.
Under this contract the Substation Manufacturer is not responsible for the installation and commissioning of the substation.
-- End of Section --
SECTION 26 23 10.10 26
480 VOLT SWITCHGEAR
03/22
PART 1 GENERAL
1.1 SUMMARY
The Cole Rivers Hatchery electrical substation is to be designed, assembled and tested by one manufacturer. The Substation Manufacturer is to use these drawings and specifications as a guideline to complete their design, assembly and testing. The final design is to be approved by the Government.
The substation is to be completely designed, assembled and tested at the Substation Manufacturer's factory and shipped to the Cole Rivers site as a complete unit or as factory designed modules that the Substation Manufacturer is to assemble on the Government supplied concrete pad. The Substation Manufacturer's scope of work ends after the substation is unloaded from the Substation Manufacturer's delivery truck, craned on to the Government supplied concrete pad or if in modular pieces is connected together yielding a complete ready to use substation. The Government realizes size of the equipment and realizes that it may have to be shipped in sections due to shipping restrictions on the Oregon highway systems using standard trucking. The Substation Manufacturer is to minimize the amount of assembly at the site.
This section specifies the design, fabrication, assembly, wiring, and factory testing of the 480 volt station service switchgear. This switchgear is one part of three sections that make up the Cole Rivers Substation.
The two other associated sections of this substation are:
261216.0025 DRY-TYPE SERVICE TRANSFORMERS
261301.0025 MEDIUM-VOLTAGE, METAL-ENCLOSED SWITCH-BREAKERS
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C12.1 (2014) Code for Electricity Metering
ANSI C39.1 (1981; R 1992) Requirements for Electrical Analog Indicating Instruments
ASME INTERNATIONAL (ASME)
ASME B1.1 (2003; R 2008) Unified Inch Screw Threads (UN and UNR Thread Form)
ASME B1.20.1 (2013) Pipe Threads, General Purpose (Inch)
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2015) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM B187/B187M (2016) Standard Specification for Copper, Bus Bar, Rod and Shapes and General Purpose Rod, Bar and Shapes
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 1248 (1998; R 2007) Guide for the Commissioning of Electrical Systems in Hydroelectric Power Plants
IEEE C2 (2017) National Electrical Safety Code
IEEE C37.09 (1999; AMD 1 2005; Corr 1 2007; R 2007;
Errata 2007; Amendment B 2011) Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
IEEE C37.13 (2015) Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures
IEEE C37.16 (2009) Standard for Preferred Ratings, Related Requirements, and Application Recommendations for Low-Voltage AC (635 V and below) and DC (3200 V and below) Power Circuit Breakers
IEEE C37.17 Standard for Trip Systems for Low - Voltage (1000 V and below) AC and General Purpose (1500 V and below) DC Power Circuit Breakers
IEEE C37.20.1 (2015) Standard for Metal-Enclosed Low-Voltage (1000 Volts and Below, 3200 Vdc and Below) Power Circuit Breaker Switchgear
IEEE C37.90.1 (2012) Standard for Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated with Electric Power Apparatus
IEEE C57.13 (2016) Standard Requirements for Instrument Transformers
IEEE…