CC_Mckinney_-_Switchboard_Replacement_-_Elec_IFC_Drawing.pdf

PDF 13 MB Posted

Attached to
McKinney Main Building Switchboard Replacement
Solicitation number
FY2027-CSP-069
Issued by
Collin County, Texas

About this file

Switchboard Replacement Project - Electrical IFC Drawing Summary

This is an Electrical Issue for Construction (IFC) drawing package for Collin College's McKinney Campus Main Building Switchboard Replacement Project, located at 2200 W. University Drive, McKinney, Texas 75071. The project scope encompasses the removal of the existing main service entrance switchboard and switchboard MSA, replacement with a new 4,000-amp main service entrance switchboard (SB-MAIN) rated at 480Y/277V three-phase, and installation of new electrical distribution equipment throughout the facility. Work includes removal and replacement of multiple panelboards and transformers, installation of new generator docking stations, modifications to electrical feeders and branch circuits, door replacement to the electrical room with panic hardware and card reader access control, and comprehensive circuit tracing and identification across the building. The project mandates that the Campus Network Operations Center (NOC) and associated cooling equipment remain energized and operational throughout the entire construction period, including during the main service entrance switchboard replacement. The anticipated major utility shutdown is scheduled during the Collin College McKinney Campus 2027 summer break, with all work requiring completion within pre-approved service windows when campus classes are not in session.

The work is organized into six construction phases: pre-construction alternate work, NOC power securing and redundancy, pre-shutdown work, utility shutdown and critical path activities, post-shutdown and facility integration work, and finishing work. Key technical requirements include installation of a digital power meter (DPM) compatible with BACnet for integration with the campus building management system, provision of surge protection devices rated at 300kA per phase minimum, system commissioning by both the contractor and the electrical distribution manufacturer, and complete tracing and identification of all existing circuits with typewritten panel schedules in Excel format. Copper conductors (#10 and smaller must be solid) and compliance with the 2026 National Electrical Code and 2024 International Energy Conservation Code are required. The contractor must coordinate all work with Collin College, the serving utility (ONCOR, contact: Brian Guest, 817-980-8920), and provide detailed methods of procedure (MOP) for review at least one month before proposed shutdown windows, with owner approval required at least two weeks in advance of any shutdown.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COLLIN COLLEGE

MCKINNEY

2200 W UNIVERSITY DR

MCKINNEY, TX, 75071

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222 Project

SWITCHBOARD REPLACEMENT

ISSUE FOR CONSTRUCTION

2026-10-06

2200 W. UNIVERSITY DRIVE, MCKINNEY, TEXAS 75071

COLLIN COLLEGE MCKINNEY

MAIN BUILDING

26126-00

ISSUE FOR CONSTRUCTION 2026-10-06

PROJECT ISSUANCES:

DESCRIPTION DATE

NO SCALE

MAP - COLLIN COLLEGE MCKINNEY↑

PROJECT SHEET LIST

SHEET NO. SHEET NAME SHEET ISSUE DATE

ARCHITECTURAL

A101 ARCHITECTURAL FLOOR PLANS 2026.10.06

ELECTRICAL

E0.01 GENERAL NOTES & LEGENDS - ELECTRICAL 2026.10.06

E1.01 SITE PLAN - ELECTRICAL 2026.10.06

E2.01 OVERALL FLOOR PLAN - LEVELS 1 & 2 - ELECTRICAL 2026.10.06

E2.02 OVERALL FLOOR PLAN - LEVELS 3 & ROOF - ELECTRICAL 2026.10.06

E4.01 ENLARGED PLANS - ELECTRICAL 2026.10.06

E5.01 DETAILS - ELECTRICAL 2026.10.06

E6.01 ONE-LINE DIAGRAMS - ELECTRICAL 2026.10.06

E7.01 PANEL SCHEDULES - ELECTRICAL 2026.10.06

Grand total: 9

G

M

A P V

SPD

PNL

'A1'

A

DPM

1. THE INFORMATION ON THE EXISTING DRAWINGS ARE NOT FROM "AS BUILT" DRAWINGS

OR FIELD SURVEY, BUT FROM ORIGINAL DRAWINGS AND SITE INVESTIGATIONS. THIS

INFORMATION IS INCLUDED FOR REFERENCE ONLY. CONTRACTOR WILL BE

RESPONSIBLE FOR VISITING THE SITE PRIOR TO SUBMITTING A BID TO DETERMINE THE

AMOUNT OF WORK THAT WILL BE REQUIRED. CONTRACTOR SHALL EXAMINE THE

EXISTING BUILDING AND GENERALLY VERIFY THE LOCATION OF ALL EXISTING WORK

AND BECOME INFORMED AS TO THE RELATION TO AND EFFECT ON THE WORK

REQUIRED BEFORE SUBMITTING A BID. SUBMISSION OF A BID WILL CONSTITUTE

EVIDENCE THAT THE CONTRACTOR HAS INSPECTED THE SITE OF THE PROPOSED

WORK.

2. EXISTING MEP ITEMS TO BE REMOVED SHALL BE RETURNED TO THE OWNER OR

DISPOSED OF AS DIRECTED BY THE DESIGNATED OWNER'S REPRESENTATIVE.

3. COORDINATE DEMOLITION WORK WITH THE BUILDING MAINTENANCE PERSONNEL AND

OTHER TRADES PERFORMING WORK IN THE BUILDING PRIOR TO THE REMOVAL OF

ANY ITEMS OF EQUIPMENT OR SYSTEMS THAT WILL AFFECT OTHER SYSTEMS WITHIN

THE LIMIT OF NEW CONSTRUCTION OR OTHER AREAS OF THE BUILDING. CONTRACTOR

SHALL VERIFY WITH THE OWNER IF THE BUILDING WILL BE OCCUPIED DURING

CONSTRUCTION. ANY REQUIRED OUTAGES MUST BE COORDINATED WITH THE

OWNER.

4. PRIOR TO THE REMOVAL OF ANY MEP ITEMS OF EQUIPMENT, CONTRACTOR MUST

VERIFY THE ORIGIN AND TERMINATION OF THOSE SYSTEMS AND CONFIRM THAT THE

ITEMS BEING REMOVED DO NOT SERVE ANY ITEMS THAT ARE TO REMAIN (INCLUDING

THOSE IN AREAS OUTSIDE THE CONTRACT LIMITS).

5. DO NOT ABANDON ANY ITEMS IN PLACE. REMOVE ALL COMPONENTS ASSOCIATED

WITH EACH ITEM CALLED OUT TO BE REMOVED.

GENERAL DEMOLITION NOTES:

1. ALL WORK SHALL COMPLY WITH APPLICABLE NATIONAL, STATE, AND LOCAL CODES,

RULES, REGULATIONS, AND REQUIREMENTS OF THE SERVICE UTILITY COMPANY.

2. ALL WORK SHALL COMPLY WITH THE BUILDING OWNER’S CONSTRUCTION

GUIDELINES.

3. ALL CONDUCTORS SHALL BE COPPER (#10 AND SMALLER SHALL BE SOLID).

4. WHERE CONDUCTOR SIZES ARE NOTED ON DRAWINGS AND/OR SCHEDULES, THAT

CONDUCTOR SIZE SHALL BE THROUGHOUT THE ENTIRE RUN, UNLESS NOTED

OTHERWISE.

5. PANELBOARD DIRECTORIES SHALL BE COMPLETELY FILLED OUT TO ACCURATELY

IDENTIFY EACH CIRCUIT (EXISTING AND NEW CIRCUITS) IN ALL PANELS WITHIN SCOPE

OF WORK. DIRECTORIES SHALL BE TYPEWRITTEN.

6. ELECTRIC CONNECTIONS TO ELECTRICAL DISTRIBUTION EQUIPMENT SHALL BE MADE

ONLY WHEN SUCH EQUIPMENT HAS BEEN DE-ENERGIZED.

7. ALL ELECTRICAL EQUIPMENT, SUCH AS PANELS, SWITCHBOARDS, TRANSFORMERS,

DISCONNECTS, ETC, SHALL HAVE PERMANENT ENGRAVED LABELS AS SHOWN ON

EQUIPMENT IDENTIFICATION DETAIL.

8. THE CONTRACTOR SHALL UPDATE ROOM NAMES AND ROOM NUMBERS ON FINAL

PANEL SCHEDULES TO REFLECT FINAL BUILDING CONDITIONS.

GENERAL POWER NOTES:

CEILING MOUNTED RECTANGULAR LIGHT FIXTURE

(HATCHING INDICATES EMERGENCY FIXTURE)

LIGHT SWITCH - SINGLE / THREE WAY / FOUR WAY

MANUAL MOTOR STARTER

LOW VOLTAGE SCENE SWITCH

MOTION OCCUPANCY / VACANCY SENSOR -

WALL / CEILING MOUNTED

M

L

SWITCH WITH OCCUPANCY SENSORO

OC

SWITCH WITH SWITCH LEG DESIGNATIONa

WALL MOUNTED RECTANGULAR LIGHT FIXTURE

(HATCHING INDICATES EMERGENCY FIXTURE)

PENDANT/SUSPENDED RECTANGULAR LIGHT FIXTURE

(HATCHING INDICATES EMERGENCY FIXTURE)

OC

c

LIGHTING LEGEND

NOT ALL SYMBOLS USED

EXISTING WORK TO REMAIN

EXISTING WORK TO BE REMOVED

NEW WORK

J

RACEWAY IN WALL OR ABOVE CEILING

RACEWAY IN OR BELOW FLOOR

DISCONNECT SWITCH

JUNCTION BOX - WALL / FLOOR / CEILING MOUNTED

DUPLEX RECEPTACLE -

WALL / FLOOR / CEILING MOUNTED

QUADRAPLEX RECEPTACLE -

WALL / FLOOR / CEILING MOUNTED

MOTOR CONNECTION

SPECIAL RECEPTACLE

(NUMBER DENOTES AMPERAGE RATING)

480V PANELBOARD

208V PANELBOARD

DISTRIBUTION PANELBOARD

DRY-TYPE TRANSFORMER

NOT ALL SYMBOLS USED

J

FUSED DISCONNECT SWITCH

VARIABLE FREQUENCY DRIVE (VFD)

POWER LEGEND

EXISTING WORK TO REMAIN

EXISTING WORK TO BE REMOVED

NEW WORK

J

NOT-IN-SCOPE AREA

NOT-IN-SCOPE AREA

SAMPLE TAG: 60/2/50AF

60 = 60A; 2 = 2 POLES;

50AF = 50A FUSE

(NF = NON-FUSED DISC)

1. ALL WORK SHALL BE PERFORMED DURING PRE-APPROVED SERVICE WINDOWS WHEN

CAMPUS CLASSES ARE NOT IN SESSION. COORDINATE WORK WINDOW DATES WITH

BOTH COLLIN COLLEGE AND MCKINNEY CAMPUS FACILITIES GROUPS PRIOR TO

STARTING WORK.

2. ALL WORK SHALL BE COMPLETED AND FULLY COMMISSIONED PRIOR TO THE END OF

THE SERVICE WINDOW.

WORK DURING APPROVED WORK WINDOW:

1. THE SYSTEM SHALL BE FULLY COMMISSIONED BY THE CONTRACTOR AND THE

ELECTRICAL DISTRIBUTION MANUFACTURER AT THE END OF THE PROJECT TO

ENSURE THAT THE NEW SWITCHBOARDS, PANELBOARDS, AND POWER MONITORING

SYSTEM ARE IN FULL WORKING ORDER.

2. ALL TESTING AND METHODS OF PROCEDURE (MOPS) SHALL BE CREATED BY THE

CONTRACTOR AND SHALL BE APPROVED BY THE COLLIN COLLEGE AND THE

ENGINEER.

SYSTEM COMMISSIONING:

AVAILABLE FAULT CURRENT TAG (AMPERES)

FEEDER KEY TAG (REFER TO SCHEDULE)

PANELBOARD | DISTRIBUTION PANEL

ELECTRICAL EQUIPMENT ENCLOSURE

CIRCUIT BREAKER

ENCLOSED CIRCUIT BREAKER

AUTOMATIC TRANSFER SWITCH (ATS)

GENERATOR

GROUND

FUSE

SWITCH / DISCONNECT

FUSED SWITCH / DISCONNECT

MOTOR SWITCH / STARTER

VARIABLE FREQUENCY DRIVE SWITCH

TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

TRANSFORMER DELTA

TRANSFORMER WYE

EQUIPMENT LOAD

EQUIPMENT LOAD: RESISTIVE ONLY

EQUIPMENT MOTOR

GENERIC METER AND SUBCATEGORY

AMPERAGE / POWER / VOLTAGE METER

SURGE PROTECTION DEVICE

UTILITY SERVICE

WIRE CONTINUATION

TERMINAL

12,345

100.4C

X

NOT ALL SYMBOLS USED

ONE-LINE DIAGRAM LEGEND

ELEVATOR DISCONNECT

WIRE CONTINUATION CONNECTION GUIDE

DIGITAL POWER METER, BACNET COMPATIBLE

1. ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL CIRCUITS, SPACES, AND SPARES

SERVED FROM ALL DISTRIBUTION EQUIPMENT WITHIN THE SCOPE OF THE PROJECT.

TRACE EXISTING FEEDERS AND BRANCH CIRCUITS. PROVIDE PANELBOARDS WITH A

TYPEWRITTEN CIRCUIT DIRECTORY DESCRIBING THE NAME OF THE LOAD AND THE

ROOM NUMBER WHERE THE LOAD IS LOCATED. PROVIDE DIGITAL COPIES OF CIRCUIT

DIRECTORIES IN EXCEL (.XLSX) FORMAT. PROVIDE DISTRIBUTION PANELBOARDS WITH

PLACARDS ADJACENT TO EACH BRANCH CIRCUIT BREAKER DESCRIBING THE LOAD

AND ITS LOCATION. REFER TO OTHER GENERAL NOTES ON THIS SHEET FOR

ADDITIONAL INFORMATION.

2. DISTRIBUTION EQUIPMENT WITHIN BASE PROJECT SCOPE: 'LS', 'L1E', 'L1EA', 'HS', AND

'H1E', AND SWITCHBOARD 'MSA'.

3. DISTRIBUTION EQUIPMENT WITHIN ALTERNATE 1 PROJECT SCOPE: '1H', '1L', '2H', '2L', '2LC', '2LN', '2LN2', '2PN', '3LN', '3PN', 'CP', 'DPHE', 'DPHW', 'DPLA', 'DW3', 'H1W', 'H2E', 'H2W', 'H3E', 'H3W', 'H4E', 'H4W', 'HE', 'H-LAB', 'HSA', 'HSB1', 'HSB2', 'K', 'K1', 'K2' (AKA 'PN'), 'KH', 'KL', 'L1A', 'L1A2', 'L1W', 'L1WA', 'L1WB', 'L2E', 'L2EA', 'L2W', 'L2WA', 'L2WB', 'L2WC', 'L2WD', 'L2WE', 'L3E', 'L3EA', 'L3W', 'L3W1', 'L3W2', 'L3WA', 'L3WB', 'L3WC', 'L3WD', 'LB2', 'LB3', 'LCR', 'LCRA', 'LIDA', 'LIDB', 'LK', 'LKS', 'LN', 'LN2', 'LN3', 'LN4', 'LSA', 'LSB1', 'LSB2', 'MCC-2N', 'MCC-PN', 'MDPS', 'MSB', 'PLN', AND 'UNNAMED' (ROOM C225).

4. REFER TO ELECTRICAL DISTRIBUTION SCHEDULE ON THIS SHEET FOR ADDITIONAL

INFORMATION ON EACH PANEL LISTED ABOVE.

TRACING OF EXISTING FEEDERS AND

BRANCH CIRCUITS:

THE FOLLOWING CODES HAVE BEEN ADOPTED BY THE CITY OF MCKINNEY:

• 2026 NATIONAL ELECTRICAL CODE

• 2024 INTERNATIONAL ENERGY CONSERVATION CODE

RELEVANT ADOPTED CODES:

RECORDED MAXIMUM EXISTING DEMAND LOAD

ADJUSTMENT FACTOR PER NEC 220.87 (x125%)

TOTAL REMOVED LOAD

TOTAL ADDED LOAD

NET TOTAL

KVA AMP

991.88

991.88

1,193

1,193

VOLTAGE: 480 V PHASE: 3-PH

793.50

0.00

0.00

LOAD CALCULATION SUMMARY: 'MSB'

RATING: 4000 A

B-4

HOMERUN : PANEL NAME-CIRCUIT NUMBER(S).

THE WORD "ON" IS ADDED WHEN THE CIRCUIT FEEDING

CONTENTS FROM THIS HOMERUN ALSO FEEDS CONTENT

ELSEWHERE

REFER TO THE FOLLOWING AND ENSURE THE CAMPUS NETWORK OPERATIONS CENTER

(NOC) AND ASSOCIATED COOLING EQUIPMENT REMAIN OPERATIONAL THROUGHOUT THE

DURATION OF THE PROJECT, INCLUDING DURING THE REPLACEMENT OF THE MAIN

SERVICE ENTRANCE SWITCHBOARD:

PLANNING & COORDINATION:

1. DRAFT A DETAILED METHOD OF PROCEDURE (MOP) EXPLAINING HOW THE NOC WILL

REMAIN POWERED.

2. REVIEW THE MOP AND SCHEDULE ALL SERVICE SHUTDOWNS WITH THE COLLEGE FOR

APPROVAL.

3. CONFIRM WHETHER THE EXISTING GENERATOR OR A TEMPORARY FEEDER FROM

PANEL H1B (AT WELCOME CENTER) WILL BE USED.

A. REFER TO SITE PLAN ON SHEET E1.01 FOR INFORMATION ON THE LOCATION OF

THE EQUIPMENT NOTED ABOVE.

IMPLEMENTATION & TRANSITION:

1. ROUTE AND CONNECT TEMPORARY CABLES FROM THE SELECTED SOURCE TO THE

NOC AND COOLING EQUIPMENT AS NEEDED. NOTE THAT THE GENERATOR IS ALREADY

CONNECTED TO PANEL 'LCR' IN THE NOC SPACE. REFER TO ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

2. SAFELY SWITCH THE NOC AND ITS COOLING SYSTEMS OVER TO THE TEMPORARY

POWER SOURCE.

3. CONFIRM THE COOLING UNITS AND NOC ARE RUNNING STABLY BEFORE PROCEEDING.

SWITCHBOARD REPLACEMENT & RESTORATION:

1. SHUT DOWN, REMOVE, AND REPLACE THE MAIN SERVICE ENTRANCE SWITCHBOARD.

2. POWER UP THE NEW SWITCHBOARD AND TEST IT UNDER LOAD.

3. SWITCH THE NOC AND COOLING EQUIPMENT BACK TO THE PERMANENT MAIN SYSTEM

AND REMOVE ALL TEMPORARY GEAR.

NETWORK OPERATIONS CENTER POWER:

GENERAL

1. CONTRACTOR SHALL COORDINATE ALL WORK WITH OWNER, ENGINEER, AND SERVING

UTILITY. PERFORM WORK DURING APPROVED SERVICE WINDOWS AND MAINTAIN

NETWORK OPERATIONS CENTER (NOC) OPERATION THROUGHOUT THE UTILITY

SHUTDOWN. CONTRACTOR SHALL SEQUENCE THE WORK IN SUCH A WAY AS TO

MINIMIZE THE UTILITY SERVICE INTERRUPTION.

2. FOR EACH SCOPE OF WORK, CONTRACTOR SHALL PROVIDE A METHOD OF

PROCEDURE (MOP) FOR REVIEW AT LEAST ONE MONTH BEFORE THE PROPOSED

SHUTDOWN WINDOWS. THE OWNER MUST APPROVE ALL SHUTDOWNS AT LEAST TWO

WEEKS IN ADVANCE OF THE PROPOSED SHUTDOWN WINDOW.

PHASE 1: PRE-CONSTRUCTION ALTERNATE WORK

1. IF ALTERNATE #1 BID IS AWARDED, COMPLETE THIS WORK BEFORE THE MAIN

ELECTRICAL ROOM SHUTDOWN SEQUENCE.

PHASE 2: NOC POWER SECURING AND REDUNDANCY

1. ENSURE THAT ALL CRITICAL NOC EQUIPMENT IS CIRCUITED TO ELECTRICAL PANELS

PROVIDED WITH STANDBY GENERATOR POWER. THIS SHOULD INCLUDE ALL

TECHNICAL POWER AND HVAC EQUIPMENT REQUIRED TO OPERATE THE NOC.

2. PROVIDE, TEST, AND COMMISSION NEW GENERATOR DOCKING STATIONS AT EXISTING

GENERATOR. ENSURE LEAD TIME FOR GENERATOR DOCKING STATIONS DO NOT

CONFLICT WITH MAIN ELECTRICAL ROOM SHUTDOWN SEQUENCE.

3. COORDINATE WITH FACILITY’S NOC PERSONNEL TO TRANSFER NOC LOADS TO

EXISTING GENERATOR.

4. PROVIDE TEMPORARY SOURCE OF EMERGENCY POWER DURING TIME WHEN

EXISTING GENERATOR IS DISCONNECTED AND OFFLINE.

PHASE 3: PRE-SHUTDOWN WORK

1. VERIFY GENERATOR DOCKING STATION COMPATIBILITY WITH TEMPORARY

GENERATOR CONNECTION.

2. VERIFY NOC EMERGENCY POWER OPERATION. FUEL AND MAINTAIN EXISTING

GENERATOR FOR THE ENTIRE ANTICIPATED SHUTDOWN. ESTABLISH PROCEDURES

FOR IMMEDIATE CONNECTION OF TEMPORARY GENERATOR THROUGH DOCKING

STATION IF EXISTING GENERATOR BECOMES UNAVAILABLE. REFER TO “NETWORK

OPERATIONS CENTER POWER” NOTES ABOVE FOR ADDITIONAL INFORMATION.

3. COORDINATE UTILITY SHUTDOWN AND OBTAIN REQUIRED OWNER, UTILITY, AND

OTHER APPLICABLE APPROVALS. ANTICIPATED MAJOR UTILITY SHUTDOWN IS

EXPECTED AT A POINT DURING THE COLLIN COLLEGE MCKINNEY CAMPUS 2027

SUMMER BREAK.

4. DURING PRE-APPROVED AFTER HOURS AND/OR WEEKEND SHUTDOWNS, COMPLETE

ALL WORK THAT CAN BE PERFORMED WITHOUT UTILITY SERVICE INTERRUPTION,

INCLUDING:

A. ISOLATE AND LOCK-OUT/TAG-OUT DISCONNECTS ON SWITCHBOARD ‘MSA’

FEEDING EXISTING EQUIPMENT TO BE REMOVED.

B. REMOVE EXISTING PANELBOARDS, TRANSFORMERS, WALL-MOUNTED EQUIPMENT,

AND WIREWAYS.

C. IDENTIFY, LABEL, AND PROTECT EXISTING FEEDERS AND BRANCH-CIRCUIT

CONDUCTORS TO BE REUSED.

D. COMPLETE ACCESSIBLE CRAWLSPACE FEEDER MODIFICATIONS AND REMOVE

FEEDER DESIGNATED FOR COMPLETE REMOVAL.

E. REMOVE EXISTING DOOR AND DOOR FRAME.

F. EXPAND MASONRY OPENING AND INSTALL NEW DOUBLE-DOOR FRAME AND DOOR

LEAVES, INCLUDING NEW CARD READER AND ACCESS-CONTROL WIRING.

G. ACCESS CRAWLSPACE TO PRE-INSTALL NEW PULL BOXES, ROUTE CONDUIT

ADDITIONS, AND PREP UNDERGROUND FEEDERS FOR SHIFTING.

H. PREPARE FEEDER ROUTES, JUNCTION BOXES, WIREWAYS, AND OTHER

INFRASTRUCTURE INSIDE ROOM B102 THAT CAN BE COMPLETED BEFORE

SHUTDOWN.

I. PREPARE ACTIVE NEGATIVE-PRESSURE HEPA FILTRATION AND EXHAUST

VENTILATION OUT OF BUILDING FOR UPCOMING CONCRETE POUR AND CURING

TIMEFRAME.

PHASE 4: UTILITY SHUTDOWN — CRITICAL PATH

1. DO NOT BEGIN UTILITY SHUTDOWN UNTIL:

A. NEW SWITCHBOARD AND ALL COMPONENTS REQUIRED FOR RESTORATION ARE

ON SITE, COMPLETE, AND VERIFIED READY FOR INSTALLATION.

B. REQUIRED MATERIALS AND MANPOWER ARE AVAILABLE.

C. NOC GENERATOR/DOCKING STATION ARE OPERATIONAL.

D. DOOR REPLACEMENT IS COMPLETE.

E. CONTRACTOR HAS DEMONSTRATED READINESS TO PROCEED CONTINUOUSLY

THROUGH RESTORATION OF UTILITY SERVICE.

2. TRANSFER NOC LOADS TO GENERATOR. VERIFY NOC EQUIPMENT AND COOLING

SYSTEM ARE OPERATIONAL.

3. EXECUTE UTILITY SOURCE LOCK-OUT/TAG-OUT TO COMPLETELY DE-ENERGIZE AND

ISOLATE THE INCOMING SERVICE. VERIFY ABSENCE OF VOLTAGE.

4. DISCONNECT, LABEL, AND PROTECT EXISTING SERVICE FEEDERS, GROUNDING

ELECTRODE CONDUCTORS, AND FEEDERS SERVING EQUIPMENT TO REMAIN.

5. SECTIONALIZE, RIG OUT, AND REMOVE THE EXISTING SERVICE ENTRANCE

SWITCHBOARD AND ‘MSA’ SWITCHBOARD.

6. REMOVE EXISTING CONCRETE EQUIPMENT PADS AND PROTECT EXISTING

CONDUIT/STUB-UPS TO REMAIN.

7. COMPLETE REQUIRED FLOOR/DECK CORE DRILLING, BOTTOM-ENTRY FEEDER STUB-

UPS, AND RELATED MODIFICATIONS.

8. DEPLOY ACTIVE NEGATIVE-PRESSURE HEPA FILTRATION AND EXHAUST VENTILATION

OUT OF BUILDING.

9. INSTALL NEW EQUIPMENT CONCRETE PAD. PROVIDE RAPID-STRENGTH CONCRETE OR

OTHER APPROVED METHOD CAPABLE OF ACHIEVING REQUIRED INSTALLATION

STRENGTH WITHIN THE APPROVED SHUTDOWN SCHEDULE. DO NOT INSTALL

SWITCHBOARD UNTIL REQUIRED CONCRETE STRENGTH HAS BEEN ACHIEVED.

10. INSTALL AND ANCHOR NEW MAIN SERVICE ENTRANCE SWITCHBOARD ‘SB-MAIN’.

ENSURE EACH ENCLOSURE SECTION APPROPRIATELY ALIGNS WITH BOTTOM-ENTRY

FEEDER STUB-UPS.

11. INSPECT EXISTING CONDUCTORS FOR SERVICE FEEDER AND ‘MSB’ FEEDER AND

EXTEND CONDUCTORS VIA COMPRESSION BARRELS AND HEAT-SHRINK IF REQUIRED.

12. CONNECT EXISTING SERVICE FEEDER CONDUCTORS AND ‘MSB’ FEEDER

CONDUCTORS.

13. CONNECT GROUNDING ELECTRODE CONDUCTORS AND REMAINING

FEEDER/RACEWAY CONNECTIONS.

14. COMPLETE REQUIRED TESTING, INSPECTIONS, AND UTILITY APPROVAL.

15. REMOVE UTILITY SOURCE LOCK-OUT/TAG-OUT AND RESTORE UTILITY SERVICE AS

SOON AS NEW SERVICE EQUIPMENT IS READY FOR ENERGIZATION.

16. VERIFY VOLTAGE, PHASE ROTATION, GROUNDING, AND NORMAL SWITCHBOARD

OPERATION.

PHASE 5: POST-SHUTDOWN AND FACILITY INTEGRATION WORK

1. INSTALL NEW TRANSFORMER RACKS AND TRANSFORMERS.

2. INSTALL NEW PANELBOARDS AND RECONNECT/EXTEND EXISTING BRANCH CIRCUITS

AND FEEDERS. MATCH CIRCUIT NUMBERS AND BREAKER SIZES/TYPES AS REQUIRED.

REFER TO ALTERNATE 1 WORK, IF AWARDED.

3. INSTALL NEW WIREWAYS, JUNCTION BOXES, FEEDER CONNECTIONS, WALL-MOUNTED

EQUIPMENT, LIGHTING FIXTURES, DPM/BMS CONNECTION, AND OTHER DEVICES.

4. COMPLETE ELECTRICAL TESTING AND COMMISSIONING.

5. VERIFY NOC NORMAL/EMERGENCY POWER OPERATION AND GENERATOR DOCKING

STATION OPERATION.

6. TRANSFER NOC LOADS TO NORMAL SOURCE. VERIFY NOC EQUIPMENT AND COOLING

SYSTEM ARE OPERATIONAL.

PHASE 6: FINISHING WORK

1. COMPLETE WALL PATCHING, FLOOR REPAIRS, PAINTING, DOOR/ACCESS-CONTROL

FINISH WORK, CLEANING, AND OTHER RESTORATION.

CRITICAL REQUIREMENTS

1. UTILITY SHUTDOWN SHALL BE LIMITED TO THE MINIMUM DURATION NECESSARY TO

REMOVE EXISTING SERVICE EQUIPMENT, REPLACE THE EQUIPMENT PADS, INSTALL

AND CONNECT THE NEW SERVICE ENTRANCE SWITCHBOARD ‘SB-MAIN’, COMPLETE

REQUIRED TESTING/INSPECTION, AND RESTORE UTILITY SERVICE.

2. DO NOT EXTEND THE UTILITY SHUTDOWN SOLELY TO COMPLETE DOWNSTREAM

PANEL, TRANSFORMER, BRANCH-CIRCUIT, DEVICE, OR FINISH WORK THAT CAN

SAFELY PROCEED AFTER UTILITY SERVICE IS RESTORED.

3. MAINTAIN NOC ENERGIZED CONTINUOUSLY THROUGHOUT THE SHUTDOWN. MAINTAIN

GENERATOR FUEL AND PERSONNEL/EQUIPMENT NECESSARY TO RESPOND TO

GENERATOR FAILURE.

4. ANY CONDITION THAT MAY DELAY UTILITY RESTORATION SHALL BE IMMEDIATELY

REPORTED TO OWNER AND ENGINEER.

PROPOSED SEQUENCE OF CONSTRUCTION:

ALTERNATE #1:

UNDER ALTERNATE #1, PROVIDE THE FOLLOWING THROUGHOUT THE FULL BUILDING, UP

TO BUT NOT INCLUDING THE PARKING GARAGE BUILDING, ON ALL EXISTING PANELS AND

SWITCHBOARDS:

A. TRACE AND IDENTIFY ALL BUILDING BRANCH CIRCUITS AND FEEDERS.

B. PROVIDE UPDATED PANEL SCHEDULES.

C. CHECK AND RE-TORQUE ALL CIRCUIT AND FEEDER TERMINATIONS IN ACCORDANCE

WITH MANUFACTURER-RECOMMENDED VALUES.

ALTERNATES:

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E0.01

GENERAL NOTES &

LEGENDS -

ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

ES

26126-00

2026.10.06

ELECTRICAL DISTRIBUTION SCHEDULE

EQUIPMENT

TYPE PANEL NAME SECTIONS # OF SPACES LOCATION

I-Line Panelboard DPHW 1 PENTHOUSE AREA A

I-Line Panelboard DPHE 1 PENTHOUSE AREA B

Panelboard CP 1 24 A102

Panelboard H1W 2 84 A102

Panelboard L1W 1 24 A102

Panelboard L1WA 1 36 A102

Panelboard LCR 1 24 A111

Panelboard LCRA 1 24 A111

Panelboard LIDA 1 42 A116H

Panelboard LIDB 1 42 A116H

Panelboard L1A 1 84 A116M

Panelboard L1A2 1 30 A116M

Panelboard L2WE 1 26 A203B

Panelboard L2WC 1 26 A208A

Panelboard DW3 2 84 A306A

Panelboard L3WD 1 42 A306A

Panelboard L3WB 1 42 A311

Panelboard L3WC 1 42 A311D

Panelboard ECB 1 84 B102

Panelboard H1E 2 18 B102

Panelboard HS 1 42 B102

Panelboard L1E 1 42 B102

Panelboard L1EA 1 18 B102

Panelboard LS 1 42 B102

Panelboard HE 1 42 B103A

Panelboard H2E 2 60 B202

Panelboard H2W 2 60 B202

Panelboard L2E 1 24 B202

Panelboard L2EA 1 36 B202

Panelboard L2W 1 24 B202

Panelboard L2WA 1 36 B202

Panelboard LB2 2 84 B213

Panelboard H3E 2 84 B303

Panelboard H3W 2 56 B303

Panelboard L3E 1 24 B303

Panelboard L3EA 1 30 B303

Panelboard L3W 1 42 B303

Panelboard L3WA 1 42 B303

Panelboard L3W2 2 42 B303B

Panelboard LB3 2 42 B303B

Panelboard K 1 42 C112E

Panelboard K1 1 24 C112E

Panelboard K2 (PN) 1 36 C112E

Panelboard KH 1 18 C112E

Panelboard KL 1 30 C112E

Panelboard LN 1 42 C113

Panelboard LN2 1 42 C113

Panelboard LN3 1 24 C113

Panelboard LN4 1 30 C113

Panelboard LK 1 84 C117G

Panelboard LKS 1 42 C117G

Panelboard HSA 2 84 C117I

Panelboard LSA 2 84 C117I

Panelboard HSB1 1 42 C122G

Panelboard HSB2 1 42 C122G

Panelboard LSB1 2 84 C122G

Panelboard LSB2 1 42 C122G

Panelboard 1H 1 42 C128

Panelboard 1L 2 84 C128

Panelboard 2LN 1 42 C213

Panelboard 2LN2 1 18 C213

Panelboard 2PN 1 24 C213

Panelboard UNNAMED 1 20 C225

Panelboard 2H-old 1 42 C238

Panelboard 2L 2 84 C238

Panelboard 2LC 1 42 C238

Panelboard 3LN 1 42 C315

Panelboard 3PN 1 24 C315

Panelboard CONTROL PANEL 1 42 C315

Panelboard L3W1 3 126 C315

Panelboard H-LAB 1 42 C316

Panelboard H4W 1 24 PENTHOUSE AREA A

Panelboard H4E 1 24 PENTHOUSE AREA B

Panelboard PLN 1 18 PENTHOUSE AREA D

Switchboard DPLA 1 A102

Switchboard MAIN-A 1 B102

Switchboard MAIN-B 1 B102

Switchboard MSA 1 B102

Switchboard SERVICE ENTRANCE 1 B102

Switchboard SWBD 2000A 1 B102

Switchboard MSB 1 C112E

Switchboard MDPS 1 C117I

Switchboard MCC-2N 1 C220

Switchboard MCC-PN 1 PENTHOUSE AREA D

SCHEDULE REMARKS

1. REFER TO SHEETS E2.01 AND E2.02 FOR ROOM LOCATIONS ON FLOOR PLANS.

2026 / 10 / 06

NOPARKING

NOPARKING

(E ) 'G

E N -C

EXISTING ELECTRICAL

UTILITY TRANSFORMER

EXISTING

GENERATOR

(E) 'UTIL

XFMR'

APPROXIMATE LOCATION OF EXISTING

PANEL 'H1B' LOCATED IN THE FIRST

FLOOR SOUTH ELECTRICAL ROOM IN

THE WELCOME CENTER BUILDING.

CAMPUS NOC IN

SERVER ROOM A111

REFER TO SHEET (VIEW 1)

EXISTING DISTRIBUTION EQUIPMENT

SERVING CAMPUS NOC

IN ELECTRICAL ROOM B103A

REFER TO SHEET (VIEW 1)

EXISTING MAIN SERVICE ENTRANCE

SWITCHBOARD IN ELECTRICAL ROOM B102

REFER TO SHEET (VIEW 1)

E2.01

E2.01

E2.01

E1.01

1. REFER TO SHEET FOR ELECTRICAL LEGEND AND GENERAL PROJECT

ELECTRICAL NOTES.

2. ALL UNDERGROUND AND ABOVE GRADE ELECTRICAL INSTALLATIONS SHOWN

ON THE SITE SHALL BE WEATHERPROOF.

3. ALL EXISTING SITE UTILITIES SHALL BE FLAGGED AND MARKED PRIOR TO

CONSTRUCTION. THESE FLAGS SHALL BE MAINTAINED THROUGHOUT

CONSTRUCTION. ALL UTILITIES ARE TO REMAIN ACTIVE UNLESS NOTED

OTHERWISE IN THE CONSTRUCTION DOCUMENTS.

4. REFER TO PROPOSED SEQUENCE OF WORK ON SHEET .

GENERAL SHEET NOTES:

E0.01

E0.01

COLLIN COLLEGE ACCOUNT MANAGER:

BRIAN GUEST

BRIAN.GUEST@ONCOR.COM

817-980-8920

ONCOR CONTACT:

'GDS400'

'GDS100'

(E) 'GEN-C'

EXISTING

GENERATOR

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A s i n d ic a te d

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E1.01

SITE PLAN -

ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

2026-10-06

ES

26126-00

TRUE

NORTH

PLAN

NORTH

SCALE: 1" = 30'-0"

SITE PLAN - ELECTRICAL1

◯ NOTES BY SYMBOL ' ':

1 THE CAMPUS NETWORK OPERATIONS CENTER (NOC) AND ASSOCIATED

COOLING EQUIPMENT SHALL BE OPERATIONAL THROUGHOUT THE DURATION

OF THE PROJECT, INCLUDING DURING THE REPLACEMENT OF THE MAIN

SERVICE ENTRANCE SWITCHBOARD. REFER TO NOTES ON THE NOC POWER

ON SHEET E0.01 FOR ADDITIONAL INFORMATION.

2 PROVIDE NEW GENERATOR DOCKING STATION. COORDINATE FINAL

INSTALLATION LOCATION ON THE FIELD WITH THE OWNER, TO ENSURE

PROPER EXISTING FEEDER INTERCEPTION. MAINTAIN ALL REQUIRED WORKING

SPACE CLEARANCES, PER NEC. REFER TO ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

TRUE

NORTH

PLAN

NORTH

SCALE: 1/8" = 1'-0"

ENLARGED SITE PLAN - GENERATOR2

C.J.

C.J.

C.J.

C.J.

C.J.

E4.01

A

B103A

A102

C128

C122G

C

2E

C

C

7I

C

7G

A

6H

A

6M

(E) UTILITY

TRANSFORMER

(E) GENERATOR

CAMPUS NETWORK

OPERATIONS CENTER (NOC)

E4.01

E4.01

E4.01

A103

(E) 'L1WA'

(E) 'LCR'

A

8A A

3B

B213

A201

B202

C238

C

C

C

1. REFER TO SHEET FOR ELECTRICAL LEGEND, AND GENERAL PROJECT

POWER NOTES.

2. REFER TO SHEET FOR ELECTRICAL ONE-LINE DIAGRAMS.

3. REFER TO SHEET FOR ELECTRICAL PANEL SCHEDULES.

4. REFER TO ELECTRICAL DISTRIBUTION SCHEDULE ON SHEET FOR A LIST

OF PANELS AND SWITCHBOARDS IN EACH ROOM.

GENERAL SHEET NOTES:

E0.01

E6.01

E7.01

E0.01

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A s i n d ic a te d

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E2.01

OVERALL FLOOR

PLAN - LEVELS 1 & 2 -

ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

2026-10-06

ES

26126-00

TRUE

NORTH

PLAN

NORTH

SCALE: 1" = 30'-0"

OVERALL FLOOR PLAN - LEVEL 1 - ELECTRICAL1

TRUE

NORTH

PLAN

NORTH

SCALE: 1" = 30'-0"

OVERALL FLOOR PLAN - LEVEL 2 - ELECTRICAL2

NO SCOPE OF WORK ON THIS VIEW.

VIEW PROVIDED TO DEPICT LOCATIONS OF EXISTING ELECTRICAL EQUIPMENT.

HW

ROO

F P

EN

TH

OU

SE

C

A

1D

A

6A

B303 B

B303

A301

C

C

P

EN

TH

O U S E

AR

E A D

P E N

TH

O

U S E

A R

E A A

PENTH

O

USE

AREA B

1. REFER TO SHEET FOR ELECTRICAL LEGEND, AND GENERAL PROJECT

POWER NOTES.

2. REFER TO SHEET FOR ELECTRICAL ONE-LINE DIAGRAMS.

3. REFER TO SHEET FOR ELECTRICAL PANEL SCHEDULES.

4. REFER TO ELECTRICAL DISTRIBUTION SCHEDULE ON SHEET FOR A LIST

OF PANELS AND SWITCHBOARDS IN EACH ROOM.

GENERAL SHEET NOTES:

E0.01

E6.01

E7.01

E0.01

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A s i n d ic a te d

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E2.02

OVERALL FLOOR

PLAN - LEVELS 3 &

ROOF - ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

2026-10-06

ES

26126-00

TRUE

NORTH

PLAN

NORTH

SCALE: 1" = 30'-0"

OVERALL FLOOR PLAN - LEVEL 3 - ELECTRICAL1

TRUE

NORTH

PLAN

NORTH

SCALE: 1" = 30'-0"

OVERALL FLOOR PLAN - ROOF LEVEL - ELECTRICAL2

NO SCOPE OF WORK ON THIS VIEW.

VIEW PROVIDED TO DEPICT LOCATIONS OF EXISTING ELECTRICAL EQUIPMENT.

NO SCOPE OF WORK ON THIS VIEW.

VIEW PROVIDED TO DEPICT LOCATIONS OF EXISTING ELECTRICAL EQUIPMENT.

S P

D

S

J

S

S P

D

J

GENERAL SHEET NOTES:

1. REFER TO SHEET FOR ELECTRICAL LEGEND, GENERAL PROJECT POWER

NOTES, NOC POWER NOTES, AND PROPOSED SEQUENCE OF WORK NOTES.

2. REFER TO SHEET FOR ELECTRICAL DETAILS AND OTHER VIEWS AND

DIAGRAMS.

3. REFER TO SHEET FOR ELECTRICAL ONE-LINE DIAGRAMS.

4. REFER TO SHEET FOR ELECTRICAL PANEL SCHEDULES.

5. INSTALL ALL ELECTRICAL EQUIPMENT WITH CODE-COMPLIANT WORKING

CLEARANCE SPACES. REFER TO "WORKING SPACES" TABLE 110.26(A)(1) ON

2026 NFPA 70 (NEC).

6. INVESTIGATIVE PHASE, PRIOR TO START OF CONSTRUCTION:

A. COORDINATE WITH COLLEGE FOR A SHORT WEEKEND SHUTDOWN TO

OPEN THE FRONT COVERS OF THE SWITCHBOARDS AND PANELBOARDS

TO INVESTIGATE AND DOCUMENT EXISTING CONDITIONS, SUCH AS

FEEDER SIZES AND SPARE CIRCUIT BREAKERS.

B. INVESTIGATE AND DOCUMENT CURRENT USAGE FOR EACH CONTROLLER

BOX, TIME-CLOCK, AND DISCONNECT CURRENTLY MOUNTED UNDER

PANELS 'LS', 'HS', AND 'L1E'. MARK ANY UNUSED OR DISCONNECTED ITEMS

FOR REMOVAL.

E0.01

E6.01

E7.01

E5.01

'L1E'

'H 1E

'H S'

'L S'

'TLS'

'TL1E'

WIREWAY

'S B

-M A

IN

MGB

3 4

HS-1

L1WA-37

G

FI

'MSA'

'TL1E

'TLS

'L S'

'H S'

'L 1E

'H 1E

'L

1EA'

'S E

R V

IC

E

E N

T R

A N

C E

'M

A

IN

-B

'M A

IN

-A

WIREWAY

WIREWAY

ECB

'M A

IN

-B

'S

E R

V

IC

E E

N T

R A

N C

E

'M A

IN

-A

'MSA'

'L S'

'H S'

'L 1E

'H 1E

'L

1EA'

BURIED (5) 4" C

TO 'MSB' (C112E)

(2 ) 3

" C

TO

'2

H' ( C

8)

BURIED (10) 4" C

FROM UTILITY

TRANSFORMER (1) 1.5" C (PVC)

(1) 1" C (PVC)

(1) 2" C

(1) 1.5" C - TO ELEVATORS (A103)

(1) 2.5" C - TO 'H1W' (A102)

(1) 1" C

(1) MC CABLE

(1) 1.5" C

(1) 3/4" C

'L1E'

'H 1E

'H

S'

'L S'

'TLS'

'TL1E'

'S B

-M A

IN

BURIED (5) 4" C

TO 'MSB' (C112E)

BURIED (10) 4" C

FROM UTILITY

TRANSFORMER

(1) 1.5" C (PVC)

(1) 1" C (PVC)

(1) 1" C

(1) MC CABLE

(1) 2" C

(1) 1.5" C - TO ELEVATORS (A103)

(1) 2.5" C - TO 'H1W' (A102)

(2 ) 3

" C

TO

'2

H' ( C

8)

WIREWAY

9 (1) 1.5" C

(1) 3/4" C

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A s i n d ic a te d

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E4.01

ENLARGED PLANS -

ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

ES

26126-00

2026.10.06

◯ NOTES BY SYMBOL ' ':

1 PROVIDE NEW SERVICE ENTRANCE SWITCHBOARD PER MAXIMUM DIMENSIONS

SHOWN ON PLANS. ENSURE 4000A SERVICE FEEDER SECTION FITS OVER

EXISTING SERVICE FEEDERS. EXTEND AS NECESSARY AND CONNECT

EXISTING SERVICE FEEDERS. EXTEND AS NECESSARY AND RECONNECT

EXISTING GROUNDING ELECTRODE CONDUCTORS TO NEW GROUND BUS IN

THE ROOM, WITH MINIMUM EXTENSION WIRE SIZE OF #3/0.

2 PROVIDE NEW ELECTRICAL PANEL. EXTEND EXISTING BRANCH CIRCUITS AS

NECESSARY AND RE-TERMINATE TO NEW PANEL. MATCH CIRCUIT NUMBERS

AND CIRCUIT BREAKER SIZES AND TYPES FROM PREVIOUSLY REMOVED

PANEL. REWORK EXISTING WALL TO ACCOMMODATE NEW PANEL.

3 PROVIDE NEW WIREWAY TO ROUTE FEEDERS TO EXISTING FLOOR STUB-UPS

AS NEEDED.

4 CONNECT ALL CIRCUITS FROM PREVIOUSLY REMOVED PANEL 'L1EA' TO NEW

PANEL 'L1E'. EXTEND EXISTING BRANCH CIRCUITS AS NECESSARY. MATCH ALL

CIRCUIT BREAKER SIZES AND TYPES AS RECORDED PRIOR TO REMOVING

PANEL 'L1EA'.

5 CONNECT BOTH CIRCUITS FROM PREVIOUSLY REMOVED ENCLOSED CIRCUIT

BREAKER (ECB) TO PANEL 'LS'. EXTEND EXISTING BRANCH CIRCUITS AS

NECESSARY. MATCH ALL CIRCUIT BREAKER SIZES AND TYPES AS RECORDED

PRIOR TO REMOVING ECB.

6 PROVIDE NEW 6-FOOT DOUBLE DOOR. ENSURE DOOR SWINGS OUTWARDS TO

COMPLY WITH NEC WORKING SPACE AND LIFE SAFETY REQUIREMENTS.

PROVIDE PANIC DOOR HARDWARE. REFER TO ARCHITECTURAL DRAWINGS

FOR ADDITIONAL DOOR INFORMATION.

7 PROVIDE NEW EQUIPMENT CONCRETE PAD WITH CHAMFERED EDGE.

COORDINATE WITH SHOP DRAWINGS TO ENSURE CONCRETE PAD EXTENDS 6

INCHES BEYOND THE FRONT FACE OF EQUIPMENT ENCLOSURES.

8 INSTALL PREVIOUSLY REMOVED WALL-MOUNTED EQUIPMENT, PROVIDE NEW

WIREWAY AS NEEDED, AND CONNECT TO CIRCUITS MAINTAINED TO BE

REUSED, AFTER NEW DOOR HAS BEEN INSTALLED. DO NOT INSTALL CONTENT

PREVIOUSLY MARKED FOR REMOVAL DURING INVESTIGATIVE PHASE (SEE

GENERAL SHEET NOTE ABOVE). COORDINATE FINAL LOCATION WITH NEW

DOOR WIDTH.

9 PROVIDE JUNCTION BOX TO RECONNECT EXISTING FEEDERS. SIZE JUNTION

BOX PER NEC 314.28 REQUIREMENTS. SPLICE AND EXTEND EXISTING FEEDERS

AS NECCESARY AND CONNECT TO NEW CIRCUIT BREAKERS. MOUNT BOX TO

UNDERSIDE OF FIRST FLOOR DECK.

10 CORE THROUGH EXISTING DECK AND PROVIDE NEW STUB-UPS FOR EXISTING

CRAWLSPACE FEEDERS.

11 PROVIDE DATA OUTLET TO ALLOW DIGITAL POWER METER (DPM) DEVICE TO

COMMUNICATE AND INTERFACE WITH CAMPUS’ BUILDING MANAGEMENT

SYSTEM (BMS). REFER TO ONE-LINE FOR ADDITIONAL INFORMATION.

12 PROVIDE MAIN GROUND BAR WITH APPROPRIATE LENGTH TO CONNECT TO

ALL GROUNDING TERMINATIONS REQUIRED IN THIS SPACE, INCLUDING 10%

SPARE TERMINATION POINTS.

13 PATCH, REPAIR, AND PAINT ALL NEWLY EXPOSED WALL SPACES PRIOR TO

INSTALLATION OF NEW EQUIPMENT AND DEVICES TO MATCH SURROUNDING

WALLS.

14 REFER TO DEMOLITION NOTE ON THIS FEEDER. PROVIDE NEW FEEDER IF

REQUIRED.

15 PROVIDE NEW LINEAR SUSPENDED EMERGENCY LIGHT FIXTURE.

BASIS-OF-DESIGN: LITHONIA, CLX L48 4000LM SEF L/LENS MVOLT GZ10 40K

80CRI E10W WH. MOUNT BELOW ALL OVERHEAD CONDUITS, BUT NO LOWER

THAN 8 FEET ABOVE FINISHED FLOOR. CONNECT NEW LIGHT FIXTURES TO

EXISTING LIGHT SWITCH IN THE ROOM.

16 COORDINATE WITH SWITCHBOARD MANUFACTURER TO ENSURE ENCLOSURE

STUB-UPS FIT INTO SECTION'S BOTTOM OPENING.

17 EXISTING FIRE ALARM DEVICE. DEVICE SHALL REMAIN OPERATIONAL AND

PROTECTED FROM PHYSICAL DAMAGE THROUGHOUT CONSTRUCTION.

18 PROVIDE (1) FLUSH MOUNT DOUBLE GANG BOX WITH SINGLE GANG PLASTER

RING AND COVER PLATE FOR FUTURE CARD READER PROVIDED BY OTHERS.

MOUNT AT +36” AFF. PROVIDE 1" EMPTY CONDUIT WITH PULL STRING STUBBED

TO ACCESSIBLE LOCATION IN SECURE SIDE ABOVE CEILING.

DEMOLITION NOTES BY SYMBOL ' ':

1 REMOVE EXISTING SERVICE ENTRANCE SWITCHBOARD. DISCONNECT AND

PROTECT EXISTING MAIN SERVICE FEEDERS, FEEDERS FOR SWITCHBOARD

'MSB', AND EXISTING GROUNDING ELECTRODE CONDUCUTORS.

2 REMOVE EXISTING SWITCHBOARD 'MSA'. DISCONNECT, LABEL, AND PROTECT

EXISTING DOWNSTREAM BRANCH FEEDERS AND PREPARE THEM TO BE

MODIFIED FOR CONNECTION TO NEW EQUIPMENT.

3 REMOVE EXISTING ELECTRICAL PANEL. DISCONNECT AND PROTECT EXISTING

FEEDERS AND BRANCH CIRCUITS TO BE REUSED. PREPARE EXISTING

FEEDERS TO BE MODIFIED FOR CONNECTION TO NEW EQUIPMENT. LABEL

EXISTING BRANCH CIRCUIT CONDUCTORS WITH ASSOCIATED CIRCUIT

NUMBERS AND CIRCUIT BREAKER SIZES AND TYPES IN ORDER TO FACILITATE

THE MATCHING OF CIRCUIT NUMBERS INTO THE NEW PANEL.

4 NOTE THAT A NEW PANEL WILL NOT BE PROVIDED IN THE PLACE OF THIS

EQUIPMENT BEING REMOVED. REFER TO NEW PANEL SCHEDULES FOR

INFORMATION ON DESTINATION OF EXISTING BRANCH CIRCUITS TO BE

DISCONNECTED FROM THIS EQUIPMENT.

5 REMOVE EXISTING TRANSFORMER AND ABOVE-CEILING STRUCTURAL

SUPPORT.

6 REMOVE EXISTING CONCRETE EQUIPMENT PAD AND PROTECT EXISTING

CONDUIT FEEDER STUB UPS THAT ARE TO REMAIN.

7 REMOVE DOOR AND DOOR FRAME TO ALLOW ACCESS FOR EXISTING AND NEW

SWITCHBOARD IN AND OUT OF THE ROOM. PROVIDE TEMPORARY BARRIERS

AS NEEDED DURING CONSTRUCTION TO PREVENT THE PUBLIC FROM

ACCESSING THE ELECTRICAL ROOM. COORDINATE WITH DOOR INSTALLER TO

ENSURE EXISTING PANELBOARDS AND WALL-MOUNTED ELECTRICAL

EQUIPMENT NEAR EXISTING DOOR FRAME ARE REMOVED PRIOR TO WORK ON

NEW DOOR.

8 DISCONNECT, REMOVE, AND PROTECT EXISTING WALL-MOUNTED EQUIPMENT

TO MAKE SPACE FOR NEW DOOR AND PREPARE FOR RE-INSTALLATION.

MAINTAIN BRANCH CIRCUIT WIRES TO BE REUSED. DISCONNECT AND REMOVE

CONTENT MARKED FOR REMOVAL DURING INVESTIGATIVE PHASE (SEE

GENERAL SHEET NOTE ABOVE).

9 DISCONNECT AND PROTECT CRAWLSPACE FEEDER. FILL AND SEAL DECK

STUB-UP HOLE AND REPAIR FLOOR TO MATCH SURROUNDING CONDITIONS IN

ROOM B102.

10 DISCONNECT AND REMOVE CRAWLSPACE FEEDER. FILL AND SEAL DECK

STUB-UP HOLE AND REPAIR FLOOR TO MATCH SURROUNDING CONDITIONS IN

ROOM B102.

11 REMOVE EXISTING LIGHTING FIXTURES. REMOVE BRANCH CIRCUIT CONDUIT

AND CONDUCTORS BACK TO SOURCE.

12 FIELD-INVESTIGATE EXISTING FEEDER DESTINATION THEN COORDINATE WITH

COLLIN COLLEGE ELECTRICAL TEAM TO DETERMINE WHETHER FEEDER NEEDS

TO BE REPLACED OR SIMPLY REMOVED.

13 EXISTING CEILING-MOUNTED FIRE ALARM DEVICE TO REMAIN. PRIOR TO

CEILING REMOVAL, PROVIDE INDEPENDENT SUPPORT FOR DEVICE AND

ASSOCIATED CABLING FROM STRUCTURE ABOVE, MAINTAINING EXISTING

LOCATION AND HEIGHT. DEVICE SHALL REMAIN OPERATIONAL AND

PROTECTED FROM PHYSICAL DAMAGE THROUGHOUT CONSTRUCTION.

TRUE

NORTH

PLAN

NORTH

SCALE: 1/4" = 1'-0"

ENLARGED NEW PLAN

RM B102 - ELECTRICAL3

TRUE

NORTH

PLAN

NORTH

SCALE: 1/4" = 1'-0"

ENLARGED DEMO PLAN

RM B102 - ELECTRICAL1

TRUE

NORTH

PLAN

NORTH

SCALE: 1/4" = 1'-0"

ENLARGED DEMO PLAN

RM B102 CRAWLSPACE - ELECTRICAL2

TRUE

NORTH

PLAN

NORTH

SCALE: 1/4" = 1'-0"

ENLARGED NEW PLAN

RM B102 CRAWLSPACE - ELECTRICAL4

SWBD

'MSB-NAME'

TYP.

480Y/277V

PANEL

TYP.

208Y/120V

PANEL

PANEL 'L1A'

480Y/277V, 3PH

FROM H1A-1,3,5

EQUIPMENT NAME

EQUIPMENT TYPE

EQUIPMENT VOLTAGE

AND PHASE

EQUIPMENT SOURCE AND

SOURCE LOCATION

PHENOLIC NAMEPLATE

WITH 1/4" LETTERS

INSCRIBED AS INDICATED.

PROVIDE WHITE LABELS

WITH BLACK LETTERS

(PANELBOARD SAMPLE)

DETAIL NOTES:

1. PROVIDE EQUIPMENT LABEL AS DETAILED ABOVE FOR ALL

PANELBOARDS, SWITCHBOARDS, TRANSFORMERS, DISCONNECT

SWITCHES, VARIABLE FREQUENCY DRIVERS (VFD), ETC.

2. SERVICE ENTRANCE EQUIPMENT SHALL HAVE AVAILABLE FAULT

CURRENT VALUE LABELED, IN ADDITION TO THE THE

INFORMATION DETAILED ABOVE. ACQUIRE AVAILABLE FAULT

INFORMATION FROM ELECTRICAL UTILITY TO PERFORM

CALCULATIONS.

3. REFER TO SPECIFICATION SECTION 26 05 53 FOR ADDITIONAL

INFORMATION.

LOCKWASHER

(NEWTON P.N. 3015-8)

4"

NEWTON P.N. A-6056

2"

4"

9/16" DIA.

3/4"

1"

2-3/4" INSULATOR

(NEWTON P.N.

3061-4)

3/8" DIAMETER

5/8 - 11 x 1" H.H.C.S.

(NEWTON P.N. 3012-1)

AS R

EQUIR

ED

1/4'`NOTE: VERIFY ALL HEIGHTS WITH ARCHITECT

FINISHED FLOOR

DATA TERMINAL OUTLET

TELEPHONE OUTLET

RECEPTACLE

WALL SWITCH

DIMMER SWITCH

THERMOSTAT OR FIRE

ALARM PULL STATION

FIRE ALARM HORN/LIGHT

LOWEST OF 8" BELOW

FINISHED CEILING OR 80"

AFF

FINISHED CEILING

CLOCK HANGER OUTLET

A F

F

A

F F

1'-0'' BELOW FINISHED

CEILING (MOUNT 8'-0"

AFF FOR NO CEILING

OR SLOPED CEILING

CONDITION)

G

N

G

N

G G

N

20" CONCRETE ENCASED ELECTRODE

TRIAD GROUND RING.

10' GROUND RODS SHALL BE PLACED 30' APART

BOND TO BUILDING STRUCTURAL STEEL

BOND TO COLD WATER PIPE

LOCATE IN EACH IDF ROOM

'TGB''MGB'

DETAIL NOTES BY SYMBOL:

1. PROVIDE #3/0, BARE, TINNED COPPER.

2. PROVIDE #3/0 IN 3/4" PVC CONDUIT.

3. PROVIDE CONDUCTOR PER ONE-LINE DIAGRAM.

4. SIZE PER NEC TABLE 250.66. ROUTE TO NEAREST GROUND

BAR OR TO EFFECTIVELY GROUNDED STEEL STRUCTURE.

TYP ∆-Y

TRANSFORMER

LOCATE IN EACH ELEC ROOM

'GB'

DETAIL NOTES:

1. PROVIDE MINIMUM OF 12 INCHES CLEARANCE ABOVE LOWER TRANSFORMER.

2. PROVIDE MINIMUM OF 6 INCHES CLEARANCE BEHIND TRANSFORMER.

3. HEIGHT AS REQUIRED FOR VERTICAL CLEARANCES.

4. WIDTH AS REQUIRED TO SUPPORT UPPER TRANSFORMER. REFER TO UPPER

TRANSFORMER DIMENSIONS FOR ADDITIONAL INFORMATION.

5. PROVIDE HORIZONTAL CLEARANCE TO ALLOW MAINTENANCE ACCESS TO LOWER

TRANSFORMER. REFER TO LOWER TRANSFORMER DIMENSIONS FOR ADDITIONAL

INFORMATION.

6. PROCURE STRUCTURAL ENGINEER TO REVIEW EQUIPMENT RACK DIMENSIONS AND

TOTAL COMBINED WEIGHT.

DRY-TYPE UPPER

TRANSFORMER

AS SCHEDULE, ANCHORED

TO SUPPORT FRAME

DRY-TYPE LOWER

TRANSFORMER

AS SCHEDULE

3"X3"X1/4" STEEL SUPPORT

ANGLE FRAME PRIMED

AND PAINTED TO MATCH

TRANSFORMER

4" CONCRETE

EQUIPMENT PAD

PROVIDE ISOLATION

PAD ON EACH CORNER

FOR EACH TRANSFORMER

(TYPICAL OF 8)

SPD SUB-SECTION

(SPD MOUNTED EXTERNALLY)

4,000 A

MAIN CIRCUIT BREAKER

SUB-SECTION

BRANCH

CIRCUIT BREAKERS

SUB-SECTION

SECTION 2SECTION 1 SECTION 3

CONCRETE PAD

W A

L L

CONCRETE DECK

(10) 4"C

FROM UTILITY

TRANSFORMER

(5) 4"C

TO 'MSB' (C112E)

CRAWLSPACE

3' - 0" TO 4' - 0" 3' - 6" 3' - 0" MAX

10' - 4" MAX

1,600 A

CIRCUIT BREAKER

SUB-SECTION

DETAIL NOTES:

A. DIMENSIONS PROVIDED ARE APPROXIMATE. COORDINATE ENCLOSURE'S BOTTOM OPENING WITH LOCATION OF EXISTING UTILITY TRANSFORMER AND SWITCHBOARD 'MSB' FEEDERS. FIELD VERIFY ALL MEASUREMENTS AND

SPACE REQUIREMENTS PRIOR TO ORDERING SWITCHBOARD.

B. TO SIMPLIFY WIRING, PLACE ALL CIRCUIT BREAKERS TO BE CONNECTED TO CRAWLSPACE FEEDERS NEAR THE BOTTOM OF SECTION 1. COORDINATE ALL LAYOUT REQUIREMENTS WITH MANUFACTURER AND FIELD

CONDITIONS.

DETAIL NOTE:

ALL CONNECTIONS TO BE DOUBLE COMPRESSION (CRIMP) TYPE.

NO MECHANICAL CONNECTIONS, MINIMUM 4 CRIMPS FOR DOUBLE

COMPRESSION FITTING.

STAINLESS

STEEL NUT

STAINLESS STEEL

BELLEVILLE WASHER

STAINLESS STEEL

FLAT WASHER

DOUBLE HOLE LONG BARREL

LUG W/ INSPECTION HOLE

PROVIDE ENGRAVED 145C TAG.

DESCRIPTION SHALL IDENTIFY

CABLE DESTINATION.

FEEDER CONDUIT

LOCKNUT

(NOT SHOWN)

PANELBOARD

ENCLOSURE

PANELBOARD EQUIPMENT

GROUND BUS BONDED

TO CABINET

EQUIPMENT GROUNDING

CONDUCTOR INSTALLED

WITH FEEDER

BONDING JUMPER.

SAME SIZE AS EQUIPMENT

GROUNDING CONDUCTOR

INSULATED THROAT

GROUNDING BUSHING

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A s i n d ic a te d

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E5.01

DETAILS -

ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

ES

26126-00

2026.10.06

NO SCALE

EQUIPMENT IDENTIFICATION2

NO SCALE

BUS BAR3NO SCALE

WIRING DEVICE TYPICAL MOUNTING HEIGHTS6

NO SCALE

GROUND RISER DIAGRAM5

NO SCALE

TRANSFORMER STACKING RACK7

NO SCALE

SWITCHBOARD ELEVATION VIEW8

NO SCALE

GROUND BUS BAR CONNECTION4 NO SCALE

PANELBOARD BONDING1

SWBD 'MSA'

1600A, 480Y/277V, 3PH, 4W, MCB

'H2W' 'H3W''H2E' 'H3E''2H'

'HE'

'H1E' 'H1W'

'ELEV-1' 'ELEV-2'

'LCR'

'L1W'

'CP'

'L1WA'

'HS'

'L1E'

'L1EA'

'LS'

SWBD 'MAIN-B'

2000A, 480Y/277V, 3PH, 4W, 50KAIC

SWBD 'MAIN-A'

2000A, 480Y/277V, 3PH, 4W, 50KAIC

'L2W'

'L2WA'

'LB2''L2E'

'L2EA'

'L3E'

'L3EA'

'L3W2' 'L3W'

'L3WA'

'LB3'

'1H'

'2L'

'1L' '2LC'

P

P

SPD

SPD

'L1A'

'L1A2'

SWBD

'MSB'

DIST PANEL

'DPHE'

DIST PANEL

'DPHW'

DIST PANEL

'DPLA'

P

'KH'

'KL'

'HE'

'H1E'

'ELEV-1' 'ELEV-2'

'LCR'

'HS'

'L1E' 'LS''L1A'

'L1A2'

SPD

DPM

SWBD 'SB-MAIN'

4000A, 480Y/277V, 3PH, 4W, MCB

SWBD

'MSB'

DIST PANEL

'DPHE'

DIST PANEL

'DPHW'

DIST PANEL

'DPLA'

'2H' '1H'

'2L'

'1L' '2LC'

SPD

SPD

'H2W' 'H3W''H2E' 'H3E''H1W'

'L1W'

'CP'

'L1WA'

'L2W'

'L2WA'

'LB2''L2E'

'L2EA'

'L3E'

'L3EA'

'L3W2' 'L3W'

'L3WA'

'LB3'

P

K

'KH'

'KL'

KK

K

1. REFER TO SHEET FOR ELECTRICAL ONE-LINE LEGEND, FEEDER KEY

SCHEDULES, AND GENERAL PROJECT POWER NOTES.

2. REFER TO POWER PLANS FOR LOCATIONS OF ELECTRICAL EQUIPMENT ALONG

WITH ADDITIONAL REQUIREMENTS AND INSTRUCTIONS

3. REFER TO SHEET E5.01 FOR GROUNDING RISER DIAGRAM.

GENERAL SHEET NOTES:

E0.01

400 AS600 AS 600 AS 400 AS 400 AS 400 AS 400 AS 400 AS 400 AS 400 AS 400 AS400 AS

'TL1W'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TL1E'

75 KVA

480V:

208Y/120V

3PH, 4W

'TLS'

30 KVA

480V:

208Y/120V

3PH, 4W

'T-COMP-RM'

112.5 KVA

480V:

208Y/120V

3PH, 4W

5%Z

400 AS

A S

A S

SERVICE ENTRANCE

4000A, 480Y/277V

3PH, 4W, 50KAIC

'UTIL XFMR'

2500KVA,

PAD-MOUNTED

480Y/277V

'UTILITY'

UTILITY

METER

'TL2W'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TLB2'

45 KVA

480V:

208Y/120V

3PH, 4W

5.2%Z

'TL2E'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TL3E'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TL3W2'

112.5 KVA

480V:

208Y/120V

3PH, 4W

5.5%Z

'TL3W'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TLB3'

45 KVA

480V:

208Y/120V

3PH, 4W

5.2%Z

'T2L'

150 KVA

480V:

208Y/120V

3PH, 4W

5.36%Z

200 AS 200 AS

'GEN-C'

375 kVA 480Y/277V

3PH, 4W, 0.8PF

DIESEL

'TL1A'

75 KVA

480V:

208Y/120V

3PH, 4W

4.87%Z

'INVERTER'

100 AF

100 AT

400 AF

400 AT

(10) 3"C - (3) 500KCMIL, (1) 350KCMIL

ELEC ROOM

C112E

PENTHOUSE

EAST

PENTHOUSE

WEST

200 AS

'TDPLA'

112.5 KVA

480V:

208Y/120V

3PH, 4W

5.75%Z

ELEC ROOM

C112E

(B103A)

(B103A)

(A103)

(C238) (C238) (B102) (B102) (A102) (B202) (B202) (B303) (B303)`

ROOM NUMBER (TYP)

(A116M) (B102)

(B102)

(B102)

2,6

FROM 'K2'

'TKL'

45 KVA

480V:

208Y/120V

3PH, 4W

3.51%Z

(C112E)

(C112E)

'TL1E'

75 KVA

480V:

208Y/120V

3PH, 4W

'TLS'

30 KVA

480V:

208Y/120V

3PH, 4W

400 AS

'T-COMP-RM'

112.5 KVA

480V:

208Y/120V

3PH, 4W

5%Z

400 AS

'TL1A'

75 KVA

480V:

208Y/120V

3PH, 4W

4.87%Z

225 AF

225 AT

225 AF

225 AT

225 AF

225 AT

225 AF

225 AT

225 AF

225 AT

400 AF

400 AT

400 AF

400 AT

0 AF

0 AT

400 AF

400 AT

175 AF

175 AT

600 AF

600 AT

600 AF

600 AT

125.3C

250.4X 100.4X

50.3C

100.4C

400.4C

100 AS 100 AS

'GEN-C'

375 kVA 480Y/277V

3PH, 4W, 0.8PF

DIESEL

100 AF

100 AT

400 AF

400 AT

1600 AF

1600 AT

LSIG, 100%

SECTION 3 SECTION 2 SECTION 1

'UTIL XFMR'

2500KVA,

PAD-MOUNTED

480Y/277V

'UTILITY'

4000 AF

3800 AT

LSIG, 100%

100 AF

100 AT

ELEC ROOM

C112E

PENTHOUSE

EAST

PENTHOUSE

WEST

200 AS

'TDPLA'

112.5 KVA

480V:

208Y/120V

3PH, 4W

5.75%Z

ELEC ROOM

C112E

'T2L'

150 KVA

480V:

208Y/120V

3PH, 4W

5.36%Z

200 AS 200 AS

'TL1W'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TL2W'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TLB2'

45 KVA

480V:

208Y/120V

3PH, 4W

5.2%Z

'TL2E'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TL3E'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TL3W2'

112.5 KVA

480V:

208Y/120V

3PH, 4W

5.5%Z

'TL3W'

45 KVA

480V:

208Y/120V

3PH, 4W

4.9%Z

'TLB3'

45 KVA

480V:

208Y/120V

3PH, 4W

5.2%Z

'INVERTER'

UTILITY

METER

(10) 3"C - (3) 500KCMIL, (1) 350KCMIL

2,6

CAM-LOCK

INPUT

LOAD

BANK

GENERATOR DOCKING STATION WITH

LOAD BANK, AND KIRK-KEY INTERLOCK

'GDS400'

400A, 480Y/277V, 3PH, 4W, 42KAIC

FROM 'K2'

'TKL'

45 KVA

480V:

208Y/120V

3PH, 4W

3.51%Z

CAM-LOCK

INPUT

LOAD

BANK

GENERATOR DOCKING STATION WITH

LOAD BANK, AND KIRK-KEY INTERLOCK

'GDS100'

100A, 480Y/277V, 3PH, 4W, 42KAIC

400.4C

100.4C

DESCRIPTIONTAG

3#12, #12G, 3/4"C15.3C

3#12, #12G, 3/4"C20.3C

3#10, #10G, 3/4"C25.3C

30.3C

3#8, #10G, 3/4"C35.3C

40.3C

3#6, #10G, 3/4"C45.3C

50.3C

3#4, #10G, 1"C60.3C

70.3C

3#3, #8G, 1"C80.3C

3#2, #8G, 1 1/2"C90.3C

100.3C

110.3C

125.3C

150.3C

175.3C

200.3C

225.3C

250.3C

300.3C

350.3C

400.3C

500.3C

600.3C

DESCRIPTIONTAG

FEEDER SCHEDULE - COPPER - 3 PHASE

700.3C

800.3C

1000.3C

1200.3C

1600.3C

2000.3C

2500.3C

3000.3C

4000.3C

15.4C

20.4C

25.4C

30.4C

35.4C

40.4C

45.4C

50.4C

60.4C

70.4C

80.4C

90.4C

100.4C

110.4C

125.4C

150.4C

175.4C

200.4C

225.4C

250.4C

300.4C

350.4C

400.4C

500.4C

600.4C

700.4C

800.4C

1000.4C

1200.4C

1600.4C

2000.4C

2500.4C

3000.4C

4000.4C

3#10, #10G, 3/4"C

3#8, #10G, 3/4"C

3#6, #10G, 3/4"C

3#4, #8G, 1"C

3#1, #8G, 1 1/2"C

3#2, #6G, 1 1/2"C

3#1, #6G, 1 1/2"C

3#1/0, #6G, 1 1/2"C

3#2/0, #6G, 2"C

3#3/0, #6G, 2"C

3#4/0, #4G, 2"C

3-250, #4G, 3"C

3-350, #4G, 3"C

3-500, #3G, 3"C

3-600, #3G, 3"C

2 SETS OF 3-250, #2G, 3"C

2 SETS OF 3#3/0, #3G, 2"C

450.3C 450.4C2 SETS OF 3#4/0, #2G, 2"C

2 SETS OF 3-350, #1G, 3"C

2 SETS OF 3-500, #1/0G, 3"C

3 SETS OF 3-300, #1/0G, 3"C

4 SETS OF 3-250, #2/0G, 3"C

4 SETS OF 3-350, #3/0G, 3"C

5 SETS OF 3-400, #4/0G, 3"C

6 SETS OF 3-400, 250G, 3"C

7 SETS OF 3-500, 350G, 4"C

8 SETS OF 3-500, 400G, 4"C

12 SETS OF 3-400, 500G, 3"C

4#12, #12G, 3/4"C

4#12, #12G, 3/4"C

4#10, #10G, 3/4"C

4#8, #10G, 1"C

4#6, #10G, 1"C

4#4, #10G, 1 1/2"C

4#3, #8G, 1 1/2"C

4#2, #8G, 1 1/2"C

4#10, #10G, 3/4"C

4#8, #10G, 1"C

4#6, #10G, 1"C

4#4, #8G, 1 1/2"C

4#2, #8G, 1 1/2"C

4#1, #6G, 1 1/2"C

4#1, #6G, 1 1/2"C

4#1/0, #6G, 2"C

4#2/0, #6G, 2"C

4#3/0, #6G, 2"C

4#4/0, #4G, 3"C

4-250, #4G, 3"C

4-350, #4G, 3"C

4-500, #3G, 4"C

4-600, #3G, 4"C

2 SETS OF 4-250, #2G, 3"C

2 SETS OF 4#3/0, #3G, 3"C

2 SETS OF 4#4/0, #2G, 3"C

2 SETS OF 4-350, #1G, 3"C

2 SETS OF 4-500, #1/0G, 4"C

3 SETS OF 4-300, #1/0G, 3"C

4 SETS OF 4-250, #2/0G, 3"C

4 SETS OF 4-350, #3/0G, 3"C

5 SETS OF 4-400, #4/0G, 4"C

6 SETS OF 4-400, 250G, 4"C

7 SETS OF 4-500, 350G, 4"C

8 SETS OF 4-500, 400G, 4"C

12 SETS OF 4-400, 500G, 4"C

DESCRIPTIONTAG

60.4X

100.4X

FEEDER SCHEDULE

TRANSFORMER SECONDARY COPPER

4#4, 1#8G, 1 1/2"C

250.4X

400.4X

4#1, 1#6G, 1 1/2"C

4-250, 1#2G, 3"C

2 SETS OF 4#3/0, 1#1/0G, 2"C

800.4X 3 SETS OF 4-300, 1#3/0G, 3"C

150.4X 4#1/0, 1#6G, 2"C

500.4X 2 SETS OF 4-250, 1#1/0G, 3"C

1000.4X 4 SETS OF 4-250, 1#3/0G, 3"C

1. THE DIGITAL POWER METER (DPM) DEVICE SHALL BE EQUIPPED WITH A

DISPLAY TO PROVIDE LOCAL ACCESS TO METERED DATA. THE FOLLOWING

INSTANTANEOUS READINGS SHALL BE MONITORED, DISPLAYED, AND

COMMUNICATED BY THE DPM:

A. FREQUENCY

B. CURRENT, PER PHASE AND 3-PHASE AVERAGE RMS, PEAK DEMAND

C. VOLTAGE, PHASE-TO-PHASE AND PHASE-TO-NEUTRAL

D. POWER FACTOR, PER PHASE AND 3-PHASE TOTAL

E. REAL POWER (KW), 3-PHASE TOTAL, PEAK DEMAND, CUMULATIVE (KWH)

F. REACTIVE POWER (KVAR), 3-PHASE TOTAL

2. PROVIDE DPM WITH THE CAPABILITY TO COMMUNICATE AND INTERFACE WITH

CAMPUS’ BUILDING MANAGEMENT SYSTEM (BMS) VIA BACNET IP OR BACNET

MSTP TO REMOTELY MONITOR THE SERVICE ENTRANCE EQUIPMENT’S POWER

QUALITY AND USAGE. CONTRACTOR SHALL PROVIDE ALL HARDWARE,

CONDUITS, LOW VOLTAGE CABLING, AND THE NECESSARY PROGRAMMING TO

THE EXISTING BMS.

3. APPROVED MANUFACTURER: SQUARE D POWER LOGIC PM5000.

4. THE POWER MONITORING SYSTEM SHALL INCLUDE AN APPLICATION

DESIGNED TO MONITOR ALL DPM DEVICES IN THE BACKGROUND FOR ALARMS,

EVENTS, AND DATA LOGGING.

A. DISPLAY INFORMATION SHALL INCLUDE REAL TIME DATA AND TREND

DISPLAYS, HISTORICAL REPORTS, GRAPHICAL DISPLAYS WITH REAL-TIME

UPDATES.

B. GRAPHICAL WAVEFORM SHALL DISPLAY VOLTAGES, PHASE CURRENTS,

TOTAL HARMONIC DISTORTION (THD), AND PEAK VALUES.

5. THE SYSTEM SHALL MAINTAIN MAXIMUM AND MINIMUM VALUES FOR EACH OF

THE INSTANTANEOUS VALUES REPORTED, AS WELL AS THE TIME AND DATE OF

THE HIGHEST PEAK FOR ALL PEAK DEMAND READINGS.

6. STARTUP AND TRAINING:

A. ONSITE STARTUP AND TRAINING OF THE POWER MONITORING SYSTEM

SHALL BE INCLUDED IN THE PROJECT BID. STARTUP SHALL INCLUDE A

COMPLETE WORKING DEMONSTRATION.

B. TRAINING SHALL INCLUDE ANY DOCUMENTATION AND HANDS-ON

EXERCISES NECESSARY TO ENABLE ELECTRICAL OPERATIONS

PERSONNEL TO ASSUME FULL OPERATING RESPONSIBILITY AFTER

COMPLETION OF THE TRAINING PERIOD.

POWER MONITORING SYSTEM NOTES:

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E6.01

ONE-LINE DIAGRAMS

- ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

ES

26126-00

2026.10.06

◯ NOTES BY SYMBOL ' ':

1 OVERCURRENT PROTECTION RATING IS UNKNOWN. RECORD THE

OVERCURRENT PROTECTION RATING OF EACH BRANCH CIRCUIT DURING

SWITCHBOARD REMOVAL PHASE TO FACILITATE MATCHING RATINGS TO NEW

CIRCUIT BREAKERS IN NEW EQUIPMENT.

2 ELECTRICAL CIRCUIT BRANCH FEEDING EQUIPMENT AT NETWORK

OPERATIONS CENTER (NOC). ENSURE THIS BRANCH, FROM PANEL 'HE'

THROUGH 'LCR', REMAINS ENERGIZED THROUGHOUT ENTIRE CONSTRUCTION

PERIOD.

3 DISCONNECT EXISTING FEEDER FROM EXISTING GENERATOR AND PREPARE

TO CONNECT TO NEW GENERATOR DOCKING STATION.

4 REFER TO POWER MONITORING SYSTEM NOTES IN THIS SHEET FOR

INFORMATION ON DIGITAL POWER METER REQUIREMENTS. REFER TO

SPECIFICATION SECTIONS 26 24 13 AND 26 09 00 FOR ADDITIONAL

INFORMATION.

5 PROVIDE CIRCUIT BREAKER THAT MATCHES RECORDED OVERCURRENT

PROTECTION RATING OF EXISTING BRANCH CIRCUIT.

6 PROVIDE MAIN CIRCUIT BREAKER WITH LONG-TIME PICK-UP SETTING

REACHING ABSOLUTELY NO HIGHER THAN 3800 A. PROVIDE RED PLACARD

STATING “MAXIMUM LONG-TIME PICK-UP SETTING: 3,800 AMPS” IN WHITE FONT

AND ATTACH IT ON SAME ENCLOSURE SECTION AS MAIN CIRCUIT BREAKER.

7 PROVIDE EXTERIOR SURFACE-MOUNTED TYPE 2 SURGE PROTECTION DEVICE

(SPD), RATED AT 300KA/PHASE MINIMUM. CONNECT SPD TO LOAD BUS VIA

DEDICATED CIRCUIT BREAKER MOUNTED IMMEDIATELY DOWNSTREAM OF

MAIN CIRCUIT BREAKER. TIGHTLY TWIST FEEDER CONDUCTORS AND MAINTAIN

A MAXIMUM LENGTH OF 12 INCHES. COORDINATE CIRCUIT BREAKER RATING

AND ADDITIONAL FEEDER REQUIREMENTS WITH SPD MANUFACTURER.

8 PROVIDE EXISTING CIRCUIT BREAKER IN GENERATOR WITH KIRK-KEY

INTERLOCK DEVICE.

9 CONNECT EXISTING FEEDER TO NEW GENERATOR DOCKING STATION. EXTEND

EXISTING FEEDER AS NECESSARY

NO SCALE

ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION1

NO SCALE

ELECTRICAL ONE-LINE DIAGRAM - NEW2

NOTE:

THESE DOCUMENTS ARE

INTENDED FOR INTERIM

REVIEW AND NOT

INTENDED FOR BIDDING,

PERMIT, OR

CONSTRUCTION PURPOSES

ELECTRICAL ENGINEER

DRAWN BY:

CHECKED BY:

SHEET NO.

REVISIONS

F

IL

E P

A T

H

D A

T E

/T

IM

E

P L O

T S

C A

L E

APPROVED BY:

EDGAR B. SOARES

P.E. # 155472

12222 Merit Dr

Suite 400

Dallas, TX 75251

TX Firm #F-2176

(972) 788-4222

Project

A u to d e s k D o c s /C

C M c K in n e y M a in

B ld g S w it c h b o a rd

R e p la c e m e n t/

-C

C M c K in n e y M a in

B u ild in g S w it c h b o a rd

R e p la c e m e n t-

R W

B -r

.r v t

/6

/2

:0 :2

P

M

JD

DB

E7.01

PANEL SCHEDULES -

ELECTRICAL

S W

IT

C

H B

O A

R D

R E

P L A

C E

M E

N T

C O

L L

IN

C O

L L E

G E

M

C K

IN

N

E Y

C A

M P

U S

M

A

IN

B U

IL

D

IN

G

W

U

N

IV

E R

S

IT

Y D

R

IV

E M

C K

IN

N

E Y

T

E X

A S

ES

26126-00

2026.10.06

[1] PROVIDE NEW CIRCUIT BREAKER THAT MATCHES EXISTING OVERCURRENT PROTECTION RATING OF EXISTING BRANCH CIRCUIT.

NOTES:

THIS SWITCHBOARD REPLACES THE EXISTING SWITCHBOARD. ASSOCIATED EXISTING LOADS ARE TO BE RE-CONNECTED. NO NEW LOADS ARE ADDED.

14 (E) ELEVATORS 3 400.0 A 0.0 A 0 VA SEE ONE-LINE SEE NOTE 1

13 PANEL 'H3W' - RM B303 3 225.0 A 225.0 A 0 VA SEE ONE-LINE

12 PANEL 'H3E' - RM B303 3 225.0 A 225.0 A 0 VA SEE ONE-LINE

11 PANEL '2H' - RM C238 3 400.0 A 400.0 A 0 VA SEE ONE-LINE

10 PANEL 'H2W' - RM B202 3 225.0 A 225.0 A 0 VA SEE ONE-LINE

9 PANEL 'H2E' - RM B202 3 225.0…