CMC Edwards Rad Shielding Report-Update final.pdf
PDF 829 KB Posted
- Attached to
- 1111-24P General Contractor for Radiology Lab Remodel State and local contract opportunity
- Solicitation number
- 1111--24P
- Issued by
- Eagle County, Colorado
About this file
The document is an X-ray Shielding Design Analysis and Recommendations report prepared by Colorado Associates in Medical Physics (CAMP) for the Sharp FM Radiographic System at the Colorado Mountain College Radiology Lab in Edwards, CO. The report provides a comprehensive technical analysis of radiation shielding requirements for a new radiography facility, including detailed specifications for lead barriers, wall construction, windows, and operator booth design. The analysis is based on national radiation protection standards and focuses on achieving radiation exposure levels that are "As Low As Reasonably Achievable" (ALARA) for both occupational workers and the general public.
The report includes specific technical recommendations such as using 0.11 mm lead thickness for certain walls, implementing 6 mm plate glass for the control room window, and ensuring lead shielding extends to 7 feet in height. The analysis calculates expected weekly radiation doses for various adjacent areas, including the control room, offices, hallways, and classrooms, with all projected exposures falling below the design goal of 0.1 mGy/week. The document is signed and reviewed by medical physicists Stephanie C. Franz and Nathan Busse, with final approval from Dr. Amy Connerton, indicating a rigorous professional review process. The report is dated April 10, 2024, and supersedes a previous report from September 16, 2024.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 1111-24P General Contractor for Radiology Lab Remodel.pdf | ||
| Bid Sheet.xlsx | XLSX spreadsheet | |
| Construction Documents.pdf | ||
| 1111-24P Addendum 001.docx | DOCX document | |
| Project Manual.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(719) 471-7425 www.campphysics.com office@campphysics.com
X-RAY SHIELDING DESIGN ANALYSIS
AND RECOMMENDATIONS
Update – this report supersedes report dated September 16, 2024
PROJECT:
Sharp FM Radiiographic System Radiology Lab Colorado Mountain College 150 Miller Ranch Road Edwards, CO 81632
CONTACTS:
Gwen Gilley, Principal Architect Hord Coplan Macht
(303) 222-0228 GGilley@hcm2.com
Dr. Amy Connerton Assistant Dean of Instruction
(970) 569-2970 aconnerton@coloradomtn.edu
Shielding Analysis Completed by:
Stephanie C Franz, MS, DABR, QE #121 Date Diagnostic Medical Physicist Colorado Associates in Medical Physics
Reviewed by:
Nathan Busse, MS, DABR, QE #238 Date Diagnostic Medical Physicist Colorado Associates in Medical Physics
Dr. Amy Connerton Date
All required shielding is identified on attached layout. Calculations and assumptions are outlined in the report. For further information, please call Stephanie Franz at (303) 817-1108 or email at s.franz@campphysics.com.
04/10/2024
Nathan Busse (Oct 6, 2024 08:59 MDT) Nathan Busse 06/10/2024
Dr. Amy Connerton (Oct 6, 2024 17:20 MDT) Dr. Amy Connerton 06/10/2024
RADIOGRAPHIC SHIELDING
PREFACE
These calculations are done according to, and consistent with recommendations contained in the National Council on Radiation Protection and Measurements (NCRP) Report No. 147 “Structural Shielding Design for Medical X-Ray Imaging Facilities” and Report No. 151 “Structural Shielding Design and Evaluation for Megavoltage X- and Gamma-Ray Radiotherapy Facilities”. The calculations herein are based on a design limit of 20 μGy/week to members of the general public and 100 μGy/week to occupationally exposed workers whose dose is monitored. This is consistent with 10 CFR Part 20, State of Colorado Regulations 6 CCR 1007, and with the International Commission on Radiological Protection Publication No. 26 to keep exposures "As Low As Reasonably Achievable" (ALARA).
This shielding analysis applies to the specified room layout, application, workload, and occupancy of surrounding areas. If there are any changes to any of these conditions, the shielding must be re-evaluated by a Qualified Expert (QE).
BACKGROUND INFORMATION AND ASSUMPTIONS
Standard Assumptions
• Walls are assumed to include two 5/8 inch gypsum sheets, with a 3 inch interspace.
• Windows are assumed to be glass or acrylic. Windows are assumed to have zero lead equivalence.
Facility Description
• Multi-story building, x-ray room on the first floor.
• Floor to floor distance of 12 ft assumed.
• Floor construction: at least one inch of normal density concrete in the floor above is assumed.
Occupancy
• Full occupancy above the x-ray room is assumed. First floor is slab on grade.
• Refer to the attached diagram for occupancy adjacent to the x-ray room.
Workload
• For x-ray: 100 radiographic exposures (equivalent to 50 patients) per week.
SHIELDING SPECIFICATIONS
1. The control room window requires a minimum of 6 mm plate glass.
2. The door may be any type of door. Shielding is not required.
3. Please refer to the enclosed color-coded diagram for the specified shielding.
4. It is important to note that the recommended shielding is the minimum thickness required. However, it may turn out that a thicker lead is less expensive or more easily available. In that case, it is advisable to use the thicker lead as a cost-effective alternative.
5. Records of shielding must be maintained by the facility, available for inspection, as required by 6CCR 1007-1 Part 6, RH 6.3.2.3.
SHIELDING NOTES
1. Lead barriers should extend to a height of 7 feet unless otherwise specified.
2. All lead seams and joints should be overlapped with adjacent shielding. Screw holes created while hanging the lead do not require lead caps.
3. All penetrations of the lead shielding (electrical outlets, light fixtures, locksets, switches , pipes, ducts, etc.) must be shielded by placing equivalent lead shielding behind the penetration with sufficient overlap to prevent a direct "line of sight" path from the x-ray tube or patient. Special designs may be necessary for large penetrations. Design of shielding for major penetrations should be reviewed by the
QE.
4. All doors should be shielded with lead thickness equal to or greater than that of the adjacent wall. Doors should extend as close to the floor as possible. Locksets and door frames must also provide equivalent lead protection. Often steel doors can be substituted for lead lined doors. Consult the QE if you wish to pursue that option.
5. Windows must have a lead equivalence equal to or greater than that of the wall in which they are mounted. Window frames must also be shielded to overlap both the window and adjacent wall. If only minimal shielding is required, plate glass may be specified. If so, special attention must be given to transparency of laminated sheets of glass. Windows must be sized and positioned so that operators of various heights may view the patient.
6. A survey should be conducted by a registered medical physicist to verify adequacy and proper installation of shielding, x-ray equipment, and radiation safety program within 3 months of the installation. For CT and fluoroscopy rooms, the survey should be completed prior to patient exams.
7. Any barriers specified in concrete shall have a density of 147 lbs/cu ft unless otherwise specified. Any structures embedded in the concrete (conduits, switchboxes,etc.) may require compensating shielding. Barriers specified in wallboard should be sheets of 5/8" or thicker type "X" wallboard with seams arranged in a non-overlapping fashion.
DESIGN REQUIREMENTS FOR AN OPERATOR'S BOOTH
(From Colorado Department of Public Health and Environment Regulations, Part 6 Appendix 6B)
6B.1 Space Requirements:
6B.1.1 The operator shall be allotted not less than 0.7 m2 (8 ft2) of unobstructed floor space in the booth.
6B.1.2 The operator's booth may be of any geometric configuration with no dimension less than 0.6 m (2 ft).
6B.1.3 The space shall be allotted excluding any encumbrance by the x-ray control panel, such as overhang, cables, or other similar encroachments.
6B.1.4 The booth shall be located or constructed such that unattenuated scatter radiation originating on the examination table or at the wall cassette cannot reach the operator's location within the booth.
6B.2 Structural Requirements:
6B.2.1 The booth walls shall be permanently fixed barriers at least 2 m (6.5 ft) high.
6B.2.2 When a door or movable panel is used as an integral part of the booth structure, it must have an interlock that will prevent an exposure when the door or panel is not closed in its shielding position.
6B.2.3 Shielding shall be provided to meet the requirements of Part 4.
6B.3 Viewing System Requirements:
6B.3.1 Each booth shall have at least one viewing device that will:
(1) Be so placed that the operator can view the patient during any exposure, and
(2) The device shall be so placed that the operator can have full view of any occupant of the room and should be so placed that the operator can view any entry into the room. If any door that allows access to the room cannot be seen from the booth, then that door must have either an interlock controlling the exposure that will prevent the exposure if the door is not closed; or a warning light must be activated at the control panel when the door is opened.
6B.3.2 When the viewing system is a window, the following requirements also apply:
(1) The viewing area shall be at least 0.1 m2 (1 ft2).
(2) The design of the booth shall be such that the operator's expected position when viewing the patient and operating the x-ray system is at least 0.5 m (1.5 ft) from the edge of the booth.
(3) The material constituting the window shall have at least the same lead equivalence as that required in the booth's wall in which it is mounted.
6B.3.3 When the viewing system is by mirrors, the mirror(s) shall be so located as to accomplish the general requirements of 6B.3.1.
7'-2"
TABLE TOP
FRONT
2' -8
TA
BL
E
TO
P
1'
1.2.3.
D
IM
EN
SIO
N
S IN
D
IC
ATED
AR
E TO
FAC
E O
F FIN
ISH
M
ATER
IAL O
F
PAR
TITIO
N
O R
W
ALL AN
D G
R
ID
LIN
ES, U
O N
VER
IFY & C
O O
R D
IN
ATE ALL R
EQ
U
IR
EM
EN
TS FO
R O
W N
ER
FU
R N
ISH
ED
ITEM
S PR
IO
R
TO
PER
FO
R M
AN
C
E O F W
O R
K TH
AT M
AY IN
TER
FAC
E W
ITH
SU
C
H
ITEM
S.
PR
O
VID
E PAIN
TED
AC
C
ESS PAN
ELS IN
W
ALLS & C
EILIN
G
S AT
C O
N C
EALED
ITEM
S, SU
C
H
AS VALVES, C
O N
TR
O
LS, SW
ITC
H
ES O
R
AN
Y O
TH
ER
ITEM
S TH
AT R
EQ
U
IR
ES AC
C
ESS. G
C
TO
D
ETER
M
IN
E AC
C
ESS
PAN
EL LO
C
ATIO
N W
/ AR
C
H
ITEC
T PR
IO
R
TO
IN
STALLTIO
N
FLO
O
R
PLA
N
G
EN
ER
A
L N O
TES
109 SF
O
FFIC
E
111 SF
O
FFIC
E
112 SF
O
FFIC
E
237 SF
X-R A
Y R O
O M
8A
259 SF
W A
ITIN
G
A R
EA
138A
8B
9B
X-R
AY TABLE
BY O
W
N
ER
X-RAY
CONTROL,
PHONE
2' - 0"
H
ALLW
AY
C
LASSR
O O
M
H
ALLW
AY
PU
BLIC
LO
U
N G
E
AR
EA
7' - 1"
5' - 0" 135.00°
9' - 6"
W
3' - 0"
3' - 0"
6' - 5 3/4"
9' - 5 1/4" 7' - 7"
7' - 7"
109 SF
O
FFIC
E
111 SF
O
FFIC
E
112 SF
O
FFIC
E
237 SF
X-R A
Y R O
O M
R C
P G
EN
ER
A
L N O
TES
1.
R
EFER
TO
M
EP AN
D
AV/IT D
R
AW
IN
G
S FO
R
AD
D
ITIO
N
AL IN
FO
R M
ATIO
N
2.
PR
O
TEC
T EXISTIN
G
AC
O
U
TIC
C
EILIN
G
TILE SYSTEM
TH
AT W
ER
E
O
PEN
ED
U
P D U
R
IN
G D
EM
O
LITIO
N
O R
FO
R
N
EW
M
EPT ABO
VE C
EILIN
G
W O
R K. R
EPLAC
E C
EILIN
G
TILES D
AM
AG
ED
D U
R
IN
G R
EN
O
VATIO
N
TYPE C
M R
S.M
AR
TIN
R
AISED
H
ELVETIC
A M
ED
IU
M
TEXT, TYP.
BR
AILLE, TYP.
AC
R
YLIC
W
IN
D
O W
O
PEN
AT
BO
TH
EN
D
S FO
R C
H
AN
G
ABLE
TEXT (BY O
W
N
ER
R
1 1/2" 1" 1"
7"
7"
2N D
G R
AD
E
W
2' - 6"4' - 0"
5' - 0"
6' - 6"
0' - 2"
6" 6"
6' - 6" 6"
N
3' - 6"
4' - 0"
7' - 0"
2" 4' - 0"
2"
7' - 0" 2"
A
N o.
D ate
R evision
H ord C oplan M acht, Inc.
AR
C
H
ITEC
TU
R
E
LAN
D
SC
APE AR
C H
ITEC
TU
R E
PLAN
N
IN
G
IN
TER
IO
R
D
ESIG
N
D raw ing
D raw n By
D ate (YYYY/M
M /D
D
A R
C H
ITEC
T
Project N um ber
Project N am e
A B C D E
C hecked By
M
/E/P EN
G
IN
EER
C ator R um a & Associates C o
896 Tabor St #1 Lakew ood, C O
80401 p.
303. 232. 6200
H ord C oplan M acht, Inc.
1800 W azee Street, Suite 450
D enver, C
O 80202 p.
303.607.0977 f.
303.607.0767
Autodesk Docs://224089 CMC Edwards Radiology/224089 - CMC Edwards Radiology - R22.rvt9/5/2024 5:16:12 PM
EDWARDS RADIOLOGY LAB
RENOVATION
150 Miller Ranch Rd Edwards, CO 81632
D
ESIG
N D
EVELO
PM
EN
T
2024/09/20
H C
M
COLORADO MOUNTAIN COLLEGE224089
A-111
FIR
ST FLO
O
R
PLAN
ED
W
AR
D
S R
AD
IO
LO
G
Y LAB
R
EN
O
VATIO
N
H C
M
1/4" = 1'-0" A
FIR
ST FLO
O
R
PLA
N
SH
EET N
O
TES - FLO
O R
PLAN
S
N O
TE #
N
O
TE
8A N
EW
4'-0 W
ID
E W
O O
D D
O O
R
AN
D H
M
FR
AM
E
8B N
EW
4'X4' LEAD
SH
IELD
ED
W
IN
D
O W
N
EW
LVT FLO
O R
IN
G
AN
D
R U
BBER
BASE
9B
PAIN
T ALL W
ALLS
PR
O
VID
E N
EW
R O
O M
PAN
EL SIG
N
TO
M
ATC
H
(E) PAN
EL SIG
N
S O N
SITE. LO
C
ATE AD
JAC
EN
T TO
N
EW
D O
O R
FR
AM
E.
W
ALL M
O U
N
TED
G
EN
ER
ATO
R
BY O
W N
ER
SU
R
FAC
E M
O U
N T C
ABLES FO
R
X-R
AY TABLE FR
O M
G
EN
ER
ATO
R
PR
O
VID
E C
ABLE C
O
VER
O
N
FLO
O R
W H
ER
E EXPO
SED
1/4" = 1'-0" B
FIR
ST FLO
O
R R
EFLEC
TED
C
EILIN
G
PLA
N
SIG
N
A G
E TYPESSIG
N
AG
E SC
H
ED
U
LE
Signage D oor
M ark
Signage Type Signage N um ber
Signage Text Signage Placem ent C om m ents
C
X-R
AY R
O O
M C
O R
R
ID
O R
H O
LLO
W
M
ETA
L LEA
D
LIN
ED
W
IN
D O
W
FRA
M E
TYPES
D
O O
R TYPES
FRA
M
E TYPES
2 layers 5/8” gypsum 3 layers 5/8” gypsum 6 m m plate glass
1/32” Lead
Lead needs to extend at least 1 foot beyond edges of w all receptor.
1 ft 1 ft
Text
1/64” Lead
RADIO
GRAPHIC SHIELDIN
G AN
ALYSIS SU
M M
ARY
Colorado M ountain College - Edw ards
X-ray Lab Floor M ounted X-ray System
N um ber of patients per w eek
U nits
Location Control
Control W indow
O ffice
H allw ay Classroom
Classroom Public Lounge
Above D esign G oal m G y/w k
0.1 0.1
0.02 0.02
0.02 0.02
0.02 0.02
O ccupancy
0.2
0.5 0.5
0.2
U sage Factor
0.05 0.05
Prim ary/Leakage D istance m
3.3 3.3
3.9 9.1
2.9
1.8 2.1
Secondary D istance m 3.3
3.3 3.9
8.1 1.2
2.9 1.8
3.1 Prim
ary Source RR(floor or other)
RR(floor or other) RR(chest bucky)
Secondary Source RR(all barriers)
RR(all barriers) RR(floor or other)
RR(floor or other) RR(chest bucky)
RR(all barriers) RR(all barriers)
RR(all barriers) Side or Forw ard/Backscatter Sidescatter
Sidescatter Sidescatter
Sidescatter Forw ard/Backscatter Sidescatter
Sidescatter Forw ard/Backscatter Select Preshielding
N one
G rid/cassette only
G rid/cassette only
G rid/cassette only
Table or w all bucky
N one
N one
N one
Lead Thickness m m 0.11
0.05 0.39
0.79
0.16 0.16
0.27 Concrete Thickness
m G y/w k
Expected W eekly D ose m
G y/w k 0.037
0.072 0.007
0.005 0.009
0.016 0.016
0.019 Fraction of D
esign G oal
0.373 0.719
0.358 0.245
0.451 0.789
0.819 0.947
*Existing structure N
O TES: 1) 0.11 m m lead is equivalent to 2 layers of 5/8" gypsum
; 2) for control w indow
, 6 m m plate glass is equivalent to 0.05 m m lead.
sufficient.
Inputs
| Cover update.pdf |
| CMC Edwards Radiology-Shielding_Diagram-update.pdf |
| Summary-update.pdf |
| 2024-11-07T08:31:31-0800 | |
| Agreement certified by Adobe Acrobat Sign |
File details come from the government source that posted it. Updated .