BVY ATCT Roof and HVAC Unit Replacement Drawings.pdf
PDF 3 MB Posted
- Attached to
- BVY ATCT Roof and HVAC Unit Replacement Federal contract opportunity
- Solicitation number
- 2402506
About this file
This document is a pre-solicitation market survey for the replacement of the roof and HVAC unit at the Beverly, Massachusetts Air Traffic Control Tower (BVY ATCT). The Federal Aviation Administration (FAA) is conducting market research to gather information from interested vendors to assist with acquisition planning and determine the appropriate procurement method, which may involve a full and open competition or a set-aside for small businesses, service-disabled veteran-owned small businesses, or 8(a) firms.
The FAA is seeking capability statements from interested vendors, not to exceed 6 pages, that provide details on the types of services offered, previous contract experience, number of years in business, and contact information. Vendors certified as service-disabled veteran-owned small businesses or 8(a) firms should provide a copy of their certification. Responses are due by April 23, 2024. The FAA will not pay for any costs associated with the market survey submission. The FAA has not determined the competition type or whether this will be a small business set-aside. There is no incumbent contractor for this requirement.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SOW BVY ATCT Roof and HVAC Unit Replacement.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:4
:0
P
M lo tt e d b y S
R V
-C
-E
O
APPROVED
v
-2
-g
.d w g
8 234567
T OF TRANSPO
T A T
IO
N
IC
OF
STATES
U
IT
P A
TM
EN
AVIA
LA
TRAT
SI
NI
HVAC AND ROOF REPLACEMENT
AIR TRAFFIC CONTROL TOWER (ATCT)
BEVERLY REGIONAL AIRPORT
BEVERLY, MASSACHUSETTS
ATCT BASE BUILDING
SIDEWALK
DRAWING INDEX
DRAWING NO. DRAWING TITLE
BVY-21005020-GOO1 COVER SHEET & INDEX SHEET
ROOF REPAIRS
ELECTRICAL ONE LINE DIAGRAM
ELECTRICAL PANEL SCHEDULE
MECHANICAL HVAC SCHEDULE
MECHANICAL DUCTWORK DETAILS
MECHANICAL HVAC DETAILS
BVY-21005020-C001
BVY-21005020-E001
BVY-21005020-E002
BVY-21005020-M001
BVY-21005020-M002
BVY-21005020-M003
CIVIL DEMOLITIONBVY-21005020-D001
MECHANICAL DEMOLITIONBVY-21005020-D002
HVAC AND VIBRATION CURBBVY-21005020-S001
BVY-21005020-GOO2 GENERAL NOTES
VIBRATION CURB CUTSHEET
BASE BUILDING AS-BUILTS
BASE BUIDLING ROOFTOP HVAC DETAILS
BVY-21005020-M004
BVY-21005020-M005
BVY-21005020-M006
NOT TO SCALE
SITE PLAN
IS
01/26/2024
MGR: ENGINEERING CENTER
BEVERLY
BVY-21005020-G001
SP
ATCT
HVAC REPLACEMENT AND ROOF REHAB PROJECT
COVER SHEET & INDEX SHEET
OPS INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
BEVERLY MUNICIPAL AIRPORT
THIS DRAWING PRODUCED ON NEW ENGLAND REGION CAD SYSTEM
PROJECT ENGINEER
21005020
MA
bvy-21005020-g001
2024-01-31T06:14:31-0500
HENRY B NEWCOMB
2024-01-30T13:55:55-0500
SHREY B PATEL
FILLER FOR NOW
:2 lo tt e
SUBTITLE REFERENCE
SCALE
ELEVATION CALLOUT REFERENCE
ELEVATION REFERENCE LETTER
SECTION REFERENCE LETTER
DETAIL REFERENCE NUMBER
DETAIL CALLOUT REFERENCE
SECTION CALLOUT REFERENCE
X
XXXXXXXXXXX
SCALE: X=XXX
XXXX
ELEVATION IS LOCATED
SHEET NUMBER WHERE
DETAIL IS LOCATED
SECTION IS LOCATED
DETAIL, ELEVATION OR SECTION IS/ARE LOCATED
SHEET NUMBER(S) WHERE CALLOUT(S) TO PLAN,
(PLAN, DETAIL, ELEVATION OR SECTION)
REFERENCE NUMBER/LETTER
DRAWING PREFIXES
GXXX - GENERAL
DXXX - DEMOLITION
CXXX - CIVIL
EXXX - ELECTRICAL/ELECTRONIC
MXXX - MECHANICAL
DEMOLITION NOTES
GENERAL CONSTRUCTION NOTES
ELECTRICAL NOTES
SYMBOLS LEGEND
CONTRACTOR MUST PROVIDE TEMPORARY LIGHTING OVERNIGHT AND DURING OUTAGES15.
CONTRACTOR MUST PROVIDE A DUMPSTER ON SITE FOR ALL CONSTRUCTION DEBRIS.14.
MUST BE SERVICED ON A WEEKLY BASIS.
CONTRACTOR MUST PROVIDE A PORT-A-JOHN FOR THE DURATION OF THE CONSTRUCTION PROJECT. FACILITIES 13.
THE ENVIRONMENTAL CONDITIONS. CONTRACTOR MUST PROVIDE SHELTER IF REQUIRED.
CONTRACTOR MUST STORE NEW EQUIPMENT AND MATERIALS ON SITE IN A MANNER THAT IT IS PROTECTED FROM 12.
CONTRACTOR MUST CONTACT THE CO AND COR PRIOR TO PROCEEDING WITH CONSTRUCTION.
IF CONDITION ONSITE ARE DIFFERENT FROM THOSE INDICATED ON THE DRAWINGS OR SPECIFICATIONS, THE 11.
INDICATED. THE CONTRACTOR MUST BE RESPONSIBLE FOR ALL REQUIRED PERMITS.
THE CONTRACTOR MUST PROVIDE ALL LABOR, EQUIPMENT, AND REQUIRED TEMPORARY POWER UNLESS OTHERWISE
ALL FITTINGS, TRANSITIONS, DAMPERS, VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE INSTALLATION.
THE CONTRACTOR MUST PROVIDE ALL MATERIAL UNLESS OTHERWISE INDICATED. THE CONTRACTOR MUST PROVIDE 10.
NECESSARY. PROTECT ALL EXISTING FINISHED FLOORING, WALLS, CEILINGS, DURING DEMOLITION AND CONSTRUCTION.
DAMAGE, IMMEDIATELY NOTIFY THE CO AND COR. THE CONTRACTOR MUST MAKE REPAIRS AND REPLACEMENTS AS
THE CONTRACTOR MUST USE ALL MEANS NECESSARY TO PROTECT EXISTING WORK, AND IN THE EVENT OF 9.
RIGHT TO SUSPEND THE PROJECT SHOULD AN UNSAFE CONDITION EXIST.
THE CONTRACTOR MUST STRICTLY COMPLY WITH ALL OSHA REGULATIONS AT ALL TIMES. THE COR RESERVES THE 8.
THE COR TWO WEEKS PRIOR TO OPERATION.
PROTECTED FROM ALL CONSTRUCTION DEBRIS AT ALL TIMES. ALL SHUTDOWNS MUST SCHEDULED IN WRITING WITH
EQUIPMENT MUST REMAIN OPERATIONAL THROUGHOUT THE PROJECT DURATION. ALL FAA EQUIPMENT MUST BE 7.
MUST BE SUBMITTED FOR THE APPROVED LISTED PURCHASED EQUIPMENT.
WRITTEN INSTRUCTIONS AND RECOMMENDATIONS, UNLESS OTHERWISE NOTED. ALL NEW EQUIPMENT SUPPORTS, CONTRACTOR MUST INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH THE MANUFACTURER'S 6.
CONSTRUCTION START.
CONTRACTOR MUST COMPLY WITH ACCESS ROUTES, STAGING AREAS, AND PARKING AREAS APPROVED PRIOR TO 5.
TO START OF CONSTRUCTION.
BE SCALED TO DETERMINE THE EXACT LOCATIONS OF WORK. CONTRACTOR MUST VERIFY DIMENSIONS ONSITE PRIOR
THE DRAWINGS ARE DIAGRAMMATIC AND ARE TO CONVEY SCOPE, GENERAL ARRANGEMENT ONLY, AND MUST NOT 4.
THE CONDITIONS.
FACILITY. START OF CONSTRUCTION ACTIVITIES WILL NEED TO BE STAGGERED DURING INSTALLATION TO BEST SUITE
CONTRACTOR MUST COORDINATE ALL WORK TO AVOID ANY AND ALL CONFLICTS WITH PERSONNEL WORKING AT THE 3.
AND SIZES OF ALL DUCTWORK, EQUIPMENT, AND ACCESSORIES THAT IS TO BE DEMOLISHED.
BEFORE THE START OF ALL WORK, CONTRACTORS MUST VERIFY THEIR SCOPE OF WORK, LOCATION, ELEVATION, 2.
MA.
FOR THE AIR TRAFFIC CONTROL TOWER (ATCT) THAT SERVES THE BEVERLY REGIONAL AIRPORT (BVY), BEVERLY, THIS DRAWING PACKAGE INDICATES WORK REQUIRED FOR THE REMOVAL AND INSTALLATION OF A HVAC SYSTEM 1.
COR.
CONTRACTOR MUST RETURN SITE TO ORIGINAL CONDITION PRIOR TO PROJECT COMPLETION WITH ACCEPTANCE OF 6.
REQUIREMENTS FOR PERSONS DISPOSING OF REFRIGERANT. SEE EPA 40 CFR PART 82, SUBPARTS A AND F.
AC EQUIPMENT MUST HAVE REQUIRED CERTIFICATIONS. CONTRACTOR TO MAINTAIN RECORD KEEPING
HVAC SYSTEM. ALL REFRIGERANT RECOVER EQUIPMENT AS WELL AS PERSONNEL DISPOSING OF REFRIGERATION/
INCLUDING, BUT NOT LIMITED TO THE REMOVAL, STORAGE, AND DISPOSAL OF THE REFRIGERANT IN THE EXISTING
CONTRACTOR MUST HANDLE REFRIGERANT ACCORDING TO LOCAL, STATE, AND FEDERAL REQUIREMENTS; 5.
SUBSTANCES.
CONTRACTOR MUST PROVIDE REQUIRED DOCUMENTATION AND MANIFEST FOR THE DISPOSAL OF CONTROLLED 4.
THE FAA.
CONTRACTOR MUST LEGALLY DISPOSE OF ALL MATERIAL AND EQUIPMENT NOT RETURNED TO OR RETAINED BY 3.
POLYTARP), ETC. FAA EQUIPMENT MUST NOT BE DAMAGED DURING DEMOLITION PERIOD.
LIMITED TO, METHODS TO LIMIT DUST PRODUCTION, EXHAUST SYSTEMS, PROTECTIVE COVERS (I.E. 2 MIL
EQUIPMENT DURING CONSTRUCTION AND DEMOLITION ACTIVITIES. DUST MITIGATION PLAN MUST INCLUDE, BUT NOT
CONTRACTOR MUST SUBMIT A DUST MITIGATION PLAN TO COR FOR APPROVAL TO PREVENT DAMAGE TO FAA 2.
CONDITION AT THE END OF EACH WORK SHIFT.
IMPACT SITE OPERATIONS. THE AFFECTED WORK AREAS MUST BE THOROUGHLY CLEANED TO THEIR ORIGINAL
COMPLETION OF THE WORK SHIFT EACH DAY. SITE CONDITIONS THROUGHOUT CONSTRUCTION PERIOD WILL NOT
REMOVE ALL DEBRIS, RUBBISH, SCRAP, DIRT, AND PROTECTIVE COVERINGS FROM THE WORK AREAS UPON 1.
MECHANICAL NOTES
MAINTENANCE, OPERATION, AND SERVICE REQUIREMENTS. COORDINATE TRAINING SCHEDULE WITH COR.
CONTRACTOR MUST PROVIDE A (4) HOUR TRAINING FOR THE FAA PERSONNEL FOR THE NEW HVAC SYSTEM'S 10.
OR TABB QUALIFIED.
COPY OF TEST RESULTS AND REPORT IN CLOSE OUT DOCUMENTS. TAB CONTRACTOR MUST BE EITHER AABC, NEBB, LEVEL OF CAB DURING PACKAGE UNIT OPERATION. PROVIDE COR WITH RESULTS AS WELL AS TAB REPORT. INCLUDE
AIRFLOW, SUPPLY AIR TEMPERATURE, AND RETURN AIR TEMPERATURE AND RECORD RESULTS. MEASURE SOUND
COMPLETED HVAC SYSTEM AND ADJUST AIRFLOW RATES TO THE CFM INDICATED IN DRAWING M002. MEASURE
CONTRACTOR MUST HAVE CERTIFIED PROFESSIONAL PERFORM TESTING, ADJUSTING, AND BALANCING (TAB) OF THE 9.
ENGINEER'S REVIEW AND APPROVAL.
STRUCTURAL COMPONENTS MUST NOT BE CUT, DRILLED OR MODIFIED IN ANY MANNER WITHOUT A STRUCTURAL 8.
CONDENSATE DRAINS MUST BE MADE OF PVC SUITABLE (SCHEDULE 80) FOR THIS APPLICATION.7.
PROVIDE TEMPORARY FIRE EXTINGUISHERS DURING CONSTRUCTION.
PERFORMING THE OPERATION. COMPLY WITH OSHA STANDARDS FOR WELDING IN 29 CFR-1910 AND 29 CFR-1926.
OPERATIONS; PERSON PERFORMING FIRE PROTECTION DUTIES MUST NOT BE THE SAME INDIVIDUAL THAT IS
DESIGNATE A PERSON TO BE RESPONSIBLE FOR FIRE PROTECTION DURING WELDING BRAZING AND CUTTING 6.
WARRANTY FOR EQUIPMENT SUPPLIED.
COPIES OF SERVICE CONTRACTS, CONTRACTOR'S (ONE YEAR) WARRANTY ON INSTALLATION, AND MANUFACTURER'S
MANUAL, INCLUDING MANUFACTURER'S MANUALS FOR ALL EQUIPMENT FURNISHED, A LIST OF EQUIPMENT SUPPLIERS, PRIOR TO PROJECT CLOSE OUT, THE CONTRACTOR MUST FORWARD AN OWNER'S OPERATING AND MAINTENANCE 5.
CONTRACTOR MUST PROVIDE HVAC MANUFACTURER'S FIVE YEAR WARRANTY ON COMPRESSORS AND COILS 4.
NEW INSULATED WALL SLEEVE FOR NEW AC UNITS MUST BE INSTALLED WATER AND WEATHER TIGHT. 3.
MATERIALS OR WORKMANSHIP.
HIS OWN EXPENSE, PROMPTLY CORRECT AND REPAIR ANY AND ALL BREAKS, FAILURES OR WEAR DUE TO FAULTY
CONTRACTOR FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE. THE CONTRACTOR MUST, AT
EQUIPMENT, MATERIALS AND WORKMANSHIP OF THE MECHANICAL INSTALLATION MUST BE WARRANTIED BY THE 2.
DRAWINGS, SPECIFICATION, AND AS REQUIRED BY THE CODES AND MANUFACTURER'S INSTALLATION INSTRUCTIONS.
MECHANICAL SYSTEMS; AND MUST MAKE SURE THE NEW MECHANICAL SYSTEMS OPERATES AS INDICATED IN THE
CONTRACTOR MUST PROVIDE ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED TO COMPLETELY INSTALL THE NEW 1.
THEIR OWN LOCK OUT DEVICES. ONLY FAA PERSONNEL ARE ALLOWED TO ENERGIZE/ DE-ENERGIZE EQUIPMENT.
CONTRACTOR MUST PROVIDE A LOCK OUT TAG PLAN PRIOR TO START DEMOLITION. CONTRACTOR MUST PROVIDE 10.
CABLES.
INSULATION MEGGER TESTS MUST BE PERFORMED IN THE PRESENCE OF THE COR ON ALL NEW CONDUCTORS AND 9.
ALL NEW CONDUITS MUST BE CLEARED OF DEBRIS AND A PULL STRING INSTALLED.8.
ALL EQUIPMENT AND CABLES MUST BE TESTED AS REQUIRED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.7.
6AWG GREEN BONDING CONDUCTOR.
FLEXIBLE LIQUIDTIGHT CONDUIT MUST BE ALL PLASTIC PVC TYPE, WITH FLEXIBLE STEEL CORE AND AN EXTERNAL 6.
IN EACH PULL BOX, AND EVERY 3 FEET WHERE THE CONDUCTOR IS VISIBLE.
ALL INSULATED CONDUCTORS MUST BE PROPERLY AND PERMANENTLY IDENTIFIED AND COLOR CODED AT EACH END, 5.
AND MUST BE IN THE PRESENCE OF THE COR.
VOLTAGE AND PHASE ROTATION TESTS MUST BE PERFORMED BEFORE AND AFTER ANY DISCONNECTION OF POWER 4.
THE CONTRACTOR MUST FURNISH ALL LABOR, MATERIAL AND EQUIPMENT UNLESS OTHERWISE INDICATED.3.
FAA.
COMPLETION OF THE PROJECT. COORDINATE REQUIRED EQUIPMENT SHUTDOWNS WITH THE RESIDENT ENGINEER AND
CONTRACTOR TO FIELD VERIFY ALL CONDITIONS AND REROUTE CONDUITS AS NECESSARY TO SUPPORT THE 2.
WORK) AND FAA-STD-019. (DOCUMENTATION AVAILABLE AT CONTRACTOR'S REQUEST)
ALL ELECTRICAL WORK MUST COMPLY WITH LATEST EDITION OF SPECIFICATIONS FAA-C-1217 (INTERIOR ELECTRICAL 1.
CIVIL NOTES
TO THE ATTENTION OF FAA CONTRACTING OFFICER'S REPRESENTATIVE ANY DISCREPANCIES.
DISCREPANCIES: CONTRACTOR MUST VERIFY ALL DIMENSIONS, CONDITIONS AND ELEVATIONS AT JOB SITE AND BRING 6.
THE CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS AFFECTED BY THE PROJECT.5.
THE CONTRACTOR IS REQUIRED TO MEET OSHA'S FALL PROTECTION AND SAFETY RULES AND REGULATIONS.4.
ANY WORK BEING PERFORMED. ANY DELAYS OR RESCHEDULING OF THE WORK MUST BE COORDINATED WITH THE COR.
A DETAILED WORK SCHEDULE MUST BE PRESENTED FOR APPROVAL TO THE COR AT LEAST 24 HOURS IN ADVANCE OF 3.
COORDINATE ACCESS TO THE SITE WITH THE FAA AHEAD OF TIME.
CONSTRUCTION SITE ACCESS: THE CONSTRUCTION SITE IS LOCATED WITHIN A GATED FACILITY. THE CONTRACTOR MUST 2.
DRAWINGS, SPECIFICATION, AND AS REQUIRED BY THE CODES AND MANUFACTURER'S INSTALLATION INSTRUCTIONS.
ROOFING SYSTEMS; AND MUST MAKE SURE THE NEW ROOFING SYSTEM MUST BE INSTALLED AS INDICATED IN THE
CONTRACTOR MUST PROVIDE ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED TO COMPLETELY INSTALL THE NEW 1.
ABBREVIATIONS
CO - CONTRACTING OFFICER
COR - CONTRACTING OFFICER'S REPRESENTATIVE
PEL - PROJECT ENGINEER LEAD
SXXX - STRUCTURAL
BVY-21005020-G002
GENERAL NOTES
bvy-21005020-g002
2024-01-31T06:14:47-0500
HENRY B NEWCOMB
2024-01-30T13:56:07-0500
SHREY B PATEL
REFER TO E001 AND E002 FOR ELECTRICAL REQUIREMENTS.8.
CONTRACTOR MUST FIELD LOCATE UNIT HEATER THERMOSTATS WITH COORDINATION OF COR.7.
SUBMIT ALL EQUIPMENT AND ACCESSORIES FOR APPROVAL PRIOR TO INSTALLATION.6.
FOR COMPLETE INSTALLATION.
CONTRACTOR MUST PROVIDE AND INSTALL EQUIPMENT AND ACCESSORIES ACCORDING TO MANUFACTURER'S INSTALLATION INSTRUCTIONS 5.
BRACKETS (DAYTON CATALOG NUMBER 2YV16).
PROVIDE AND INSTALL DAYTON 804T17, OR APPROVED EQUAL (EUH-2). PROVIDE AND INSTALL MANUFACTURER CEILING MOUNTING 4.
BRACKETS (DAYTON CATALOG NUMBER 2YV16).
PROVIDE AND INSTALL DAYTON 804T20, OR APPROVED EQUAL (EUH-1). PROVIDE AND INSTALL MANUFACTURER CEILING MOUNTING 3.
AND PTAC-2).
PROVIDE AND INSTALL FREDRIECH PVH09K, INSULATED WALL SLEEVE, AND CONDENSATE DRAIN; OR PROVIDE APPROVED EQUAL (PTAC-1 2.
PROVIDE AND INSTALL FREDRIECH 12B33A, INSULATED WALL SLEEVE, AND CONDENSATE DRAIN; OR PROVIDE APPROVED EQUAL (WAC-1). 1.
NOTES:
WAC-1
MARK TYPE
UNIT IDENTIFICATION
TOTAL
HEATING
REFRIGERANT
VOLTS PHASE HZ
208/230 1 60
DESCRIPTION/ REMARKS
ELECTRICAL DATACOOLING
FREDRIECH
CEW12B33A
HEATING
AIR CONDITIONER SCHEDULE
MOP
(AMPS)
MCA
FAN MOTOR
MOISTURE
TONNAGE
COOLING
1 10600 BTU
REMOVAL
3.3
PTS./HR
R-410A
MOTOR
H.P.
INDOOR
CFM
NEMA
PLUG
6-20P 16"W X 20"H, FIRST FLOOR EQUIPMENT ROOM, WINDOW AC UNIT
PTAC-1 3600 WATTS 208/230 1 60
FREDRIECH
PVH09K
20 19.9.75 9400 BTU 1.4R-410A 400 6-20P
PTAC-2 208/230 1 60
ELECTRIC HEAT
WINDOW UNIT W/
PTAC UNIT W/ 42"W X 16"H, SECOND FLOOR EQUIPMENT ROOM, PACKAGE TERMINAL AC UNIT
PTAC UNIT W/ 2500 WATTSFREDRIECH
PVH09K
15 13.9.75 9400 BTU 1.4R-410A 400 6-15P 42"W X 16"H, THIRD FLOOR EQUIPMENT ROOM, PACKAGE TERMINAL AC UNIT
AND MODEL
MANUFACTURER
REMARKS:
MANUFACTURE'S CONDENSATE DRAIN KIT4.
MANUFACTURE'S INSULATED WALL SLEEVE3.
WASHABLE FILTER2.
AUTO-RESTART1.
INCLUDE THE FOLLOWING OPTIONS AND ACCESSORIES
1060 WATTS
ELECTRIC UNIT HEATER SCHEDULE
MARK MANUFACTURER MODEL
AIR DELIVERY DATA FAN MOTOR DATA ELECTRICAL DATA
TYPE
EUH-1 DAYTON 804T20 970 7.5
KWCFM FPM RPM
1600 1/30650
SS FIN
TUBULAR
AMPS
20.8
VOLTS PHASE
HZ
3 PHASE208
DELTA T °F
37°
HP
PHYSICAL
EUH-2 DAYTON 804T16 800 3.71600 1/100350
SS FIN
TUBULAR
18.0 60 1 PHASE20845°
DIMENSIONS
H X W X D
COMMENTS
21.75" X 19" X 8.5" ELECTRIC UNIT HEATER, FIRST FLOOR STAIRWELL
ELECTRIC UNIT HEATER, CAB STAIRWELL16" X 14" X 8.5"
CEILING MOUNT (DAYTON 2YV16)2.
WALL MOUNTED LINE VOLTAGE THERMOSTAT1.
OF OUTDOOR AIR.
THE MANUAL OUTSIDE AIR DAMPER MUST BE OPENED ALL FOR APPROXIMATELY 100 CFM (ADJUSTABLE) ··
COORDINATION OF COR BASED ON LOCATION SHOWN IN DETAIL 3 (M002)
ROOFTOP UNIT'S THERMOSTAT MUST BE INSTALLED IN THE CONDITIONED SPACE, FIELD LOCATE WITH ··
NOTES·
WHEN SUPPLY SMOKE DETECTOR DETECTS SMOKE, THE ROOFTOP UNIT MUST SHUTDOWN.7.1.3.
7.1.2.
7.1.1.
SETPOINTS FOR BASE BUILDING MUST MAINTAIN BETWEEN 7.1.
BASEBUILDING7.
WHEN SUPPLY SMOKE DETECTOR DETECTS SMOKE, THE ROOFTOP UNIT MUST SHUTDOWN6.1.4.
6.1.3.
6.1.2.
6.1.1.
6.1.
CAB LEVEL6.
SETPOINTS OF EXISTING WINDOW AC UNIT WILL NOT BE ADJUSTED5.1.
FOURTH FLOOR EQUIPMENT ROOM5.
4.1.2.
4.1.1.
4.1.
THIRD FLOOR EQUIPMENT ROOM4.
3.1.2.
3.1.1.
3.1.
SECOND FLOOR EQUIPMENT ROOM3.
2.1.1.
2.1.
FIRST FLOOR STAIRWELL2.
1.1.3.
1.1.2.
1.1.1.
1.1.
FIRST FLOOR EQUIPMENT ROOM 1.
SEQUENCE OF OPERATIONS
PACKAGE ROOFTOP AIR CONDITIONER SCHEDULE
MARK MANUFACTURER MODEL
EVAPORATOR
RTU-1 TRANE 3
NOMINAL
EXT. S.P.
IN H20
1.17
°F
EDB
°F
EWB
67 3400
MBH
MBH
SENSIBLE
105.6 81.0
CONDENSOR
QTY. STAGES
HP
FAN
0.7
SCROLL
MANIFOLD
TYPE
COMPR.
TEMP
AMBIENT
95 °F (32/68/100)
HEAT
27 KW
KWTYPE
ELECTRIC
DEHUMIDIFIER
REHEAT
HOT GAS
MODULATING
ELECTRICAL DATA
PHASE
HZVOLTS
MOCPMCA
107 110
FAN HP
8.8
FAN FLA
RLA
LRA
20.2 136
FLA
LRA
3.3 12.3**A2C1A2B0A0B410A
THJ102A3S0K
FILTER DATA
- 24 X 16 X 2(3)
- 18 X 24 X 2(2)
QUANTITY
STD
ASHRAE
MERV 8COMPR.
RTU-2 CARRIER
0A5F0
50FC-B05M3Q5-
1.96.6 80 67 160048.4 34.3
1 R-410A 0.25 1100
SCROLL
MANIFOLD
95 °F
13.7 83 1.5COMPR. 16 KWELECTRIC
REHEAT
HOT GAS
MODULATING
360208 57 60
- 16 X 25 X 2(1)
- 20 X 24 X 1(1)
MERV 8
ACCESORIES
E-COAT AL/CU ON CONDENSER AND EVAPORATOR COILS
2 4 5 8 9 10 12 13 14 1716 19 21 23
2 3 5 6 7 9 10 11 12 14 15 17 18 19 20 21 22 23
HIGH STATIC INDOOR MOTOR24.
LOW AMBIENT CONTROLS (DOWN TO 0°F)23.
STAINLESS STEEL CONDENSATE DRAIN PAN22.
CONDENSATE DRAIN PAN OVERFLOW SWITCH21.
CLOGGED FILTER SWITCH20.
SUPPLY AIR SMOKE DETECTOR19.
DEHUMIDIFICATION COIL: MODULATING HOT GAS REHEAT18.
POWERED CONVENIENCE OUTLET17.
NON-FUSED DICSONNECT16.
UNIT MOUNTED CIRCUIT BREAKER15.
THROUGH THE BASE ELECTRIC14.
COIL PROTECTION13.
LOVUERED HAIL GUARD12.
STANDARD COIL11.
INCH MERV 8 FILTERS HINGED ACCESS PANELS/ 2 10.
ADJUSTABLE MANUAL OUTSIDE AIR DAMPER 0-50% 9.
14.4 KW STAGED ELECTRIC HEAT8.
27 KW (2 STAGE) ELECTRIC HEAT7.
UNIT CONTROLS: SYMBIO 7006.
208-230 VOLT/ 60 HZ/ 3 PHASE5.
4 TON, SINGLE COMPRESSOR4.
8.5 TON, DUAL COMPRESSOR3.
R-410A2.
DX COOLING1.
NOTES
APPROVED EQUAL.
PROVIDE AND INSTALL TRANE ROOFTOP UNIT OR
APPROVED EQUAL.
PROVIDE AND INSTALL CARRIER ROOFTOP UNIT OR
CORROSION RESISTANT COIL COAT ON CONDENSER COIL
lo tt e
-m
BVY-21005020-M001
MECHANICAL HVAC SCHEDULE
bvy-21005020-m001
2024-01-31T06:15:57-0500
HENRY B NEWCOMB
2024-01-30T13:58:06-0500
SHREY B PATEL
CONTROL
CAB LEVEL
AIR SUPPLY DROP
RETURN
AIR DUCT
DISTRIBUTION
BOXDISTRIBUTION
BOX
STRIP DIFFUSERS
8" FLEXIBLE
DUCT
M002
ATCT PARTIAL ELEVATION
8" FLEXIBLE
DUCT
SUSPENDED
CEILING
HVAC UNIT
M002 NOT TO SCALE
NEW DUCTWORK LAYOUT1 2
HVAC PLAN
SUPPLY
ROOF
HATCH
IC
L
INSTALL NEW SEISMIC CURB
POWERED CONVENIENCE OUTLET
THROUGH THE BASE ELECTRICAL WITH
UNIT MOUNTED CIRCUIT BREAKER
M003
RETURNING APPROX CFM.
LINEAR SLOT DIFFUSER MUST BE BALANCED TO APPROX 185 CFM AND THE RETURN AIR SHOULD BE
NEW HVAC SYSTEM AND DUCTWORK MUST BE BALANCED BY A CERTIFIED BALANCER. BALANCE EACH 13.
NEW CEILING PANELS MUST BE REPLACED TO MATCH EXISTING PANELS.
CONTRACTOR MUST REPLACE ANY DAMAGED CEILING PANELS THAT GET DAMAGED DURING CONSTRUCTION. 12.
SHOWN FOR CLARITY.
MUST BE INSTALLED INLINE WITH RETURN DUCTWORK. ONLY FLEX CANVAS DUCT CONNECTOR IN RETURN IS
INSTRUCTIONS. (1) CONNECTOR MUST BE INSTALLED INLINE WITH SUPPLY DUCTWORK AND (1) CONNECTOR
DUCT CONNECTOR ACCORDING TO VIBRATION ISOLATION CURB MANUFACTURER'S INSTALLATION
CONTRACTOR MUST PROVIDE AND INSTALL (2) FLEX CANVAS DUCT CONNECTORS. INSTALL FLEX CANVAS 11.
WITH DUCT SUPPORTS. SEE STATEMENT OF WORK FOR CONSTRUCTION DETAILS.
CONTRACTOR MUST PROVIDE AND INSTALL NEW 16 GAUGE GALV. STEEL SUPPLY DUCTWORK (34" X 12") 10.
SEE STATEMENT OF WORK FOR CONSTRUCTION DETAILS.
CONTRACTOR MUST PROVIDE AND INSTALL NEW INSULATED SUPPLY FLEX DUCT (8") WITH DUCT SUPPORTS. 9.
INSTALL PLASTIC COVER TO PROTECT THERMOSTAT FROM DIRECT SUNLIGHT
CONTRACT MUST PROVIDE AND INSTALL NEW ROOFTOP UNIT THERMOSTAT ON WALL IN CAB. PROVIDE AND 8.
CERTIFICATION PRIOR TO BALANCING, AND PROVIDE BALANCING REPORT AFTER COMPLETION
INSTALLED IN NEW DUCTWORK. BALANCING MUST BE DONE BY CERTIFIED PERSONNEL, PROVIDE
BALANCE ALL (18) LINEAR DIFFUSERS TO 275 CFM, USING THE MANUAL BALANCERS THAT SHALL BE 7.
COMPRESSION LUG ONTO BARE METAL.
CONTRACTOR TO REUSE EXISTING GROUNDING CONDUCTOR. ATTACH TO NEW UNIT USING TWO BOLT 6.
CLEAN ROOF DRAIN, AND REMOVE DEBRIS DURING CONSTRUCTION.5.
INSTALL A NEW PVC CONDENSATE DRAIN ACCORDING TO MANUFACTURER'S INSTRUCTIONS.4.
ISOLATION CURB AND ROOFTOP UNIT
CONTRACTOR MUST PROVIDE COORDINATION DRAWINGS OF THE INSTALLATION OF THE NEW VIBRATION
THE NEW HVAC UNIT MUST FIT ON THE NEW VIBRATION ISOLATION CURB. NEW UNIT MUST BE APPROVED. 3.
WHEN INSTALLING NEW UNIT, THE POWER CONDUCTORS WILL BE RE-USED FROM THE EXISTING UNIT.2.
ALL FLEX DUCTWORK SHALL HAVE A MAXIMUM LENGTH OF 6 FEET.1.
(SEE DETAIL B)
CONDENSATE DRAIN
CONDENSATE DRAIN DETAIL
0.75 INCHES (2021 IMC)
CONDENSATE DRAIN MUST HAVE A MINIMUM INNER DIAMETER OF ·
DRAIN MUST BE SLOPE 1/2' PER 10 FEET OF HORIZONTAL RUN.·
THE CAB ROOF DRAIN.
HORIZONTAL PIPE LENGTH MUST BE LONG ENOUGH TO REACH TO ·
INSTALLATION INSTRUCTIONS.
80) CONDENSATE DRAIN ACCORDING TO MANUFACTURER'S
CONTRACTOR MUST PROVIDE AND INSTALL NEW PVC (SCHEDULE ·
NOTE:
36" 48"
36"
36"
ISOLATION CURB
HVAC VIBRATION
SEE NOTE 11
(TYP. OF 2)
FLEX CONNECTOR
SEE NOTE 1
36"X12'H
GALV DUCT
MANUAL
VOLUME DAMPER
(TYP OF 18)
AIR DUCT/GRILL
TURNING
VANES (TYP)
8" FLEX DUCT
36"X12"H
AIR DUCT
TO EXISTING GRILLE
DUCT CONNECTED
NEW FLEX SUPPLY
36"X12"H
DISTRIBUTION BOX
CAB
EQUIP
FLOOR
THERMOSTAT
(SEE NOTE 8)
SEE NOTE 13
PANEL ENCLOSURE
.75 INCH NPT FEMALE CONNECTOR
1.5"
LENGTH CAN BE FIELD DETERMINED
SEE DETAIL NOTES
CLEANOUT PLUG
:5 lo tt e
BVY-21005020-M002
MECHANICAL DUCTWORK DETAIL
bvy-21005020-m002
2024-01-31T06:16:08-0500
HENRY B NEWCOMB
2024-01-30T13:57:12-0500
SHREY B PATEL
ATCT ELEVATION
PTAC-1
PTAC-2
WAC-2
CABINET HEATER
UH-2
ELECTRIC 10KW
UH-1
ELECTRIC 5KW
STAIRWELL
EQUIP. RM.
REFER TO SCHEDULES ON M001 FOR UNIT SCHEDULES·
MUST VERIFY LOCATIONS AND CONNECTIONS PRIOR TO CONSTRUCTION.
ELEVATION VIEW IS DIAGRAMMATIC TO SHOW APPROXIMATE LOCATIONS. CONTRACTOR ·
FIRST/GROUND FLOOR EQUIPMENT ROOM
SECOND FLOOR EQUIPMENT ROOM
THIRD FLOOR EQUIPMENT ROOM
FOURTH FLOOR EQUIPMENT ROOM
1 HVAC UNIT DETAIL
27 9/16"
HVAC UNIT PENETRATION PLAN
Y
ALL FLANGES 1 1/4"
2 DOWNFLOW DUCT CONNECTIONS
4 3/16"
32 1/8"
33"
3 7/8"
17 1/2" 17 1/2"
9 13/16"
3 5/8"
RETURN SUPPLY
THROUGH THE
BASE ELECTRICAL
CONDENSER FAN
CONTROL BOX
ACCESS PANEL
CONDENSER COIL WITH
COIL GUARD
UNIT CONRTOL WIRE 7/8" DIA.HOLE
SERVICE GAUGE PORT ACCESS 1 3/8" DIA. HOLE
UNIT POWER WIRE
COMPRESSOR ACCESS
PANEL
CONDENSATE DRAIN (ALT)
3/4" - 14 NPT DIA. HOLE
EVAPORATOR SECTION
HVAC ELEVATION
HVAC ELEVATION - ACCESS PANELS
CONDENSER FAN
4 1/4"
BASERAIL LENGTH
27 9/16"
CONTROL PANEL ACCESS
COMPRESSOR ACCESS PANEL
CONTROL PANEL ACCESS
SECTION
EVAPORATOR
88 1/2"
4 7/8"
9"
53 1/4"
BASERAIL WIDTH
9 5/8"
11 1/4"
50 15/16"
15 1/4"
52 5/16"
17 3/4"
17 3/4"
TOP PANEL
3/4' 14 NPT DIA.HOLE
CONDENSATE DRAIN
THROUGH THE BASE
5 7/8"
3 3/4"
2 3/4"
5"
33 3/4"
(NEW)
(EXISTING)
DETAIL SHOWS DUCT UPWARDS FOR CLARITY.
NOTE: DIRECTION OF THE DUCT WORK IS DOWNWARDS TOWARDS THE BUILDING.
(EXISTING)
RTU-1
lo tt e
BVY-21005020-M003
MECHANICAL HVAC DETAILS
bvy-21005020-m003
2024-01-31T06:16:20-0500
HENRY B NEWCOMB
2024-01-30T13:57:23-0500
SHREY B PATEL
S R
6" 0
HARD DUCT
8" 0 HARD DUCT
8" 0
.A
IN
6" 0 HARD DUCT
12" X 12"
LINED DUCT
200 CFM
150 CFM
200 CFM
125 CFM
75 CFM
75 CFM
125 CFM200 CFM
8" 0
FLEX DUCT
24" X 12"
LINED R.A.
24" X 24"
R.A. GRILLE
16" X 12" R.A.
.A
IN
12" X 12" R.A.
16" X 16"
16" X 16"
12" X 12" R.A. GRILLE
16" X 12" R.A.
12"X12" R.A. GRILLE
12" X 12" RETURN
REGISTER ABOVE CEILING
1" UNDERCUT @
BOTTOM OF DOOR
(TYPICAL)
1" UNDERCUT @
BOTTOM OF DOOR
(TYPICAL)
24" X 24"
TO CEILING PLENUM
10" 0 HARD DUCT
100 CFM
12" X 12"
42'-0"
25'-0"17'-0"
PANELS MUST BE REPLACED TO MATCH EXISTING PANELS.
CONTRACTOR MUST REPLACE ANY DAMAGED CEILING PANELS THAT GET DAMAGED DURING CONSTRUCTION. NEW CEILING 13.
ONLY FLEX CANVAS DUCT CONNECTOR IN RETURN IS SHOWN FOR CLARITY.
INSTALLED INLINE WITH SUPPLY DUCTWORK AND (1) CONNECTOR MUST BE INSTALLED INLINE WITH RETURN DUCTWORK.
ACCORDING TO VIBRATION ISOLATION CURB MANUFACTURER'S INSTALLATION INSTRUCTIONS. (1) CONNECTOR MUST BE
CONTRACTOR MUST PROVIDE AND INSTALL (2) FLEX CANVAS DUCT CONNECTORS. INSTALL FLEX CANVAS DUCT CONNECTOR 12.
SUPPORTS. SEE STATEMENT OF WORK FOR CONSTRUCTION DETAILS.
CONTRACTOR MUST PROVIDE AND INSTALL NEW 16 GAUGE GALV. STEEL SUPPLY DUCTWORK (34" X 12") WITH DUCT 11.
CONTRACTOR MUST PROVIDE AND INSTALL NEW ROOFTOP UNIT THERMOSTAT INSIDE BASE BUILDING, TO BE FIELD LOCATED.10.
ONTO BARE METAL.
CONTRACTOR TO REUSE EXISTING GROUNDING CONDUCTOR. ATTACH TO NEW UNIT USING TWO BOLT COMPRESSION LUG 9.
CLEAN ALL ROOF DRAINS, AND REMOVE DEBRIS DURING CONSTRUCTION.8.
INSTALL A NEW PVC CONDENSATE DRAIN ACCORDING TO MANUFACTURER'S INSTRUCTIONS.7.
AND ROOFTOP UNIT
CONTRACTOR MUST PROVIDE COORDINATION DRAWINGS OF THE INSTALLATION OF THE NEW VIBRATION ISOLATION CURB
THE NEW HVAC UNIT MUST FIT ON THE EXISTING VIBRATION ISOLATION CURB. NEW UNIT MUST BE APPROVED. 6.
WHEN INSTALLING NEW UNIT, THE POWER CONDUCTORS WILL BE RE-USED FROM THE EXISTING UNIT.5.
MOUNTED ON TOP OF A CURB.
WITH 16 KW OF ELECTRIC HEAT (SEE APPENDIX FOR EQUIPMENT TAG AND PICTURES OF EXISTING UNIT). EXISTING UNIT IS
CONTRACTOR MUST DEMOLISH EXISTING ROOFTOP UNIT. ONE CARRIER 4 TON PACKAGED ROOFTOP AIR CONDITIONING UNIT 4.
SUPPLY DUCTWORK. VERIFY EXISTING CFM MEETS NEW CFMS.
SUPPLY DIFFUSER ACCORDING TO CFM RATINGS LISTED ON DETAIL 1 OF DRAWING USING ADJUSTABLE DAMPERS IN
THIRD-PARTY TAB MUST BE PERFORMED ON THE NEW SYSTEM BY TABB OR NEBB CERTIFIED BALANCER. BALANCE EACH 3.
NADCA STANDARDS.
GRILLES AFTER NEW PACKAGE ROOFTOP UNIT INSTALLATION IS COMPLETE. PERFORM DUCT CLEANING IN ACCORDANCE WITH
CONTRACTOR MUST CLEAN EXISTING SUPPLY AND RETURN AIR DUCTS, AS WELL AS EXISTING SUPPLY AND RETURN 2.
AND FIRST TRANSITION.
ONLY. THE SCOPE IS LIMITED TO THE CONTRACTOR REPLACING SUPPLY AND RETURN DUCTWORK BETWEEN ROOFTOP UNIT
SUPPLY DUCTWORK PLAN VIEW AND RETURN DUCTWORK PLAN VIEW SHOWS THE EXISTING DUCTWORK AND FOR REFERENCE 1.
ATCT ATCT
:1 lo tt e
AS BUILT: SUPPLY DUCTWORK
M005
AS BUILT: RETURN DUCTWORK
M005
FOR REFERENCE ONLY FOR REFERENCE ONLY
BVY-21005020-M005
BASE BUILDING AS-BUILTS
bvy-21005020-m005
2024-01-31T06:16:41-0500
HENRY B NEWCOMB
2024-01-30T13:57:33-0500
SHREY B PATEL
CAB ROOFTOP
BASE BUILDING ROOFTOP
RTU-2
BUILDING LINK
(REFER TO SOW FOR DETAILS)
PROTECTION SYTEM
INSTALL TEMPORARY FALL
PROTECTION PLAN PRIOR TO CONSTRUCTION FOR APPROVAL BY FAA.
PROTECTION SYSTEM ON WEST SIDE OF ROOF BETWEEN ROOFTOP UNIT AND ROOF EDGE. PROVIDE FALL
CONTRACTOR MUST PROVIDE AND INSTALL TEMPORARY FALL PROTECTION SYSTEM. INSTALL FALL 9.
UNIT.
BUBBLE COVER TO INSTALL. MAINTENANCE RECEPTACLE MUST BE EXTERNALLY MOUNTED ON ROOFTOP
GFI DUPLEX RECEPTACLE, 20A, 120V, WR RATED, IN EXTERIOR RATED BOX WITH WEATHERPROOF IN-USE
CONTRACTOR MUST REPLACE EXISTING HVAC MAINTENANCE RECEPTACLE AND PROVIDE NEW EXTERIOR 8.
COR WILL VERIFY ALL SEEMS ARE PROTECTED, PRIOR TO FINAL ACCEPTANCE.
COMPLETE INSTALL MUST INCLUDE ALL PENETRATIONS BEING SEALED WATERTIGHT AND WEATHERTIGHT. 7.
WORK FOR ANCHORING DETAILS.
CURB TO STEEL DECKING TO BE ATTACHED WITH SELF-TAPPING ANCHORING; REFER TO STATEMENT OF
STEEL DECKING. PROVIDE COORDINATION DRAWINGS FOR APPROVAL PRIOR TO INSTALLATION. VIBRATION
UNIT. NEW CURB MUST HAVE 2" DEFLECTIONS AND BE ANCHORED TO BASE BUILDING ROOF TO THE
CONTRACTOR MUST PROVIDE AND INSTALL NEW VIBRATION ISOLATION CURB FOR NEW ROOFTOP AC 6.
PERIOD MUST RESTART AFTER CONTRACTOR HAS ADDRESSED DEFICIENCY.
ENVELOPE SET AT THE THERMOSTAT. IF UNIT CANNOT MEET DESIRED TEMPERATURE, 72 HOUR PROVING
A CONTINUOUS 72 HOUR PERIOD. DURING THIS PERIOD UNIT MUST HOLD THE DESIRED TEMPERATURE
INSTALLATION.NEW UNIT MUST PROVIDE THE HEATING AND COOLING NEEDS OF THE BASE BUILDING FOR
NEW PACKAGE ROOFTOP UNIT MUST COMPLETE A 72 HOUR PROVING PERIOD FOR COMPLETE 5.
PROVIDE (4) 2 KW PORTABLE ELECTRIC HEATERS4.B.
PROVIDE AND INSTALL (4) 1.5 TON PORTABLE AC UNITS AND FLEX DUCT WORK.4.A.
TEMPORARY EQUIPMENT BEING DEMOLISHED.
EXISTING PACKAGE ROOFTOP BEING DEMOLISHED; NEW ROOFTOP MUST BE INSTALLED PRIOR TO
SEPARATE CIRCUITS TO AVOID NUISANCE TRIPS. TEMPORARY EQUIPMENT MUST BE INSTALLED PRIOR TO
FIELD LOCATE ALL EQUIPMENT WITH COORDINATION OF COR. EQUIPMENT MUST BE INSTALLED ON
INSTRUCTIONS. PROVIDE ALL ELECTRICAL AND CONTROLS EQUIPMENT FOR COMPLETE INSTALLATION.
PERIOD. ALL EQUIPMENT MUST BE INSTALLED ACCORDING TO MANUFACTURER'S INSTALLATION
HEATING SOLUTION THROUGHOUT THE BASE BUILDING FOR THE DURATION OF THE CONSTRUCTION
CONTRACTOR MUST PROVIDE A PLAN, FOR APPROVAL, FOR A COMPLETE TEMPORARY COOLING AND 4.
COMPLETED START-UP CHECKLIST TO COR.
CONTRACTOR MUST COMPLETE START-UP CHECKLIST UPON COMPLETE INSTALLATION, AND PROVIDE 3.
AND COMPRESSORS.
TO COMMISSION INSTALLATION AND VERIFY MANUFACTURE'S EXTENDED 5 YEAR WARRANTY ON COILS
PACKAGE ROOFTOP UNIT MANUFACTURER MUST HAVE REPRESENTATIVE VISIT SITE AFTER INSTALLATION 2.
INSTRUCTIONS. POWER IS FED FROM CIRCUIT BREAKERS 17, 19, AND 21 IN PANEL LP.
MUST INSTALL PACKAGE ROOFTOP UNIT ACCORDING TO MANUFACTURER'S RECOMMENDED INSTALLATION
CONTRACTOR MUST PROVIDE AND INSTALL NEW 4 TON PACKAGED AIR CONDITIONING UNIT. CONTRACTOR 1.
MEMBRANE
BASE FLASHING
REMOVABLE SHEET METAL
COUNTER FLASHING
EDGE RAIL
OF RTU
ROOF DECK
INSULATION
CONTINOUS
RAISED
CURB
SEALING
MATERIAL
ACCORDING TO MANUFACTURER'S INSTALLATION INSTRUCTIONS.
INSTALL ROOFTOP UNIT, VIBRATION ISOLATION CURB, AND FLASHING ·
DIAGRAM FOR REFERENCE ONLY·
TO BE REPLACED.
VIBRATION ISOLATION CURB
ROOFTOP UNIT AND
POWER ACCESS KNOCKOUT
CONVENIENCE OUTLET
CONTROL ACCESS KNOCKOUT
CONDENSER COIL
CONTROL BOX
HANDLE
INDOOR BLOWER ACCESS
LOCATION
DISCONNECT
ELECTRICAL
HANDLE
39" 70"
(SEE NOTE 8)
CONVENIENCE OUTLET
lo tt e
SCALE: NTS
MAIN PLAN VIEW
M006
BASE BUILDING ROOFTOP FLASHING DIAGRAM
M006
BASE BUILDING ROOFTOP LEFT SIDE
M004
BASE BUILDING ROOFTOP FRONT SIDE
M004
BVY-21005020-M006
BASE BUILDING ROOFTOP HVAC DETAILS
bvy-21005020-m006
2024-01-31T06:16:51-0500
HENRY B NEWCOMB
2024-01-30T13:57:39-0500
SHREY B PATEL
3'-5 1/2 "
6'-2" 3'-2" 1'
4'-5 1/4 " 7'-4 1/2 "
7'-3 1/8 "
4'-5 1/8 "
S001
23'-8"
3'-7 1/4 " 3'-3" 3'-3" 10 1/2 "
4'-8 1/2 " 1'-1 1/2 "
3'-3" 3'-7 1/4 "
4'-5 1/8 "
3'-5 1/2 " 3'-3"
SCALE: 1/2" = 1'-0"
VIBRATION CURB SECTION
HVAC & CURB SECTION
BUILT UP ROOFING
W
.5
C6X8.2
2C12X20.7
W6X8.5
CURB ANCHORS PLAN VIEW
(COORDINATE WITH HVAC MANUF)
BOLT ROOF-TOP UNIT TO CURB
1. FIELD VERIFY EXISTING CONDITIONS AND ROOF OPENING DIMENSIONS BEFORE
STARTING CONSTRUCTION.
2. EQUIPMENT (HVAC, VIBRATION CURB, ETC.) MUST INSTALLED PER MANUFACTURER'S
RECOMMENDATIONS AND INSTRUCTIONS.
3. VIBRATION CURB TO ROOF STEEL PLATE FRAMING TO BE ATTACHED WITH TEKS HEX
HEAD 1/4" DIA. SELF DRILL SELF TAP SCREWS 1" LENGTH WITH STANDARD WASHERS.
PRE-DRILL HOLES IN STEEL PLATE AND USE TOTAL OF SIX (6) SCREWS, THREE (3) ON
TWO SIDES AS SHOWN ON DRAWING.
4. ELASTOMERIC COATING TO BE FIELD INSTALLED ON EXTERIOR OF VIBRATION CURB.
5. APPROXIMATE UNIT WEIGHT OF 300 LBS FOR VIBRATION CURB AND 1200 LBS FOR
HVAC UNIT. FINAL UNIT WEIGHT AND DIMENSIONS PER VENDOR MANUFACTURER.
6. REMOVE ROOFING AND OTHER MATERIALS TO GET DOWN TO STEEL ROOF DECKING.
7. REFER TO M004 FOR VIBRATION ISOLATION CURB DETAILS.
(SEE NOTE 3)
SELF TAPPING SCREWS
HVAC ROOF-TOP UNIT
(SEE NOTE 2)
VIBRATION CURB
UNIT (SEE NOTE 2)
HVAC ROOF-TOP
SCALE: 1" = 1'-0"
CURB CORNER DETAIL
CURB CORNER DETAIL
ELASTOMERIC COATING (SEE NOTE 4)
EXISTING BUILT UP ROOFING (SEE NOTE 1)
EXISTING 1/4" PL STEEL DECKING
SELF TAPPING SCREWS
ELASTOMERIC COATING (SEE NOTE 4)
BUILT UP ROOFING (SEE NOTE 1)
EXISTING 1/4" PL STEEL DECKING
.2
C8x11.5
C8x11.5
2C12X20.7
X
X
X
X
CAB ROOF FRAMING PLAN
HVAC UNIT
OPEN FOR
:3 lo tt e
-s
1' 0 3' 5'
1' 2' 4'
1' 0 1' 2'
BVY-21005020-S001
CJO
CJO
HVAC AND VIBRATION CURB
-s bvy-21005020-s001
2024-01-31T06:15:46-0500
HENRY B NEWCOMB
2024-01-30T15:17:30-0500
CHRISTIAN J O'CONNOR
C001
CAB PARTIAL ELEVATION
OVER EXISTING ROOFING SYSTEM.
APPLY ELASTOMERIC COATING
TO THE CATWALK
CONTINUE DOWN THE FACADE
OVER PARAPET WALL AND
APPLY ELASTOMERIC COATING
(SEE NOTE 5 AND 6)
HATCH AND THE HVAC CURBS.
THE VERTICAL SIDES OF THE
APPLY ELASTOMERIC COATING UP
ELASTOMERIC COATING.
PRIOR TO APPLICATION OF
AROUND CAB WINDOWS
ALL RAILINGS AND STEEL
EXPOSE BARE METAL ON
SYSTEM TO AVOID TRIPPING HAZARD
PROTECT DURING CONSTRUCTION ACTIVITIES. CONDUCTOR MUST BE STRAPPED DOWN TO ROOFING
TO COUNTERPOISE. USE A 2 LUG CONNECTOR TO ATTACH TO NEW HVAC UNIT. REMOVE AND
CONTRACTOR MUST REUSE EXISTING GROUND CONDUCTOR AND RECONNECT ROOFTOP HVAC UNIT 9.
ROOF WARRANTY.
SYSTEM MEETS MANUFACTURER'S INSTALLATION REQUIREMENTS AND MUST RECEIVE NEW 20 YEAR
CONTRACTOR MUST HAVE COATING MANUFACTURER'S REPRESENTATIVE VERIFY THAT NEW ROOFING 8.
THE APPLICATION OF ELASTOMERIC COATING
EPDM. SOME OF THE EPDM HAS BECOME UN-ADHERED AND WILL NEED TO REPAIRED PRIOR TO
BELOW THE STEEL CATWALK, THERE ARE AREAS OF THE ROOF DECK THAT IS COVERED IN AN 7.
WARRANTY.
HVAC FLASHING MUST BE COVERED IN ELASTOMERIC TOPCOAT TO OBTAIN MANUFACTURER'S ROOF 6.
TO MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CURB/SEISMIC STAND AS WELL AS THE HATCH. FLASHING COATING MUST BE APPLIED ACCORDING
ELASTOMERIC COATINGS SHALL BE APPLIED UP THE VERTICAL FLASHING OF THE HVAC 5.
APPROVED EQUAL).
ELASTOMERIC COATING SHALL BE SIKALASTIC ROOFING PRIMER, REMAT PREMIUM AND 641 (OR 4.
AROUND HVAC UNIT. ADD GRIT MATERIALS TO FINISHED WALKING AREA.
RE-ADHERE EXISTING LOOSE WALKWAY PADS ON BASE BUILDING FROM LADDER TO HVAC AND 3.
CONTRACTOR TO CLEAN ROOF DRAINS, AND REMOVE ANY DEBRIS FROM THE AREA.2.
CONTRACTOR TO SUBMIT ALL MATERIALS FOR APPROVAL FOR THE NEW ROOFING SYSTEM1.
(SEE NOTE 2)
ROOF DRAIN (TYP)
(TYP)
WALKWAY PADS
SEE NOTE 9
EXISTING TO REMAIN
EQUIPMENT TO COUNTERPOISE
C001
ATCT AND BASE BUILDING PLAN VIEW
SEE NOTE 3
WALKWAY PADS
LINE
DRAIN ALONG THE ROOF
TO THE NEAREST ROOF
CONDENSATE DRAIN PIPED
(SEE NOTE 4)
OF ELECTROMETRIC COATING
LET DRY PRIOR TO APPLICATION
FROM EXISTING ROOF SYSTEM AND
CLEAN LOOSE SAND AND DEBRIS
EXISTING TO REMAIN
BILCO ROOF HATCH,
UNIT & CURB
ROOF TOP HVAC
(TYP. OF 4 PLACES)
TO ELASTOMERIC COATING
NEED TO REPAIRED, PRIOR
DAMAGED EPDM LAYER WILL
LOWER EXPOSED ROOF WITH
DAMAGED WALKWAY MATS.
HATCHING INDICATES EXISTING
CREATE A TRAFFIC SURFACE.
ENTIRE ROOF SURFACE TO
COATING WILL BE APPLIED TO
APPLICATION OF GRIT MATERIAL
:5 lo tt e
-c
01/29/2024
BVY-21005020-C001
ROOF REPAIRS
-c bvy-21005020-c001
2024-01-31T06:15:02-0500
HENRY B NEWCOMB
2024-01-30T13:56:15-0500
SHREY B PATEL
24'-0"
44'-0"
D001
ATCT AND BASE BUILDING DEMOLITION PLAN VIEW
EQUIPMENT NOT SHOWN FOR CLARITY.
LOCATION OF DETERIORATED ROOFING MATERIALS. ALL ROOF
NOTE: PLAN VIEW IS DIAGRAMMATIC TO SHOW APPROXIMATE
(TYP)
ROOF DRAIN
A1
A2
TO ROOF
LADDER
IN PLACE.
INCLUDE, BUT NOT LIMITED TO, SCOPE OF WORK TO BE ACCOMPLISHED AND RISK MITIGATION TO BE PUT
CONTRACTOR MUST SUBMIT A FALL PROTECTION PLAN FOR ROOF WORK TO BE APPROVED. PLAN MUST 3.
NEW INSULATION AND MATERIALS MUST MATCH EXISTING MATERIALS.2.2.
INSTRUCTIONS
NEW INSULATION AND MATERIALS MUST BE INSTALLED ACCORDING MANUFACTURER'S INSTALLATION 2.1.
CONTRACTOR MUST PROVIDE NEW INSULATION AND PATCH WITH DRY ROOF MATERIALS WHERE REMOVED.2.
AREA A2 IS APPROX. 3' X 5'1.2.
AREA A1 IS APPROX. 2' X 2'1.1.
SINCE SURVEY WAS COMPLETED (SURVEY DATE WAS 4/11/2023).
SURVEY TO LOCATE DAMAGED REGIONS. DAMAGED REGIONS MAY HAVE GROWN DUE TO FURTHER MOISTURE
AREAS ARE APPROXIMATE, AND ARE FOR REFERENCE ONLY. USE THE PROVIDED INFRARED ROOF MOISTURE 1.
1 & 2
SEE NOTE
(3' X 5')
1 & 2
SEE NOTE
(2' X 2') lo tt e
-d
BVY-21005020-D001
CIVIL DEMOLITION
bvy-21005020-d001
2024-01-31T06:15:12-0500
HENRY B NEWCOMB
2024-01-30T13:56:22-0500
SHREY B PATEL
GROUND LEVEL
C-1 LEVEL
C-3 LEVEL
C-2 LEVEL
PANEL MDP
PANEL A
EQUIP. RM.
CH-1
UH-1
FIRST/GROUND FLOOR EQUIPMENT ROOM
SECOND FLOOR EQUIPMENT ROOM
THIRD FLOOR EQUIPMENT ROOM
FOURTH FLOOR EQUIPMENT ROOM
UH-2
ELECTRIC 3.7K
PANEL C
PANEL B
CAB FALSE CEILING
PARAPET
"ROOF DECK
1'-8.5"
RECORD KEEPING REQUIREMENTS FOR PERSONS DISPOSING OF REFRIGERANTS. SEE EPA 40 CFR PART 82, SUBPART A AND F
CONTRACTOR MUST HANDLE REFRIGERANT ACCORDING TO LOCAL, STAT, AND FEDERAL REQUIREMENTS. CONTRACTOR TO MAINTAIN
EQUIPMENT AS WELL AS PERSONNEL DISPOSING OF REFRIGERATION/ AC EQUIPMENT MUST HAVE REQUIRED CERTIFICATIONS.
CONTRACTOR MUST REMOVE REFRIGERANT FROM EXISTING ROOFTOP UNIT PRIOR TO DEMOLITION. ALL REFRIGERANT RECOVERY 17.
REFER TO STATEMENT OF WORK FOR WORK HOURS.16.
REMOVE THE STRAIGHT SECTION OF SUPPLY AND RETURN DUCT BETWEEN ROOFTOP UNIT AND FIRST TRANSITION.15.6.
REMOVE EXISTING ROOFING MATERIALS AROUND CURB TO GAIN ACCESS TO STRUCTURAL ELEMENTS OF ROOF. 15.5.
REMOVE EXISTING THERMOSTAT AND CONDUCTORS15.4.
REMOVE EXISTING FLEXIBLE DUCT CONNECTOR.15.3.
REMOVE EXISTING STANDARD CURB. 15.2.
ONLY FAA PERSONNEL MAY OPERATE BREAKERS AND DISCONNECTS.
PRIOR TO EXISTING PACKAGE ROOFTOP DEMOLITION, CONTRACTOR MUST LOTO BREAKERS 17,19, AND 21 IN PANEL LP. 15.1.1.
EPA, STATE, AND LOCAL GUIDELINES.
REMOVE EXISTING PACKAGE ROOFTOP UNIT FROM THE SITE AND DISPOSE OR RECYCLE OF PROPERLY IN ACCORDANCE WITH 15.1.
EXPECTED DEMOLITION ACTIVITIES FOR BASE BUILDING ARE INCLUDING BUT NOT LIMITED TO THE FOLLOWING:15.
METHOD TO TO PROTECT FAA PERSONNEL AND EQUIPMENT, AS WELL AS METHODS TO LIMIT DUST PRODUCTION.
CONTRACTOR SHALL SUBMIT A DUST MITIGATION PLAN FOR APPROVAL PRIOR TO DEMOLITION START. PLAN MUST INCLUDE 14.
CONTRACTOR MUST DEMOLISH ALL EXISTING EQUIPMENT REQUIRED FOR COMPLETE NEW HVAC INSTALLATION.13.
CONTRACTOR MUST MODIFY EXISTING OPENINGS TO ACCOMMODATE NEW AC UNIT INSULATED SLEEVES.12.
CONTRACTOR MUST DEMOLISH THE EXISTING VIBRATION ISOLATION ROOF CURB.11.
CONTRACTOR MUST DEMOLISH ALL EXISTING SUPPLY DUCT CLAMPS AND HANGERS.10.
FOR ELECTRIC UNIT HEATERS AND PTAC UNITS.
CONTRACTOR MUST DEMOLISH EXISTING THERMOSTAT FOR CAB ROOFTOP UNIT, AS WELL AS ANY WALL MOUNTED THERMOSTATS 9.
CONTRACTOR MUST PROTECT ALL EQUIPMENT FROM DEMOLITION 8.
PANELS THAT GET DAMAGED DURING CONSTRUCTION PERIOD. NEW CEILING PANELS MUST MATCH EXISTING.
CONTRACTOR MUST REMOVE CEILING PANELS TO REMOVE/ INSTALL HVAC SYSTEM. CONTRACTOR MUST REPLACE ANY CEILING 7.
72 HOUR TESTING PERIOD.
PROVIDE CONTINUOUS COOLING, DURING 72 HOUR TESTING PERIOD, CONTRACTOR MUST ADDRESS THE ISSUE AND RESTART THE
SUCCESSFULLY PROVIDED CONTINUOUS COOLING TO THE CONDITIONED SPACED FOR 72 HOURS. IF TEMPORARY UNIT FAILS TO
THE DEMOLITION WORK IS TO COMMENCE AFTER THE TEMPORARY HVAC UNIT AND DUCTWORK ARE IN PLACE AND HAVE 6.
OPERATION WITH AN APPROVED PLAN.
UNSCHEDULED LOSS OF EQUIPMENT IS UNACCEPTABLE. DISRUPTION OF POWER SHALL ONLY BE ALLOWED AS A SCHEDULED
ALL SPACES IN CONTROL TOWER ARE OPERATIONAL SPACES. EQUIPMENT WILL GO INTO ALARM IF COOLING IS NOT SUPPLIED. 5.
EQUIPMENT THAT IS CONDITIONING THE CAB, IS PROVIDED.
TEMPORARY HVAC EQUIPMENT IS REQUIRED DURING REPLACEMENTS OF ALL (3) PTAC UNITS. SCHEDULE FOR TEMPORARY 4.
INSTALL METHOD, AND CUTOVER PROCEDURE.
CONTRACTOR MUST SUBMIT A TEMPORARY HVAC PLAN PRIOR TO DEMOLITION FOR APPROVAL. PLAN MUST INCLUDE EQUIPMENT, 3.
DUCTWORK FROM UNIT TO FIRST TRANSITION.
CONTRACTOR MUST DEMOLISH BASE BUILDING ROOFTOP HVAC UNIT, VIBRATIONS ISOLATION CURB, AND SUPPY AND RETURN 2.
AREAS INDICATED BY HATCHING ARE TO BE DEMOLISHED, EXACT DIMENSIONS TO BE VERIFIED ON SITE.1.
TO BE DEMOLISHED:
1. 8.5 TON YORK ROOFTOP HVAC UNIT
2. HVAC VIBRATION ISOLATION CURB
3. ROOFTOP UNIT THERMOSTAT (ALL ASSOCIATED CONTROLS)
4. WINDOW AC UNIT - FIRST FLOOR EQUIPMENT ROOM
5. 7.5 KW ELECTRIC UNIT HEATER - FIRST FLOOR STAIRWELL
6. PACKAGE TERMINAL AC UNIT - SECOND FLOOR EQUIPMENT ROOM
7. PACKAGE TERMINAL AC UNIT - THIRD FLOOR EQUIPMENT ROOM
8. 3.7 KW ELECTRIC UNIT HEATER - CAB STAIRWELL
9. FLEX SUPPLY DUCTWORK (10") - TYPICAL OF 18
10. SUPPLY DUCTWORK, VOLUME DAMPERS, AND PLENUM
TO REMAIN:
1. WINDOW AC UNIT - FOURTH FLOOR EQUIPMENT ROOM
2. SUPPLY DROP GRILLE
3. RETURN DUCTWORK
4. RETURN GRILLE
5. LINEAR SUPPLY DIFFUSER - TYPICAL OF 18
6. ROOF HATCH AND DROP DOWN STAIRS
7. AIR TERMINALS - TYPICAL
8. CABINET HEATER - FIRST FLOOR EQUIPMENT ROOM
9. PANEL MDP
10. PANEL A
11. PANEL B
12. PANEL C
TEMP-1
MARK SERVICE TYPE
UNIT IDENTIFICATION
NOMINAL
3,000
NO. OF
CIRCUITS
HEAT
TYPE STAGES
AMBIENT
VOLTS PHASE HZ
208/230 3 60
THICKNESSTYPE ASHRAE STD
AIR COOLED
KW
EFFICIENCY
FILTER DATA
TEMP.°F
ELECTRICAL DATAEVAPORATOR
AIR
CONDITIONING
COIL 27
CONDENSER
TEMPORARY HEATING AND AIR CONDITIONING SCHEDULE - TEMPORARY EQUIPMENT PROVIDING COOLING TO CAB
MOP
100 PLEATED
MCA
HUMDIFIER
2"
NONE
MERV 8
LOW
TONNAGE
COOLING
7.5 102 MBH
D002
EXISTING DUCTWORK LAYOUT
CEILING
SUSPENDED
ROOFTOP UNIT DEMOLITION DETAIL
(SEE NOTE 6)
ATCT ELEVATION-EXISITNG
REFER TO M001 FOR MECHANICAL REQUIREMENTS·
ALL ELECTRICAL PANELS SHOWN ARE TO REMAIN·
HATCHING INDICATES EQUIPMENT TO BE DEMOLISHED·
ELEVATION VIEW IS DIAGRAMMATIC TO SHOW APPROXIMATE LOCATION OF EQUIPMENT·
lo tt e
BVY-21005020-D002
MECHANICAL DEMOLITION
bvy-21005020-d002
2024-01-31T06:15:29-0500
HENRY B NEWCOMB
2024-01-30T13:56:30-0500
SHREY B PATEL
ONE LINE, SCHEMATIC DIAGRAM SYMBOLS
DISCONNECT SWITCH
CONTACT, NORMALLY OPEN
CONTACT, NORMALLY CLOSED
METER
CURRENT TRANSFORMER
BUILDING GROUND
ELECTRICAL ABBREVIATIONS
AUTOMATIC TRANSFER SWITCH
POWER TRANSFORMER
XXXKVA, OWNED & MAINTAINED
BY LOCAL UTILITY
FUSED
DISCONNECT
SWITCH
CURRENT LIMITING
FUSE, SIZED AS
INDICATED
COMBINATION MAGNETIC
MOTOR STARTER &
MOLDED CASE THERMAL MAGNETIC
CIRCUIT BREAKER, POLES
AND SIZE AS INDICATED
FIRE ALARM RADIO
MASTER BOX
A A AMPERE
AC ALTERNATING CURRENT
AF AMPERE FRAME
B BCRP BACKUP
C CB CIRCUIT BREAKER
CKT CIRCUIT
C CONDUIT
D DC DIRECT CURRENT
DISC DISCONNECT
D PNL DISTRIBUTION PANEL
DT DOUBLE THROW
E EG ENGINE GENERATOR
F FSS FUSIBLE SAFETY SWITCH
FDR FEEDER
FLA FULL LOAD AMPERES
G GFM GROUND FAULT MONITOR
H HTR HEATER
K KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERES
KW KILOWATT
M MDT MAIN DISTRIBUTION TERMINAL
MLO MAIN LUGS ONLY
MCB MAIN CIRCUIT BREAKER
N N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
P P POLE
PF POWER FACTER
PNL PANELBOARD
S ST SHUNT TRIP
SW SWITCH
V V VOLT, VOLTAGE
VA VOLT AMPERE
W W WATT
X XFMR TRANSFORMER
MISCELLANEOUS
O PHASE
MDP
PANEL 1
DISTRIBUTION
MAIN
2 POLE, 3 WIRE
240 VAC, 30A
30A
7KW ENGINE
GENERATOR SET
240/120 VAC, 3 WIRE
2# 12, 1 #12G
FACP
ALARM
FIRE
LEVEL C-3
CAB ROOF
(240 VAC, 1 PHASE, 3 WIRE)
FAN, SP-1
PRESSURIZATION
STARTER
3 #10 & 1# 10G
3 #10, 1 #10G
TRANSFER SWITCH
AUTOMATIC
LEVEL C-2
MLO
3 PHASE, 4 WIRE
208/120VAC
CAB FLOOR
90A MLO
2# 12 & 1 #12G
PROTECTOR
SURGE
LEVEL C-1
FIRST FLOOR
(3) 1/0 AWG, (1) 6 AWG GND
IN 2" EMT
(3) 1/0 AWG, (1)#6 AWG GND
ATCT ROOFTOP HVAC UNIT
INTEGRAL CIRCUIT BREAKER
FACTORY INSTALLED
4 - 350 KCMIL, #2G
4 #2, 1 # 8G
4 #2, 1 #8G
LP
BASE BUILDING
100A MCB
(4) #2 AWG, (1) #8 AWG GND, 2"C
ADJACENT TO UTILITY J-BOX
METER LOCATED
UTILITY COMPANY
400A, MCB
2# 12 (DWG -E011, NOTE 10)
GEN
TVSS
UTILITY COMPANY
CABINET HEATER
UNIT HEATER
CAB STAIRWELL
E001
ELECTRICAL ONE-LINE DIAGRAM
ROOFTOP HVAC UNIT
BASE BUILDING
NON-FUSED DISCONNECT SWITCH
FACTORY INSTALLED
FIRST FLOOR
EUH-1WAC-1
CLOUDED AREAS INDICATES SCOPE OF WORK
EQUIPMENT ROOM
100A MCB
4 #2, 1 #8G
DC BUS
(2) 3 #10, 1 #10G
(2) 3 #12, 1 #12G
MAINTENANCE OUTLET
FIELD INSTALLED
lo tt e
-e
BVY-21005020-E001
ELECTRICAL ONE LINE DIAGRAM
bvy-21005020-e001
2024-01-31T06:17:01-0500
HENRY B NEWCOMB
2024-01-30T13:57:47-0500
SHREY B PATEL
MOUNTING: SURFACE
LOCATION: 1ST FLOOR ELECTRICAL ROOM
SERVICE: 120/208V, 3 PH, 4W
PANEL NAME: MDP
SCC RATING: 10,000 AIC
TOTAL SPACE: 30 CIRCUITS
MAIN DEVICE: 300A MCB
TOTAL:
PHASE C:
PHASE B:
PHASE A:
ASSIGNED LOAD (KVA)
CIRCUIT DESCRIPTION
OCP CKT #A B
PANEL A - 1ST FLOOR, 208V, 3PH
PANEL LP - BASE BUILDING, 208V, 3PH
LOAD (VA)
CKT # OCP A B
TOTAL LOAD EACH PANEL SIDE
TOTAL LOAD OF PANEL
PH CC
300A
120/208V, 3 PH, 4W
MODEL # I-LINE HCM
MANUFACTURER: SQD
ROOFTOP HVAC, 208V, 3P
SPACE
3P
2P
SPARE, 208V, 1PH
PANEL B - 4TH FLOOR, 208V, 3P
SPARE, 208V, 3P
PANEL C - 3RD FLOOR, 208V, 3P
LOCATION: 1ST FLOOR ELECTRICAL ROOM
PANEL NAME: PANEL A
TOTAL SPACE: 30 CIRCUITS
MAIN DEVICE: MLO
100A
120/208V, 3 PH, 4W
MODEL # NQOB
EXIT SIGNS
BATTERY CHARGER FOR EG
FIRE ALARM CONTROL PANEL
ACU (ASOS)
HEATER TAPE
ELEV SHAFT LTS
EQPT ROOM RECEPTACLES
EQPT ROOM LTS
SPARE
EG BLOCK HEATER
MOTORIZED DAMPERS
THERMOSTAT FOR HEATER #3
RECEPT - (TELCO)
OUTSIDE LIGHTS
STAIRWLL LTS/ ROTING BEACON
STAIRWELL AND EMERGENCY LTS
ELECTRIC HEATER, 208V, 3PH
GROUND FLOOR STAIRWELL
TO FIRE-LIFE-SAFETY TRANSFER SWITCH
1PH
HVAC - BATTERY/EQUIPMENT ROOM, 208V,
1PH
WALL HEATER- EQUIPMENT ROOM, 208V,
LOCATION: 4TH FLOOR
PANEL NAME: PANEL B
TOTAL SPACE: 42 CIRCUITS
MAIN DEVICE: 100A MCB BACKFED
A/C (4TH FLR EQ ROOM)
2ND AND 3RD FLOOR LTS
RECEPTACLES IN CONSOLES
OBSTRUNCTION AND EXIT FLOOD LTS
CONSOLE RECEP/ ACE IDS MONITOR
HUMIDIFIER
DALR
CAB CONVENIENCE OUTLET
20 5
20 7
20 9
20 11
20 17
20 19
30 21
20 23
20 25
33 34 20
35 36
37 38
39 40
41 42
CAMERA
CAMERA
STARS PCU/ LIGHT GUNS
RECEP UNDER RIGHT SIDE CONSOLE/
STARS DISPLAY
JUNCTION AND EMERGENCY LIGHTS
HW HEATER & EF-1
STARS/ ACE IDS BVY 2 MONITOR
ILS MONITOR PANEL PLUGMOLD
C-3 HEATER TAPE
TROUGH MOUNTED RECEP
225A
240V MAX, 3PH, 4W
MODEL # NQOD
CAB B LTS & ROOF N LTS
CAB LTS UNDER CONSOLE
STARS PCU & VIDEO RECEIVER
ACE IDS
RECEP UNDER RUGHT SIDE CONSOLE
CAB RECEP (LEFT SIDE MOULDING)
MICROWAVE
RECEP UNDER LEFT SIDE CONSOLE
MAIN BREAKER, 208V, 3PH
ELEC HTR #1 (BATHROOM), 208V, 1PH
ELECTRIC HEATER #2 C-3, 208V, 1PH
C-2A A/C UNIT (2ND FLOOR), 208V, 1PH
C-2 A/C UNIT (3RD FLOOR)
CAB RECEP(RIGHT SIDE MOULDING)
LOCATION: BASE BUILDING
PANEL NAME: PANEL LP
SCC RATING: 22,000 AIC
TOTAL SPACE: 42 CIRCUITS
MAIN DEVICE: 200A MCB
EMERGENCY LIGHT OUTLET
ASSISTANT MANAGER LIGHTS
OUTSIDE GFCI OUTLETS
SECURITY VIDEO/ DOOR LOCKS
CONFERENCE ROOM RECEPTACLE
20 5
20 7
20 9
20 11
20 23
20 25
33 34
35 36
37 38
39 40
41 42
RECEPTION AND VESTIBULE OUTLETS
HALLWAY AND LOUNGE OUTLETS
MANAGER AND ASST MGR OFFICE OUTLETS
TRAINING AND HALLWAY OUTLETS
MANAGER OFFICE LIGHTS
LIGHTS
CONFERENCE AND TRAINING ROOM
225A
240V MAX, 3PH, 4W
MODEL # NQOD
WESTINGHOUSE
MANUFACTURER: CHALLENGER/
LAVATORY LIGHTS AND FAN
LOUNGE AND LAVATORY OUTLETS
HOT WATER HEATER
EMERGENCY EXIT LIGHTS
ENTRY LOCK AND CHIMES
RECEPTION AREA LIGHTS
SPACE SPACE
208V, 3PH
BASE BUILDING ROOFTOP UNIT,
A/C HEATER
20 20
REFRIGERATOR AND LIGHTS
LOUNGE LIGHTS
LIGHTS OFFICE
A/C ROOFTOP UNIT OUTLET GFCI RECEP
THEIR OWN LOCK OUT DEVICES.
COR PRIOR TO ANY ELECTRICAL WORK. CONTRACTOR MUST SUPPLY
CONTRACTOR MUST SUBMIT A LOCK OUT TAG OUT PLAN TO THE ·
ONLY FAA PERSONNEL MAY OPERATE BREAKERS·
TO OUTAGE
COORDINATE ALL EQUIPMENT OUTAGES WITH COR, 48 HOURS PRIOR ·
BE UTILIZED DURING CONSTRUCTION
STARRED NOTES IDENTIFY FEEDERS/ CIRCUIT BREAKERS THAT WILL ·
6 8
LOCATION IDENTIFIED BY STAR #1
ELECTRICAL REQUIREMENTS TO EXISTING UNIT'S MOP AND MCA. BREAKER
UNIT FOR THE NEW ROOF TOP PACKAGHE HVAC UNIT. MATCH NEW UNIT'S
REUSE CONDUIT, CONDUCTORS, AND BREAKERS 1,3,5 FROM EXISTING HVAC 1.
MAIN DISTRIBUTION PANEL NOTES
ONLY).
BOX WITH WEATHERPROOF IN-USE BUBBLE COVER (FOR REFERENCE
GFCI DUPLEX RECEPTACLE, 20A, 120V, WR RATED, IN EXTERIOR RATED
REPLACE EXISTING HVAC MAINTENANCE RECEPTACLE WITH EXTERIOR
BREAKERS 16 IS IDENTIFIED BY STAR #10, REUSE EXISTING BREAKER. 2.
RATED (OR APPROVED EQUAL)
BREAKER WITH NEW EATON # BAB3070H, 70A, 3 POLE, BOLT-ON, HACR
ROOFTOP PACKAGE AC UNIT TO BE REPLACED. REPLACE EXISTING
BREAKERS 17, 19, AND 21 ARE IDENTIFIED BY STAR #9. BASE BUILDING 1.
PANEL "LP" NOTES
HEATER TO BE RE-USED (FOR REFERENCE ONLY).
BREAKERS 18 AND 20 ARE IDENTIFIED BY STAR #4. EXISTING CABINET WALL 3.
IDENTIFIED BY STAR #3
REQUIREMENTS TO EXISTING UNIT'S MOP AND MCA. BREAKER LOCATIONS
UNIT FOR NEW WINDOW AC UNIT. MATCH NEW UNIT'S ELECTRICAL
REUSE CONDUIT, CONDUCTORS, AND BREAKERS 2 AND 4 FROM EXISTING AC 2.
EXISTING UNIT'S MOP AND MCA. BREAKER LOCATIONS IDENTIFIED BY STAR #2
FOR NEW EUH-1. MATCH NEW UNIT'S ELECTRICAL REQUIREMENTS TO
REUSE CONDUIT, CONDUCTORS, AND BREAKERS 1 ,3, 5 FROM EXISTING EUH 1.
PANEL "A" NOTES
IDENTIFIED BY STAR #8
AC UNIT FOR NEW PTAC UNIT. MATCH NEW UNIT'S ELECTRICAL
REUSE CONDUIT, CONDUCTORS, AND BREAKERS 28 AND 30 FROM EXISTING 4.
IDENTIFIED BY STAR #7
EXISTING EUH FOR NEW EUH-2. MATCH NEW UNIT'S ELECTRICAL
REUSE CONDUIT, CONDUCTORS, AND BREAKERS 23 AND 25. FROM 3.
IDENTIFIED BY STAR #6
AC UNIT FOR NEW PTAC UNIT. MATCH NEW UNIT'S ELECTRICAL
REUSE CONDUIT, CONDUCTORS, AND BREAKERS 27 AND 29 FROM EXISTING 2.
USED (FOR REFERENCE ONLY).
BREAKER 5 IS IDENTIFIED BY STAR #5. EXISTING WINDOW AC UNIT TO BE RE-1.
PANEL "B" NOTES
:3 lo tt e
BVY-21005020-E002
ELECTRICAL PANEL SCHEDULE
bvy-21005020-e002
2024-01-31T06:17:12-0500
HENRY B NEWCOMB
2024-01-30T13:58:24-0500
SHREY B PATEL
File details come from the government source that posted it. Updated .