This is Addendum No. 1 for the City of Parker, Texas Parker Ranch 1.0-MG Elevated Storage Tank project, issued September 4, 2026. The project involves furnishing all necessary materials, machinery, equipment, superintendence, and labor for construction of an AWWA D107 Composite Tank with a capacity of 1.0 million gallons, including site work, piping, and all necessary appurtenances. Bids were to be received until 3:00 p.m. on Thursday, September 17, 2026. The City of Parker owns the property designated as the tank site, which is located in Collin County, Texas.
The addendum addresses clarifications regarding permitting requirements and project specifications. The City will not require a building permit for the project, and no building permits from Collin County are anticipated. Non-inspected work is permitted on Saturdays, but no work is allowed on Sundays. A critical specification clarification requires the new tank to match the existing elevated storage tank at City Hall with a 40-foot head range and maintain consistency with distribution system operations and pressures. The City will allow adjustments to the bowl diameter to achieve the required 40-foot head range while maintaining the 1.0-MG volume, departing from the contractor's standard 38-foot head range for a 70-foot diameter tank.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| City of Parker - Parker Ranch 1-MG Elevated Storage Tank - Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J:\CLERICAL\Parker\2025-130 Parker Ranch 1-MG EST\Specs\Addendum\Add. No. 1\Addendum No. 1.docx Addendum No. 1
CITY OF PARKER, TEXAS
PARKER RANCH 1.0-MG ELEVATED STORAGE TANK
ADDENDUM NO. 1
September 4, 2026
Plans and specifications for the Parker Ranch 1.0-MG Elevated Storage Tank project, for the City of Parker, Texas, on which bids are to be received until 3:00 p.m., Thursday, September 17, 2026, are hereby modified as follows:
GENERAL CLARIFICATIONS (QUESTIONS RECEIVED)
1. Question: “Will a building permit be required for this project?”
Answer: The City will not require a building permit for this project.
2. Question: “How soon must an application for a building permit be submitted”?
Answer: See response to Question No. 1 above.
3. Question: “If a building permit is required, can you please advise to what forms must be submitted”?
Answer: See response to Question No. 1 above.
4. Question: “Can you advise what documents (i.e. construction drawings) must be provided”?
Answer: See response to Question No. 1 above.
5. Question: “Once a building application has been submitted, typically how long is the review process”?
Answer: See response to Question No. 1 above.
6. Question: “Can you provide a fee schedule and/or estimated cost to obtain a building permit”?
Answer: See response to Question No. 1 above.
7. Question: “Will a building permit for Collin County also be required for this project”?
Answer: The City owns the property that will be the tank site and there is no anticipated building permits required from Collin County.
8. Question: “Due to the nature of tank erection work and the travel distance for our field personnel, working weekends is advantageous for the project from both a cost and schedule perspective.
This is even true if the work allowed on the weekends is restricted to non-inspected work. Can you confirm that weekend work will not be restricted”?
Answer: The City will allow non-inspected work on Saturdays. The City does not allow work to be performed on Sundays.
9. Question: “Our standard head range for this size tank with a 70’ tank diameter is 38’, is that acceptable”?
Answer: The City’s existing tank at City Hall has a 40-foot head range. To maintain consistency of distribution system operations and pressures, the new tank needs to match the existing tank in head range and elevations. The City will allow adjustments to the bowl diameter to achieve the 40-foot head range and 1.0-MG volume.