BoQ 191T7023Q0050.pdf
PDF 262 KB Posted
- Attached to
- MSB South East Wing VRF Replacement, Rome, Italy
- Solicitation number
- 191T7023Q0050
- Issued by
-
Department of State
About this file
This document contains a bill of quantities for a federal contract opportunity to replace a variable refrigerant flow system at the MSB South East Wing in Rome, Italy. The scope of work includes removal of the existing VRF system, installation of a new 3-pipe Panasonic VRF system with outdoor units providing a total nominal cooling capacity of 67 kW and heating capacity of 75 kW, 17 indoor units of varying sizes, new control wiring and configuration, electrical distribution panel, and system testing and balance. The contractor must protect surfaces, remove and dispose of existing equipment, reinstall piping and wiring, install new thermostats and configure controls. The total cost is estimated at EUR 4,000. The solicitation was issued by the Department of State under opportunity number 191T7023Q0050.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ - 191T7023Q0050.docx | DOCX document | |
| Technical Specifications 191T7023Q0050.pdf | ||
| Cover Letter - 191T7023Q0050.pdf | ||
| SF-1442 - 191T7023Q0050.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
No. DESCRIPTION QUANTITY
UNITY COST
TOTAL COST
1 Protection of floor and surfaces with cardboard sheeting and poly sheets lump sum
Removal of all furniture that may impact on the correct execution of the work and transportation to a storage location as directed by the COR, within the Tri‐Missions Campus.
lump sum
Removal of the existing VRF outdoor and indoor units and selector branches and transportation to authorized landfill lump sum
4 Wall finishing and painting of the walls to restore them to their original conditions lump sum
Supply and installation of a new 3‐pipes VRF system composed of:
2x Outdoor units (2‐pipe, nominal cooling capacity 33.5 kW each, voltage 400V, 4‐wire, including additional refrigerant charge and start up) ‐ PANASONIC U12MF3E8
Nominal cooling capacity: 33.5 kW
Nominal heating capacity: 37.5 kW
Wall mounted indooor unit PANASONIC S‐22MK2E5B
Nominal cooling capacity: 2.2 kW
Nominal heating capacity: 2.5 kW
4‐ways cassette indooor unit PANASONIC S‐22MU2E5B
Nominal cooling capacity: 2.2 kW
Nominal heating capacity: 2.5 kW
4‐ways cassette indooor unit PANASONIC S‐28MU2E5B
Nominal cooling capacity: 2.8 kW
Nominal heating capacity: 3.2 kW
4‐ways cassette indooor unit PANASONIC S‐36MU2E5B
Nominal cooling capacity: 3.6 kW
Nominal heating capacity: 4.2 kW
4‐ways cassette indooor unit PANASONIC S‐45MU2E5B
Nominal cooling capacity: 4.5 kW
Nominal heating capacity: 5.0 kW
6 Replace piping and branch connecting the two outdoor units lump sum
7 Supply and install new wall mounted room thermostats 17
8 Connect and configure the new VRF system to the existing control panel. lump sum
9 Connect indoor and outdoor unit to the existing electrical cables lump sum
10 Connect indoor and outdoor unit to the existing BAS network lump sum
11 Connect indoor units to the existing condensate drain lines lump sum
Supply and install on the roof room a new wall mounted IP 65, with terminals and solid door, electrical distribution panel. Supply and install the new electrical cables as described below. The new panel shall be composed of:
oDisconnector: 4 poles 100 A oMagneto thermic and GFCI serving the Outdoor unit 1: 4 poles, type C, In: 25A, Ith:25A, Idn: 0.30 (B type), Im: 250A, Icu/Icn: 10kA – electrical cable: FG16OM16 0,6/1 kV, Cca‐s1,d1,a1, 5G2.5 oMagneto thermic and GFCI serving the Outdoor unit 2: 4 poles, type C, In: 25A, Ith:25A, Idn: 0.30 (B type), Im: 250A, Icu/Icn: 10kA – electrical cable: FG16OM16 0,6/1 kV, Cca‐s1,d1,a1, 5G2.5 oMagneto thermic and GFCI Ground floor indoor units: 2 poles Type K, In: 16A, Ith:16A, Idn: 0.03 (AC type), Im:160A, Icu/Icn: 20kA oMagneto thermic and GFCI Mezzanine indoor units: 2 poles Type K, In: 16A, Ith:16A, Idn: 0.03 (AC type), Im:160A, Icu/Icn: 20kA oMagneto thermic and GFCI Service outlets: 2 poles Type C, In: 16A, Ith:16A, Idn: 0.03 (AC type), Im:160A, Icu/Icn: 6kA oMagneto thermic and GFCI Ground floor indoor units: 2 poles Type C, In: 16A, Ith:16A, Idn: 0.03 (AC type), Im:160A, Icu/Icn: 6kA lump sum
Test and balance of the system in both heating and cooling mode. Start‐up of the unit must be performed by Manufacturer’s authorized technicians.
lump sum
14 Costs for safety lump sum 4000 4000
Total
The makes indicated in this Bill of Quantities are intended as a point of reference and therefore, the words or approved equivalent are implicit.